Tenant Criteria Manual Architectural

Size: px
Start display at page:

Download "Tenant Criteria Manual Architectural"

Transcription

1 Water Tower Place Tenant Criteria Manual Architectural 835 North Michigan Chicago, IL September 2008

2

3 TABLE OF CONTENTS INTRODUCTION Building Description...1 Tenant Design Criteria Introduction...2 Directory...3 Location Map...4 PLANS Ground & Mezzanine Floor Plans...5 Second & Third Floor Plans...6 Fourth and Fifth Floor Plans...7 Sixth & Seventh Floor Plans...8 TENANT SUBMISSIONS & PERMIT REQUIREMENTS Design Submissions...9 Building Code Information...11 Required Permits & Inspections...12 ARCHITECTURAL DESIGN CRITERIA Architectural Drawing Requirements...13 Landlord Supplied Architectural Items...14 General Design Criteria...17 Structure...21 Lighting...22 Storefront Design Criteria...24 Display Zone...28 DIAGRAMS Store Design Plan Diagram...30 Storefront Criteria...31 Storefront Section...32 Storefront Section at Well...33 Storefront Detail Section...34 Storefront Reflected Ceiling Plan...35 Typical Neutral Pier Detail...36 Neutral Pier Detail at Existing Store...37 Neutral Pier Detail at a Corner...38 Neutral Pier Detail at Corridor...39 Typical Neutral Pier Elevations...40 Typical Neutral Pier Elevations...41 Tenant Storefront at Mall Column...42 Typical Tenant Demising Wall...43 Tenant Service Corridor Door...44 Construction Barricade...45 SIGNAGE DESIGN CRITERIA Signage Submittal Requirements...46 Tenant Signage...47 Blade Sign Elevation...51 Blade Sign Detail...52 Water Tower Place i

4 TABLE OF CONTENTS MECHANICAL DESIGN CRITERIA HVAC Drawing Requirements...53 Tenant Work...54 Tenant VAV Box Detail...57 ELECTRICAL DESIGN CRITERIA Electrical Drawing Requirements...58 Electrical Construction Requirements...59 Electrical Service Diagram...61 Emergency Lighting Diagram...62 PLUMBING DESIGN CRITERIA Plumbing Drawing Requirements...63 Public and Employee Toilets...63 Work by Tenant...64 Floor Penetration Details...67 Plumbing Riser Diagram...68 Water Meter Diagram...69 Dishwasher Moisture Eliminator...70 FIRE PROTECTION DESIGN CRITERIA Sprinkler System Design Criteria...71 Sprinkler Drawing Requirements...73 Building Fire Riser Diagram...76 Equivalent Lengths...77 Tenant Sprinkler Water Supply Data...80 Tenant Sprinkler Efficiency/ GPM Supply Curve...83 Tenant Sprinkler Pressure/ GPM Supply Curve...84 Tenant Sprinkler Riser Diagram Tenant Sprinkler Riser Diagram Tenant Sprinkler Riser Diagram Sprinkler Riser Number for Tenant Spaces..88 FIRE ALARM DESIGN CRITERIA Existing Fire Alarm System...89 Emergency Message System...89 Future Alarm System...89 CONSTRUCTION REQUIREMENTS Preconstruction Meeting Site Access General Contractor Requirements INSURANCE LANDLORD PUNCH LIST Water Tower Place ii

5 INTRODUCTION Building Description Water Tower Place is a mixed-use, cast-in-place concrete mega-structure built in It combines eight floors of retail shopping, an office floor, the Drury Lane Theatre, The Ritz-Carlton Hotel and some of Chicago s premier residential condominiums. Located diagonally across Michigan Avenue from Chicago s Historic Water Tower, Water Tower Place is the best-known shopping destination in the metropolitan area. It is the intent of these criteria to permit a wide range of design opportunities, to encourage excitement in the retail environment and to maintain the high standards of retail design and construction that have been a hallmark of Water Tower Place. The building includes a diverse mix of Tenants that combine an entertainment factor as part of their overall appeal. Minimum restraints are imposed on the Tenant s creativity and imagination. However, the Landlord reserves the right to reject any Tenant design proposals in part or in whole if it is determined that they would not contribute to the design quality of Water Tower Place Vision of the Design Team Exciting and unique storefronts and merchandising designs create a shopping and entertaining environment that attracts customers and results in increased sales. Tenants are encouraged to create innovative and dramatic storefronts, shop interiors and graphics. Classic interior materials of marble, chrome and brass create an ideal, neutral palate for great store design. Water Tower Place 1

