15kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

Size: px
Start display at page:

Download "15kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:"

Transcription

1 15kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7605 1/16/2014

2 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V. TEST SAMPLES... 2 VI. TESTING SEQUENCE... 2 VII. TESTING Sequence A Dielectric Tests Sequence Partial Discharge Test Bushing Insert Partial Discharge Test Elbow AC Withstand Voltage Test Bushing Insert AC Withstand Voltage Test - Elbow DC Withstand Voltage Test Bushing Inert and Elbow Impulse Withstand Voltage Test - Bushing Insert and Elbow Test Point Test Sequence B Accelerated Life Tests Sequence Accelerated Sealing Life Test Bushing Insert and Elbow Sequence C Switching and Fault-closure Individual Testing Short-time Current Test Current-cycling Test Elbow and Bushing Insert Elbow Cable Pull-Out Test Operating Force Test Elbow Operating Eye Test Test Point Cap Test Shielding Test APPENDIX -External Test Report Summary

3 I. OBJECTIVE To evaluate the Chardon 15kV Loadbreak bushing insert and elbow to the 15kV class performance requirements of IEEE Std II. SUMMARY All samples are qualified to the full design testing sequence of IEEE , including partial discharge test, AC withstand testing, DC withstand testing, impulse withstand testing, short time current test, cable pull out test, operating force test, elbow operating eye pulling test, test point cap test, test point test, shielding test, switching and fault closure. III. CONCLUSION By passing the above test requirements, it is concluded that 15kV series Loadbreak Bushing Insert and Elbow design is suitable for use as a fully shielded, fully separable submersible cable connections for 15kV class 3Φ 200A medium voltage circuits. IV. CABLE DATA Class: Conductor: Insulation: Jacket: 15kV 1/0 Str Al 175 mils, TRXLP PVC V. TEST SAMPLES The required number of 25kV 200A Bushing Insert and Elbow samples, according to each specific test requirements, were mated with each other according to the installation instruction provided by Chardon. VI. TESTING SEQUENCE The samples were tested in accordance with IEEE Standard. Table 1 shows the different test sequence and sections the samples were subjected to. The section numbers refer to the corresponding sections in the standard. 2

4 Design test No. Samples Reference Sequence A B C Individual Four each Thermal cycle withstand 7.20 N/A Partial discharge test 7.4 X X AC withstand voltage X X DC withstand voltage X Impulse withstand voltage X X Short-time current 7.6 X Switching 7.7 X Fault-closure 7.8 X Current cycling 7.9 to 7.11 X Accelerated sealing life test 7.12 X Cable pull-out 7.13 X Operating force 7.14 X Operating eye 7.15 X Test point cap 7.16 X Test point 7.17 X X Shielding 7.18 X Bushing well stud torque 7.19 N/A Impulse withstand voltage X Table 1 : Design test sequence Samples were tested according to the sequence and quantities shown in Table 1. 3

5 VII. TESTING 1. Sequence A Dielectric Tests Sequence 1.1 Partial Discharge Test Bushing Insert Object To verify the connectors that the parts meet the ANSI/IEEE Standard kV partial discharge spec of 11kV/3pC. Testing Samples Bushing Insert 15-LBI PCS Mating Parts Bushing Well Elbow Elbow Test Rod Elliott 200 Amp Bushing Well # B 15-LE200TB 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall be raised to 20% above the corona voltage level of 11kV. If corona exceeds 3pC, the test voltage shall be lowered the corona voltage level of 11kV and maintained at this level for at least 3 seconds but not more than 60 seconds. Corona readings taken during this period shall not exceed 3 pc. Results All samples passed. 4

6 1.2 Partial Discharge Test Elbow Object 11kV/3pC To verify the connectors that the parts meet ANSI/IEEE Standard kV partial discharge requirement of 11kV/3pC. Testing Samples Elbow 15-LE200TB 10 PCS Mating Parts Bushing Insert Bushing Well Elbow Test Rod 15-LBI200 Elliott 200 Amp Bushing Well # B 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall be raised to 20% above the corona voltage level of 11kV. If corona exceeds 3pC, the test voltage shall be lowered the corona voltage level of 11kV and maintained at this level for at least 3 seconds but not more than 60 seconds. Corona readings taken during this period shall not exceed 3 pc. Results All samples passed. 5

