1 Pharmaceutical PART 1 - GENERAL 1.01 OVERVIEW A. This document provides design and construction criteria for rooms/suites used for the compounding of non-hazardous and hazardous pharmaceuticals at (Owner). B. Refer to the D series Owner s Design Guideline Elements for requirements relating to mechanical, plumbing, and electrical work. Refer to Element D for mechanical requirements specific to pharmaceutical air handling distribution. C. Design shall be in accordance with The United States Pharmacopeia and The National Formulary (USP-NF) latest Edition, and General Chapters <797>, Pharmaceutical Compounding- Sterile Preparations (CSP) and <800>, Hazardous Drugs - Handling in Healthcare Settings. D. Design shall be in accordance with requirements of the following: 1. Texas State Board of Pharmacy. 2. The Facility Guidelines Institute, Guidelines for Design and Construction of Healthcare Facilities. 3. International Standards Organization, ISO Clean. 4. Code of Federal Regulations, Title 21, Part 211, Chapter 1, Subpart C, Sections 42, 44, 46, 48, and 52. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. Basic design for the compounding space shall consist of an ISO Class 5 Primary Engineering Control (PEC) located within an ISO Class 7 Buffer, IV, or Chemo room. Access to these rooms shall be through an ISO Class 7 Anteroom. B. Design shall allow a High Risk Level of compounding to be performed. C. Provision for an airlock (in addition to an Anteroom) may need to be made, depending on volume of compounding to be done. D. The PEC function is typically satisfied through the use of a five (5) foot or six (6) foot Class II B2 biological safety cabinet (BSC) where non-hazardous and hazardous compounds are involved. Use of another type PEC, such as a laminar airflow work station, requires approval of Owner s Project Manager. 1. Provide a closure panel between the top of PECs and the ceiling. 2. PECs shall be located out of traffic patterns and away from circulating air currents. ODG OF 7
2 Pharmaceutical 3. The following minimum clearances shall be provided around individual BSCs: a. Forty (40) inches by the full length of BSC, as work space, in front. b. Twelve (12) inches to nearest side wall or column. c. Eighty (80) inches to opposing wall. d. Five (5) feet to opposing bench tops or areas of occasional traffic. e. Forty (40) inches to bench tops at perpendicular walls. 4. Where rooms contain multiple BSCs, a staggered design arrangement is preferred. If offsetting of BSCs cannot be accomplished, the following minimum clearances shall be provided at the BSCs: a. Ten (10) feet, when facing each other. b. Forty (40) inches, when located next to each other along the same wall. c. Four (4) feet (in both directions), when located along perpendicular walls. 5. BSCs shall not be located near entry doors. If locating BSCs a substantial distance from in-use doors is not possible, a minimum distance of forty (40) inches at the side and five (5) feet at the front of the BSC to the nearest door jamb shall be provided. E. The following pressure relationships shall be maintained: 1. Non-hazardous clean (Buffer and IV) rooms: 0.01-inch to 0.03-inch positive air pressure with respect to their anterooms, with an operational design objective of 0.02-inch air pressure. 2. Hazardous clean (Chemo) rooms: 0.01-inch to 0.03-inch minimum negative air pressure with respect to their anterooms, with an operational design objective of 0.02-inch air pressure. 3. Anterooms: 0.02-inch minimum positive air pressure with respect to adjoining circulation/workroom spaces. 4. Pressure gauges shall be provided to continuously monitor the differential air pressure between the compounding rooms, Anteroom, and general environment outside the compounding area. F. Design conditions for Buffer, IV, and Chemo rooms shall be sixty eight (68) degrees Fahrenheit and fifty (50) sixty (60) percent relative humidity. G. Where swing type doors are provided, doors at negative pressure hazardous clean (Chemo) rooms shall swing into the room, and doors at positive pressure non-hazardous clean (Buffer and IV) rooms and Anterooms shall swing outward from the space. H. Non-hazardous and hazardous clean rooms and Anterooms shall be designed for thirty (30) air changes/hour. If recirculating BSC(s) are used, they may provide up to fifteen (15) of the ODG OF 7