6 INTRODUCTION Tenant Design Criteria Manual Introduction The requirements of this Manual are referenced and included in Tenant leases, and has been prepared to guide you, as well as your architect, store designer, and contractor in guiding the expediting the design and construction of your lease premises. This information describes the Landlord s obligations, the Tenant s design responsibilities, and the Contractor s requirements. General Design Criteria pertaining to storefront design, materials, colors, signage, interiors and lighting must be addressed by all Tenants. In addition, stores must adhere to specific criteria which are determined by their location and their specific architectural context. In this way, each store will be reviewed on an individual basis in context to ensure diverse and creative design solutions. Through the criteria in this Manual, the Landlord has set certain quality and design standards, which will help the Tenants to create stores that are compatible with the overall design quality of Water Tower Place. The General Growth encourages designs that shall add richness to the built environment. Nationally or regionally recognized merchants may creatively interpret these criteria as it applies to their prototype design. The Tenant Print Package ( Print Package ) consists of: Tenant Design Criteria Manual Exhibits A, A-1, B or Lease Outline Drawing (L.O.D.) Record drawings of the previous Tenant build-out (if available) The lease agreement requires that all Tenant plans be prepared by an architect and engineer(s) licensed by the State of Illinois. Tenants are encouraged to retain an architect familiar with the City of Chicago s Self Certification Process. Contact the Tenant Coordinator for information for contacts of firms that can offer this service. Note: This Manual is also available on General Growth s web site at Water Tower Place 2

7 INTRODUCTION Directory Water Tower Place 835 North Michigan Avenue Chicago, Illinois Landlord General Growth Properties, Inc. 110 North Wacker Drive Chicago, IL (312) Operations Manager General Growth Properties, Inc. Suite 987W 845 North Michigan Avenue Chicago, IL (312) (312) Fax Tenant Coordination General Growth Properties, Inc. 110 North Wacker Drive Chicago, IL (312) (312) Fax Building Engineer Johnson Controls, Inc. 845 North Michigan Avenue Chicago, IL (312) (312) Fax Building Security (312) Building Dock Manager (312) Building Permits City of Chicago Department of Buildings 9th Floor 121 North LaSalle Street Chicago, IL (312) Health Department City of Chicago Department of Public Health Food Protection Division 2133 West Lexington Chicago, IL (312) (312) Fax Construction Inspections City of Chicago Department of Buildings 120 North Racine Chicago, IL (312) nd Ward Alderman Brendan Reilly Suite West Superior Chicago, IL (312) Electric Utility ComEd Customer Care Center P.O. Box Chicago, IL Gas Utility Peoples Gas 130 East Randolph Drive Chicago, IL (866) Building Telephone Service AT&T 219 South Dearborn Chicago, IL (312) Water Tower Place 3

8 INTRODUCTION Location Plan Water Tower Place 4

9 INTRODUCTION Ground Floor & Mezzanine Plans Water Tower Place 5

10 INTRODUCTION Second and Third Floor Plans Water Tower Place 6

11 INTRODUCTION Fourth and Fifth Floor Plans Water Tower Place 7

12 INTRODUCTION Sixth and Seventh Floor Plans Water Tower Place 8

13 TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS Design Submissions Prior to starting construction, the Tenant shall prepare and submit a preliminary design package (2 sets) and subsequently a final submission package (3 sets) for review and approval. Submissions are to be made to General Growth Tenant Coordination. Preliminary Design Submission The preliminary design submission should communicate the design intent to the Tenant Coordinator. Drawings submitted shall include a comprehensive floor plan, ceiling plan, storefront elevations, interior elevations and necessary wall sections. Color renderings, representative photos and material sample boards should be prepared. Documents in compliance with the Tenant Design Criteria will have the best opportunity for a prompt review and approval returned to the Tenant. Final Submission The final submission shall consist of complete project construction drawings and specifications. Reference the Architectural and Engineering Design Criteria for drawing requirements. Final Design Approval Landlord, upon final review and approval of the final submission, shall forward to the Tenant (1) one copy of the documents with the Landlord s comments and conditions of approval in paper or digital format. Tenant s contractor shall have one (1) Landlord-approved set at the job site at all times and may not commence work until said approved plans are physically within the demised premises. Code Requirements It is the Tenant s responsibility to ensure compliance with all relevant codes, obtain all approvals, acquire all permits, and pay all fees in connection therewith. Landlord s review of Tenant submittals does not signify review and/or approval of the submittals for code compliance. It is the Tenant and/or Tenant s architect who shall be solely responsible for compliance with applicable code requirements. Additional Submittals Fire Protection Submittals Reference the Fire Protection Design Criteria for sprinkler shop drawing requirements. The sprinkler contractor is required to submit sprinkler shop drawings to the Operations Manager and to the Landlord s insurance underwriter for review and approval. Drawings and hydraulic calculations must be sealed and signed by a registered fire protection engineer from the State of Illinois. HVAC Submittals Reference the HVAC Design Criteria for testing & balancing and exhaust submittals. Signage Submittals Reference the Signage Design Criteria for sign submittals for signage shop drawings and Blade sign artwork. Water Tower Place 9

14 TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS Construction barricade graphics must be submitted to the Operations Manager for approval prior to application. All Tenant improvements are subject to the Landlord s approval and shall conform to all design criteria and lease agreement. No deviation from the approved drawings will be permitted. Any deviation shall be resubmitted for Landlord approval. Tenants should discuss specific thoughts about their design concept and raise any questions about these criteria with the Landlord s Tenant Coordinator before beginning preliminary design work. Any requested deviations from the Tenant Design Criteria must be approved by the Landlord s Tenant Coordinator. Each Tenant is required to retain an architect registered in Illinois to prepare design and construction documents. It is imperative that all the requirements outlined above be strictly adhered to by the Tenant and Tenant s architect. Failure to do so will only result in unnecessary and costly delays in the approval of drawings. Design Submissions are to be sent to: General Growth Properties, Inc. Attn: Water Tower Place Tenant Coordination 110 North Wacker Drive Chicago, IL Information to be included: Store Name & Space No. Tenant Name and Contact Information (Mailing address, telephone, fax and ) Architect and Contact Information Water Tower Place 10

