Masonry: Cavity Wall Insulation: Partial Fill Isometric cut-away view

Size: px
Start display at page:

Download "Masonry: Cavity Wall Insulation: Partial Fill Isometric cut-away view"

Transcription

1 Legend Insulation zone Blue text Air tightness barrier (note: this can also act as a vapour control layer) Guidance on thermal continuity Red text Guidance on air tightness Values used in psi calculations Material λ-values used in calculations (W/mK) Plasterboard 0.21 Insulation (generic) 0.04 Plywood sheathing 0.13 Brick outer leaf 0.77 Mineral wool insulation Concrete block 1.13 (dense) protected Concrete block (lightweight, high strength) 0.19 Timber frame 0.13 Concrete floor beam 2.3 Concrete screed 1.15 Render (cement/sand) 1.0 Gypsum plaster 0.4 (1000kg/m3) Concrete roof tiles 1.5 EPDM membrane 0.25 Timber battens 0.13 Timber flooring 0.13 Chipboard 0.13 Floor joists 0.13 Aluminium 160 Steel 50 Stainless steel 17 Glass 1 Sarking felt 0.23 Insulation board Masonry: Cavity Wall Insulation: Partial Fill Isometric cut-away view Plasterboard Service void / protection zone for air tightness membrane (optional) Air tightness barrier Insulation supported within secondary timber stud frame Inner leaf (block shown) Insulation Wall ties Cavity Outer leaf (render on block shown) General guidance notes Alternative constructions 1. The thermal resistance of cavity insulation needs to be greater than that used in the inner leaf insulation, to reduce the risk of interstitial condensation. 2. Different constructions can be used to provide an outer leaf but check that there is sufficient ventilation provision to prevent moisture from being trapped within the wall. Sealing membrane junctions 3. All membranes should be taped, stapled or bedded in adhesive as identified by manufacturer. Repair all tears in membranes before commencing next stage of work. Psi-value calculations 4. For details of all thermal conductivity values of materials used in the psi-value calculations, see also Appendix B of the Introduction. Detail 2.00

2 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 2. Check that roof insulation butts against the cavity wall insulation, with minimum of 50mm overlap at narrowest point 3. Install cavity barrier at the top of the wall. Ventilation gap equivalent to 5mm minimum continuous opening at ridge is required where the roof pitch is greater than 35 or the roof span is more than 10m 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Proprietary cross flow ventilator to maintain minimum 25mm air gap Timber batten to provide fixing for plasterboard sheet Ventilation gap equivalent to 10mm minimum continuous opening is required where roof pitch is above 15 or ventilation gap equivalent to 25mm minimum continuous opening is required where the roof pitch is below 15 Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material in wall and ceiling Insulation between the studs in addition to the cavity insulation. This insulation to be tightly fitted against the wall, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.02 and 2.21 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Ventilated Roofspace - Eaves Detail 2.01

3 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 2. Ensure that roof insulation butts against the gable wall 3. Install cavity barrier at the top of the wall. 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Cavity insulation continued full height of gable or to the top of the loft insulation Insulation between the last truss and the gable wall Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Timber batten to provide fixing for plasterboard sheet in wall and ceiling Insulation between the studs in addition to the cavity insulation. This insulation to be tightly fitted against the wall, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.01 and 2.21 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Ventilated Roofspace - Gable Detail 2.02

4 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 2. Ensure that roof insulation butts against the gable wall 3. Install cavity barrier at the top of the wall. Minimum 50mm ventilation path over insulation 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Insulation between joists and covering cavity insulation Cavity barrier giving 30 minute fire resistance - thin calcium silicate board or similar across top of wall Note: this construction is typically used where there are habitable rooms within the roof construction Where two insulation types are used together see supplementary guidance Timber runner to provide fixing for plasterboard sheet in wall and ceiling Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.04, 2.05 and 2.22 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Ventilated Rafter Void - Gable Detail 2.03

5 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 2. Ensure that roof insulation butts against the cavity wall insulation, with minimum of 50mm overlap at narrowest point 3. Install cavity barrier at the top of the wall Rigid insulation used as sarking Insulation to be vapour permeable Vapour permeable membrane (with a vapour resistance of not more than 0.25MN.s/g) Ventilation gap equivalent to 5mm minimum continuous opening is required at ridge to batten space 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Lap roof and wall insulation minimum 150mm thickness at narrowest point Proprietary over fascia ventilator Ventilation to batten void Timber batten to provide fixing for plasterboard sheet Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Note: this construction is typically used where there are habitable rooms within the roof construction in wall and ceiling Alternative air barrier - parge coat of plaster finish on blockwork Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.03, 2.05 and 2.22 for other junctions using this roof construction Psi value = 0.034W/mK Pitched Roof: Ventilated Batten Void (warm roof) - Eaves Detail 2.04