7 Fig 7-1 Partial Discharge Testing Setup - I Fig 7-2 Partial Discharge Testing Setup - II 6

8 1.3 AC Withstand Voltage Test Bushing Insert Object To verify the connectors that the parts meet ANSI/IEEE Standard kV AC withstand voltage testing requirements 34kV/1 min. Testing Samples Bushing Insert 15-LBI PCS Mating Parts Bushing Well Elbow Elbow Test Rod Elliott 200 Amp Bushing Well # B 15-LE200TB 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall be raised to the value of 34kV in 30 seconds. The test sample shall withstand the specified test voltage for 1 minute without flashover or puncture. Results All samples passed. 7

9 1.4 AC Withstand Voltage Test - Elbow Object To verify the connectors that the parts meet ANSI/IEEE standard kV AC withstand requirement of 34kV/ 1 min. Testing Samples Elbow 15-LE200TB 10 PCS Mating Parts Bushing Insert Bushing Well Elbow Testing Rod 15-LBI200 Elliott 200 Amp Bushing Well # B 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall be raised to the value of 34kV in 30 seconds. The test sample shall withstand the specified test voltage for 1 minute without flashover or puncture. Results All samples passed. 8

10 Fig 7-3 Testing in Progress Fig 7-4 Test Fixture Setup 9

11 1.5 DC Withstand Voltage Test Bushing Inert and Elbow Object To verify the connectors that the parts meet the ANSI/IEEE Standard kV DC withstand voltage testing spec of 53kV/15 min. Testing Samples Elbow 15-LE200TB 10 PCS Bushing Insert 15-LBI PCS Mating Parts Bushing Well Elbow Test Rod Elliott 200 Amp Bushing Well # B 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall have a negative polarity and shall be raised to the value of 53kV. The connector shall withstand the specified test voltage for 15 minutes without flashover or puncture. Results All samples passed. 10

12 Fig 7-5 DC Withstand Testing Fixture Setup 11

13 1.6 Impulse Withstand Voltage Test - Bushing Insert and Elbow Object To verify the connectors that the parts meet ANSI/IEEE Standard kV impulse withstand testing requirements of μs ±95kV wave., 3 positive and 3 negative full-wave impulses. Testing Samples Elbow 15-LE200TB 10 PCS Bushing Insert 15-LBI PCS Mating Parts Bushing Well Elbow Testing Rod Elliott 200 Amp Bushing Well # B 15kV#B Testing Rod Φ18.20mm Procedure and Testing Spec The test voltage shall be 1.2/50µs wave having the crest value (BIL) of 95kV. The connector shall withstand 3 positive and 3 negative full-wave impulses without flashover or puncture. Results All samples passed. 12

14 Elbow and Bushing Insert, 4 sets Fig 7-6 Positive Wave (Data Amplification: 5,000). Elbow and Bushing Insert, 4 sets Fig 7-7 Negative Wave (Data Amplification: 5,000) 13

15 Fig 7-8 Impulse Withstand Testing Fixture Setup 14

16 1.7 Test Point Test Object To verify the elbow test point meeting the ANSI/IEEE Standard testing requirement. Testing Samples Elbow 15-LE200TB 10 PCS Mating Parts LCR Meter Testing Fixture CHENHWA 1012F Procedure and Testing Spec The purpose of this test is to verify that the capacitance values of the test point meet the requirements of of IEEE 386. The connector shall be installed on a cable of the type for which it is designed to operate, and the shielding shall be grounded in the normal manner. The capacitances from test point to cable and test point to ground shall be measured with suitable instruments and proper shielding techniques. The measured values shall be within the tolerances specified in of IEEE 386. Results All samples passed. 15

