Waterproofing Membranes- a 2016 view of problems, standards, and solutions.
|
|
|
- Jeffry Neal Bridges
- 9 years ago
- Views:
Transcription
1 Grayson Wagner Co Ltd Consulting Chemists 4 Cain Road, PO Box Penrose, Auckland, NZ Ph/Fax: Mobile: [email protected] [email protected] [email protected] Waterproofing Membranes- a 2016 view of problems, standards, and solutions. This paper was first prepared for the NZ Institute of Architects Technical Series- June 2011 by Bill Grayson BSc, FNZIC. This version was updated August It remains the copyright property of Grayson Wagner Co Ltd, but is freely available as PDF at on condition that it is only copied, or reproduced in full. This paper was written in frustration at the destructive power of an assumption, particularly when combined with a brand name. The assumption is that waterproof means what it says. However this may make an ASS/U/ME. The brands and materials are many, and shall remain nameless for the present, but please contact us if you require specific advice. Early membrane problems Common themes: By 2004 problems with water ingress beneath membranes were surfacing in NZ. We later found membrane failures to be a big issue in Canada and in other areas of high rainfall/humidity. Exterior areas affected were flat roofs and exposed decks, particularly where tiles were directly stuck to membranes. A common factor was a lack of falls on decks and roofs, ponding at drain heads, and in gutters. Structural concrete and timber/plywood structures were all affected. Furthermore the continued rise of interest in green roofs and planter boxes will further accentuate this already problematic area. The problem with interior spaces has been leaks in showers where bathrooms are in daily use. The failure of sub-grade membranes particularly on deeply excavated carparks where the repair options are extremely limited/expensive; causes leaks, rebar corrosion and a loss of amenity. Symptoms of leaks and membrane failure: Leaks into structure, corrosion of steel reinforcement, and water damage. Structural movement of timber constructions. Wear surfaces lifting and moving, cracking of tiles and grout lines. Paint and membrane colour changes, stickiness, sliminess and smell. Efflorescence especially on concrete blocks, structural concrete, and brick work.
2 Waterproofing Membranes August 2016 Page 2 of 14 Investigations and failure mechanisms Our work on many different sites and membranes is usually initiated by litigation relating to water damage. We must dismantle the affected area to photograph the membrane, particularly at movement joints and changes of plane. We are looking for membrane swelling, crinkling, blistering, and tearing due to structural movement, and delamination of seams. We take samples of the membrane in sealed containers, particularly at any lap joints, together with any associated materials such as acoustic and adhesive layers, and surrounding water. Water absorption testing and the Second Law of Thermodynamics: The Second Law of Thermodynamics asserts that a natural process spontaneously runs only in one direction, which is not reversible unless work is performed. In this case the process is the absorption of water into dry materials. Hence water on one side of a semipermeable membrane (Not a barrier) will be transmitted through to the dry side. The rate of transmission of water through a polymer is defined by Fick s law, which is called up appropriately in Standard ISO 62:2008- Water absorption of plastics. ISO 62 has long been the method of test adopted by Lloyds Register for approval of plastics used in ship building. The amount of water a membrane absorbs at equilibrium is proportional to its barrier properties (effectiveness as a waterproofing membrane). Typically an effective construction barrier membrane such as polyethylene has a water absorption of about 0.1%. On the other hand ineffective membranes such as water based acrylic emulsions absorb more than 10% water under these conditions. To accurately judge a membrane s waterproofing effectiveness, or otherwise, waterproofing membrane data sheets must disclose the % weight of water absorbed when immersed for 4-7days at 50 C and 23 C. Real world waterproofing membrane failure: Water is always trapped beneath tiles directly stuck to the surface of a membrane, causing it to remain constantly wet. It is this constant wetness that creates the conditions for membrane failure by water absorption. A common finding in membrane samples taken from site, is the surprisingly high levels of absorbed water, often more than 50%. Such absorption of water by a waterproofing membrane causes it to swell, giving a loss of tensile strength and adhesion, delamination/fracturing of tiles, fracturing of grout lines, and leading to further water ingress. A number of standards have attempted to use such indirect methods to demonstrate a waterproofing membrane; but with the NZBC regulatory requirements only an equilibrium water absorption test will provide the data required for durability. Laboratory prepared membrane samples immersed in water at 23 C and 50 C show that water absorption is a slow process that may take weeks or even months to generate an equilibrium water result. The rate that membranes absorb water is a function of the formulation/ composition Liquid applied acrylic, APP modified bitumen sheet, PVC sheet, Polyethylene sheet, etc.
