1 Building Division MULTI-TRADES INSPECTION Mechanical, Plumbing, Electrical, Frame, Roof City of Palo Alto (CPA) Building Inspection Division 285 Hamilton Ave. Inspection Request: Inspection Code IVR# 301 Revision Date: 6/7/14 General Requirements/Checklist for: COMMERCIAL Codes Enforced: California Building, Mechanical, Electrical and Plumbing Codes Palo Alto Municipal Code (PAMC) The information provided in this document is general and intended as a guide only. Each project is unique and additional requirements may be enforced as deemed appropriate. WARNING Failure to complete items below prior to inspection may result in a re-inspection fee. Recently This section shall be completed prior to All Trades inspection Building shall be watertight (roof complete, walls papered/waterproof, and windows installed. Exception: Contractor shall submit to Building Official a letter of responsibility for damaged materials due to weather exposure AND must use water resistant materials such as paperless interior drywall and siliconized/waterproof fire caulking. Any damaged work shall be completed under a separate permit. Prior to inspection verify all required sequential inspections and correction notices are complete. All required special inspections have been performed including HERS testing. Verify revisions have been submitted and approved. Gas stub-out location shall be approved and Green tagged by WGW, contact Thomas Fire blocking and caulking as required shall be completed at All-Trades inspection prior to insulation NO EXCEPTIONS. Fire sprinklers: Fire Department approval of fire sprinkler system is required. Alternate Methods and Materials Alternate methods and materials shall be submitted and approved prior to installation and inspection (i.e. CSST, PEX, PV Systems, Foam insulation, Blown-In-Insulation, Clothes dryer inline booster fans, Tankless Water Heaters, etc.) Photovoltaic System If photovoltaic is part of the permit, a separate inspection shall be scheduled. Helpful Reminder Don t forget to install the thermostat and communication wires.

2 Mechanical If applicable see Kitchen Hood Guidelines. Enclosed space housing mechanical equipment shall have a minimum (1) receptacle outlet and light installed near the equipment with the light switch located at the entrance to the passageway. CPA Policy Structural support for grab bars, tubs and shower seats Verify that structural support for grab bars, tub and shower seats, fasteners and mounting devices are designed to resist a single concentrated load of 250 pounds in any direction at any point. CBC 1115B.7.2 ; (Residential CBC ) Structural support for handrails and guards Verify that handrail assemblies and guard supports resist a load of 50 pounds per lineal foot in any direction and shall resist a single concentrated load of 200 pounds applied in any direction. CBC , Plumbing If applicable, see attached Island Venting Illustration. Identify roof drain pipes with Label Palo Alto Municipal Code Requirements All commercial and industrial building whose building face is parallel to the City sidewalk shall have a HOSE BIB for washing the building face or watering plants. PAMC If applicable, verify that Backflow Prevention Device is installed (water supply) PAMC see backflow prevention inspection guidelines Drainage piping serving fixtures with flood level rims located below one foot above the elevation of the next upstream manhole cover of the public or private sewer serving such drainage piping shall be protected from backflow of sewage by installing an approved backwater valve. PAMC Section Materials CPC 701.1: Drainage piping shall be of *cast iron, galv. Steel, galv. Wrought iron, lead, **copper, brass, stainless steel 304 or 316L, schedule 40 ABS DWV, schedule 40 PVC DWV, extra-strength vitrified clay pipe, or other approved material having a smooth and uniform bore, except that: No galv. Wrought iron, stainless steel 304 or galv. steel pipe shall be used underground and shall be keep (6) inches above ground. ABS and PVC is allowed within COMMERCIAL BUILDINGS except when piping is exposed within ducts or plenums. Important: highly recommend solid core PVC ABS and PVC installations are limited to RESIDENTIAL construction not more than two stories of areas of residential accommodation. [ HCD 1 & 2] CPC