17 Fig 7-9 Capacitance Test Setup 16

18 2. Sequence B Accelerated Life Tests Sequence 2.1 Accelerated Sealing Life Test Bushing Insert and Elbow Object To verify the connector can maintain a long-tern seal at all interfaces to prevent the entrance of moisture. Testing Samples and Mating Parts Elbow 15-LE200TB 4 PCS Bushing Insert 15-LBI200 4 PCS Mating Parts Bushing Well Cable Conductor Type Cable Insulation Thickness Chardon 200A Bushing Well CH200BW 1/0 AWG Aluminum Cable 175 mil 4 PCS Conductor Chardon 200A BiMetal Connector 1/0 Equalizers Bushing Bus Aluminum Equalizers Size:106mm(L)20mm(OD)10.1mm(ID) 356mm(L), 102mm(W),10mm(T) Testing Spec 1. The four connector assemblies shall be placed in an oven having 121 C temperature and remain there for three weeks. 2. After the time has elapsed, the four samples shall be subjected to 50 cycles of the following sequence of operations: The assemblies shall be heated in air using sufficient current to raise the temperature of the connector of the control cable to 90 C ± 5 C for 1 hour. 3. The assemblies shall be de-energized and within 3 min, submerged in 25 C ± 10 C conductive water (5000 Ω-cm maximum) to a depth of 30 cm (1 ft) for 1 hour. 4. After 50 th cycle, the connector and cable assembly shall withstand a design impulse test of IEEE 7.5.3(1.2*50µS impulse wave of 125kV, 3 positive and 3 negative) and test point voltage test.( During the impulse test, the bushing well and bushing bus were soaked into the silicone oil.) Results All samples passed. 17

19 Fig 7-10 : Testing Setup of Accelerated Life Sealing Test 18

20 Fig 7-11 Partial Discharge Test - Fig 7-12: Impulse Test Setup 19

21 Fig 7-13: Testing Samples Assembly Fig 7-14: Testing Samples in the Chamber 20

22 Fig 7-15: Current On Testing Loop Fig 7-16: Current Off Testing Loop 21

23 Fig 7-17: Impulse test after accelerated sealing life test I. Fig 7-18: Impulse test after accelerated sealing life test II. 22

24 Description 3. Sequence C Switching and Fault-closure The purpose of these tests is to verify that the Loadbreak Bushing Insert and Elbow are capable of closing and interrupting the rated switching current of 200A rms. Additionally, these tests will verify the parts are capable of closing on a 10,000A rms fault current for 0.17 sec. Requirement The Loadbreak Bushing Insert shall withstand 10 complete switching operations without arcing to ground or impairing its ability to meet the spec of IEE Std The Loadbreak Elbow shall also withstand 10 complete switching without arcing to ground or impairing its ability to meet the spec of IEE Std Failures are permitted; however, none of the failures are permitted in 10 consecutive samples of a maximum lot size of 30. Procedures 1. Assemble 30 Bushing Inserts and Elbows assemblies on cable. 2 Test all samples in accordance with IEEE Standard sections 7.7 Switching Test under the conditions described in Tables 7 and 8, Figure 19(a) of the standard. Each sample is subjected to 10 complete switching operations at 15.2/26.3 kv, 200A using a mechanical fixture. 3. Test all samples that successfully passed 10 switching operations in accordance with IEEE Standard sections 7.8 Fault-closure Test under the conditions described in Table 8 and 9, Figure 20(a) of the standard. Each sample is subjected to 1 fault-close operation. 4. The procedure above was repeated with elbow samples from Elastimold and Cooper Industries, in compliance with IEEE standard section Complete Interchangeability Results Switching passed; Fault-closure passed. Testing performed at Powertech Labs Inc, Surrey BC Canada. Chardon Powertech Report D-26 Elastimold Interchangeability Powertech Test Report B-26 Cooper Interchangeability Powertech Test Report C-26 23

25 5. Individual Testing 4.1 Short-time Current Test Object To verify the connectors that the parts meet ANSI/IEEE Standard A short-time current test requirements. Testing Samples Elbow 15-LE200TB 4 PCS Bushing Insert 15-LBI200 4 PCS Mating Parts Bushing Well Elastimold K1601PC-S2-R 2 PCS Bushing Extender Hubbell 625BE Cable Conductor Type #1 AWG Procedure and Testing Spec The rms value of the first major loop of a current wave shall be not less than the value specified in Table 2 multiplied by 1.3 (X/R=6) for 200 A connectors The magnitude shall be measured in accordance with ANSI/IEEE C Connectors shall withstand the current without separation of interfaces or impairing the ability to meet the other requirements of the standard. Results All samples passed. 24