6 1. Ensure that insulation layers are fitted perpendicularly, to cover junctions 2. Ensure that roof insulation butts against the gable wall 3. Install cavity barrier at the top of the wall. 50mm ventilation path over insulation 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Vapour permeable membrane (with a vapour resistance of not more than 0.25 MN.s/g) Insulation between joists and inner face of the wall Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Note: this construction is typically used where there are habitable rooms within the roof construction Where two insulation types are used together see supplementary guidance Timber runner to provide fixing for plasterboard sheet in wall and ceiling Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.03, 2.04 and 2.22 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Ventilated Batten Void (warm roof) - Gable Detail 2.05

7 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 2. Ensure that roof insulation butts against the gable wall 3. Install cavity barrier at the top of the wall. turned up edge of roof insulation, lapped with roof waterproofing layer and sealed Eaves - fix full height blocking piece and tightly fit insulation into void and under deck Membrane roof construction 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Verge option - tightly fit insulation into void over wall and under deck to maintain thermal continuity Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Vapour control layer in ceiling Timber runner to provide fixing for plasterboard sheet Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling 2. A vapour control layer is required at ceiling level, to prevent moisture from entering into the roof construction 3. The option shown here includes a vapour control layer and insulation as part of a membrane roof construction. Similar details could be used for a profiled metal decking roof but consult with manufacturer regarding ventilation requirements. Roof (m²K)/W Psi value = W/mK Timber Flat Roof Detail 2.06

8 1. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 3. Ensure that roof insulation butts against the gable wall 4. Install cavity barrier at the top of the wall 1. Check that any air tightness barrier used in the ceiling overlaps with the layer in the wall Compressible filler Roofing membrane to be taken minimum 150mm above finished roof level turned up edge of parapet, lapped over top of blockwork and sealed Membrane roof construction in wall and roof Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check ventilation paths are clear before installing insulation above the ceiling 2. A vapour barrier is required at ceiling level, to prevent moisture from entering into the roof construction 3. The option shown here includes a vapour control layer and insulation as part of a membrane roof construction. Similar details could be used for a profiled metal decking roof but consult with manufacturer regarding ventilation requirements. Roof (m²K)/W Psi value = W/mK Timber Flat Roof with Parapet Detail 2.07

9 1. Check that there is no debris in the cavity 2. Install cavity barrier around opening 3. Install insulation in the window reveal Cavity tray with minimum upstand of 140mm and stop ends 1. Install window to overlap with outer leaf of wall finish. Alternative: If window lines through with the bottom of the opening in the external finish, some means of preventing a direct line of air infiltration will be required 2. Install air tightness seal between the inside face of the window and the structural finish of the window opening. 30 minute fire resisting proprietary insulating cavity barrier with integral DPC - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Sealant at window frame If position of window head is lower than or level with the underside of the lintol, a larger compressible filler will be required to stop up a potential air infiltration route Insulate the window reveal Air tightness tape Sealant to back of frame Insulation to be tightly fixed back to inner leaf of wall Vapour control layer Lintol - any type Compressible fill Detail shows window fixed to plywood frame set into window opening Note: the timber batten in window reveal is shown smaller than actual size, to allow the membrane corner strip to be seen 1. Alternative internal finish at window reveal - use insulation backed plasterboard General notes 2. The window head and jamb details shown have used a plywood box lining around the window opening in the internal leaf of the wall, to allow for window fixings. Alternative details are possible but the continuity of insulation and air tightness should be considered. Insulated plasterboard (m²K)/W Psi value = W/mK Lintel at Window Head Detail 2.08

10 1. Check that there is no debris in the cavity 2. Install cavity barrier around opening 3. Install insulation in the window reveal 30 minute fire resisting proprietary insulating cavity barrier with integral DPC Sealant at window frame 1. Install window to overlap with outer leaf of wall finish. Alternative: If window lines through with the external jamb, some means of preventing a direct line of air infiltration will be required 2. Install air tightness seal between the inside face of the window and the structural finish of the window opening. Air tightness tape and sealant to back of frame Insulate the window reveal Detail shows window fixed to plywood frame set into window opening Psi value (jamb) =0.2224W/mK Psi value (cill) =-0.02W/mK Compressible filler between window and cill Solid cill acts as cavity closer. If pressed cill is used, a 30 minute fire rated thermally insulated cavity closer will be required DPC lapped behind cill and below window 30 minute fire rated thermally insulated cavity barrier Jamb detail Air tightness tape and sealant to back of frame Insulate the window reveal Windows and Doors - Jambs and Cills Air tightness barrier in wall Note: the timber battens in the window reveal and cill are shown smaller than actual size, to allow the membrane corner strip to be seen in wall Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps Cill detail 1. Alternative internal finish at window reveal - use insulation backed plasterboard General notes 2. The window head and jamb details shown have used a plywood box lining around the window opening in the internal leaf of the wall, to allow for window fixings. Alternative details are possible but the continuity of insulation and air tightness should be considered. Insulated plasterboard (m²K)/W Detail 2.09