15 TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS Building Code Information It is the sole responsibility of the Tenant s architect, engineer(s) and general contractor to comply with all applicable federal, state, and local codes and ordinances for their occupancy type. Height - 74 Story Mixed Use 8 story Retail with Mezzanine 1 story Office 20 story Hotel 40 story Condominiums 5 story Mechanical Gross Building Area - Retail Ground Floor 87,754 square feet Mezzanine- 68,994 square feet Floor 2-110,179 square feet Floor 3-111,076 square feet Floor 4-111,238 square feet Floor 5-110,299 square feet Floor 6-111,242 square feet Floor 7-111,105 square feet Floor 8-113,772 square feet ` Total 935,659 square feet Type of Construction Type 1A, Fire Resistive, Fully Sprinklered Primary Occupancy Classification Mercantile - Group F Required Occupancy Separation / Tenant Separation Mercantile to Assembly - 2 hour Tenant to Tenant / Tenant to Corridor - 2 hour Applicable Codes: Current City of Chicago Building Code (Issued Annually), including Energy Conservation Ordinance Current Chicago Zoning Ordinance (Issued Annually) 1997 Illinois Accessibility Code 2005 Illinois Plumbing Code Illinois Energy Conservation Code (IBC 2006) 2000 National Fire Protection Association (NFPA 1) 2006 Life Safety Code Water Tower Place 11

16 TENANT DESIGN SUBMISSION AND BUILDING PERMIT REQUIREMENTS Required Permits & Inspections A building permit issued by the City of Chicago must be presented to the Operations Manager prior to work start. It is the responsibility of the Tenant to obtain required approvals from the City of Chicago and to pay for and secure all applicable permits. City website: City of Chicago Self Certification Permit Process The City of Chicago Department of Buildings (DOB) has established a program to expedite the permitting process for Tenant Improvement Projects. The majority of retailers can benefit from the program. Major features and requirements of the Self Certification Program are: Project must meet DOB Self Certification eligibility requirements. Owner/Tenant, design professionals and the general contractor certify that the Project meets applicable codes and so only a cursory review of the documents is performed. Design professionals must be certified by DOB for the Commercial Self Certification Program. A list of certified architects is available on the City website. Permit application information must be entered online. Application information includes the General Contractor and all major sub-contractors; all must be licensed to perform work in the City of Chicago. The request for a permit Intake Appointment is submitted via fax. The meeting date is usually within two to four weeks after the application is received. Zoning review and approval is required before the Intake Appointment. Written aldermanic acknowledgement is required for the issuance of a permit without a mandatory ten business day review period after the Intake Appointment. Upon submission of the permit application and all required documents, a permit is usually issued within one (1) week. Chicago Energy Conservation Code Compliance with the City of Chicago Energy Conservation Code is mandatory. Plans submitted for permit must include a compliance statement by a City of Chicago Registered Energy Professional. The Chicago Energy Conservation Code (Chapter 18-13) is published as a part of the twovolume Chicago Building Code. The code and a list of Registered Energy Professionals are available at the City website at at the Department of Construction and Permits. Other Permits The City of Chicago requires sign permits for signs visible to the public. These must be obtained through a City-licensed Sign Contractor. Note that documents for all Tenant store signage must be submitted to the Landlord for review; approval must be issued prior to sign installation. Construction Inspections It is the responsibility of the Tenant s general contractor to arrange all field inspections required by the City of Chicago Department of Buildings. Final inspections and the issuance of an Occupancy Certificate are required for projects exceeding $400,000 in construction cost. Water Tower Place 12

17 ARCHITECTURAL DESIGN CRITERIA Architectural Drawing Requirements The following is a list of design information required to expedite plan approval by the Landlord. We urge you to read this Manual in its entirety in order to fully understand the requirements needed to generate an acceptable set of construction documents. Lease Outline Document Landlord will provide Tenant with a Lease Outline Document (LOD) or Lease Exhibits. The Tenant is responsible to field verify the dimensions of the space and other existing conditions prior to starting construction documents. Contact the Operations Manager to gain access to the space. Drawing and Specification Submission Requirements Tenant s working drawings and specifications shall be prepared in strict compliance with these design criteria. Drawings and specifications shall be submitted to Landlord for approval in the form of three (3) sets of prints and specifications. Working drawings and specifications shall include, but not be limited to the following: Note that scales indicated are minimums. Key plan showing location of the premises. Floor plan at 1/8 = 1-0. Furnishings, fixtures and equipment plan at 1/8 = 1-0. Floor finishes plan at 1/8 = 1-0. Reflected ceiling plan at 1/8 = 1-0. Overall sections at 1/4 = 1-0. Plan, elevations, and section of storefront at 1/4 = 1-0. Interior elevations at 1/4 = 1-0. Full sections of types of partitions used at 1-1/2 = 1-0. Descriptive drawings of store display fixtures. Details of storefront at 1-1/2 = 1-0. Door schedule with jamb details at 1-1/2 = 1-0. HVAC, electrical, sprinkler, and plumbing plans at 1/8= 1-0. Mechanical details at 1-1/2 = 1-0. Lighting plan at 1/8 = 1-0. Emergency & exit lighting plan at 1/8 = 1-0 (required for DCAP permit review). Electrical details, fixture schedules, and one-line electrical load tabulations. Structural plans (if required) at 1/8 = 1-0. Load tabulations and calculation if structural work is included. Specifications covering all of Tenant s work, including, but not limited to, architectural, HVAC, electrical, plumbing, fire protection; and other plans and specifications as may be required by the local fire and building authorities or other governing bodies. Water Tower Place 13