3 Waterproofing Membranes August 2016 Page 3 of 14 Swelling and wrinkling of urethane membrane beneath tiles due to water absorption. Swelling and deformation of acrylic membrane during lab testing due to water absorption. Water on acoustic cork mat substrate transmitted through bitumen/sbs membrane due to water absorption.
4 Waterproofing Membranes August 2016 Page 4 of 14 Water transmitted through an acrylic membrane due to water absorption, on concrete substrate. Swelling and dimensional change due to water absorption of two equal sized sheets of the same acrylic membrane during lab testing.
5 Waterproofing Membranes August 2016 Page 5 of 14 Cracking of tiles and grout due to membrane swelling causing jacking effect due to water absorption. Osmotic blistering: The Second Law of Thermodynamics also applies to the formation of osmotic blisters, which are caused by differences in salt concentration. When water is trapped against a semipermeable membrane surface, and salts are present either within the body of the membrane (as part of the formulation) or on the opposite side (such as from a concrete substrate) water is transmitted to even out the salt concentration. This results in large water filled blisters being formed in the body of the membrane. Osmotic blister formation between 2 layers of urethane membrane beneath tiles. Osmotic blisters in urethane membrane filled with water and solvents beneath tiles.
6 Waterproofing Membranes August 2016 Page 6 of 14 Other failure mechanisms: Compatibility issues have also occasionally been found. These are usually obvious due to other components such as acoustic barriers being present, and the dramatic effects on the membrane integrity. Poor welding of bitumen sheet membranes at lap joints, or tearing of the membrane at movement joints allowing water ingress. UV degradation caused by exposure to sunlight. Poor lap formation between APP modified bitumen membranes allowing water ingress. Degradation and cracking of SBS modified bitumen membrane due to UV exposure. Applicable NZ Regulations and Standards for waterproofing membranes The NZ Building Code contains a number of Definitions, and Regulations for building elements (which includes membranes), which have been tested in the Courts and upheld. The definitions relating to membranes follow. Building Code Handbook definitions: Term Damp-proof membrane (DPM) Impervious Membrane Waterproof and waterproofing Definition A sheet material, coating or vapour barrier, having a low water vapour transmission, and used to minimise water and water vapour penetration into buildings. Usually applied against concrete in contact with the ground. (Also known as a concrete underlay.) Surprisingly this membrane type is almost invariably Polyethylene sheet, which is the most waterproof of all membranes we have tested, and yet it is referred to as damp-proof? That which does not allow the passage of moisture. A non-metallic material, usually synthetic, used as a fully supported roof cladding, deck surface or, in conjunction with other claddings, as gutters or flashings. The complete and total resistance of a building element to the ingress of any moisture.
7 Waterproofing Membranes August 2016 Page 7 of 14 The NZ Building Code contains the following regulatory clauses which apply to membranes. Clause B1 Structure: Functional Requirement B1.2- Buildings, building elements and sitework shall withstand the combination of loads that they are likely to experience during construction or alteration and throughout their lives. Performance B Account shall be taken of all physical conditions likely to affect the stability of buildings, building elements and sitework including: a) Self-weight b) Imposed gravity loads arising from use c) Temperature d) Earth pressure e) Water and other liquids m) Differential movement n) Vegetation q) Time dependant effects including creep and shrinkage (e.g. due to absorption and swelling) B Due allowance shall be made for: a) The consequences of failure d) Variation in the properties of materials and the characteristics of the site Clause B2 Durability: Functional Requirement B2.2- Building materials, components and construction methods shall be sufficiently durable to ensure that the building, without reconstruction or major renovation, satisfies the other functional requirements of this code throughout the life of the building. This sets out a durability requirement of 50years for tanking and beneath concrete slabs, and 15years for membranes on top of concrete slabs, behind tiles, and for roofing membranes. Verification Method B2/VM requires consideration of the in-service exposure of a building element (3) for: a) Length of service (e.g. 15 or 50 years?) b) Environment of use (e.g. exterior or interior?) c) Intensity of use (think about this!) d) Reaction with adjacent material (compatibility?) e) Limitations of performance (do people read labels/ data sheets etc?) f) Degree of degradation (e.g. UV exposure) Clause E2 External Moisture Functional Requirement E2.2- Buildings must be constructed to provide adequate resistance to penetration by, and the accumulation of, moisture from the outside. Acceptable Solution E2/AS Limitations- This Acceptable Solution is limited to membranes composed of butyl or EPDM installed over plywood substrates E2/AS Butyl and EPDM- Butyl rubber and EPDM rubber sheet on timber, and system components used for membrane roofing or decks shall: b) Comply with the following parts of Table 1 in ASTM D6134: iii) Water absorption (maximum 2% for butyl and 4% for EPDM) iv) Water vapour permeance Clause E3 Internal Moisture Functional Requirement E3.2- Buildings must be constructed to avoid the likelihood of: (b) Free water overflow penetrating to an adjoining household unit; and (c) Damage to building elements being caused by the presence of moisture.