3 Pharmaceutical total air changes/hour required in a room. BSC(s) shall not provide the sole means of exhaust in a space. I. A storage area separate from compounding rooms shall be provided for storage of selected hazardous pharmaceuticals. The space shall be designed with negative air pressure with respect to adjacent spaces, and with twelve (12) air changes/hour. J. Anteroom: 1. Provide a hands-free hand washing sink of adequate dimensions to allow for washing up to the elbow. Hot and cold water volume shall be adjustable, with hot water provided at a consistent one hundred (100) degrees Fahrenheit maximum. Locate the sink near the entry door when possible. 2. An eyewash located at the sink or an eyewash station shall be provided. 3. A bench and storage facilities for personnel garbing shall be provided. 4. Two distinct colors shall be provided at the floor to form a demarcation line between clean and dirty areas of the space. 5. A rectilinear footprint, without offsets, is preferred for its relative design advantage in achieving uniformity of air flow. 6. Space for package handling and storage shall be provided unless separate rooms are provided for these functions. K. Separate clean and dirty store rooms, receiving/break-down room, pump room, housekeeping, and workroom support areas shall typically be provided. These spaces are typically located outside the ISO Class 7 environment; however, requirements shall be confirmed with Owner s Project Manager and the Facility Program. 1. The receiving/break-down room shall comply with USP-NF Chapter <800>. 2. The pump room shall contain shelving for storage of miscellaneous items, as well as shelves for use in charging equipment. Provide a quantity of charging shelves and associated duplex electrical outlets based on equipment needs and requirements of the Facility Program, but not less than four (4) shelves, each with six (6) duplex outlets. 3. Space for a large container for dirty personal protective equipment shall be provided in the receiving/break-down room or dirty-storage room, if provided. L. The rooms/suites shall be designed to operate twenty four (24) hours/day, seven (7) days/week. M. Compounding rooms and associated Anterooms shall have a redundant (N+1) air handling unit source connected to a common air distribution system and building automation system (BAS) controls. This requirement may be modified to suit the Facility Program, which will be developed with participation by Pharmacy representatives, and confirmed by the Owner s Project Manager. ODG OF 7
4 Pharmaceutical 1. Provide a minimum of two BSCs in each compounding room. Overall design shall enable one or more BSCs to remain in use should the other(s) become inoperable. N. Provide emergency power, where available, to storage spaces and equipment as required to maintain proper temperature and humidity of critical pharmaceuticals. Confirm requirements with the Facility Program ARCHITECTURAL REQUIREMENTS A. Non-hazardous and hazardous clean rooms (Buffer, IV, Chemo) and Anterooms: 1. Walls: Gypsum board with epoxy paint finish. Provide integral cove trim (with approximately one inch radius) at intersection with the ceiling and at inside corners of walls. 2. Ceiling: Suspended, epoxy painted gypsum board. Provide gasketed access doors, as required, for all above-ceiling items requiring access. 3. Floor: Seamless sheet vinyl flooring with heat welded seams and smooth surface. Avoid flooring with hard-to-clean textured surfaces. 4. Base: Coved (radiused), seamless sheet vinyl integral with floor finish and flush with wall surface. Use of projecting trim at top of base is to be avoided. 5. Light fixtures shall be designed specifically for clean room application. Light fixtures shall be flush with the surface of the ceiling and have smooth lenses. Fixture perimeter and any openings shall be sealed. 1) Provide emergency power, where available, to selected light fixtures at spaces/equipment storing critical pharmaceuticals. Confirm requirements with the Facility Program. 6. All fixed work surfaces shall be stainless steel. 7. Buffer, IV, and Chemo rooms shall not contain sinks or floor drains. 8. Acoustical design for noise from building systems shall be NC 40, maximum. 9. Doors shall be forty two (42) inches wide with a vision panel, and have stainless steel hardware. a. Doors between the Anteroom and Chemo, IV, and Buffer room(s) shall be poweroperated, provided with emergency power, and be activated by a touch-free hand wave type sensor. 1) Aluminum sliding glass doors with seals/gaskets appropriate for maintaining air pressure differentials shall typically be provided. 2) Use of fiberglass swing doors may be considered in lieu of sliding type doors if it can be confirmed that the design (room shape, door separation, air device placement, etc.) will allow the room(s) to maintain proper air segregation/pressure differentials when doors are opened and closed. ODG OF 7