18 ARCHITECTURAL DESIGN CRITERIA Landlord Required Notes The following notes must appear on the cover sheet of all Tenant final construction documents: The Tenant s general contractor must conduct a pre-construction meeting with the General Growth Properties, Inc. Operations Manager prior to work start. The Tenant s contractor shall perform first-class workmanship. Acceptance of workmanship is contingent upon Landlord approval. The Tenant s contractor will repaint and/or repair Landlord s property (bulkhead, neutral piers, rear corridor, etc.) damaged during Tenant improvement. All materials used in the construction of Tenant space must be asbestos free. Supports for Tenant construction must not be connected to any of the Landlord s electrical, plumbing, fire protection piping or mechanical equipment. Any penetration or modifications to structural concrete deck must be coordinated and approved by the General Growth Properties, Inc. Operations Manager prior to performing work. All slab penetrations must be sleeved, sealed liquid tight and firestopped. No trenching of structural slabs (i.e. for electrical conduit, etc.) is allowed. Waterproof membrane water tested to be performed; approval of the test by the Operations Manager or Building Engineer is required. Tenant storefront must be self-supported. Storefront cannot be suspended from the building structure. Demising partitions must be of 2-hour fire-rated construction, taped and sealed airtight to deck above. The ceiling systems are to be constructed using materials with class A Fire Rating, but only require fire rating as an assembly in exit corridors and any other locations required by code. Access panels in ceilings must be located to provide access to Landlord s mechanical equipment as determined by the Building Engineer. All reused material and equipment must be refurbished to like new condition. Sign contractor to supply an insurance certificate to the Operations Manager prior to sign installation. All electrical devices and conduit systems above the finish ceiling are to be Chicago plenum rated. Only emergency lighting and exit lights are to be connected to the Landlord emergency power system. No battery-powered emergency lighting is allowed. The Tenant must submit four (4) copies of sprinkler contractor s shop drawings for approval by Landlord s risk consultant for approval or Tenant may not be allowed to open. Water Tower Place 14

19 ARCHITECTURAL DESIGN CRITERIA Landlord Supplied Architectural Items Walls Demising Walls New partitions dividing the premises from adjacent Tenant spaces may be installed by the Landlord; these will consist of 3-5/8 metal stud framing and shall run from floor to underside of deck above as shown on the Lease Outline Drawing. The wall type, typical spacing and dimensions will be such as to provide adequate fire separations and sound barriers. These walls are not designed to support additional loads. Tenant is required to install in-wall blocking if Tenant wishes to place additional loads on these walls. Drywall and acoustic insulation shall be provided by Tenant. Partitions dividing the premises from service corridors or similar areas may be constructed by Landlord consisting of concrete masonry units or of gypsum board and metal studs. Acoustic insulation and gypsum board at the interior (Tenant) face of the metal studs shall be provided by the Tenant. Exterior Walls The building is constructed of a reinforced concrete frame with stone façade and concrete or masonry back-up. Neutral Piers A variety of neutral pier configurations exist in the project. Refer to Architectural Details for general storefront conditions for particular criteria and neutral pier details. Floors Floor Slab The slab is reinforced, cast-in-place concrete. Construction includes areas of flat-plate construction with drop panels and areas with concrete beams. Care must be taken to avoid damage to existing reinforcing. Floor Loading Design Floor Live Load: 100 pounds per square foot Design Floor Fill Allowance: 20 pounds per square foot Floor Depressions Tenant shall fill all floor depressions, if any, in the premises greater than 1/2" with 4000 psi minimum structural lightweight concrete topping on Landlord's structural slab. Where the depression is greater than 1 in depth, the Tenant shall fill floor depressions prior to the performance of any other Tenant's Work. Water Tower Place 15

