REFLECTIVE INSULATION, RADIANT BARRIERS,
|
|
|
- Jody Hampton
- 9 years ago
- Views:
Transcription
1 REFLECTIVE INSULATION, RADIANT BARRIERS, AND INTERIOR RADIATION CONTROL COATINGS FOR USE IN PRE-ENGINEERED METAL BUILDINGS Technical Bulletin #107 Scope: In both the United States and Canada there is significant growing interest throughout the pre-engineered steel building industry for the application of reflective insulation materials and IRCCs in pre-engineered steel buildings. This bulletin has been prepared by the Reflective Insulation Manufacturers Association International (RIMA-I) to address applications and their performance. Definitions: Reflective Insulation: Thermal insulation consisting of one or more low emittance surfaces, bounding one or more enclosed air spaces. Radiant Barrier: A reflective material having a surface emittance of 0.1 or less used for the sole purpose of limiting heat transfer. Interior Radiation Control Coatings: A non-thickness dependent, low-emittance coating. Formulated coatings with thermal emittance less than Emittance: Emittance refers to the ability of the surface to emit radiant energy. Emittance ranges from 0 to 1. A lower value indicates a reflective surface with a low level of radiation. High- Emittance Facer: White Plastic films Numbers Low-Emittance Facer: Foil or metalized films R-Value: Property of an insulation material used to characterize the effectiveness of the insulation in reducing heat transfer. The higher the R value, the better the insulation s ability to reduce heat transfer. U-Value: A measure of the heat transmission through a building part or given thickness of a material (as insulation). The lower the U value, the better the insulation s ability to reduce heat transfer. Types of Products 1. Foil or metallized film-faced polyethylene bubblepack reflective insulation. 2. Foil or metallized film-faced polyethylene or polypropylene foam reflective insulation. 3. Reflective insulation and mass insulation combinations (hybrid systems). 4. Interior radiation control coating (IRCC) low-emittance coatings. Applications Wall Assembly: (See Drawings Appendix A) 1. Reflective insulation - One side facing one-inch closed air space and other side facing an open air space. 2. Reflective insulation - One side facing eight-inch closed air space and other side facing an open air space. 3. Radiation control coatings (low-emittance sprayed to the inside of wall panels). Roof Assembly: (See Drawings Appendix B) 1. Reflective insulation - Draped over purlins. One-inch closed air space facing up with an open air space below. 2. Reflective insulation - Attached to bottom of purlin. Eight-inch closed air space facing up with an open air below. 3. Reflective insulation - Installed over existing metal roof with ¾-inch spacers and new metal roof with ¾-inch enclosed air space between the reflective insulation and the roof panels
2 4. Radiation control coating (low-emittance) sprayed to the underside of the roof deck. Roof Assembly Hybrid System: (See Drawings Appendix C) 1. Reflective insulation and mass insulation combination. 2. Radiation control coatings (low-emittance) sprayed to the underside of the roof deck. Thermal Performance The thermal resistance values for reflective insulation systems installed in metal buildings depend on heat flow direction and the design of the reflective insulation material. The overall thermal performance also depends on the type of exposed facing material that is used. The following tables show a range of R-values that can be anticipated for systems that are presently in use. (Three reflective insulation systems for walls, four reflective insulation systems for roofs, and four reflective hybrid systems per the drawings in the appendix.) The hybrid systems consist of 6.25-in. thick (R 19) batts installed between 8-in. purlins. These tables are not intended to represent all available products or systems. (References: Calculated Thermal Performance of Reflective Systems in Metal Building Applications based on ASHRAE R&D Services, Inc.) Table 1 Calculated R-values and U-factors for Pre-engineered Metal Buildings Wall 1 U-Value No Thermal Summer E= 0.03 * n/a E= n/a Winter E= n/a E= n/a * Effective emittance Wall 2 U-Value No Summer E= n/a E= n/a Winter E= n/a E= n/a Wall 3 U-Value No Summer - E= n/a 0.42 n/a E= n/a 0.56 n/a E= n/a 0.59 n/a E= n/a 0.62 n/a Winter - E= n/a 0.44 n/a E= n/a 0.56 n/a E= n/a 0.59 n/a E= n/a 0.59 n/a Table 2 Calculated R-values and U-factors for Pre-engineered Metal Buildings Roof 1-2 -