5 Pharmaceutical b. Doors to Anterooms shall be designed to interlock such that no two doors in the room can be open at the same time. 10. Provide windows set in stainless steel frames in the rooms for vision between each other, and from the adjacent work/support spaces. B. Typically provide pass-through chambers to minimize the need for movement between working areas and Chemo, IV, and Buffer rooms. Chambers shall be a minimum of eighteen (18) inches by eighteen (18) inches by eighteen (18) inches in size and have double interlocked doors to maintain air pressure differentials AIR DISTRIBUTION REQUIREMENTS A. Refer to Owner s Design Guideline Element D for additional information/requirements. B. HEPA filters are to be located at ceiling level, and installed with provisions to facilitate testing and recertification from inside the room. Provide gasketed ceiling access doors as required. C. Air distribution grilles at non-hazardous and hazardous clean rooms (Buffer, IV, Chemo) and Anterooms: 1. Locate HEPA-filtered supply air grilles and return/exhaust grilles so as to avoid the formation of areas of relatively low, or no air movement within the room, and to create a general top-down dilution of the area air. Typically, locating supply air at the ceiling and return/exhaust air at walls six (6) inches from the floor, with adequate dispersion of the various types of devices around the room, is required to achieve this goal. Ceilingmounted return/exhaust air devices shall not be used. a. Downward, unidirectional air flow for supply air is preferred, provided an overall laminar flow design, without turbulence, can be achieved. b. Supply air grilles shall not be located directly over, or at the front of BSCs. 2. Proper laminar, uniform air circulation within the room shall be confirmed through a smoke visualization testing method prior to Substantial Completion. D. Where a BSC is exhausted to the exterior, the fan shall be dedicated and provided with emergency power. E. Differential air pressure, temperature, and humidity of non-hazardous and hazardous clean rooms (Buffer, IV, Chemo) and Anterooms shall be monitored through tie-in to the BAS. Status displays shall be located outside the entrance door to each room. F. Provide an exhaust adjacent to the compressor for each refrigerator located in a negative pressure clean (Chemo) room. G. Air flow at BSCs shall be monitored through tie-in to the BAS. H. Low-mounted exhaust and return air grilles shall be installed in rooms with PECs to allow for functionality in the event a BSC becomes inoperable. ODG OF 7
6 Pharmaceutical 2.04 SECURITY A. Access to the Pharmacy suite, which includes compounding areas and their support spaces, shall be through secured doors with keyed entry and card access control hardware. B. Provide video coverage at locations where pharmaceuticals are mixed, dispensed, and distributed, and at locations approved by the Owner s Project Manager and UTPD. Refer to Owners Design Guideline Element D5038 for additional information EQUIPMENT AND FURNISHINGS A. Provide standard refrigerators, ultra-low refrigerators, rolling shelving units, and movable work stations as required by the Facility Program. 1. All refrigerators and freezers shall be provided with emergency power and be monitored through the BAS. 2. Additional equipment, such as BSCs may be provided with emergency power depending on Facility Program requirements. B. All carts, shelving, movable work stations, and similar items within non-hazardous and hazardous clean rooms (Buffer, IV, Chemo) and Anterooms shall be provided with casters. C. Automated systems to be supported include Cato, Pyxis, and Barcode scanning for inventory receipt. 1. Provide data connections and electrical power to equipment as required by the Facility Program. 2. Pyxis equipment shall be provided with emergency power. D. The status board requirement is to be satisfied through use of large-format televisions mounted to the walls. E. Trash bins, when provided, shall have lids. F. All surfaces of fixtures, shelving, casters, and cabinets/work stations, etc. shall be smooth, impervious, and without cracks, crevices or other design which would make cleaning and disinfecting difficult. PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. Obtain approval from Owner s Project Manager/Planner Designer for all finish schedules prior to issuance of Construction Documents. B. All finishes should reflect the standard finish application for the specific building in which the pharmaceutical compounding rooms and support spaces are located. ODG OF 7