8 Waterproofing Membranes August 2016 Page 8 of 14 Acceptable Solution E3/AS Showers- b) Ceramic or stone tile finishes shall be laid on a continuous impervious substrate or membrane. NZ and International Standards, and Industry Codes of Practice While the regulatory environment, and types of site failures set out previously are reliable and must be kept in mind, we now enter the much less certain world of Standards. These should be considered much more carefully, due to their method of development, process of review for ongoing approval or not, and the industry funding of their development. AS/NZS 4858:2004 for wet area membranes The NZBC clause E2/AS1 used to state that wet area membranes (waterproof?) must meet the requirements of NZS 4858:2004. This no longer appears to be the case. However NZS 4858:2004 still appears in in the Concrete Code of Practice CCP:01 and some of the Membrane Code of Practice documents. It must be struck down as: NZS4858:2004 requires testing of a membrane by the methods given in AS Testing of plastics, composite materials, and sanitary plumbing fixtures. A water absorption test is performed by one sided exposure to water for 24hrs at room temperature- Result to be recorded? Water vapour transmission rate (WVTR), is tested by ASTM E96/M. The result if >8g/sqm/day, and if it is to be used on particleboard, the water absorption into the particleboard must be <10%. This approach is not sufficient for testing the long term performance/durability of waterproof membranes for the following reasons: 1. The NZBC requires a minimum 15 year durability to be assessed on a 24hour test period only? NZ frequently has wet weather for more than 24 hours at a time, also entrapment of water beneath tiles leads to constant wetness. 2. But in NZS4858:2004 there is no maximum specified water absorption! Rather, the result is simply recorded and reported, and frequently not disclosed in technical documentation. 3. WVTR by ASTM E96 can only be carried out on carefully prepared lab samples, is useless for testing field samples for compliance, neither does it provide any assurance as to durability. 4. Neither of these test methods respond to the primary definitions requiring a response in the NZBC, or in NZS 4858:2004 own scope; is it waterproof? Default Standards for membranes We have carried out a review of applicable standards for waterproofing membranes, and as you can see the most comprehensive are the ASTM standards, but they are not perfect. To clarify the standards that provide testing criteria that will provide reliable data for Durability assessment, we have highlighted those titles in green. Disclosure Bill Grayson sits on the ASTM technical committee D08 for roofing and membrane materials.