26 4.2 Current-cycling Test Elbow and Bushing Insert Object The purpose of this accelerated test is to demonstrate that 200 A insulated connectors can carry rated current under usual service conditions. Successful completion of the test shall be considered as evidence that the connector meets its rating. Testing Samples Elbow 15-LE200TB 4 PCS Bushing Insert 15-LBI200 4 PCS Mating Parts Bushing Well Chardon 200A Bushing Well CH200BW 4 PCS Cable Conductor Type Cable Insulation Thickness 1/0 AWG Aluminum Cable 175 mil Conductor Chardon 200A BiMetal Connector 1/0 Equalizers Bushing Bus Aluminum Equalizers Size:106mm(L), 20mm(OD), 10.1mm(ID) 356mm(L),102mm(W),10mm(T) Testing Spec A control cable, used for the purpose of obtaining conductor temperature, shall be installed in the heat cycle loop between two equalizers. Its length shall be 183 cm (72 in). The control cable shall be the same type and size as the cable used to join the connectors under test. Four connectors shall be assembled in series on AWG No 1/0 insulated aluminum conductors having a length of 91 cm (36 in). The cable insulation thickness shall be selected according to its voltage class (see Table 10 of IEEE 386).Equalizers used shall be in accordance with ANSI C119.4.The bushing bus shall be a flat, rectangular, bus bar 356 mm (14 in) long, 102 mm (4 in) wide, and 10 mm (3/8 in) thick. The bushing wells 25

27 shall be mounted 31 cm (12 in) apart centered along the midline of the bus bar. The bushing well studs shall be tightened to the bus bar using an installation torque of 9 N m ± 1 N m (80 lbf in ± 10 lbf in). Unless otherwise specified by the manufacturers, the elbow male contact probe shall be threaded into the elbow compression lug using an installation torque of 9 N m ± 1 N m (80 lbf in ± 10 lbf in). Current-cycling tests shall be conducted at an ambient temperature of 15 C to 35 C in a space free of drafts. The current-cycle amperes shall be adjusted during the current-on period of the first five cycles to result in a steady-state temperature rise of 100 C to 105 C on the control conductor. This current shall then be used during the remainder of the test current-on periods, regardless of the temperature of the control conductor. The test shall consist of 50 current cycles, with the current on 4 h and off 2 h for each cycle. At the end of each current-on cycle, the assembly shall be de-energized and within 3 min be submerged in water at 5 C ± 5 C for the remainder of the current-off cycle. At the end of the 10th, 25th and 40th cycles (± 2 cycles), after the samples have returned to room temperature, a short time ac current of 3500 A ± 300 A rms shall be applied to each sample for a minimum of 3 s. The temperature of at least the following current transfer points shall be measured at the end of each cycle with the current on: a) Probe to compression lug b) Probe to female contact c) Female contact structure to metallic housing (piston contact) d) Between bushing insert and bushing well. These temperatures shall not exceed the temperature of the control conductor. The temperature differences between the control conductor and the connector shall show a condition of stability from the fifth cycle to the end of the test. Stability is indicated when the change in the individual differences is not more than 10 C from the average of the measured differences in this interval for this connector. The dc resistance of the connector system shall be measured at the end of cycles 10, 20, 30, 40, and 50 (± 2 cycles). The dc resistance measurements shall be made between the elbow cable equalizer and the bushing stud after the connector system has stabilized at ambient temperature. Ambient temperature shall be measured by devices located within 61 cm (2 ft.) of the test loop but in a location that minimizes the effect of thermal convection. The ambient temperature shall be recorded at the same time as each set of resistance measurements, and the resistance shall be corrected to 20 C. The dc resistance shall be stable over the period of measurement. 26

28 Stability is achieved when any resistance measurement, including allowance for instrument accuracy, does not vary more than ± 5% from the average of all the measurements in this interval. Results All samples passed. Fig 7-19: Testing Setup Diagram 27