11 1. Use a perimeter strip of insulation where the concrete slab abuts the concrete blockwork wall 2. Ensure that insulation level in external wall overlaps with the insulation at the floor slab Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant below timber floor finish 1. Check that any air tightness barrier used in the wall overlaps with the layer in the floor The wall insulation installed below the wall dpc must be fit for purpose with regards to water absorption External ground level Psi value = W/mK Ground Bearing Floor: Insulation Above Slab Damp proof membrane above or below slab 20mm strip of perimeter insulation with thermal conductivity (λ value) not exceeding W/mK around slab and any screed 1. Check that concrete slab is level and clear of debris before fitting the insulation at floor level 2. If a screed finish is used instead of a timber floor, use a strip of perimeter insulation with a minimum R value of 0.75 m²/kw for the depth of the screed Alternative detail 3. Using lightweight blockwork (e.g. with λ value of 0.19W/mK) to improve the thermal performance at the junction where the external wall and ground floor constructions meet will change the psi value Insulated perimeter strip (m²k)/w Floor (m²k)/w Detail 2.10

12 1. Use a perimeter strip of insulation where the concrete slab abuts the concrete blockwork wall 2. Ensure that insulation level in external wall overlaps with the insulation at the floor slab Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant 1. Check that any air tightness barrier used in the wall overlaps with the layer in the floor The wall insulation installed below the wall dpc must be fit for purpose with regards to water absorption External ground level Damp proof membrane 20mm strip of perimeter insulation with thermal conductivity (λ value) not exceeding W/mK around slab and any screed 1. If a screed finish is used instead of a timber floor, use a strip of perimeter insulation with a minimum R value of 0.75 m²/kw for the depth of the screed Alternative detail 2. Using lightweight blockwork (e.g. with λ value of 0.19W/mK) to improve the thermal performance at the junction where the external wall and ground floor constructions meet will change the psi value Insulated perimeter strip (m²k)/w Floor (m²k)/w Psi value = 0.175W/mK Ground Bearing Floor: Insulation Below Slab Detail 2.11

13 1. Use a perimeter strip of insulation between the floor joists and blockwork wall 2. Ensure that insulation level in external wall overlaps with the insulation at the floor construction Minimum 50mm strip of insulation with thermal conductivity (λ value) not exceeding W/mK should be installed between wall and the last joist Use air tightness tape at junction of air barrier in wall and floor. Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant Air tightness barrier below timber floor finish 1. Check that any air tightness barrier used in the wall overlaps with the layer in the floor External ground level Solum Floor joist ends supported on joist hangers or using scarcement wall Insulation directly under flooring - supported on netting draped over joists and stapled at the required depths Damp proof membrane Sub floor ventilation should be provided, minimum 1500mm² per run of external wall or 500mm² per m² of floor area 1. Check that all ventilation paths are clear before installing the floor insulation Alternative detail 2. Using lightweight blockwork (e.g. with λ value of 0.19W/mK) to improve thermal performance at the junction where the external wall and ground floor constructions meet will change the psi value 3. If there are concerns about damaging the air tightness membrane in the floor finish during construction, an additional services void can be created using timber battens on top of the floor joists Insulated perimeter strip (m²k)/w Floor (m²k)/w Psi value = W/mK Timber Suspended Ground Floor Detail 2.12

14 Design stage 1. Install thermally insulated cavity barrier in line with separating wall 2. Check that there is no debris in the cavity Cavity barrier giving 30 minute fire resistance - ensure cavity barriers are not breeched by inappropriate insulation material 1. Check that any air tightness barrier used in the internal wall overlaps with the layer in the external wall Minimum specification of 8kg/m2 gypsum based plasterboard required if 13mm plaster not used, to comply with acoustic requirements Air tightness layer, 13mm plaster shown 1. Check that insulation is fitted tightly to concrete block wall at corner junctions For more information on acoustic details see guidance in Section 5 of the Technical Standards Psi value = W/mK Separating Wall Detail 2.13

15 1. Check that there is no debris in the cavity Vapour barrier lapped over corner junction and taped to surface of floor construction Design stage 1. Check that any air tightness barrier used in the external wall is secured onto the floor slab 2. If plaster is use as an air tightness barrier seal over junction at floor with barrier tape below timber floor finish lapped over corner junction and taped to underside of floor construction Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps Alternative air barrier - parge coat of plaster finish on blockwork 1. Check that insulation is tightly fixed into the studs adjacent to the floor junction, leaving no gaps Separating floors require to comply with Section 2: Fire and Section 5: Noise Psi value = W/mK Concrete Separating Floor Detail 2.14