9 Waterproofing Membranes August 2016 Page 9 of 14 Membrane Type Liquid Applied Neoprene and Chlorosulfonated Polyethylene used in Waterproofing and Roofing ASTM Standard Specification Number ASTM Standard Test Number Immersion Test Parameters D D C 4% Max Water Absorption EPDM Sheet used in Single Ply Roof Membrane D4637 / D4637M-14e1 D C Range +8, -2% Nonvulcanised (Uncured) Rubber Sheet used as Roof Flashing Type 1 only Reinforced Chlorosulfonated Polyethylene sheet used in Single Ply Roof Membrane Withdrawn 2011 Liquid Applied Acrylic Coating used in Roofing Withdrawn 2014 Atactic Polypropylene Modified Bituminous Sheet Materials using Polyester Reinforcing D (2013)e1 D471 Type 70 C Type 70 C D a D C 10% D D C 20% D6222 / D6222M-11 D C 3.2% Range +8, -2% Atactic Polypropylene Modified Bituminous Sheet Materials using a Combination of Polyester and Glass Fibre Reinforcing Atactic Polypropylene Modified Bituminous Sheet Materials using Glass Fibre Reinforcing D6223 / D6223M- 02(2009)e1 D6509 / D6509M- 09(2015) D C 3.2% D C 3.2% Thermoplastic Polyolefin based Sheet Roofing D6878 / D6878M-13 D C 3.0% Liquid Applied, Single Pack, Moisture Triggered, Aliphatic Polyurethane Roofing Membrane Withdrawn 2013 D ASTM E96 / E96M 14 Desiccant method Water Vapour Transmission 32 50% RH permeability Max = 8.52 g/m²/day Spray Polyurethane Foam used for Roofing Applications D7425 / D7425M-13 D C 5% v/v Standard Specification for High-Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane With C957 NA NA NA Integral Wearing Surface Fiberglass Reinforced Styrene-Butadiene-Styrene (SBS) Modified Bituminous Sheets with a Factory Applied Metal Surface D D C 1.0% Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements D6162 / D6162M- 00A(2015)e1 NA NA NA Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using Glass Fiber Reinforcements D6163 / D6163M- 00A(2015)e1 NA NA NA Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using Polyester Reinforcements D6164 / D6164M-11 NA NA NA Thermoplastic Fabrics Used in Cold-Applied Roofing and Waterproofing Thermoplastic Fabrics Used in Hot-Applied Roofing and Waterproofing D5665 / D5665M- 99a(2014)e1 D (2013) NA NA NA NA NA NA Standard Specification for Vulcanized Rubber Sheets Used in Waterproofing Systems D (2013) D C Type 1- EPDM 4% Type 2- Butyl 2%
10 Waterproofing Membranes August 2016 Page 10 of 14 Membrane Type Australian/New Zealand Standards for Wet Area Membranes Australian/New Zealand Standards for Wet Area Membranes ISO EN DIN-Plastics/ Lloyds Register European/British Standards for coatings for exterior masonry and concrete Standard Number AS/NZ 4858:2004 AS/NZ 4858:2004 European/British Standards for liquid-applied water BS EN impermeable products for 14891:2012 use beneath ceramic tiling bonded with adhesives European Standards for plastics- determination of water absorption ISO 62:2005 Methods 1-3 Standard Test Method AS (AS Methods of testing plastics and composite materials sanitary plumbing fixtures. Method 1: Determination of water absorption characteristics) ASTM E96 / E96M 14 Desiccant method Immersion Test Parameters Max Water Absorption Room Temperature Record and Report 32 50% RH EN1062.1:2004 EN1062.3: C DIN EN ISO 62:2008 BS EN 14891:2012 Method A.7 DIN EN ISO 62:2008 Method 1 23 C and 150 kpa Until 23 C Suitability for use over particleboard = 10% gain in moisture content of particleboard If >8g / m² / day. Testing to AS will be required for suitability over particleboard Class 1 High- <0.5 kg/(m²xhr 0.5 ) Class 2 Medium kg/(m²xhr 0.5 ) Class 3 Low- <0.1 kg/(m²xhr 0.5 ) No penetration and 20g weight gain of concrete/membrane sample NA The ASTM standards test a variety of membrane types in different ways and with different specifications, however the common themes of the test methods are: a) Water immersion for ~7days/166hrs at 23 C Specification < 4% b) Water immersion for ~4days/100hrs at 50 C Specification < 3.2% c) Water immersion for ~7days/166hrs at 70 C Specification < 3.0% The good news about these three water immersion performance criteria is that they readily allow testing of field samples of problem membranes. Recently a number of ASTM standards have been withdrawn, it is worth noting that the withdrawn standards all have water absorption >10%. The use of water absorption testing to ASTM standard methods is a key requirement for determining the durability of any waterproofing membrane, and is referenced in a number of leading professional publications. Will a particular membrane waterproof a structure? To clarify this question, we decided to test a number of membrane samples by ASTM methods, using water immersion at 23 C and 50 C, until they reached equilibrium, and stopped absorbing water. This data is presented for 24 unnamed membranes, all having been available in the NZ market, and all tested for 4-30 days as follows: a) 23 C water immersion results ASTM D471 b) 50 C water immersion results ASTM D5147 The results are separated into membrane families for ease of understanding: a) Liquid applied Acrylic emulsion b) Liquid applied Urethane c) Modified bitumen and sheet membranes Please note that the vertical Y axis on the following graphs vary, so please check the values. Note: this testing is currently being repeated to accommodate changes in formulations and product availability in NZ since 2011 when this data was generated.