3 * CPC (6) Cast iron soil pipe and fittings materials shall be marked with the following: Manufacturer s name OR registered trademark* Country of origin Date of manufacture (pipe only) *Note: Manufacturers trademark MUST be readily identifiable CPC Materials shall comply with referenced standards CISPI 301: The following documents are required by CISPI 301, and shall be provided to the City inspector upon request: 1. Radiation screening records 2. Mechanical testing records to verify tensile strength (test done every 4 hours) 3. Chemical testing records (test done every 4 hours) 4. Dimensional inspection records (test done every 12 hours) 5. Certification letter from manufacturer legal name and address of actual manufacturer Note: a) All records MUST be provided by the manufacture, and kept by the manufacturer for a period of seven (7) years. b) All testing and record keeping are to be performed by the manufacture at the time the product is cast ( analysis of castings or test bars after the time of production shall not be used as evidence of compliance with this specification. - CISPI 301) **CPA ORDINANCE Section amended Materials. NOTE: CPA Ordinance Supersedes the California Plumbing Code Section of the California Plumbing Code is amended to read: Copper, copper alloys, lead and lead alloys, including brass, shall not be used for building sanitary sewer systems except for domestic waste sink traps and short lengths of associated connecting pipes where alternate materials are not practical. Where permitted by the Building Official, copper tube for drainage and vent piping shall have a weight of not less than that of copper drainage tube type DWV Table 7-1 amended - Materials for drain, waste, vent pipe and fittings. Footnote 2 is added to Table 7-1 to read as follows: 2 For limitations on the use of Brass and Copper (Type DWV) refer to Section Section amended Storm drainage, material uses. Section of the California Plumbing Code is amended to read: Material Uses. Rainwater piping placed within the interior of a building or run within a vent or shaft shall be of cast iron, galvanized steel, wrought iron, Schedule 40 ABS DWV, Schedule 40 PVC DWV, stainless steel 304 or 316L (stainless steel 304 pipe and fittings shall not be installed underground and shall be kept not less than six (6) inches (152 mm) aboveground), or other approved materials, and changes in direction shall conform to the requirements of Section ABS and PVC DWV piping installations shall be installed in accordance with IS 5 and IS 9. Except for individual single-family dwelling units, materials exposed within ducts or plenums shall have a flame-spread index of a maximum of twenty-five (25) and a smoke-developed index of a maximum of fifty (50), when tested in accordance with the Test for Surface-Burning Characteristics of the Building Materials (see the Building Code standards based on ASTM E 84 and UL 723.). [HCD 1 & HCD 2] ABS or PVC installations are limited to not more than two stories of areas of residential accommodation.

4 Drainage piping shall maintain a minimum ¼ inch per foot uniform slope. CPC Exception: At the discretion of the building official and when impractical due to the depth of the street sewer or structural features or to the arrangement of any building or structure, pipes 4 or larger may have a slope no less than 1/8 per foot. Testing piping system: Drain, waste, and vent (DWV) system shall be tested with water and no less than 10 of head water for 15 minutes OR 5 psi air test for 15 minutes. CPC Push-Fit Fittings and Heat Fusion Weld Joints are allowed. CPC , 11 Water pipe shall be tested and proved tight under water pressure not less than the working pressure under which used CPC Water service from meter to building shall be tested prior to or during this inspection. Sewer line clean-out Cleanout shall be approved type WYE, combo fittings or approved two way cleanout such as head to head double combos. Verify building clean-out is within 2 feet of the building terminating at grade level. CPC Additional clean-outs are required at property lines, end of line, horizontal change of direction exceeding 135 degrees, and runs exceeding 100 in length. CPC and Clean-out shall be installed so that it opens to allow cleaning in the direction of flow. CPC Vent size per CPC Table 7-5. The min. diameter of individual vent pipe shall not be less than 1-1/4 nor less than one-half the diameter of the drain to which it is connected and shall be vented by means of one or more vent pipes, the aggregate cross-sectional area shall not be less than the largest required building sewer pipe. CPC See attached pipe circumferences table. Vents that connect to a horizontal drainage pipe shall have its invert taken off above the drainage centerline of such pipe downstream of the trap being served. CPC 905.2