20 ARCHITECTURAL DESIGN CRITERIA Acoustic Considerations Landlord construction has been designed to provide general protection to guard against typical sound and vibration transmission between spaces. Tenant is responsible to ensure that sound generated in their premises produce no more sound that transmits through the Landlord s demising wall and floor structure design. If, in the Landlord s opinion, additional sound attenuation is needed to sufficiently isolate sound from within the demised premises, Tenant shall design and provide sound attenuation as required. Existing Construction within the Premises All existing conditions shall be verified by the Tenant. Failure to verify the existing conditions shall not relieve Tenant of any expenses or responsibilities resulting from that failure. It is the responsibility of the Tenant to field check all dimensions, utilities, locations and conditions prior to and during construction. Demolition Demolition of existing construction is the responsibility of the Tenant, including flooring and floor topping. Tenant may reuse portions of existing improvements subject to Landlord's prior written approval. Reuse of existing improvements shall be clearly indicated on the Store Layout and Working Drawings. Landlord makes no warranty or representation as to the condition or suitability of existing improvements reused by Tenant. Reference the Construction Requirements section of this document for additional demolition information. Water Tower Place 16

21 ARCHITECTURAL DESIGN CRITERIA General Design Criteria Overview These criteria are a basic set of tools that the Tenant is required to work with and expand upon. Criteria are written to allow freedom of individual expression and to provide a common point of departure for all Tenants. Construction Requirements Landlord s building shell is constructed as Type I-A, fire-resistive, fully sprinklered construction. Tenant s work must conform to this construction type and will use only noncombustible materials within the demised premises except where treated, fire-resistant materials are permitted in accordance with local codes. Only new, first-class materials, equipment, fixtures (including trade fixtures) and furnishings shall be used in the premises. All finishes shall have a flame spread rating as required by applicable codes. Interior wood doors shall be solid-core. Interior hardware shall be of appropriate commercial grade. All entrances into Tenant premises must remain open and clear of any permanent structural elements. All Tenant work, with the exception of approved sign installation and approved work performed above and below the space, shall be done from within the demised premises. Tenant is obligated to verify conditions pertaining to the demised premises from time to time prior to and after the commencement of Tenant s work. Tenant shall coordinate its work with the Landlord and other Tenants and with existing conditions above and below the demised premises, and shall make changes from time to time as required to accommodate such work or conditions. Any proposed adjustments to the work arising due to field conditions not apparent on drawings, other building documents and previous site surveys shall be submitted to the Operations Manager and receive written approval prior to execution. Architectural/Engineering Fee Architectural or engineering fees incurred by the Landlord as a result of investigating or planning work to be performed on Tenant s behalf will be paid by the Tenant. Storefronts Tenant s storefronts are a critical component of Water Tower Place, therefore all storefronts must complement and enhance the ambiance of common retail areas. Storefronts should emphasize a sense of entry, and the display of merchandise. National or regional Tenants who have a typical or recognizable storefront design are expected to review this design criterion and adjust their designs accordingly to ensure compatibility and compliance. They will work closely with the Landlord to achieve a high level of quality. Storefront Design Criteria is a separate section within this document. In addition to the storefronts, the area inside within 5-0 of storefronts have been identified as Tenant Display Zones and special design criteria apply to these areas. Water Tower Place 17

22 ARCHITECTURAL DESIGN CRITERIA Store Interiors Walls All storefronts and interior areas of the store which are visible to the public are subject to design approval by the Landlord. The vibrancy of rich merchandising concepts should not be relegated simply to the storefronts, but as total experiences, where entire stores become showcases of well-crafted merchandise and Tenant identity. The Store Layout, fixtures etc., must be designed to comply with handicapped accessible requirements as defined by local, state or national codes or laws. Interior Finishes are to be high quality, long lasting and, durable. All finishes shall comply with building code and the Landlord s insurance underwriter requirements for appropriate fire resistance and flame spread ratings. All trade fixtures shall be first class new fixtures with durable finishes consistent with the anticipated public exposure. All Exposed, Finished Wood shall be millwork quality kiln dried wood with a durable protective finish where exposed to public contact. Wood blocking, decking, and framing is permitted below the ceiling line and must be stamped fire retardant. All raised platforms shall be constructed of non-combustible materials. All interior partitions, including column covers, within the demised premises shall be metal stud construction and shall have one layer of gypsum board (5/8 minimum) finish on both sides with taped and sanded joints. Demising Walls: Shall provide a 2-hour fire rating as required by code and shall comply with one of the following two conditions: In existing spaces which are not reconfigured, demising walls are existing and the Tenant shall be responsible for maintaining and performing any necessary modifications or repairs to maintain the required fire rating. In reconfigured spaces, metal stud framing only shall be provided by the Landlord at all new wall locations. The Tenant shall provide acoustic insulation and two layers of 5/8 fire code gypsum board, taped and sanded and finished on the Tenant side of the metal studs to achieve the code required wall rating. The gypsum board shall extend full height from the floor to the underside of the structural floor above. Exterior Walls: Where the demised premises include an exterior wall, the Tenant shall provide and install board insulation with an R-19 rating (minimum), an interior vapor barrier up to the structure above. Interior Walls: All walls visible to the public must be finished in an appropriate manner. If painted, walls must receive two finish coats of paint, minimum. Concrete masonry unit or other masonry construction shall not be permitted within the demised premises without Landlord s prior written consent. Tenant shall provide fire dampers and stops as required by local codes. All painting, decorating, paneling, wallpapering and all other finishes on walls and columns located in the demised premises shall have a minimum flame spread rating as required by local codes. Penetration of exterior walls will not be permitted without Landlord s prior written approval. Water Tower Place 18