11 Waterproofing Membranes August 2016 Page 11 of 14 Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full
12 Waterproofing Membranes August 2016 Page 12 of 14 Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full
13 Waterproofing Membranes August 2016 Page 13 of 14 Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full Grayson Wagner Co Ltd, 4 Cain Rd Penrose. Ph: Web: This document remains the property of Grayson Wagner Co Ltd and may not be copied except in full
14 Waterproofing Membranes August 2016 Page 14 of 14 Conclusions from test data We are firmly of the view that the NZ Building Code approach is correct and robust, and that waterproofness of waterproofing building elements is a legally binding obligation on suppliers that must be achieved. Consequently any membrane that serves a waterproofing function should not absorb more that 3% water at equilibrium. From the data presented, this equilibrium will be effectively established after 7days immersion in water at 50C, if less than 3% water is absorbed. At this stage of their development we have not found any liquid applied membranes which could be considered for waterproofing applications. In general torch-on or welded seam sheet membranes appear to provide durable performance; but be very afraid if they utilise adhesive based lap joints if these adhesives have not been so tested. Welded aluminium or stainless steel shower trays, fitted with O-ring gully traps remain a robust solution. Other significant influences on waterproofing membrane success or failure From this data, it is clear that higher water immersion temperatures increase a membrane s rate of water absorption. Water absorption can be a reversible process if heat energy is applied, so periods of drying will reduce water content, if only temporarily. Useful improvements to system design are: a) Provide an air gap above the membrane, such as through the use of tile jacks. Capillary action will keep a membrane constantly wet when in contact with a wear surface. This severely limits the long standing industry method of direct sticking tiles to waterproofing membranes. b) Ensure good falls with no ponding to reduce water contact time. c) Choose a membrane with the lowest possible water absorption- ask to see water absorption data for that membrane for at least 7days at 50 C!!! Protect membranes from UV light, which generally causes membrane surface breakdown Check compatibility of the membrane with all the components that it will be exposed to. Example: Peel and stick membranes on LOSP treated framing timber? Please do not hesitate to contact us if you require specific advice, and remember: The quoted price is never the final cost! This paper remains the copyright property of Grayson Wagner Co Ltd, but is freely available in PDF at on the condition that it may only be copied, or reproduced in full.
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane
DENSO WATERPROOFING SYSTEMS
DENSO WATERPROOFING SYSTEMS Approved Quality Management System AS/NZS ISO 9001:2008 Lloyds Register Certificate N o Mel 0927759 Denso (Australia) Pty Ltd A MEMBER OF WINN & COALES INTERNATIONAL 411 413
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING
USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING Welcome to Gripset Betta, Over the past 3 decades through the tireless commitment to improve and enhance the way buildings are waterproofed,
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades
Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial
BELOW GROUND TANKING
BELOW GROUND TANKING Basement & Foundation Waterproofing Systems - What, Why & How By Paul Evans MBAV Specialist Contractor, Registered Building Practitioner Vice President Australian Institute of Waterproofing
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.
Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA 18000 / Israel. J. Magner Dipl.-Ing. N. Machill.