16 1. Check that there is no debris in the cavity lapped over corner junction and taped to air tightness barrier Air tightness barrier corner strip lapped over top of joists and joist hangers 1. Check that any air tightness barrier used in the internal wall overlaps with the layer in the floor or ceiling Alternative: If the air tightness barrier is installed onto the face of the blockwork wall and runs continuously through the floor construction, infill any gaps where floor fixing is made to external wall Minimum 50mm strip of rigid insulation with thermal conductivity (λ value) not exceeding W/mK should be installed between joists Joists shown supported on joist hangers Air tightness barrier to be continuous behind joists in wall Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps Alternative air barrier - parge coat of plaster finish on blockwork 1. Check that insulation is tightly fixed into the studs adjacent to the floor junction, leaving no gaps Insulated infill strip (m²K)/W Psi value = W/mK Timber Intermediate Floor Detail 2.15

17 1. Ensure that insulation is tightly fitted to the back of the masonry wall Air tightness barrier in wall (plaster option shown) Use air tightness tape at junction of air barrier in wall and floor. Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant Air tightness layer below timber floor finish 1. Check that any air tightness barrier used in the wall overlaps with the layer in the floor 2. Consider gluing joints between floor boards Insulation directly under flooring - supported on netting draped over joists and stapled at the required depths Solum Damp proof membrane Sub floor ventilation should be provided, minimum 1500mm² per run of external wall or 500mm² per m² of floor area 1. Check that all ventilation paths are clear before installing the floor insulation Alternative Detail 2. Lightweight thermal blockwork can be used in the separating wall to improve the thermal performance but this will also reduce the acoustic performance of the wall. If this alternative is used then additional elements will be required to meet Section 5 of the Technical Standards. Internal Wall (m²k)/w Floor (m²k)/w Psi value = W/mK Ground Floor / Separating Wall junction - Timber susp. floor Detail 2.16

18 1. Ensure that insulation is tightly fitted against the separating wall Tape corner strip of air tightness membrane over wall / floor junction Air tightness barrier in wall (plaster shown) Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant Minimum 50mm strip of insulation with thermal conductivity (λ value) not exceeding W/mK should be installed between wall and the slab in floor 1. Check that there are no gaps between the wall and floor constructions 2. Check that any air tightness barrier used in the wall overlaps with the layer in the floor Damp proof membrane 1. If a screed finish is used instead of a timber floor, use a strip of perimeter insulation with a minimum R value of 0.75 m²/kw for the depth of the screed Alternative Detail 2. Lightweight thermal blockwork can be used in the separating wall to improve the thermal performance but this will also reduce the acoustic performance of the wall. If this alternative is used then additional elements will be required to meet Section 5 of the Technical Standards. Insulated infill strip (m²k)/w Floor (m²k)/w Psi value = W/mK Concrete Ground Floor/ Separating Wall: Insulation Below Slab Detail 2.17

19 1. Ensure that insulation is tightly fitted against the separating wall Tape corner strip of air tightness membrane over wall / floor junction Air tightness barrier in wall (plaster option shown) Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant Minimum 20mm strip of insulation with thermal conductivity (λ value) not exceeding W/mK should be installed between wall and the slab in floor 1. Check that there are no gaps between the wall and floor constructions 2. Check that any air tightness barrier used in the wall overlaps with the layer in the floor Damp proof membrane 1. Check that concrete slab is level and clear of debris before fitting the insulation at floor level 2. If a screed finish is used instead of a timber floor, use a strip of perimeter insulation with a minimum R value of 0.75 m²/kw for the depth of the screed Alternative Detail 3. Lightweight thermal blockwork can be used in the separating wall to improve the thermal performance but this will also reduce the acoustic performance of the wall. If this alternative is used then additional elements will be required to meet Section 5 of the Technical Standards. Internal Wall (m²k)/w Insulated infill strip (m²k)/w Floor (m²k)/w Psi value = W/mK Concrete Ground Floor/ Separating Wall: Insulation Above Slab Detail 2.18

20 1. Ensure that there are no gaps between floor slabs or between the top of the wall and the underside of the floor slab. 2. Ensure that the insulation is tightly fitted to the top of the floor slab. Air tightness barrier in wall (plaster option shown) 1. Check that any air tightness barrier used in the internal wall overlaps with the layer in the floor or ceiling Cavity barrier is used in to prevent thermal bypass.use dense insulation or proprietary cavity barrier in sleeve 5mm minimum resilient flanking strip to be used at floor junction. See Technical Standards Guidance Notes for Section 5 for details If membrane used, seal onto top of screed. If render or plaster used as airtightness layer, add a corner strip of membrane to cover junction before applying finish Air tightness barrier lapped over corner junction Air tightness barrier in wall (plaster shown) 1. Check that concrete slab is level and clear of debris before fitting the insulation at floor level Separating floors require additional layers and components to comply with Section 2: Fire and Section 5: Noise Psi value = W/mK Concrete Separating Floor / Separating Wall junction Detail 2.19