29 Fig 7-20: Current On Cycle Fig 7-21: Current Off Cycle 28

30 4.3 Elbow Cable Pull-Out Test Object To verify the compression lug and cable assembly that the parts can meet ANSI/IEEE Standard Cable Pull-Out Test requirements. Testing Samples Elbow Compression Lug Chardon BiMetal 1/0 200A Connector 4 PCS Mating Parts Cable 1/0 AWG Aluminum Cable Procedure and Testing Spec The purpose of this test is to determine if the connection between the cable conductor and compression lug of the connector is capable of withstanding a tensile force of 890 N (200 lbf). The compression lug shall be held in a manner that will not affect the strength of the connection. The tensile force shall be applied to the cable conductor. The connection shall withstand the applied force for 1 minute without impairing the connector's ability to meet the other requirements of this standard. Results All samples passed. 29

31 4.4 Operating Force Test Object To verify the force of the elbow connector operating force when mating with bushing insert that the force meets NSI/IEEE Standard operating force requirement. Testing Samples Elbow 15-LE200TB 4 PCS Mating Parts Bushing Insert 15-LBI200 4 PCS Cable 1/0 AWG(Al) Procedure The purpose of this test is to demonstrate that the force necessary to operate a connector meets the requirements of 6.2.( 222 N N (50 lbf lbf) for connectors without hold-down bails) The elbow shall be assembled with a probe and compression lug and the connector system shall be lubricated in accordance with the manufacturer's instructions. Results All samples passed. 30

32 4.5 Elbow Operating Eye Test Object To verify the elbow operating eye that the part meet ANSI/IEEE Standard requirements. Testing Samples Elbow 15-LE200TB 4 PCS Mating Parts Testing Fixture Procedure and Testing Spec The purpose of this test is to demonstrate that the operating eye meets the requirements of 6.2 at 25 C ±5 C. A tensile force shall be gradually applied to the operating eye in the direction of normal operation. The operating eye shall withstand the force for 1 minute. A rotational force shall be applied with a suitable live-line tool to the operating eye in a clockwise direction and in a counter-clockwise direction. Some distortion of the operating eye is acceptable provided the connector is serviceable after the test and meets the corona voltage-level requirement specified in Table 1 of IEEE standard Results All samples passed. 31

33 Fig 7-22 Torque Testing Setup 32

34 4.6 Test Point Cap Test Object To verify the test point cap of the elbow that the part meets ANSI/IEEE Standard requirement. Testing Samples Elbow 15-LE200TB 4 PCS Test Point Cap Testing Fixture Procedure and Testing Spec 4 PCS The purpose of this test is to demonstrate that the removal force of the test point cap meets the requirements of and the cap operating eye is capable of withstanding the maximum operating force Results All samples passed. 33

35 4.7 Shielding Test Object To verify the outer conductive layer of the connector that the material meet ANSI/IEEE Standard requirement of shielding test Testing Samples Elbow 15-LE200TB 4 PCS Procedure 1. Shield Resistance. The shield resistance measured between the cable entrance and the farthest extremity of the shield from the cable entrance shall be 5000Ω or less. 2. Fault-Current Initiation. The semi-conducting shield shall be capable of initiating two consecutive fault-current arcs to ground specified in 4.3, IEEE 592. Results 1. Shield Resistance : 4 testing samples resistance measured are less than 5000Ω, all samples passed. 2. Fault-Current Initiation: 2 testing samples successfully initiate two consecutive fault-current arcs to ground in the test performed in Powertech Labs, Surrey, B.C., Canada. All 2 samples passed. Powertech Test Report PL-26015B. 34

36 APPENDIX -External Test Report Summary 35

37 36

38 37

39 38

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Waterproof Connectors for Outdoor Use

Waterproof Connectors for Outdoor Use Waterproof Connectors for Outdoor Use HR41A Series Mated condition diagram Nut-tightening rear mount type (panel thickness=mm) 70.5 Features 1. Waterproof connector designed for outdoor use Light-weight

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

ENGINEERING COMMITTEE

ENGINEERING COMMITTEE ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 02 2006 Specification for F Port, Female, Indoor NOTICE The Society of Cable Telecommunications Engineers (SCTE)