TENANT ARCHITECTURAL DESIGN CRITERIA HANDBOOK #1

TENANT ARCHITECTURAL DESIGN CRITERIA HANDBOOK #1 TENANT ARCHITECTURAL DESIGN CRITERIA HANDBOOK #1 QuickTime and a TIFF (LZW) decompressor are needed to see this picture. Briarwood Mall 100 Briarwood Circle Ann Arbor, Michigan 48108 (734) 769-9610 Briarwood

More information

Walmart 4th Wall. Advertising and Lease Line Guidelines. June 2009. Customerexperience

Walmart 4th Wall. Advertising and Lease Line Guidelines. June 2009. Customerexperience Walmart 4th Wall Advertising and Lease Line Guidelines June 2009 Customerexperience Contents Storefront Design Control Zone 1 Unacceptable Sign Types in 5-0 Control Zone 2 Tenant Promotional Signs 3 Hours

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

ST. MONICA FOOD PANTRY HOUSTON, TEXAS

ST. MONICA FOOD PANTRY HOUSTON, TEXAS PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,

More information

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)

SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

TAX APPRAISAL DISTRICT OF BELL COUNTY STORES & COMMERCIAL IMPROVEMENT CLASSIFICATION GUIDE

TAX APPRAISAL DISTRICT OF BELL COUNTY STORES & COMMERCIAL IMPROVEMENT CLASSIFICATION GUIDE TAX APPRAISAL DISTRICT OF BELL COUNTY STORES & COMMERCIAL IMPROVEMENT CLASSIFICATION GUIDE 1/22/2008 1 STORES & COMMERCIAL BUILDINGS 1. General Construction Class Descriptions 2. Types a. Class A - Fireproofed

More information

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS

COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications

More information

Design Development Quality Management Phase Checklist Project Phase Checklist Series

Design Development Quality Management Phase Checklist Project Phase Checklist Series Best Practices Design Checklist Project Phase Checklist Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA

More information

DESIGN GUIDELINES FOR COMMERCIAL, INDUSTRIAL AND MIXED-USE BUILDINGS

DESIGN GUIDELINES FOR COMMERCIAL, INDUSTRIAL AND MIXED-USE BUILDINGS CITY OF CHICAGO DESIGN GUIDELINES FOR COMMERCIAL, INDUSTRIAL AND MIXED-USE BUILDINGS WALL MATERIALS Original wall materials such as brick, stone and terra cotta should be repaired and maintained. Dry-vit

More information

DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines

DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines A. Offices a. Office buildings should be built to the minimum required setback. b. Surface parking should be located towards the

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE

More information

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table

More information

Technical Writing For the Tenant S Architect and Engineer

Technical Writing For the Tenant S Architect and Engineer A r i z o n a C e n t e r P h o e n i x, a r i z o n a TENANT DESIGN CRITERIA GENERAL GROWTH PROPERTIES, INC. 35 CENTURY PARK WAY. SALT LAKE CITY. UT. 84115 Arizona Center The beautiful landscaped gardens

More information

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION

More information

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3 TOWN OF SIDNEY Multi-Family, Commercial, Industrial and Institutional Building Permit Guide The information provided is intended as a guide only and does not replace current bylaws and regulations. Complete

More information

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No. Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two

More information

Tenant Design Criteria Section a Architectural Design Criteria Updated: July 2015. 3710 Route 9 South, Freehold, NJ 07728

Tenant Design Criteria Section a Architectural Design Criteria Updated: July 2015. 3710 Route 9 South, Freehold, NJ 07728 3710 Route 9 South, Freehold, NJ 07728 TABLE OF CONTENTS ARCHITECTURAL DESIGN CRITERIA General Storefront Requirements Storefront Design Criteria Windows & Glazing Rolling Grille Design Guidelines Awning

More information

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the

More information

Exhibit C Design Review Guidelines

Exhibit C Design Review Guidelines Exhibit C Design Review Guidelines January 2015 Included in this Exhibit for Design Guidelines includes: Electrical Design Guidelines Electrical and Mechanical /Plumbing Construction Requirements Temporary

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

16 2 10.3 Materials and Colors

16 2 10.3 Materials and Colors 16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall

More information

REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N

REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N

More information

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids

More information

Gramercy Place Condo Association, Inc.

Gramercy Place Condo Association, Inc. Gramercy Place Condo Association, Inc. UNIT MODIFICATION REQUEST Date of Application: Name of Owner (s): Telephone: (Home) (Cell) E-Mail: Anticipated start date: Anticipated ending date: Permission is

More information

GENERAL GROWTH PROPERTIES, INC.