Kiwa Polymer Institut GmbH Quellenstraße 3 65439 Flörsheim-Wicker Tel. +49 (0)61 45-5 97 10 Fax +49 (0)61 45-5 97 19 www.kiwa.de Test report P 7013-E Testing order: Test of the waterproofing system based
Table of Contents. Benefits of UNIFLEX Fluid Applied Roofing Systems 2 3. Elastomeric Finish Coats 4 5. Aluminum Finish Coats 6
PORTFOLIO Table of Contents Benefits of UNIFLEX Fluid Applied Roofing Systems 2 3 Elastomeric Finish Coats 4 5 Aluminum Finish Coats 6 Asphalt Emulsion Coatings 7 Base Coats & Primers 8 9 Patch & Repair:
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures
WATERPROOFING PRODUCTS
PARCHEM CONSTRUCTION SUPPLIES WATERPROOFING PRODUCTS THE LEADING CHOICE FOR THE WATERPROOFING INDUSTRY IN AUSTRALIA WATERPROOFING PRODUCT SPECIALISTS Reliable waterproofing is essential to ensure the longevity
System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY
CI/SfB Oct 12 (47) Ln Uniclass L524 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY Bailey Flame-free felt roofing Bailey
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
MASTICS. 275 Centre St., Unit 15 Holbrook, MA 02343 (617) 996-0400. 15236 Shedd Rd. Middlefield, OH 44062 (440) 345-6900
MASTICS AQUAHALT MASTIC- A AQUAHALT MASTIC- A is a heavily consistent, trowel- applied mastic formulated with refined asphalt, fibers and solvent. It is designed as an all- purpose repair cement, it bonds
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
Roof Systems Overview
Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Gas Membrane and Waterproof Tanking Systems
Gas Membrane and Waterproof Tanking Systems Improving Choice, Quality & Service Why Choose Miers? About Miers Miers Construction Products is an independent supplier of construction products delivering
waterproofing products
P A R C H E M C O N S T R U C T I O N S U P P L I E S waterproofing products The leading choice for the waterproofing industry in Australia P: 1800 801 108 www.parchem.com.au Construction Products Parchem
EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES
Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING
LAMA has developed over the years a wide range of products that can be used in the waterproofing
LAMA has developed over the years a wide range of products that can be used in the waterproofing and damp-proofing of roofs, decks, car parkings, walls, foundations, basements, roads, etc. In this catalogue,
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
Fosroc Proofex Engage
Technical Data Sheet Pre-applied waterproofing membrane conforming to the requirements of BS EN 13967:2004 and BS 8102:2009. Proofex Engage mechanically bonds to poured concrete, remaining in place if
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com
AND MEMBRANES 010 ROOFING UNDERLAYS 1 HO DOES YOUR ROOF BREATHe? MEMBRANES THE WAY to A WARM AND DRY ROOF HO HO HO HO HO HO WATERTIGHTNESS The FAKRO Company offers a wide range of membranes and underlays
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
4. Cryogenic gloves are generally designed to protect the hands from intense cold or heat.
PROTECTIVE GLOVES In many University laboratories, exposure to chemicals, infectious agents, sharp objects, extreme temperatures and other hazards can create a potential for injury to the hand. Wherever
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
European Technical Assessment ETA-15/0028 of 23/02/2015
ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet ww.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011 of
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Comment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to [email protected] by October 10 th, 2012 with the subject line
CREEK Technical Services, LLC
EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality
USER GUIDE Easier, Safer, Betta! gripsetbetta.com WATERPROOFING
USER GUIDE Easier, Safer, Betta! WATERPROOFING INDEX Welcome to the Gripset Betta Range Over the past 3 decades through the tireless commitment to improve and enhance the way buildings are waterproofed,
CHAPTER I. INTRODUCTION
CHAPTER I. INTRODUCTION 1.1 Background There is a national need to develop asphalt wearing surfaces for modern timber bridges that are not only skid resistant, but also limit the transport of moisture
DELTA Premium Moisture Management Systems for Foundations.
DELTA protects property. Saves energy. Creates comfort. DELTA Premium Moisture Management Systems for Foundations. DELTA Premium Moisture Management Systems provide the best protection for foundations.