21 1. Check that there are no gaps between the floors and the separating wall. Air tightness barrier in wall (plaster shown) Seal between the wall and floor membrane with a flexible sealant or seal the gap between skirting board and floor using a flexible sealant 1. Check that any air tightness barrier used in the internal wall overlaps with the layer in the floor or ceiling Alternative: If the air tightness barrier is installed onto the face of the blockwork wall and runs continuously through the floor construction, infill any gaps where floor fixing is made to the wall Air tightness barrier in to be continuous behind joists Air tightness barrier in wall (plaster shown) See general guidance notes Psi value = W/mK Timber Intermediate Floor / Separating Wall junction Detail 2.20

22 1. Install a cavity barrier at the top of the wall 2. Ensure that insulation layers in roof are fitted perpendicularly, to cover junctions 1. Check that there are no gaps between the top of the masonry wall and the underside of the roof 2. Check that the air tightness barrier used in the ceiling overlaps with the layer in the wall Minimum 50mm strip of rigid insulation with thermal conductivity (λ value) not exceeding W/mK should be installed between wall and the last joist Cavity barrier is used in to prevent thermal bypass.use low or soft density insulation wrapped in plastic or membrane in wall and ceiling For more information on acoustic details see guidance in Section 5 of the Technical Standards 1. Check ventilation paths are clear before installing insulation above the ceiling Roof (m²K)/W Note: See detail numbers 2.01 and 2.02 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Cold Roof / Separating Wall junction Detail 2.21

23 1. Install a cavity barrier at the top of the wall 2. Ensure that insulation layers are fitted perpendicularly, to cover junctions Minimum 50mm ventilation path over insulation 1. Check that there are no gaps between the top of the masonry wall and the underside of the roof 2. Check that the air tightness barrier used in the ceiling overlaps with the layer in the wall Cavity barrier giving 30 minute fire resistance - ensure cavity barrier is not breeched by inappropriate rigid sheathing insulation material Cavity barrier is used in to prevent thermal bypass.use low or soft density insulation wrapped in plastic or membrane Separating walls require additional layers and components to comply with Section 2: Fire and Section 5: Noise Where two insulation types are used together see supplementary guidance Air tightness barrier in wall and ceiling (plaster shown on wall) Note: this construction is typically used where there are habitable rooms within the roof construction 1. Check ventilation paths are clear before installing insulation above the ceiling Internal Wall (m²k)/w Roof (m²K)/W Note: See detail numbers 2.03, 2.04 and 2.05 for other junctions using this roof construction Psi value = W/mK Pitched Roof: Ventilated Batten Void/ Separating Wall junction Detail 2.22

24 1. Check that there is no debris in the cavity. 2. Check that there are no gaps in insulation fitted at the corner junction in the cavity 1. Check that any air tightness barrier used in the external walls overlaps at the corner Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check that insulation is tightly fixed into the studs at the corner junction, leaving no gaps Plan view Psi value = W/mK Wall Junction Detail 2.23

25 1. Check that there is no debris in the cavity 1. Check that any air tightness barrier used in the external walls overlaps at the corner Insulation between the studs in addition to the cavity insulation. This insulation must be tightly fitted, leaving no gaps 1. Check that insulation is tightly fixed into the studs at the corner junction, leaving no gaps Plan view Psi value = W/mK Wall Junction - Inward Corner Detail 2.24

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37 Contents Pages Full fill cavity walls 2-13 Partial fill cavity walls 14-25 Solid externally insulated walls 26-37 Appendix (BRE confirmation of Ψ and y-values) 38-40 Page 1 of 40 APA Construction Details

More information

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5 Accredited Construction Details (Scotland) 2010 For the limitation of thermal bridging and air infiltration in low and medium rise domestic buildings Introduction & Principles Issued in support of Junction

More information

Multi-layer Insulation Blanket for Roofs

Multi-layer Insulation Blanket for Roofs Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

Building Regulations for the Conservation of Fuel and Power

Building Regulations for the Conservation of Fuel and Power Insulation CI/SfB Rn7 M2 First Issue April 2014 Building Regulations for the Conservation of Fuel and Power ENGLAND EXISTING DWELLINGS 2013 EDITION Low Energy Low Carbon Buildings Contents Page Introduction

More information

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining Section Timber Frame Walls Single layer between studs Product: Earthwool FrameTherm Rolls and Slabs Tf01 Single layer between studs with service void Product: Earthwool FrameTherm Rolls and Slabs Tf02

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

NRG 75 CRF NRG GREENBOARD WALL SYSTEM NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and

More information

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org Rev 1-12.2013 Code of Practice SIP Technology www.uksips.org What are Structural Insulated Panels (SIPS)? SIPS are prefabricated, high performance, lightweight, building panels that can be used in floors,

More information

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing Good Craftsmanship Guide Carpentry and Joinery- Carcassing Introduction This Good Craftsmanship Guide highlights key problems with the major elements of Carpentry and Joinery - Carcassing, and gives guidance

More information

Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls.

Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls. Improving the flood resistance of your home Advice sheet 4: Flood-resilient walls. This sheet provides guidance on identifying different types of wall, and reducing the flow of floodwater through them

More information

The formation of roof waterproofing details calls for

The formation of roof waterproofing details calls for 3.5 BUILT-UP ROOFING DETAIL DESIGN INTRODUCTION The formation of roof details calls for a combination of the skills of the designer and the roofer. There are many different approaches to detail design

More information

Manual lifting and handling

Manual lifting and handling Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details

More information

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external

More information

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction TGD L 2011 Limiting Thermal Bridging and Air Infiltration Acceptable Construction Details Introduction Government of Ireland 2015 1 INTRODUCTION This guide to Acceptable Construction Details (ACDs) is

More information

British Gypsum Guide to Timber Frame Construction. March 1998

British Gypsum Guide to Timber Frame Construction. March 1998 British Gypsum Guide to Timber Frame Construction March 1998 Timber frame construction has a centuries long tradition in the UK, however, over the last 80 years it has continuously evolved to meet the

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Including. Rubershield-Pro. Breather Membrane

Including. Rubershield-Pro. Breather Membrane Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against

More information

Innovation - High performance roof, wall and floor insulation board. delivering better performance

Innovation - High performance roof, wall and floor insulation board. delivering better performance 2010 VERSION 1 IRL High performance roof, wall and floor insulation board Innovation - delivering better performance PRODUCT SPECIFICATION INSTALLATION GUIDE I ve worked with Xtratherm for years, they

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection PB301 July 2009 Lightweight Building Solutions Bushfire Protection www.boral.com.au/bushfireprotection Attached or adjacent within 6m roofed structures such as garages, carports, verandas and the like,

More information

The Pocket Guide To Insulation August 2013

The Pocket Guide To Insulation August 2013 The Pocket Guide To Insulation August 2013 Introduction Knauf Insulation is the UK s leading manufacturer of insulation products, including: Earthwool glass and rock mineral wool Polyfoam ECO extruded

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture Rochdale Building Control Guide Approved Document C Site preparation and resistance to contaminants and moisture Dampness is often misdiagnosed within buildings, the approved document deals with prevention

More information

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1 Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.

More information

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES Crown copyright 2006 Cover designed and produced by Astron Text pages

More information

- 1 - Element Type. 9 mm gypsum board, 50 mm mineral wool (glued) 9 mm gypsum board, 50 mm mineral wool (on wooden studs, at 300 mm centres)

- 1 - Element Type. 9 mm gypsum board, 50 mm mineral wool (glued) 9 mm gypsum board, 50 mm mineral wool (on wooden studs, at 300 mm centres) concrete 160 mm concrete 180 mm concrete 200 mm concrete 220 mm concrete 230 mm concrete 240 mm concrete 260 mm calcium silicate block 214 mm calcium silicate block 240 mm calcium silicate block 265 mm

More information

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls

More information

Building Control Guidance Note

Building Control Guidance Note Elements Renovation / Replacement. Issued 25/01/13 Rev a Page 1 of 9 (Applies to both Domestic and Non-Domestic Premises) Works relating to thermal elements can arise in building an extension, a material

More information

Low Energy Low Carbon Buildings

Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Eighth Issue March 2011 TR27 LPC/FM INSULATION FOR FLAT ROOFS WATERPROOFED WITH FULLY ADHERED SINGLE PLY, PARTIALLY BONDED BUILT UP FELT, MASTIC ASPHALT AND COLD

More information

The Kingspan Insulation Price List 1 st January 2013

The Kingspan Insulation Price List 1 st January 2013 Insulation The Kingspan Insulation Price List 1 st January 2013 FOR BUILDING FABRIC INSULATION, CAVITY CLOSERS AND MEMBRANES Visit our website: www.kingspaninsulation.co.uk Low Energy - Low Carbon Buildings

More information

- Version 2 Total R-value calculations for typical building applications

- Version 2 Total R-value calculations for typical building applications - Version 2 Total R-value calculations for typical building applications - Version 2 Total R-value calculations for typical building applications Acknowledgements Version Date Description 1 Nov 2010 Initial