5 Waste vents shall terminate vertically not less than 6 above roof, nor Less than 1 from any vertical surface and 10 from or 3 above any opening such as windows, doors, air intake, nor less than 3 from any lot line. Side wall vent may not terminate under vented soffit. CPC 906.1, 2 Venting shall be vertical until 6 above the flood rim of the fixture. CPC Fire rated walls: All plastic pipe such as condensate lines, vacuum lines, exhaust lines, drain lines, waste & vent lines require an approved U.L. tested fire stop collar or equivalent at fire rated wall/ceiling OR use cast iron for DWV pipes. Transition fittings between metal and plastic pipe shall be listed for that use. Island sink foot vent cleanout (WYE) CPC Check for steam shower requirements. Ejector vent shall be run separately through roof, vent size per Table 7-3 but never smaller than 1-1/2. CPC Floor Drains CPC (Verify at Underslab Plumbing Inspection) Floor drains shall be installed in the following areas: All floor drains shall be provided with a continuous type primer. Toilet rooms containing (2) or more water closets or a combination of (1) water closet and (1) urinal, except in dwelling unit. Commercial kitchens. Laundry rooms in commercial buildings and common laundry facilities in multi-family dwelling buildings. Fire service backflow device closet area. Note: Flushing of the fire system to sanitary sewer shall not exceed 30 GPM. Higher flushing rates shall be diverted to a detention tank to achieve the 30 GPM flow to sewer. See WGW plan review condition. Verify floor drain with a continuous drip type primer is available within the fire service backflow device closet. If no drain, area subject to splash shall be protected with paperless drywall such as DensGlass.

6 2013 CPC CONDENSATE Point of Discharge. Air-conditioning condensate waste pipes shall connect indirectly to the drainage system through an air gap or air break to properly trapped and vented receptors, dry wells, leach pits, or the tailpiece of plumbing fixtures

7 Gas Other checklist See CSST gas piping See attached Gas Pipe Stub Out detail for location requirements. See Under Structure Gas Pipe checklist, if applicable. Gas piping 5 psi and above located inside a structure is prohibited unless one of the following conditions are met: 1. Pipe is located in a ventilated chase, 2. Pipe is located in buildings or separate area of building used exclusively for industrial heating or processing, research, warehousing or boiler or mechanical equipment room. 3. Pipe system is welded. CPC Label gas piping Prohibited locations: Gas piping shall not be installed in or through a circulating air duct, clothes chute, chimney or gas vent, ventilation duct, dumbwaiter, or elevator shaft. CMC Verify that WGW approved location of gas stub out prior to this inspection; a green sticker must be attached to gas stub out (call ) Where more than one gas meter exists, each separate gas meter shall be identified with a brass tag. CPC Gas pipe stub out shall extend a min. 4, max. 6 beyond face of wall. WGW Assembly Standard * Gas pipe passing through outside wall shall be protected against corrosion by coating, wrapping or sleeve. Sleeved pipe shall be sealed at the annular space between the gas pipe and sleeve. (Recommend prime and wrap using 20 mill tape with two wraps) CPC and All branch piping in yard must be tied in prior to whole house gas test and shall be configured for isolated shut off lockable valve. Any underground metallic gas pipe that is extended below grade requires a dielectric union to be installed at a minimum of 6 above grade (CPC ) It is recommended that a full way valve be installed on underground lines to provide for an ability to isolate them if needed. Test gauges shall have a pressure range not greater than twice the test pressure applied CPC 319 Test pressure not less than 1-1/2 times the maximum working pressure, but not less than 3 psi for 10 minutes CPC ,2,3 Recommend 15 psi test. Gas Shut-off valve shall be accessible rigid piping upstream from the flexible connector and within 6 of the gas appliance. CPC Verify gas shutoff valve is within 6 from appliance. Recommend shutoff be readily accessible in adjacent cabinet space. CPC Shutoff valves installed in firebox of fireplace shall be installed per manufacturer instructions. Gas pipe penetration into fireplace shall be sealed with refractory sealant. Verify gas flex lines are rated to supply max BTU input of appliances.