GENERAL GROWTH PROPERTIES, INC. T E N A N T C R I T E R I A M A N U A L GENERAL GROWTH PROPERTIES, INC. TUCSON MALL Tucson, Arizona www.shoptucsonmall.com Cover: Architect s rendering of Center Court GENERAL GROWTH PROPERTIES, INC. www.generalgrowth.com

More information

09 00 03 GENERAL PROVISIONS

09 00 03 GENERAL PROVISIONS 09 00 03 GENERAL PROVISIONS A. For renovation projects, consider the building s character and existing finishes. All material patches should blend as closely as possible. Some buildings on campus have

More information

GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES

GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES PAGE 13 DESIGN GUIDELINES The following design guidelines have been developed to guide appropriate design in the Downtown

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

OPTIMUS WORK CLASSIFICATION LIST ENTER ALL THAT APPLY

OPTIMUS WORK CLASSIFICATION LIST ENTER ALL THAT APPLY Cost Code # Description Cost Code # Description 01 00 00.001 General Requirements 02 00 00.001 Existing Conditions 01 31 19.13.001 Preconstruction Meetings 02 21 00.001 Surveys 01 32 33.001 Photographic

More information

Facility Assessment for. 11801 East Main Street, Huntley, IL

Facility Assessment for. 11801 East Main Street, Huntley, IL Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested

More information

Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.

Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman. Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal

More information

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level

More information

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal. 2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other

More information

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are: When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory

More information

How to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014

How to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings CPE Candidate No. 0714108 December 2014 1 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings Table

More information

KIEWIT CM/GC Enabling/Utilities

KIEWIT CM/GC Enabling/Utilities South Terminal Redevelopment Program KIEWIT CM/GC Enabling/Utilities Contract Value $50 million M/WBE Goal 20 percent Contact John Todd, LEED AP Project Manager 303.930.9046 john.todd@kiewit.com General

More information

SWAN POINT YACHT & COUNTRY CLUB

SWAN POINT YACHT & COUNTRY CLUB SWAN POINT YACHT & COUNTRY CLUB PROJECT INFORMATION: SCOPE OF WORK: INTERIOR ALTERATIONS ABBREVIATIONS: VICINITY MAP 33 East Charles Street PO Box 598 30-934-8078 PROPERTY MANAGER: DOTTIE HARPER BROOKFIELD

More information

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015 TENANT DESIGN MANUAL UPDATED JULY 2015 PROJECT OVERVIEW Grapevine Mills is located at the interchange of SR 121 and Grapevine Mills Parkway. It is centrally located just 20 miles northwest of Dallas and

More information

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1

More information

Mall. atthews. atthews. alls. atthews. loouisville. u i s v ille. e n t u cky. entucky. General Growth Properties, Inc. 6-11-2008.

Mall. atthews. atthews. alls. atthews. loouisville. u i s v ille. e n t u cky. entucky. General Growth Properties, Inc. 6-11-2008. Mall M alls Stt.. atthews atthews atthews llouisville,k entucky u i s v ille,k KentucKy e n t u cky loouisville General Growth Properties, Inc. 110 N. Wacker Drive General Growth Properties, Inc. 110 N.

More information

Slavic Village Building Condition Review

Slavic Village Building Condition Review Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities

More information

Automatic Door Selection Guide

Automatic Door Selection Guide Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 aaadm@aaadm.com Automatic Door Selection Guide General: The members of AAADM manufacture an assortment

More information

Repair and Remodeling Estimating Methods. 4th Edition. RSMeans

Repair and Remodeling Estimating Methods. 4th Edition. RSMeans Brochure More information from http://www.researchandmarkets.com/reports/2214808/ Repair and Remodeling Estimating Methods. 4th Edition. RSMeans Description: This estimating guide for repair and remodeling

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

Eastridge mall. San Jose, California TENANT DESIGN CRITERIA

Eastridge mall. San Jose, California TENANT DESIGN CRITERIA Eastridge mall San Jose, California TENANT DESIGN CRITERIA Table of Contents Letter of Introduction 1 Center Address: 2 Local Utility Agencies 2 Landlord Required Contractors 3 Lower Level Plan 4 Upper

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

TENANT HANDBOOK Rev. January 24, 2014

TENANT HANDBOOK Rev. January 24, 2014 TENANT HANDBOOK Rev. January 24, 2014 180 East Broad Street Columbus, Ohio 43215 614.621.9000 www.glimcher.com TABLE OF CONTENTS Section One Introduction... 1-1 Section Two Contact Information Landlord's

More information

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer

More information

PUBLIC RESTROOMS, DESIGN INTENT

PUBLIC RESTROOMS, DESIGN INTENT PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes

More information

WASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST

WASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST 0 RIVERSIDE DRIVE, OTTAWA, ON A0.0 COVER SHEET / DRAWING LIST A0. LEGEND AND GENERAL NOTES A0. GENERAL NOTES A0. GENERAL NOTES A0. TYPICAL WASHROOM WALL/SINK SECTION A0. DETAIL - CONTROL JOINT A0. DETAIL

More information

Schematic Design: Quality Management Phase Checklist Project Phase Checklist Series

Schematic Design: Quality Management Phase Checklist Project Phase Checklist Series Best Practices : Project Phase Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA members without endorsement

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

INDUSTRIALS COLD STORAGE FACILITIES

INDUSTRIALS COLD STORAGE FACILITIES CAL 98 INDUSTRIALS COLD STORAGE FACILITIES AVERAGE CLASS C LOW/AVERAGE CLASS S OCCUPANCY DESCRIPTION: Cold storage facilities are designed to keep stored commodities at various temperature levels. Some