More information

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide Residential Refurbishment September 2012 ThermoShell Internal Wall Insulation System Design Guide The importance of wall insulation in houses Buildings account for 40% of our energy consumption and in

More information

Lightweight Partition Design for Residential and Commercial Buildings

Lightweight Partition Design for Residential and Commercial Buildings Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP for Pretend Customer at: Pretend Customer Site address: Monday, 23 November 2015 Dear Pretend Customer, Subject: Thank you for your valued enquiry and instructions to quote for the above project. We are

More information

Providing protection in construction

Providing protection in construction Providing protection in construction VOLUME 2: WALLS AND FLOORS Contact Information UK office address: DuPont Tyvek Hither Green Trading Estate Clevedon, North Somerset BS21 6XU Tel: 01275 879770 Fax (sales):

More information

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION Bill Robinson BSc. C. Eng. M. I. Struct. E. Timber Design Services 1 IS440 Timber frame

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available.

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available. APR 1200 Acoustic Partition Roll CI/Sfb Ref: APR002 Glass mineral wool roll designed to provide high levels of sound insulation in walls and floors to meet Part E (England & Wales) and Section 5 (Scotland)

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

Ubiflex. Non-lead flashing system

Ubiflex. Non-lead flashing system Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof

More information

How To Certify The Scottsdale Construction System

How To Certify The Scottsdale Construction System BRE CERTIFICATION LIMITED PRODUCT SCOTTSDALE CONSTRUCTION SYSTEM CERTIFICATE NUMBER 129/07 DATE OF ISSUE December 2007 SUPPLIED BY Scottsdale Construction System Ltd SUMMARY The Scottsdale Construction

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

CHESTERFLEX ROOF WATERPROOFING MEMBRANES

CHESTERFLEX ROOF WATERPROOFING MEMBRANES CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

rationel WINDOWS WITH VISION

rationel WINDOWS WITH VISION Brick / Blockwork 340mm Cavity Wall Interface Detail Cill BW-001A 5 x 50mm Woodscrews (Staggered) By Installer 20 x 90mm Standard Timber Packer With Upstand Bedded To Frame In Silicone By Installer Aluminium

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

Internal wall insulation in existing housing

Internal wall insulation in existing housing Energy Efficiency Best Practice in Housing Internal wall insulation in existing housing A guide for specifiers and contractors Cost-effective External wall appearance maintained Easier to install and maintain

More information

Roofers Guide to Underslating Membranes

Roofers Guide to Underslating Membranes Roofers Guide to Underslating Membranes IKO is a worldwide enterprise, with more than 3000 employees, and manufacturing plants in Canada, the United States, United Kingdom, Belgium, Holland, France and

More information

Superform Products Ltd.

Superform Products Ltd. TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000

More information

Section 2.3. Flat Roofs. Warm deck single ply membrane. Warm deck single ply membrane. Warm deck built-up felt/ mastic asphalt. Protected membrane

Section 2.3. Flat Roofs. Warm deck single ply membrane. Warm deck single ply membrane. Warm deck built-up felt/ mastic asphalt. Protected membrane Section Flat Roofs Warm deck single ply membrane Product: Rocksilk Krimpact Flat Roof Slab Fl01 Warm deck single ply membrane Product: Polyfoam ECO Roofboard Fl02 Warm deck built-up felt/ mastic asphalt

More information

How To Build A Gambrel Roof And A Gable End Roof

How To Build A Gambrel Roof And A Gable End Roof Dutch Gable or Gambrel Roof and The Scotch Valley The folowing pages are an extract from Carp 12 text TAFE NSW Construction and Transport Division 71 HIP and VALLEY ROOFING GAMBREL / DUTCH GABLE The effect

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

Part 7 Roofs. Chapter 7.2. Pitched roofs. Effective from 1 January 2012

Part 7 Roofs. Chapter 7.2. Pitched roofs. Effective from 1 January 2012 Part 7 Roofs Chapter Effective from 1 January 2012 CONTENTS SCOPE DESIGN Clause Page Design standards D1 1 Statutory requirements D2 1 Loadbearing structure D3-D4 1 Trussed rafter roofs D5 1 Traditional

More information

DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP

DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP CONTENTS WHAT IS RISING DAMP STEP 1 SURVEY STEP 2 METER READINGS STEP 3 CONCLUSION STEP 4 PREPARATION FOR TREATMENT STEP 5 TYPE OF TREATMENT STEP 6

More information

FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas

FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas FERMACELL Powerpanel H 2 O for Wet & Moisture affected areas Powerpanel H 2 O is a cement based board from FERMACELL. Board Characteristics Board Thickness 12.5 mm Board Sizes 1000 x 1200 mm 50 sheets/pallet

More information

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01 Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Cupa Natural Slate Roofing design and fixing guide

Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate synonymous with quality Currently the Spanish slate industry is the undisputed market leader in natural slate production, with 90%

More information

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings

TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Fourth Issue March 2011 TR21 INSULATION FOR FLAT ROOFS WATERPROOFED WITH PARTIALLY BONDED BUILT UP FELT AND MASTIC ASPHALT High performance rigid thermoset insulation

More information

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein

More information

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................