More information

ELASTIMOLD CATALOG SP2. Issue Date: 03/2003

ELASTIMOLD CATALOG SP2. Issue Date: 03/2003 ELASTIMOLD CATALOG SP2 Issue Date: 03/2003 SEPARABLE CONNECTORS JOINTS TERMINATIONS SURGE ARRESTERS FUSES LOADBREAK SWITCHES FAULT INTERRUPTERS For 5kV-35kV Distribution Systems ELASTIMOLD System Planning

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers

More information

A Study of a MV Cable Joint

A Study of a MV Cable Joint SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

I-PEX MHF4 Micro Coaxial Connector

I-PEX MHF4 Micro Coaxial Connector PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: sales@wellshow.com.tw Tel: +886-2-24239376

More information

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20 USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

Mounting Instructions for SP4 Power Modules

Mounting Instructions for SP4 Power Modules Mounting Instructions for SP4 Power Modules Pierre-Laurent Doumergue R&D Engineer Microsemi Power Module Products 26 rue de Campilleau 33 520 Bruges, France Introduction: This application note gives the

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Givare NC-SRS 280 och 880

Givare NC-SRS 280 och 880 Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness

More information

08. SEK IDC CONNECTORS

08. SEK IDC CONNECTORS . IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED

More information

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Power Resistor for Mounting onto a Heatsink Thick Film Technology DIMENSIONS in millimeters Power Resistor for Mounting onto a Heatsink Thick Film Technology FEATURES 800 W at 85 C bottom case temperature Wide resistance range: 0.3 to 900 k E24 series Non inductive Easy

More information

SMA Interface Mating Dimensions (Per MIL-STD-348)

SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Series SMA 6 SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Interface Dimensions MALE Inches/Millimeters 3 Minimum Nominal Maximum LTR in. mm in. mm in. mm A.250 6.35.263 6.68.. B.1790 4.55.1808

More information

Hook-Up and Lead Wire

Hook-Up and Lead Wire 3.1 Hook-Up and Lead Wire 3 Table of Contents Hook-Up & Lead Wire Page Introduction: UL Style & CSA Type Listings 3.2 PVC 3.3 3.8 300V, 80 C 3.3 300V, 105 C 3.4 600V, 105 C 3.5 (Type MW) MIL-W-76C-PVC:

More information

Cables. Accessories. For Force, Torque and Strain Sensors

Cables. Accessories. For Force, Torque and Strain Sensors Accessories Cables For Force, Torque and Strain Sensors Charge mode, high impedance piezoelectric measurement demands highly insulated coaxial cables and connectors to ensure an insulation resistance greater

More information

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt

More information

Why Buy HVI VLF Products?

Why Buy HVI VLF Products? Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts Product Specification 108-19346 17 APR 2013 Rev F Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts 1. SCOPE 1.1. Content NOTE The product may not perform according

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

Allen-Bradley 1397 400-600HP AC Line Filter Kit

Allen-Bradley 1397 400-600HP AC Line Filter Kit Installation Instructions IN Allen-Bradley 1397 400-600HP AC Line Filter Kit Cat. Nos. 1397-LF600 What This Option Provides What This Kit Contains This option is intended to be applied when the primary

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

Features. Picture. Specifications

Features. Picture. Specifications Type: for level measurement Order No.: see Table 1 / Page 4 Features Picture Two wire system Piezoresistive measuring element Output signal 4-20 ma Conformity error ±0.5 % FS or Standard DIN measuring

More information

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests

More information

Directory chapter 04

Directory chapter 04 M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................

More information

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 123 2011

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 123 2011 ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 123 2011 Specification for F Connector, Male, Feed-Through NOTICE The Society of Cable Telecommunications Engineers

More information

100% EMI Emission Containment

100% EMI Emission Containment 100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.

Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02. Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

Small U-shaped Micro Photoelectric Sensor. Enables space saving and quick installation!