7 Pharmaceutical C. Include general notes which require testing of components and systems for proper functioning at the earliest opportunity during construction, and prior to any testing required to attain Substantial Completion. Smoke visualization testing shall be conducted at intervals, when practical, and shall be observed by Owner, at its option. PART 4 - PRODUCTS 4.01 GENERAL A. For all projects (renovation and new), refer to Owner s Interior Finishes Standards. These are available on the Owner s Design Guidelines website: B. For renovation projects, refer to Owner s Master Construction Specifications. These are available on the Owner s Design Guidelines website: PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Reviser Initial Adoption of Element Rev. 1 Rev. 2 Rev. 3 Rev. 4 Rev. 5 END OF ELEMENT ODG OF 7
Hazardous Drug. Cleanroom. Standards
Hazardous Drug Cleanroom Standards Module 3 Table of Contents Section A... 1 A.1 International Standards Organization (ISO) Classifications... 1 A.2 Hazardous Drug Cleanroom and Anteroom... 1 A.2.1 Location
NEW YORK. Downloaded 01.15.11
Nurses Station & Resident Call System PRE 1975: NEW YORK Downloaded 01.15.11 713 1.3 Nursing units. Each nursing unit shall include the following service areas and shall meet the following minimum requirements:
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Sample Pharmacy CLEANING AND SANITIZING PROCEDURE P-304.1
P-304.1 1.0 Definition and Purpose: To standardize and define the process by which the controlled Cleanroom environments (ISO Class 5, 7, and 8) and the general pharmacy prep area is cleaned, disinfected,
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
HEALTH FACILITY CHECKLIST SECTION 1226 [OSHPD 3] CLINICS 1226.6 PRIMARY CARE CLINICS
Compliance Checklist: [OSHPD 3] Primary Care Clinics Page 1 of 7 HEALTH FACILITY CHECKLIST SECTION 1226 [OSHPD 3] CLINICS 1226.6 PRIMARY CARE CLINICS Primary Care Clinics are Health Facilities licensed
USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC
USP Cleanroom Design and Environmental Monitoring Andrew King, USP Specialist CETA Member RCCP-SC Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Laboratory Design & Construction Guidelines
Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department
PUBLIC RESTROOMS, DESIGN INTENT
PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes
Base Cabinet with Self-storing Folding Doors and Floor
Usable Kitchens When designing a kitchen for use by persons with mobility impairments, especially those who use wheelchairs, careful layout of the kitchen is crucial to maintaining accessibility. People
Montgomery County Health Department Mobile Food Guidelines. Definitions
Montgomery County Health Department Mobile Food Guidelines Definitions Commissary A permitted food establishment to which a mobile unit returns on a daily basis for such tasks as discarding liquid and/or
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection A wide range of products to meet the needs of transferring animals, operators,
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
FLOOR MATERIALS FOR RETAIL FOOD FACILITIES
FLOOR MATERIALS FOR RETAIL FOOD FACILITIES General Appropriate floor, wall, and ceiling finishes promote good sanitation. Sanitation is an important component of public health protection. Disease outbreaks
Automatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 [email protected] Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
Laminar Flow Cabinets
Laminar Flow Cabinets The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. 24 36 48 Simple, Effective Protection for Samples and Work Processes, Uncompromised Performance, Economical
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
AMENDED January 27, 2015
Proposed Language To Amend 1735 in Article 4.5 of Division 17 of Title 16 of the California Code of Regulations to read as follows: 1735. Compounding in Licensed Pharmacies. (a) Compounding means any of
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No
patient safety A commitment to GE Healthcare
GE Healthcare A commitment to patient safety GE Healthcare is committed to providing radiopharmaceuticals that are compounded and dispensed accurately. Quality assurance and patient safety are the cornerstones
LAMINAR FLOW CABINETS
LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
Alpha System ADAPTABLE KEWAUNEE LABORATORY FURNITURE. encouraging new discovery