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

Tenant Design Criteria. CrossIron Mills 261055 CrossIron Blvd. Rocky View, AB T4A 0G3

Tenant Design Criteria. CrossIron Mills 261055 CrossIron Blvd. Rocky View, AB T4A 0G3 Tenant Design Criteria CrossIron Mills 261055 CrossIron Blvd. Rocky View, AB T4A 0G3 Welcome To CrossIron Mills! 2 CrossIron Mills is prominently and strategically situated 15 km (10 miles) north of Calgary,

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

HEATING, VENTILATING, AND AIR CONDITIONING EQUIPMENT. Application Guidelines

HEATING, VENTILATING, AND AIR CONDITIONING EQUIPMENT. Application Guidelines HEATING, VENTILATING, AND Application Guidelines The Landmarks Preservation Commission (LPC) is the Mayoral agency charged with designating and regulating individual landmarks and historic districts. The

More information

Industrial Suburban District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations

Industrial Suburban District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations 16.20.110 - Industrial Suburban District ( IS ) Figure REFERENCE Typical Buildings in the IS District Figure REFERENCE Site Plan of a typical development in the IS District Sections: 16.20.110.1 Composition

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards

More information

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by 24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International

More information

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING

More information

Contractors Rules & Regulations

Contractors Rules & Regulations Contractors Rules & Regulations November 2, 2015 (1) Pre-Construction Meeting Pg. 2 (2) Permits and Licensing Pg. 3 (3) Union Affiliated Guidelines Pg. 4 (4) Temporary Provisions Pg. 5 (5) Construction

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Physical Address/Intersection: Name of Project: Within a NFIP 100/500yr Floodzone:

Physical Address/Intersection: Name of Project: Within a NFIP 100/500yr Floodzone: Choctaw Date Recorded: Permit # RESIDENTIAL - BUILDING Permit APPLICATION Physical Address/Intersection: Name of Project: Within a NFIP 100/500yr Floodzone: YES NO Sec., Township, Range/Subdivision: Acres/Block:

More information

Saint Cloud Business Center

Saint Cloud Business Center Saint Cloud Business Center 14 7th Avenue North Saint Cloud, MN 56303 For Sale Located on 7th Avenue in the heart of downtown across from the Court House Square. A large professional reception area with

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

glass & Glazing Products

glass & Glazing Products glass & Glazing Products WallMaker Create an unlimited variety of bright, beautiful and secure interior environments with the easy-to-install Stylmark WallMaker glass wall system. This versatile system

More information

Waterfront Centre RETAIL DESIGN CRITERIA

Waterfront Centre RETAIL DESIGN CRITERIA RETAIL ISSUED MAR.2011 Welcome to Occupying two city blocks between Burrard and Howe Streets, the Complex holds a strategic position in the downtown core while commanding spectacular views across Burrard

More information

THE BOULEVARD MALL LAS VEGAS, NEVADA

THE BOULEVARD MALL LAS VEGAS, NEVADA THE BOULEVARD MALL LAS VEGAS, NEVADA TENANT DESIGN CRITERIA GENERAL GROWTH PROPERTIES, INC. 35 CENTURY PARK WAY. SALT LAKE CITY. UT. 84115 The Boulevard Mall will embrace our ethnically diverse community

More information

Tenant Design Criteria 01/02/07

Tenant Design Criteria 01/02/07 Tenant Design Criteria 01/02/07 TABLE OF CONTENTS PREFACE 5 Welcome 6 INTRODUCTION 8 Coastland Mall Introduction 9 Location Map 10 Site Plan 11 Lease Plans 12 Project Directory 13 SUBMISSION REQUIREMENTS

More information

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

LITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE -

LITITZ MUTUAL INSURANCE COMPANY 2 North Broad Street Lititz, Pennsylvania - MAIN OFFICE - The original section of this building was constructed in 1941. The exterior walls are built of good quality stone. In the early 1980 s a similar addition was added to the north elevation. The exterior

More information

645 E. Shaw Avenue, Fresno, California 93710

645 E. Shaw Avenue, Fresno, California 93710 ADDENDUM LOG June, 2009 Full Update December, 2009 Contact Directory revised/tc contact info updated January, 2011 TC contact info updated May, 2011 Required Contractor list updated / revised. February,

More information

Think Of Us First! When It s Time to Distribute Your Plans

Think Of Us First! When It s Time to Distribute Your Plans Think Of Us First! When It s Time to Distribute Your Plans CONSTRUCTION NOTEBOOK WILL LIST YOUR PLANS AND SPECS FREE CALL TODAY FOR DETAILS 702-876-8660 Why use Experience We have over 60 years of experience

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION RESIDENTIAL: REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION 2 COMPLETE SETS OF PRINTS WITH ENGINEERS STAMP ON FOUNDATION PLAN INCLUDING ELECTRICAL, PLUMBING, ETC. SITE PLAN SHOWING HOUSE LOCATION

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

How To Make A House Safe

How To Make A House Safe 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight

More information