More information

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

Domestic Extensions. Monmouthshire County Council. Building control guidance document

Domestic Extensions. Monmouthshire County Council. Building control guidance document Monmouthshire County Council Building control guidance document Domestic Extensions Building Regulations 2010 (with 2013 amendments) For use in Wales May 2013 Edition Guidance produced for Monmouthshire

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

Patio Covers / Carports

Patio Covers / Carports Patio Covers / Carports Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES. Building Control Guidance for. Loft Conversions

FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES. Building Control Guidance for. Loft Conversions FOREST OF DEAN DISTRICT COUNCIL BUILDING CONTROL SERVICES Building Control Guidance for Loft Conversions 1ST EDITION - AUGUST 2008 About this document This document intends to provide education and guidance

More information

Conventions for U-value calculations

Conventions for U-value calculations Conventions for U-value calculations 2006 edition Brian Anderson BRE Scotland BRE is committed to providing impartial and authoritative information on all aspects of the built environment for clients,

More information

MUNICODE SERVICES LTD.

MUNICODE SERVICES LTD. The Preserved Wood Foundation Guide MUNICODE SERVICES LTD. Prepared by MuniCode Services Ltd. Outline and Restrictions of this Guide The following information required for the construction of Preserved

More information

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors W42_Stand_Extra_32 15/3/05 9:17 am Page 2 NHBC s technical newsletter April 2005 Issue 32 This edition includes: 2 House building is changing fast NHBC unveils new Standards Chapters on curtain walling

More information

The WANZ Guide to Window Installation

The WANZ Guide to Window Installation The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check

More information

LINE OF EXISTING ADJACENT STRUCTURE 6" MIN. PROTECTION COURSE (NOT REQUIRED WHERE THERE IS NO ADJACENT BLDG. MOISTURE RESISTIVE MEMBRANE AT EXIST. AND NEW BLDG. AS OCCURS WATER STOP SLAB-ON-GRADE TERMINATION

More information

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Dow Construction Products Thermal Insulation of Floors This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Why a floor should

More information

SG Series 65mm Frame Windows (Fixed Lite Window Illustrated)

SG Series 65mm Frame Windows (Fixed Lite Window Illustrated) (Fixed Lite Window Illustrated) SINGLE LEAF CLADDING / CORRUGATED STEEL (Awning Window Illustrated) SINGLE LEAF CLADDING / FOAM BOARD (Casement Window Illustrated) BRICK VENEER CONSTRUCTION (Horizontal

More information

DEFAULT HEAT LOSS COEFFICIENTS

DEFAULT HEAT LOSS COEFFICIENTS DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Renovating Your Basement

Renovating Your Basement building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

Mold Preventing I nterior System

Mold Preventing I nterior System interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal

More information

ROOFS, SNOW AND ICE DAMS

ROOFS, SNOW AND ICE DAMS ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof

More information

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet.

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. STEP-BY-STEP construction guide Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. Welcome to our CONSERVATORY AND SUNROOM CONSTRUCTION GUIDE What is the specification

More information

GYPROCK PARTY WALL INTERTENANCY WALL SYSTEMS FOR CLASS 1 BUILDINGS

GYPROCK PARTY WALL INTERTENANCY WALL SYSTEMS FOR CLASS 1 BUILDINGS GYPROCK PARTY WALL INTERTENANCY WALL SYSTEMS FOR CLASS 1 BUILDINGS CONTENTS Introduction 2 Applications 3 Advantages 3 Components 3 6 Design Considerations 7 8 System Features 10 Typical installation Sequence

More information

TIMBER FRAME STANDARD DETAILS SEPTEMBER 09

TIMBER FRAME STANDARD DETAILS SEPTEMBER 09 Building 1 Grosvenor Court, Hipley Street OLD WOKING, SURREY GU22 9LL Tel: +44 (0) 1483 769518 Fax: +44 (0) 1483 770863 E-mail: design@silvatecdesign.com Internet: www.silvatecdesign.com TIMBER FRAME STANDARD

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

The right solutions. However, it is inevitable that with the introduction of any new construction system the question arises How does it compare?

The right solutions. However, it is inevitable that with the introduction of any new construction system the question arises How does it compare? Value assessment. The right solutions. We Believe We believe that Porotherm offers both short and long term value to all involved in the building process - from bricklayer to client and everyone in between.

More information