Alpha System ADAPTABLE LABORATORY FURNITURE KEWAUNEE encouraging new discovery Alpha 6 partition modules with Kemresin worktops. Minneapolis, Minnesota Alpha 6 partition modules with Alpha overhead service
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: www.cleanroom-solutions.co.uk
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: Introduction Cleanroom Solutions Ltd has a wealth of experience together with a solid track record in the
MISSISSIPPI. Downloaded January 2011
MISSISSIPPI Downloaded January 2011 101.08 Dietitian. The term dietitian shall mean a person who is licensed as a dietitian in the State of Mississippi, or a Registered Dietitian exempted from licensure
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus
Everything you want to know about USP 797
Everything you want to know about USP 797 Dr. Linda D. Lee Director of Operations Waste Management Healthcare Solutions September. 22, 2009 Goals High level understanding of USP 797 Who does it apply too
Laboratory Biosafety Level 3 Criteria
Laboratory Biosafety Level 3 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Section IV Biosafety Level 3 (BSL-3): Biosafety Level 3 is applicable to clinical, diagnostic,
Irvinton Village Apartments 2901 Fulton Houston, Texas 77009 Houston Housing Authority J. Allen Management Managing Agent
Irvinton Village Apartments 2901 Fulton Houston, Texas 77009 Houston Housing Authority J. Allen Management Managing Agent Scope for Irvinton Village Unit #512 Overall Scope: Demolition, Renovation, and
WASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST
0 RIVERSIDE DRIVE, OTTAWA, ON A0.0 COVER SHEET / DRAWING LIST A0. LEGEND AND GENERAL NOTES A0. GENERAL NOTES A0. GENERAL NOTES A0. TYPICAL WASHROOM WALL/SINK SECTION A0. DETAIL - CONTROL JOINT A0. DETAIL
GenStore Archive Cabinet
GenStore Archive Cabinet Setup and Maintenance Manual Version A April 2014 Two GenStore Archives shown mounted on optional table stand. 2 Contents Getting Started... 4 Using this Manual...4 Safety Precautions...4
Design, Operation and Management of GTP/GMP Cell Engineering Facilities
Design, Operation and Management of GTP/GMP Cell Engineering Facilities Scott R. Burger, MD Advanced Cell & Gene Therapy BFDA 2007 International Symposium on Regulation of Human Cell and Tissue- Based
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN Application 1 The first step in selecting an industrial oven is defining the required heat application that your oven will be used for. Heat processing is extensively
APPLICATION FOR FITOUT OR PLAN ASSESSMENT UNDER THE FOOD ACT 2001
Health Protection Service Howard Florey Centenary House, 25 Mulley Street, Holder ACT 2611 Locked Bag 5005, Weston Creek ACT 2611 Phone: (02) 6205 1700 Fax: (02) 6205 1705 Website: www.health.act.gov.au
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
OWNER S MANUAL FOR THE PATIO SAUNA
OWNER S MANUAL FOR THE PATIO SAUNA CONGRATULATIONS! You are about to install the world s leading portable sauna. No other sauna manufacturer can offer you the features and owner support that Saunatec,
Page 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit
COMPLIANCE CHECKLIST Page 1 of 6 > Long Term Care Facility - Nursing Unit The following checklist is for plan review of new long-term care facilities and new additions to existing long-term care facilities.
REQUIREMENT 5. Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations
Chapter Five: REQUIREMENT 5 Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations 5...covered multifamily dwellings with a building entrance on an accessible
SINKS / DISHMACHINES. Food Preparation Sink
ENVIRONMENTAL HEALTH DIVISION 2120 Diamond Blvd., Suite 200 Concord, CA 94520 Phone: (925) 692-2500 Fax: (925) 692-2505 www.cchealth.org/eh/ SINKS / DISHMACHINES Food Preparation Sink A separate stainless
CLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
Rules for Compounded Sterile Preparations (CSPs)
Introduction: Despite the attention in this document to describe the provision, maintenance, and evaluation of air quality, the avoidance of direct or physical contact contamination is paramount. Since
A1.5 Classroom Standards
A1.5 Classroom Standards Note: The following standards have been developed and adopted by KU's Instructional and Mediated Spaces Committee (IMSAC), which includes representatives from DCM, Instructional
Hospital Pharmacy Automation: Drug Storage and Retrieval
WHITE PAPER USP CHAPTER 797 CLEAN ROOM APPLICATION Hospital Pharmacy Automation: Drug Storage and Retrieval The technical information regarding USP Chapter (797) and the performance of the Swisslog device
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
LITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE -
The original section of this building was constructed in 1941. The exterior walls are built of good quality stone. In the early 1980 s a similar addition was added to the north elevation. The exterior
Procedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
LAMINAR AIRFLOW EQUIPMENT CLASS I BIOLOGICAL SAFETY CABINETS BIOLOGICAL ENCLOSURES
LAMINAR AIRFLOW EQUIPMENT CLASS I BIOLOGICAL SAFETY CABINETS BIOLOGICAL ENCLOSURES NuAire, Inc. 2100 Fernbrook Lane Plymouth, MN 55447 U.S.A. 763.553.1270 WWW.NUAIRE.COM Sustainability We at NuAire continually
Summit Series Single Section and Double Section Homes
Single Section and Double Section Homes SM-01 All New 20 Wides Now Available! SM-08 Units shown with optional features SM-01-4814 42 Bedrooms 41 Bathrooms 648 Sq. Ft. SM-01-5214 42 Bedrooms 41 Bathrooms
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
Refrigerators - Freezers. Ekofrigolab & Ekobasic Series
Refrigerators - Freezers Ekofrigolab & Ekobasic Series Angelantoni Life Science S.r.l. manufactures a wide range of refrigerated cabinets and combined refrigerator/freezer cabinets. We offer high reliability
SECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
Schedule of Maintenance Fees
Schedule of Maintenance Fees Effective July 1, 2015 It is the policy of the Housing Authority of Murray not to charge for NORMAL wear and tear. However, the Housing Authority reserves the right in every
Stainless Steel Worksurface 3 Feet Hood A10-WS-PR3 A10-WS-SR3 4 Feet Hood A10-WS-PR4 A10-WS-SR4 6 Feet Hood A10-WS-PR6 A10-WS-SR6.
Product Sampler #1 Laminar Flow Hoods / Laminar Flow Cabinets: 1- Benchtop Vertical Laminar Flow Hoods- Air Recirculation Available s: Clean Bench Class 100 Bench-top Vertical Laminar Flow Hoods with Air-recirculation
Preventative Maintenance
Preventative Maintenance Safety Committee To have a preventative maintenance plan, you should have a Safety Committee. Designate persons involved with day to day operations and grounds control. Use your
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive
WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive Warranties Time Limits for Reporting Manufacturer s
TABLE OF CONTENTS CHAPTER 14 TELEPHARMACY RULES AND REGULATIONS
TABLE OF CONTENTS CHAPTER 14 TELEPHARMACY RULES AND REGULATIONS Section 1. Authority 14-1 Section 2. Definitions 14-1 Section 3. Licensing of Facilities 14-1 Section 4. Minimum Structural, Security and
MUELLER FALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Mueller s falling film chiller is to cool food-grade
CLEAR-DIVISIONS APERTO
CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
47 Levencourt Way London SW8 1HR. Tenant: Eric Stevenson Prepared for: Elizabeth Collins
47 Levencourt Way London SW8 1HR Prepared by: John Smith Date of Inspection: 16/03/12 Tenant: Eric Stevenson Prepared for: Elizabeth Collins Inventory & Check In Report Table of Contents Schedule of Conditions...
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Biosafety Level 2 (BSL-2) Safety Guidelines
BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff
15430 SAFETY SHOWERS AND EYEWASHES
15430 SAFETY SHOWERS AND EYEWASHES PART 1: GENERAL 1.01 RELATED SECTIONS 01005 - ENVIRONMENTAL HEALTH 11600 LABORATORY EQUIPMENT 15020 - LABORATORIES 15130 - PIPING SPECIALITES 15400 - PLUMBING 15420 -
Series 18 Pass Thru Air Lock Cleanroom Entry System
OPERATION & MAINTENANCE INSTRUCTIONS FOR Series 18 Pass Thru Air Lock Cleanroom Entry System SOLUTIONS BUILT TO YOUR SPECIFICATIONS 8605 Wyoming Ave. N. Minneapolis MN 55445 fax: 763.425.2004 e-mail: [email protected]
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
REFRIGERATION. Standard Features & Accessories. Model Options. Built-In 30 W. Full-Height Wine Cellar. All models include. VCWB300 Professional
Standard Features & Accessories All models include Capacity accommodates up to 150 full-size bottles o 84 H./24 D. Exclusive TriTemp storage system o Three independent temperature zones o Settings are
GUIDELINES FOR OPERATORS OF MOBILE FOOD BUSINESSES: DESIGN, CONSTRUCTION
Southern Drive, Busselton WA 6280 All Correspondence to: The Chief Executive Officer, Locked Bag 1, Busselton WA 6280 Ph: (08) 9781 0444 Fax: (08) 9752 4958 Email: [email protected] Web: www.busselton.wa.gov.au
COST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space)
COST OF WORK FORM All costs shown are estimates using base grade materials, taxes, and labor. For houses where a higher quality is indicated, the costs should be increased for work requiring upgraded materials.