Construction. 3-part thixotropic epoxy patching mortar. Product Description. Tests
Product Data Sheet Edition 05/12/2014 Identification no: 020204030010000044 Sikadur -41 CF Rapid 3-part thixotropic epoxy patching mortar Construction Product Description Uses Characteristics / Advantages
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
ROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
Membrane Roofing. Advances in Membrane Roofing
Advances in An American Institute of Architects (AIA) Continuing Education Program Membrane Roofing Credit for this course is 1 AIA HSW CE Hour Advances in Membrane Roofing Course Sponsor POLYGLASS USA,
Chapter 2 Basis of design and materials
Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
THORO. Waterproofing Systems
THORO Waterproofing Systems Contents Welcome to the world of Thoro 3 Waterproofing 4 Thoroseal 5 Thoroseal FC 6 Thoro Acryl 60 6 Thoroseal WR 7 Thoroseal FX100 8 Thoroseal FX110 9 Thoroseal FX 1K 10 Thoro
3 BUILT-UP ROOFING THE RUBEROID BLUE BOOK
3 BUILT-UP ROOFING 3.1 MATERIALS 3.2 APPLICATION TECHNIQUES 3.3 SURFACE PROTECTION 3.4 TYPICAL SPECIFICATIONS 3.5 BUILT-UP ROOFING DETAIL DESIGN 3.6 TYPICAL DETAILS 3.1 MATERIALS INTRODUCTION Bituminous
Dow Corning PROPRIETARY. Dow Corning. A Thermal Modelling Comparison of Typical Curtain Wall Systems
Dow Corning A Thermal Modelling Comparison of Typical Curtain Wall Systems Introduction Today s Aim To understand the meaning of a U value and window energy ratings Discuss the drivers for energy efficiency
Including. Rubershield-Pro. Breather Membrane
Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against
Moisture Control. System Solutions to Prevent Mold
System Solutions to Prevent Mold How a systems approach to managing moisture is the most effective strategy for minimizing the growth of mold. Moisture Control Architects, designers, contractors and maintenance
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM This Appraisal replaces BRANZ Appraisal No. 573 (2007). Amended 05 February 2016. BRANZ Appraisals Technical Assessments of products for building and construction.
ROOF FLASHING SPRINGLOK FLASHING SYSTEM FEATURES & BENEFITS PRODUCT DESCRIPTION
SPRINGLOK SYSTEM PRODUCT DESCRIPTION FEATURES & BENEFITS Fry Reglet offers five flashing systems, each tailored for a particular type of substrate so you can get exactly what you need. SM Surface mounted
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
Polymeric membrane for roof waterproofing
Product Data Sheet Edition 09.2008 Revision no: 0 Identification no: 01 09 01 02 200 0 120000 Sarnafil TS 77-12 Polymeric membrane for roof waterproofing Construction Product Description Uses Characteristics
FATRA ROOF COVERING SYSTEMS FATRAFOL FF807 AND FATRAFOL FF807/V ROOF COVERING SYSTEMS
Fatra UK Ltd Unit 12 The Timber Yard East Moors Road Ocean Park Cardiff CF24 5EE Tel: 029 2048 7954 Fax: 029 2048 9226 e-mail: [email protected] website: www.fatra.co.uk FATRA ROOF COVERING SYSTEMS APPROVAL
Adhesive Recommendation for Altro Flooring. Porous (absorbent) subfloors (most wood subfloors and some concrete)
Adhesive Recommendation for Altro Flooring Product Safety Sheet Flooring Smooth Sheet Flooring Porous (absorbent) subfloors (most wood subfloors and some concrete) Altrofix 30/31 (excessively heavy rolling
December 2013. J-Ply Roofing, Flooring and Decking
December 2013 J-Ply Roofing, Flooring and Decking Introduction J-Ply plywood is manufactured in New Zealand by Juken New Zealand Limited (JNL) and marketed by New Zealand Wood Products Limited. The J-Ply
Photo courtesy of Delta Stone, Heber City, UT. Installation Solutions for: Manufactured Stone, Natural Thin Veneer, and Thin Brick
Photo courtesy of Delta Stone, Heber City, UT Installation Solutions for: Manufactured Stone, Natural Thin Veneer, and Thin Brick THIN VENEER INSTALLATION SYSTEMS PREMIUM BONDING MORTARS Premium PCL Stone
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls.