Small U-shaped Micro Photoelectric Sensor. Enables space saving and quick installation! 4 Small Micro Photoelectric Amplifier Built-in PM-44 SERIES PM-4 SERIES General terms and conditions... F- selection guide... P.44~ Related Information Glossary of terms / General precautions... P.39~

More information

EMC Test Chamber Solutions RF Cable Assemblies and Connectors

EMC Test Chamber Solutions RF Cable Assemblies and Connectors EMC Test Chamber Solutions RF Cable Assemblies and Connectors RF CABLE ASSEMBLY AND CONNECTOR SOLUTONS FOR EMC MMUNTY AND EMSSON COMPLANCE TESTNG E X T N T R A T E D E P T H --> POWER LEVEL: -40.00 dbm

More information

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 5 V DC, 1 V DC and 2 V DC DESIGNING For more than 2 years Vitramon has supported the automotive industry

More information

Current and Temperature Ratings

Current and Temperature Ratings Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Development of a 500-kV DC XLPE Cable System

Development of a 500-kV DC XLPE Cable System by Satoru Maruyama *, Noboru Ishii *, Michihiro Shimada *, Shinji Kojima * 2, Hideo Tanaka * 3, Mitsumasa Asano * 4, Tetsuya Yamanaka * 4, and Shin ichi Kawakami * 4 This paper describes development work

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

STANDARD MICRO-D CONNECTORS

STANDARD MICRO-D CONNECTORS STANDARD MICRO-D CONNECTORS RECTANGULAR CONNECTORS Pigtail connector - Metal shell.............................. 56 Pigtail connector - Low profile - Metal shell.................... 58 Pigtail connector

More information

Peltier Application Note

Peltier Application Note Peltier Application Note Early 19th century scientists, Thomas Seebeck and Jean Peltier, first discovered the phenomena that are the basis for today s thermoelectric industry. Seebeck found that if you

More information

SMA Connectors. RF Coax Connectors. Product Facts

SMA Connectors. RF Coax Connectors. Product Facts SMA Connectors Product Facts Performance to 12.4 GHz and beyond Available in various base metal options, including stainless steel, brass and zinc diecast Uses industry standard crimp tools and processes

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

4 A CAPACITY, THE VARIETY OF CONTACT ARRANGEMENTS FEATURES

4 A CAPACITY, THE VARIETY OF CONTACT ARRANGEMENTS FEATURES 4 A CAPACITY, THE VARIETY OF CONTACT ARRANEMENTS S RELAYS FEATURES 28. 1.12 12..472 1.4.49 The variety of contact arrangements 2 Form A 2 Form B, 3 Form A 1 Form B, 4 Form A Latching types available High

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

SFxxx-S PID Test Report (Potential Induced Degradation) TUV Rheinland Japan. ARC Product Management 2015.07 Ver. 1

SFxxx-S PID Test Report (Potential Induced Degradation) TUV Rheinland Japan. ARC Product Management 2015.07 Ver. 1 SFxxx-S PID Test Report (Potential Induced Degradation) TUV Rheinland Japan ARC Product Management 2015.07 Ver. 1 Outline SLIDE 1 2 Outline What is PID? TOPICS 3 4 5 6 7 8 Principle of PID & resistance

More information

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases

More information

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS Contents Foreword --------------------------------------------------------------------------------------------------------------------

More information

IMPORTANT DOCUMENTATION DO NOT DISCARD!

IMPORTANT DOCUMENTATION DO NOT DISCARD! PART NO.: 6441-263C SERIES GRT 3 JAW PARALLEL GRIPPERS INFORMATION SHEET IMPORTANT DOCUMENTATION DO NOT DISCARD! Use this information sheet to assist with gripper installation and setup. File with maintenance

More information

F Male DBS Connector Dimensional and Performance Specification

F Male DBS Connector Dimensional and Performance Specification SBCA Industry Standards Subcommittee Document: SBCA Connector Recommended Practices Date of Issue: F Male DBS Connector Dimensional and Performance Specification NOTICE The Satellite Broadcasting and Communications

More information

SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS

SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS Michael J Sprague Member, IEEE Cutler-Hammer, Inc. 130 Commonwealth Drive Warrendale, PA 15086 USA Abstract

More information

HIGH RELIABILITY POWER SUPPLY TESTING

HIGH RELIABILITY POWER SUPPLY TESTING HIGH RELIABILITY POWER SUPPLY TESTING Dale Cigoy Keithley Instruments, Inc. The reliability of a power supply must match or exceed the rest of the system in which it is installed. Generally, this requires

More information

Jack to Jack adapters Plug to Plug U-Link connectors PCB Right angle plastic PCB Right angle - metal. Ordering Codes