3 U-Value No Summer E= E= Winter E= E= Roof 2 U-Value No Summer E= E= Winter E= E= Roof 3 U-Value No Summer E= E= Winter E= E= Roof 4 U-Value No Summer E= n/a 0.38 n/a E= n/a 0.71 n/a E= n/a 0.76 n/a E= n/a 0.89 n/a Winter E= n/a 0.76 n/a E= n/a 1.07 n/a E= n/a 1.07 n/a E= n/a 1.20 n/a - 3 -
4 Table 3 Calculated R-values and U-factors for Pre-engineered Metal Buildings with R 19 Mass Insulation between Eight-Inch Purlins Hybrid 1 U-Value (no thermal block) Summer E= E= Winter E= E= Hybrid 2 U-Value (no thermal block) Summer E= E= Winter E= E= Hybrid 3 U-Value (no thermal block) Summer E= E= Winter E= E= Hybrid 4 U-Value (no thermal block) Summer E= Winter E= ASTM Standards ASTM C 1224, Standard Specification for Reflective Insulation for Building Applications ASTM C 727, Standard Practices for Installation and Use of Reflective Insulation in Building Constructions ASTM C 1313, Standard Specification for Sheet Radiant Barriers for Building Construction Applications ASTM C 1258, Standard Test Method for Elevated Temperature and Humidity Resistance of Vapor Retarders for Insulation ASTM C 1158, Standard Practice for Installation and Use of Radiant Barrier Systems (RBS) in Building Construction ASTM C 1321, Standard Practice for Installation and Use of Interior Radiation Control Coating Systems (IRCCS) in Building Construction Other Compliance Standards ASHRAE/IESNA Standard 90.1 IECC (International Energy Conservation Code) Chapter 5-4 -
5 Primary Testing Requirements 1. Flammability ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials i. UL 1715, Standard for Safety Fire Test of Interior Finish Material ii. NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth 2. Vapor Transmission i. ASTM E 96, Standard Test Methods for Water Vapor Transmission of Materials 3. Thermal Performance i. ASTM C 1363, Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus ii. Calculation based on data from the U.S. National Bureau of Standards (HRP 32, Robinson and Powell) iii. Calculated Thermal Performance of Reflective Systems in Metal Building Application R&D Services, Inc. (Using procedure published in ASTM STP 1116 and ASHRAE Handbook of Fundamentals) Installation In accordance with manufacturer s instructions. It is recommended to contact the manufacturer of the product being used for specific installation instructions. Aesthetics and Comfort 1. Improves lighting. Health and Safety 1. The manufacturer shall provide the users with information regarding any hazards and recommended protective measures to be employed for safe installation and use of the material. 2. Lightweight and easy to handle. 3. No itchy fibers. 4. Refer to manufacturer s MSDS Data Sheets. Storage 1. The material shall be stored in accordance with the manufacturer s recommendations
6 - 6 -
7 - 7 -
8 3 2 4 Reflective Insulation Manufacturers Association International (RIMA-I) W. 147 th Street Olathe, KS Toll-Free: (800) Fax: (913) [email protected] The Reflective Insulation Manufacturers Association International (RIMA-I), its members, and/or agents, make no guarantee as to, and assume no responsibility for, the correctness, sufficiency or completeness of the information contained herein. The information provided herein is intended to be a guide to the concept and applications of reflective insulation. TB #107 06/09 Copyright 2009 by the Reflective Insulation Manufacturers Association International - 8 -
Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature
Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION
PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
DEFAULT HEAT LOSS COEFFICIENTS
DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film
Article Protecting the Building Envelope from Water Damage Vapor Retarders Play a Crucial Role in Moisture Management Whether we like it or not, moisture in the form of water vapor diffusion and humid
Reflective Insulation, Radiant Barriers And Radiation Control Coatings
Understanding and Using Reflective Insulation, Radiant Barriers And Radiation Control Coatings Compiled by Second Edition May 2002 Second Edition Copyright May 2002 Reflective Insulation Manufacturers
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY Spray Polyurethane Foam Alliance Copyright 2005 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY 126 TECHNICAL
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
03/05/14 REVISOR RSI/JC RD3945
1.1 Department of Commerce 1.2 Proposed Permanent Rules Relating to Commerce; Thermal Insulation Standards; 1.3 Materials and Installation 1.4 7640.0100 AUTHORITY; PURPOSE; INCORPORATIONS BY REFERENCE.
Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces
center for the polyurethanes industry October 2009 Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces One of the largest growing uses of spray polyurethane foam (SPF) insulation is in
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS
FIRE-RESISTANCE RATINGS WITH STEEL JOISTS The Underwriters Laboratories (U.L.) Fire Resistance Directory lists hundreds of assemblies their fire resistance ratings. The Specifying Professional can choose
Residential Windows, 3 rd edition Corrected index 1
Residential Windows, 3 rd edition Corrected index 1 A absorptance definition, 78 determinants of, 78 79 energy performance and, 78 tinted glass, 84 acoustical properties of windows, 60 61 acrylic glazing
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver
Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver Designing an Effective Envelope Roofs Below Grade Walls and slabs Glazing & Windows Opaque portions of walls 2 3 Energy
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
Meeting the Fire Code with Continuous Foam Plastic Insulation
Dow Building Solutions Meeting the Fire Code with Continuous Foam Plastic Insulation The 2012 International Building Code (IBC) specifies the fire tests that must be passed if a foam plastic material is
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
Presented by: Jennifer Doyle, P.E., RRC, LEED AP
Presented by: Jennifer Doyle, P.E., RRC, LEED AP Moisture Gas: Molecules are spread out "Vapor" suspended in air forms a mixture, present everywhere Liquid: Molecules are closer Rain Condensation Pipes
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
Analysis II Façade Redesign: Architectural Precast Panels
Analysis II Façade Redesign: Architectural Precast Panels Analysis II Façade Redesign: Architectural Precast Panels Overview: This analysis covers the comparison of the current EIFS façade and my proposed
Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings
INSULATION FOR PRE-ENGINEERED METAL BUILDINGS ROXUL SAFE 55 & 65 and ROXUL PLUS MB Insulation for Pre-Engineered Metal Buildings ROXUL SAFE AND ROXUL PLUS MB Exterior Wall Insulation for Pre-Engineered
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3493 Reissued September 2014 This report is subject to renewal September 2015. A Subsidiary of the International Code Council DIVISION:
Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB
Fire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
Fire-Rated Glass and Glazing START
Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST Instruction: Check each test method for which you are requesting accreditation. An asterisk beside the NVLAP Test Method Code indicates that proficiency
keep moisture in check by getting fairly hot and facilitating downward time the sun came out, Then, after installation roof no longer got very
Cool Roofs Cause Condensation Fact or Fiction? by Phil Dregger, PE, RRC, Technical Roof Services, Inc. (Editor s Note: Phil Dregger is a professional engineer, registered roof consultant, author, and fellow
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the
09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS
09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS PDS SE-160 01-2006 1. PRODUCT NAME SE-160 Clear Surface Coating (water-based copolymer) Specialty Elastomeric Topcoat 2. MANUFACTURER
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
) and air spaces (R a
5.3.3 Thermal Resistance (R-value) Common thermal properties of materials and air spaces are based on steady state tests, which measure the heat that passes from the warm side to the cool side of the test
CERTIFICACIONES Y PRUEBAS DE LABORATORIO
CERTIFICACIONES Y PRUEBAS DE LABORATORIO 1. ASTM (American Society for Testing and Materials): ASTM B177 - Salt spray (fog) corrosion tests, 450h exposure (Passed) ASTM C177 - Standard Test Method for
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Selecting Energy Efficient New Windows in Georgia
Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
Selecting Energy Efficient New Windows in Arizona
Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM
CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
RESNET National Rater Test Study Guide Outline
RESNET National Rater Test Study Guide Outline The RESNET national home energy rating standard spells out a listing of the knowledge base and skills set for Home Energy Ratings. Trainers and Rating Quality
CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace
HEAT GAINS and LOSSES : ROOFS and WALLS Wall Roof Ts To Ts To Ti Ceiling/Airspace Ti Roof and wall are analyzed in the same way. In winter the heat loss is simple transmission based on the inside and outside
ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016
Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2C Energy & IAQ (201) INTRODUCTION Single wythe concrete
The Prefab Package. Modular EIFS construction offers benefits to today s busy jobsites. Building Envelope. Roland Serino, P.E., of Dryvit Systems Inc.