8 Electrical See electrical section of the book for all electrical requirements Palo Alto Municipal Code Requirements All buildings and structures (other than single or two family dwellings, apartment buildings of wood frame construction not exceeding three stories in height and accessory buildings thereto) shall be wired in an approved type raceway or metallic covered cable permitted by code. PAMC (D) Verify rough electrical for light at address numbers location. See Address and Premises guidelines. CPA Policy Electrical (Multi Family) Partition wall outlet boxes: Horizontal separation between outlet boxes on opposite sides of the wall may not be less than 24 and not allowed in the same bay vertically. See [FIGURE A-1] Exception: May be less than 24 (not back to back/shadowing) when using listed putty pads. Back to back outlet boxes are not allowed. See [FIGURE A-3] Exceptions: Horizontal separation may be less than 24 provided one of the outlet boxes is boxed out with drywall. See [FIGURE A-2] Stuff one block of thermo-fiber between back to back receptacles. Putty pad installation recommendation: Clean electrical box, Spray-Glue the box and attach putty pad, or wire pad in place. FIRE BLOCKING See Fire Blocking inspection guidelines CPA Requires siliconized fire caulking FREQUENTLY MISSED/INSPECTION FAILURE Verify fire blocking and caulking at all exit corridors.

Top 10+ Mistakes of DWV plumbing design

Top 10+ Mistakes of DWV plumbing design Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of

More information

Plumbing Code. City of San Diego 2013 Plumbing Regulations - Proposed Code Changes (revised 5/15/15)

Plumbing Code. City of San Diego 2013 Plumbing Regulations - Proposed Code Changes (revised 5/15/15) "Portions of this publication reproduce excerpts from the 2013 California Mechanical Code, Title 24, Part 4 and 2013 California Plumbing Code, Title 24, Part 5, reprinted with the permission of the International

More information

2006 Codes. Please verify the following before calling for inspection

2006 Codes. Please verify the following before calling for inspection INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.

More information

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass. CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 Bellevue Bothell Kenmore Kirkland Issaquah Mercer Island Sammamish Snoqualmie Woodinville CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 This checklist is intended for use to prepare

More information

PLUMBING ROUGH IN INSPECTION

PLUMBING ROUGH IN INSPECTION This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.

More information

INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville

INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville Bellevue Bothell Burien Issaquah Kenmore Kirkland INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville 2009 Codes This

More information

Chapter 7 Plumbing Connections

Chapter 7 Plumbing Connections Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions

More information

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

When Should Examination Preparation Begin?

When Should Examination Preparation Begin? Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

Plumbing Code in Commercial Kitchens

Plumbing Code in Commercial Kitchens Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

CLARK COUNTY DEPARTMENT OF BUILDING COMMERCIAL PLUMBING AND MECHANICAL INSPECTION CHECKLISTS 2006 CODE

CLARK COUNTY DEPARTMENT OF BUILDING COMMERCIAL PLUMBING AND MECHANICAL INSPECTION CHECKLISTS 2006 CODE CLARK COUNTY DEPARTMENT OF BUILDING COMMERCIAL PLUMBING AND MECHANICAL INSPECTION CHECKLISTS 2006 CODE GENERAL NOTES This checklist is intended for use as a GUIDE to assist and promote consistency in the

More information

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207

BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

SECTION 221413 FACILITY STORM DRAINAGE PIPING

SECTION 221413 FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER 11 STORM DRAINAGE 1101.0 General. 1101.1 Where Required. Roofs, paved areas, yards, courts, courtyards, vent shafts, light wells, or similar areas having rainwater, shall be drained into a separate

More information

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition. DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Amendments to the 2012 International Plumbing Code

Amendments to the 2012 International Plumbing Code Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007

ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 The following are general requirements pertaining to plumbing in one and two family dwellings. This does not represent all the provisions regulating plumbing

More information

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012 Plumbing Code in Commercial Kitchens NH BOA May 9, 2012 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion IPC - Chapter 10 Traps Interceptors Separators