Jack to Jack adapters Plug to Plug U-Link connectors PCB Right angle plastic PCB Right angle - metal. Ordering Codes BNC 75Ω RF CONNECTORS BNC 75Ω RF CONNECTORS To meet the need for higher performance, impedance matched cable interconnections, Amphenol offers a full line of 75 ohm BNC connectors. These connectors can

More information

Product Selection Guide

Product Selection Guide PG-CA-1109 For 5kV-35kV Distribution Systems Loadbreak & Deadbreak Cable Joints Cable Terminations Product Selection Guide Introduction Product Guide PG-CA provides an easy-to-use, comprehensive listing

More information

TC50 High Precision Power Thin Film chip resistors (RoHS compliant Halogen Free) Size 1206, 0805, 0603

TC50 High Precision Power Thin Film chip resistors (RoHS compliant Halogen Free) Size 1206, 0805, 0603 WF2Q, WF08Q, WF06Q ±%, ±0.5%, ±0.25%, ±0.%, ±0.05% TC50 High Precision Power Thin Film chip resistors (RoHS compliant Halogen Free) Size 206, 0805, 0603 *Contents in this sheet are subject to change without

More information

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH

Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

A Series 1-4 Pole Rotary Switches

A Series 1-4 Pole Rotary Switches 1-4 Pole Switches Features/Benefits Multi-pole and multi-position Positive detent Shorting & non-shorting contacts Panel and PCB mounting RoHS Compliant Typical Applications Automotive Major and small

More information

Easy Tool Retracting System CMC-SR2159ER36

Easy Tool Retracting System CMC-SR2159ER36 Easy Tool Retracting System CMC-SR2159ER36 Pepperl+Fuchs, Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 486 0002 e-mail: pa-info@us.pepperl-fuchs.com Mounting the Easy Tool Refer to

More information

Communication, Signal & Data Cables

Communication, Signal & Data Cables Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

MYTHBUSTING Takes on Shielded Cabling

MYTHBUSTING Takes on Shielded Cabling MYTHBUSTING Takes on Shielded Cabling Herb Congdon Brian Davis Objectives Take on myths of shielded cabling and use modern-day science to show what's real and what's fiction - through trial and error actually

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors Size 1206, 0805, 0603, 0402 *Contents in this sheet are subject to change without prior notice. Page 1 of 8 ASC_WWxxX_V12 Nov.- 2011

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1 2015 July 17 and Testing, ROPEC Page 1 PART 1 GENERAL 1.1. Scope.1 Equipment replacement and testing for a 44 kv 4.16kV/600V substation: a. Replacement of Insulators as indicated on the drawings in Appendix

More information

Low and High Voltage Power Supplies

Low and High Voltage Power Supplies Low and High Voltage Power Supplies We work according to ISO 9001: 2008 Since 1994 Fug works according to the quality assurance system ISO 9001. All shipped units are checked and documented in our testing

More information

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: 405003, 405004, 405005, 405006

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: 405003, 405004, 405005, 405006 Design Test Report Veri*Lite Suspension s Catalog Numbers: 0003, 000, 000, 000 This design test report records the results of laboratory tests made on the Ohio Brass Veri*Lite Suspension s. Test performed

More information

Agilent 4339B/4349B High Resistance Meters

Agilent 4339B/4349B High Resistance Meters Agilent 4339B/4349B High Resistance Meters Technical Overview Within Budget Without Compromise Introducing the Agilent Technologies 4339B and 4349B High Resistance Meters Used for Making Ultra- High Resistance

More information

U-shaped Micro Photoelectric Sensor

U-shaped Micro Photoelectric Sensor SERIES U-shaped Micro Photoelectric Extremely small size enables space saving and quick installation! Extremely small Ultra-small type PM- 24(-R) contributes to the miniaturization of your equipment. Even

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

How To Test A Power Cable For Power And Safety

How To Test A Power Cable For Power And Safety In this section... Elastimold Underground Cable Accessories Elastimold Underground Cable Accessories Overview... H-2 H-3 200-Amp Loadbreak Elbows... H-4 H-7 200-Amp Deadbreak Elbows... H-8 H-9 600-Amp

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information