Improving the flood resistance of your home Advice sheet 4: Flood-resilient walls. This sheet provides guidance on identifying different types of wall, and reducing the flow of floodwater through them
WATERPROOFING OF WET ROOMS
WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof
Rockwool Cladding Roll
Rockwool Cladding Roll High performance industrial insulation has been specifically developed for use in lightweight cladding applications to commercial or industrial framed buildings. Cladding Roll U/F
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
Essential Performance Attributes of Preapplied waterproofing
Essential Performance Attributes of Preapplied waterproofing Craig Boucher, LEED AP Grace Construction Products 62 Whittemore Ave., Cambridge, MA 02140 Phone: 617-498-4429 Fax: 617-498-4419 E-mail: [email protected]
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
MULTI ROOFING. Our Services. www.multiroofing.ie www.multiroofing.co.uk
Our Services www.multiroofing.ie About Us MultiRoofing Systems Ltd was established in 1992 to meet the needs of a growing construction industry in Ireland. Through organic sustainable growth, MultiRoofing
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION
Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows
TORCH ON WATERPROOFING
a.b.e. is an ISO 9001:2008 registered company PO Box 5100, Boksburg North, 1461, South Africa Website: www.abe.co.za Tel: +27(0) 11 306 9000 Durban Johannesburg Cape Town Port Elizabeth East London Bloemfontein
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
Standard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products
GUIDE SPECIFICATION FOR GENERAL CLEANING AND REMOVAL OF MOLD AND MILDEW ON EXTERIOR INSULATED AND FINISH SYSTEMS AND STUCCO DIVISION 07240 and DIVISION 09240 8/05 PART I: GENERAL 1.01 DESCRIPTION AND SCOPE
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
POLYGLASS ROOF WATERPROOFING MEMBRANES POLYSHIELD ROOF WATERPROOFING MEMBRANES
Polyglass SpA Via dell Artigianato, 34 31047 Ponte di Piave Treviso Italy Tel: 00 39 042 27547 Fax: 00 39 042 2854118 e-mail: [email protected] website: www.polyglass.com POLYGLASS ROOF WATERPROOFING MEMBRANES
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS Research & Development Division RD/GN/033 June 2008 THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE
Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure
Basements are Changing John Straube, Ph.D., P.Eng Basements: New & Retrofit Energy Efficient, Durable, Healthy Increasingly used as living space Not a root /coal cellar anymore! High quality space expected
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
Physically Crosslinked Foam Insulation
Physically Crosslinked Foam Insulation Thermobreak is the original All in One flexible thermal insulation made from physically crosslinked closed cell polyolefin foam, factory fused to a reinforced 9um
Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
Annex of the certificate (Page 1/6) Accreditation Scope
As a Testing Laboratory Annex of the certificate (Page 1/6) Accreditation Scope Address: Küçük Çiğli Mh. 8780/1 Sk. No:5 Çiğli 35681 İZMİR / TÜRKİYE Phone : 0 232 376 24 25 Fax : 0 232 386 33 98 E-Mail
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
Moisture Mitigation for Concrete Slabs
Moisture Mitigation for Concrete Slabs A brief description of alternative methods for dealing with slab moisture problems By Peter A. Craig M oisture-related problems with floor coverings and coatings
INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.
INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
3M Scotchkote Roofing Liquid Membrane Systems. roofing solutions
3M Scotchkote Roofing Liquid Membrane Systems Futureproof roofing solutions About 3M 3M Practical and ingenious solutions that help customers succeed 3M is a $24.5 billion diversified technology company
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING. 16.1 General...16-1. 16.2 Materials...16-1. 16.3 Equipment...
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING TABLE OF CONTENTS 16.1 General...16-1 16.2 Materials...16-1 16.3 Equipment...16-1 16.4 Installation...16-2 16.4.1 Traffic Restrictions...16-2
G VYCOR DECK PROTECTOR. For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects.
For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects. G VYCOR DECK PROTECTOR Self-Adhered Flashing NEW FROM THE MAKERS OF G Ice & Water Shield I Moisture
The assessment is described in the following pages which form integral parts of this certificate, which should be read in its entirety.
Cl/SfB (13.1) Ly (L2) BRE CERTIFICATION LTD CERTIFICATE OF ASSESSMENT PRODUCT Powerbase RB 340 and RB 370 Radon Resistant Membranes CERTICATE NO. 100/03 ISSUED: MARCH 03 REISSUED: NOVEMBER 07 SUPPLIED
Installation Solutions for: Manufactured Stone, Natural Thin Veneer, and Thin Brick ARCHITECTURAL SPECIFICATIONS / CAD MODELS TVISTM WARRANTIES
ARCHITECTURAL SPECIFICATIONS / CAD MODELS With more than 40 years of manufacturing high quality, innovative building products in the commercial and residential markets, Custom Building Products TVISTM