The following standard practices, safety equipment, and facility requirements apply to BSL-1:
Laboratory Biosafety Level Criteria Biosafety Level 1 Section IV Laboratory Biosafety Level Criteria The essential elements of the four biosafety levels for activities involving infectious microorganisms
French Door Refrigerator E23BC78IPS professional series
French Door Refrigerator E23BC78IPS professional series 23 CU. FT. COUNTER-DEPTH FRENCH DOOR REFRIGERATOR Custom Temp Drawer Enjoy the ultimate in versatility with 9 preset selections including White/Sparkling
Case Studies Illustrating Acoustic Design Guidelines for HVAC Systems in Schools
Cleveland, Ohio NOISE-CON 2003 2003 June 23-25 Case Studies Illustrating Acoustic Design Guidelines for HVAC Systems in Schools Robert M. Lilkendey, Siebein Associates, Inc. 625 NW 60 th Street, Suite
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES In order to provide fair and consistent maintenance service to all University faculty, staff and students, a work priority system
General Purpose Laminar Flow Cabinets, Horizontal and Vertical
24 36 48 60 72 96 The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. VLF-48 Provides reliable protection for samples and work processes for a multitude of applications. p:2 Product
Spetec. Laminar Flow Box. Portable Clean Room Technology
Spetec Laminar Flow Box Portable Clean Room Technology 1 Fundamentals Portable Clean Room Technology Laminar Flow The basis for the development of the clean room technology was first established in the
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
CLEAR-DIVISIONS VARIOFOLD
CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the
Freezers - Ultrafreezers. Platilab & Irilab Series
Freezers - Ultrafreezers Platilab & Irilab Series PLATILAB: top security and performances with reliable temperature control. IRILAB: combining the high reliability of PLATILAB with the possibility to store
Hamilton-Wentworth Catholic District School Board Event Listing By Ascending Event Year
Hamilton-Wentworth Catholic District School Board Event Listing By Ascending Event Year Printed On: 2003/04/03 St Patrick CES, 7932 Study [03.3-050 Plumbing Piping Systems] Study condition, remaining service
GETINGE GEW 2100LS CAGE AND RACK WASHER PREVENTING CONTAMINATION IN ANIMAL CARE
GETINGE GEW 2100LS CAGE AND RACK WASHER PREVENTING CONTAMINATION IN ANIMAL CARE GETINGE GEW 2100LS Cage and Rack Washer - Preventing contamination in animal care 3 CLEAN CAGES, RACKS AND BOTTLES WITH
Seattle Tacoma International Airport Restroom Standards
Seattle Tacoma International Airport Restroom Standards Last Updated July 10, 2015 Contents Introduction... 2 General Restroom Features:... 2 Mock up During Design... 2 Doorless Entry... 2 Entry Identification
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
Integral Kit Instructions
Integral Kit Instructions For Fisher & Paykel Cabinet widths of 525, 635, 680, 790 mm wide For curved door Models Series B, C, D & G Manual 814980 Updated August 2008 IMPORTANT If your refrigerator has
GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT
GUIDELINE FOR THE DESIGN, CONSTRUCTION AND RECONSTRUCTION OF A FOOD HANDLING ESTABLISHMENT This guideline provides general information to anyone proposing to construct a new food handling establishment,
17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
Fume Hood Questions and Answers
Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
Judy P. Rosenstreich, Senior Policy Advisor
September 7, 2012 Department of Mental Health Redstone 26 Terrace Street Montpelier, VT 05609-1101 Attention: Judy P. Rosenstreich, Senior Policy Advisor Regarding: Guidelines Conformance Assessment Final
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D.
3. It is recommended that the water supply into the facility can be obtained from two (2) separate water lines if possible.
PART VIII SANITATION AND MEDICAL WASTE 132 SANITATION 132.01 Water Supply. 1. If at all possible, all water shall be obtained from a public water supply. If not possible to obtain water from a public water