More information

PMA ONLINE TRAINING Venting for Plumbing Systems

PMA ONLINE TRAINING Venting for Plumbing Systems PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended

More information

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872

More information

Section 43. Lead Paint Risk Factor NONE WATER HEATER STORAGE ELECTRIC

Section 43. Lead Paint Risk Factor NONE WATER HEATER STORAGE ELECTRIC WATER HEATER STORAGE ELECTRIC Lead Paint Risk Factor NONE TABLE OF CONTENTS PART 1: INSTALLATION REQUIREMENTS FOR CONVENTIONAL HOMES... 1 WATER HEATER REPAIRS... 1 1. APPLIANCE REPAIR... 1 WATER HEATER

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

Does Wall Township require an inspection by the building department on resale of a home?

Does Wall Township require an inspection by the building department on resale of a home? Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,

More information

Residential Plumbing BCN 1058

Residential Plumbing BCN 1058 Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES

More information

KITCHEN HOODS GUIDELINES

KITCHEN HOODS GUIDELINES KITCHEN HOODS GUIDELINES City of Palo Alto Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Revision Date:6/27/12 General Requirements/Checklist for: Commercial Codes Enforced:

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to

More information

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:

More information

PLUMBING. For HOME OWNERS

PLUMBING. For HOME OWNERS PLUMBIG For HOM OR If your property is located in the ational cenic rea, the Columbia River Gorge IRODUCIO Commission requires you to comply with all ational cenic rea regulations. hey can be contacted

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

CITY OF SELMA, TEXAS Inspection Checklist: Commercial

CITY OF SELMA, TEXAS Inspection Checklist: Commercial Rev Y71004 The Permits and Inspections Department welcomes you to the City of Selma. The following information is provided to you as guidance through the inspection process. The City of Selma provides

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS

CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS PlumbingCode06_ch10 5/29/06 8:16 AM Page 1 CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS We have covered most of the regulations you will need to know about drains and vents. This chapter will round out

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

Orlando Home Inspection Services

Orlando Home Inspection Services PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division Brian Coppock, Regional Compliance Officer Office of Statewide Health Planning and Development Facilities Development Division CHAPTER 6 WATER SUPPLY AND DISTRIBUTION 601.0 Hot and Cold Water Required.

More information

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing

More information

Owner: Phone # Mailing Address: Contractor: Phone # Fax #

Owner: Phone # Mailing Address: Contractor: Phone # Fax # CITY OF EASTON BUREAU OF CODES AND INSPECTIONS 2 nd Floor, 123 South Third Street, Easton, PA 18042 phone (610) 250-6724 - fax (610) 250-6607 email codes@easton-pa.gov PERMIT APPLICATION Owner: Phone #

More information

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary

More information

Plumbing Code Sections For Commercial Food Facilities

Plumbing Code Sections For Commercial Food Facilities Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health

More information

Town House 11265 Center Highway North Huntingdon, PA 15642

Town House 11265 Center Highway North Huntingdon, PA 15642 APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 17 - NONPOTABLE RAINWATER CATCHMENT SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state

More information

CHAPTER 26 PLUMBING CODE

CHAPTER 26 PLUMBING CODE CHAPTER 26 PLUMBING CODE 26.01 PLUMBING CODE The Illinois Plumbing Code as promulgated by the Illinois Department of Public Health at 77 Illinois Administrative Code, Part 890, is hereby adopted as the

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

The purpose of this document is to provide standards for persons requesting or subject to County building inspections.

The purpose of this document is to provide standards for persons requesting or subject to County building inspections. STANDARD OPERATING PROCEDURE BUILDING & SITE DEVELOPMENT Number: 310.1 Approval: Yves Khawam Effective Date: December 27, 2006 Subject: Requirements for County building inspections Page 1 of 7 1.0 PURPOSE:

More information

City of Elk River BASEMENT Office Use Only

City of Elk River BASEMENT Office Use Only City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single

More information

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist #506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the

More information

Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842

Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:

More information

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SWIMMING POOL, SPA, & HOT TUB GUIDELINES SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015

More information

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application.

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. Article II provides rules governing the allowable connection to the City POTW and the construction and inspection of

More information

COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS

COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications

More information

CHAPTER 5 WATER HEATERS

CHAPTER 5 WATER HEATERS PlumbingCode06_ch05 5/29/06 8:12 AM Page 1 CHAPTER 5 WATER HEATERS Water heaters are only a small portion of a plumbing system, but they are important, and they can be dangerous. Many plumbers take water

More information

MODIFICATIONS ASSOCIATED WITH THE UNIFORM PLUMBING CODE (UPC)

MODIFICATIONS ASSOCIATED WITH THE UNIFORM PLUMBING CODE (UPC) MODIFICATIONS ASSOCIATED WITH THE UNIFORM PLUMBING CODE (UPC) 24.301.301 INCORPORATION BY REFERENCE OF UNIFORM PLUMBING CODE (1) The department adopts and incorporates by reference the Uniform Plumbing

More information

UNIFORM PLUMBING CODE and UNIFORM PLUMBING CODE STANDARDS. 2009 Edition

UNIFORM PLUMBING CODE and UNIFORM PLUMBING CODE STANDARDS. 2009 Edition WASHINGTON STATE BUILDING CODE CHAPTERS 51-56 and 51-57 WAC UNIFORM PLUMBING CODE and UNIFORM PLUMBING CODE STANDARDS 2009 Edition Washington State Building Code Council Copies of the State Building Codes

More information

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained). CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1001 SOUTH LEECHBURG HILL LEECHBURG, PA 15656 Phone: 724-845-9355 Fax: 724-845-1186 SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1. General

More information

SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES

SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES 5.1.0 GENERAL Section five reviews consolidates the various local amendments technical code information

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.

More information

Building Permit Application

Building Permit Application Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

ASX7-4-IOM-7 J30-08579

ASX7-4-IOM-7 J30-08579 INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection

EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED

More information

UNIFORM PLUMBING CODE. 2012 Edition

UNIFORM PLUMBING CODE. 2012 Edition WASHINGTON STATE BUILDING CODE CHAPTERS 51-56 WAC UNIFORM PLUMBING CODE 2012 Edition Washington State Building Code Council Copies of the State Building Codes may be obtained from: Washington Association

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU MECHANICAL PLAN REVIEW CHECKLIST PROJECT NO.: BMEC DATE: STATUS: INFORMATION PROJECT ADDRESS: WORK DESCRIPTION: APPLICANT

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table

More information

Chapter 16.130 PLUMBING CODE

Chapter 16.130 PLUMBING CODE DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,

More information

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SPECIFICATIONS SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,

More information

Backflow Bulletin #1

Backflow Bulletin #1 Backflow Bulletin #1 FIRE PROTECTION SYSTEMS Chemicals in the System Anti-Freeze, Foam, Corrosion Inhibitors, etc. Chemicals in the System Glycerin Glycerin or similar food-grade non-toxic additive Siamese

More information

Acumen Enterprises, Inc.

Acumen Enterprises, Inc. Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

DIVISION 22 PLUMBING. 22 30 00 PLUMBING EQUIPMENT 22 33 00 Domestic Water Heaters

DIVISION 22 PLUMBING. 22 30 00 PLUMBING EQUIPMENT 22 33 00 Domestic Water Heaters DIVISION 22 PLUMBING 22 00 00 PLUMBING 22 00 50 Design Criteria 22 01 00 General Requirements 22 05 00 Common Work Results 22 06 00 General Duty Valves 22 07 00 Insulation 22 08 00 Commissioning 22 10

More information

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees. The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

Applications for building permits will not be reviewed until all of the required information has been submitted.

Applications for building permits will not be reviewed until all of the required information has been submitted. NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Commercial Construction Information Packet

Commercial Construction Information Packet Commercial Construction Information Packet Inspection Requirements, Notes and Listings 9/2009 TABLE OF CONTENTS General Requirements.............................................................1 General

More information