26 D+D MARCH 2015 Building Envelope Roland Serino, P.E., Dryvit Systems Inc. here has always been a need for a more efficient way to build in large cities like Chicago, New York, Los Angeles or other central
Selecting Energy Efficient Replacement Windows in Nevada
Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows
THERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
Tsawwassen BC Arena Before & After installation of the Low-E ceiling
LOW EMISSIVITY CEILINGS Emissivity- Describes the ability of a certain material to radiate heat rather then absorb it. Materials that radiate 100% have an (EM) of 1.0, while materials that radiate no heat
National Building Code of Canada 2010
National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building
Insulation R-Value Comparisons
Insulation R-Value Comparisons American Ingenuity s component panels for the 22 48 domes contains seven inch thick rigid Expanded Polystyrene (E.P.S.) insulation which has an R value of 28. American Ingenuity
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT. awipanels.com From freezing, sub-zero temperatures to Contents dry heat or high humidity, Mother Nature continually tests the limits of building envelopes. That's
Dow Corning PROPRIETARY. Dow Corning. A Thermal Modelling Comparison of Typical Curtain Wall Systems
Dow Corning A Thermal Modelling Comparison of Typical Curtain Wall Systems Introduction Today s Aim To understand the meaning of a U value and window energy ratings Discuss the drivers for energy efficiency
Housing Fact Sheets. Insulation Check-Up
Insulation Check-Up Housing Fact Sheets Introduction Heating and cooling account for the majority of energy costs in homes throughout the United States. Although current energy prices are relatively low,
R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION
An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2B Energy & IAQ (2009) INTRODUCTION Single wythe concrete
Multi-layer Insulation Blanket for Roofs
Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
CONDENSATION. Section Break (Next Page)
CONDENSATION Elimination of condensation on or within walls and floors is as important as reducing the heat loss through the wall or floor. In addition to the moisture damage caused to buildings by condensation,
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3758 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 07 00 00 THERMAL
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Selecting Energy Efficient New Windows in Florida
Selecting Energy Efficient New Windows in Florida www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International
CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:
STATE OF CALIFORNIA RESIDENTIAL ALTERATIONS - RE-ROOF CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: CALIFORNIA ENERGY COMMISSION CF-1R-ALT-01-E (Page 1 of 2) Date Prepared: A.
Selecting Energy Efficient New Windows in Texas
Selecting Energy Efficient New Windows in Texas www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified
PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof?
PIMA Technical Bulletin #115 The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing About Polysio Insulation Polyiso is a rigid foam insulation used in over 70% of commercial roof construction,
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
SELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
Building Envelope. Overview
Building Envelope Overview The design of the building envelope involves many considerations Both indoor and outdoor materials must be durable, resistant to vandalism, easy to maintain, and affordable They
Polyurethane Products
Polyurethane Products ISSUE AX173 JULY 2011 Table of Contents Introduction Overview of U.S. Model Building Code Fire Performance Requirements Use of Amine Catalysts in Polyurethanes Manufacture Polyurethanes
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
Building Construction. Lightweight construction. Conventional Construction
Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.
5 Things. You Must Know. Before Buying. Radiant Barrier
Consumer Report: 5 Things You Must Know Before Buying Radiant Barrier 1 INDEX I: How Do Radiant Barriers Really Work pg 3 A: Understanding Heat Transfer pg 3 B: How Radiant Barriers Stop the Heat pg 4
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
A Kingspan Summary of a Building Science Corporation Report
Insulated Panels REVIEW & ANALYSIS OF EXTERIOR WALL ASSEMBLY PERFORMANCE A Kingspan Summary of a Building Science Corporation Report REVIEW & ANALYSIS OF EXTERIOR WALL ASSEMBLY PERFORMANCE Exterior Wall
DUCT SYSTEMS CHAPTER 6
CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing