Hands-On Lab Workbook. Introduction to EtherNet/IP
|
|
|
- Anne Peters
- 9 years ago
- Views:
Transcription
1 Hands-On Lab Workbook Introduction to EtherNet/IP
2 WELCOME TO THE INTRODUCTION TO ETHERNET/IP HANDS-ON LAB 7 ABOUT THIS HANDS-ON LAB 7 BEFORE YOU BEGIN 7 DOCUMENT CONVENTIONS 9 REVIEWING THE APPLICATION STORY 10 LAB 1: CONFIGURING THE COMPUTER TO COMMUNICATE TO THE PLC 11 LAUNCHING RSLINX COMMUNICATION SOFTWARE AND CONFIGURING A DRIVER 11 LAB 1 SUMMARY 14 LAB 2: ADDING FLEX I/O 15 ABOUT THIS LAB 15 LAUNCHING A PROJECT IN RSLOGIX 5000 PROGRAMMING SOFTWARE 15 ADDING THE1794-AENT ADAPTER MODULE TO THE I/O CONFIGURATION LIST 16 ADDING A 1794-OE4 MODULE TO AENT IN RSLOGIX 5000 PROJECT 18 ADDING ALIAS TAGS TO THE CONTROLLER 20 DOWNLOADING AND TESTING THE 1794-AENT AND 1794-OE4 23 VERIFYING FLEX LADDER LOGIC 24 LAB 2 SUMMARY 25 LAB 3: PROCESSOR INTERLOCKING 26 ABOUT THIS LAB 26 VERIFYING ETHERNET/IP CONNECTIVITY 27 CREATING A PRODUCED TAG IN L63 CONTROLLER 27 CONFIGURING THE CONSUMER OF THE PRODUCED TAG 30 9/21/2004 Page 2 of 98
3 ADDING A REMOTE CONTROLLER IN THE L55 PROJECT (DEFINING THE PRODUCER) 30 CREATING A CONSUMED TAG 32 SAVING AND DOWNLOADING THE CONSUMER PROJECT 34 INITIALIZING THE PRODUCED TAG 35 TESTING THE PRODUCED AND CONSUMED TAGS 36 LAB 3 SUMMARY 36 LAB 4: USING RSVIEW ME AND PANELVIEW PLUS ABOUT THIS LAB 37 DOWNLOADING TO THE 5563 PROCESSOR 37 OPENING THE EXISTING RSVIEW ME PROJECT 37 REVIEWING THE HMI COMMUNICATIONS PATH 38 CREATING AND DOWNLOADING A RUNTIME APPLICATION 39 CONFIRMING THE PANELVIEW PLUS 600 OPERATION 41 LAB 4 SUMMARY 42 LAB 5: ADD REMOTE I/O ON DEVICENET 43 ABOUT THIS LAB 43 ADD 1756-DNB TO RSLOGIX5000 PROJECT 43 CONNECTING ALIAS TAGS TO THEIR I/O POINTS 45 REVIEWING THE LADDER LOGIC FOR THE DNB 46 LAB 5 SUMMARY 46 LAB 6: ADDING A POWERFLEX70 DRIVE 47 ABOUT THIS LAB 47 ADDING THE POWERFLEX70 DRIVE TO THE I/O CONFIGURATION 47 VIEWING THE PRE-DEFINED DATA STRUCTURE FOR THE POWERFLEX 70E 50 9/21/2004 Page 3 of 98
4 CREATING ALIAS TAGS FOR USE WITH THE POWERFLEX 70 DRIVE 51 DOWNLOADING THE RSLOGIX 5000 PROJECT AND VERIFYING SUCCESSFUL COMMUNICATION 53 REVIEWING THE LADDER CODE AND OPERATING THE DRIVE 54 CHANGING THE SPEED REFERENCE 55 LAB 6 SUMMARY 56 LAB 7: WEB SERVER AND TRAFFIC MONITORING 57 ABOUT THIS LAB 57 START WEB BROWSER 57 LAB 7 SUMMARY 62 EXTRA TASK 62 LAB 8: REVIEWING FEATURES OF THE EWEB MODULE- MORE THAN WEB SERVICES 63 ABOUT THIS LAB 63 OPENING AN EXISTING RSLOGIX 5000 PROJECT AND DOWNLOADING TO THE CONTROLLOGIX PROCESSOR 63 ACCESSING THE 1756-EWEB 64 CREATING AND USING DATA VIEWS (AND REMOTE CUSTOM DATA MONITOR) 65 WRITING DATA TO THE L55 PROCESSOR FROM THE EWEB MODULE 66 SETTING UP THE EWEB TO SEND S 67 SENDING CONTROLLER GENERATED S 68 MODIFYING AND DOWNLOADING WEB PAGES 71 DATA COLLECTION THROUGH XML 72 LAB 8 SUMMARY 75 APPENDIX A: ADDING DEVICES TO THE NETWORK 76 APPENDIX B: COMMUNICATION FORMATS 83 9/21/2004 Page 4 of 98
5 APPENDIX C: ADDING MODULES TO I/O CONFIGURATION LIST 84 ADDING AN INPUT MODULE TO THE PARENT RACK 84 ADDING AN OUTPUT MODULE TO THE PARENT RACK 86 ADDING ETHERNET/IP MODULE TO THE I/O CONFIGURATION 88 CONFIGURING A REMOTE ETHERNET NODE 89 APPENDIX D: VERIFYING THE DEVICENET SCANLIST USING RSNETWORX FOR DEVICENET 92 APPENDIX E: DRIVE EXPLORER 94 CONFIGURING / MONITORING DRIVE PARAMETERS USING DRIVEEXPLORER 94 VERIFYING PARAMETERS IN THE 20-COMM-E 96 ACCESSING THE ADAPTER S MAIN WEB PAGE 98 9/21/2004 Page 5 of 98
6
7 Welcome to the Introduction to EtherNet/IP Hands-On Lab About This Hands-On Lab Welcome to the Introduction to EtherNet/IP lab. The IP in EtherNet/IP puts the industrial in standard EtherNet/IP, allowing you to perform I/O control, device configuration, and data collection on a single network. While going through this lab session, you will learn the easy and powerful features of EtherNet/IP. What You Will Accomplish In These Labs As you complete the labs in this hands-on session, you will understand the followings: How to configure a network How to do analog I/O How to do interlocking How to use PanelView Plus 600 How to use PowerFlex Drives How to use web server page for traffic monitoring How to use EWEB module Who Should Complete This Lab This hands-on lab is intended for users wondering if EtherNet/IP could work for their application. Knowledge of RSLogix 5000 and RSLinx would be helpful, but is not required. Before You Begin Before you begin this lab, please complete the following computer setup steps: 1. Close any applications that are running. 2. From the service tray in the lower right-hand corner of the computer desktop, right click on the RSLinx icon and click on Shutdown RSLinx. 3. Ensure that the RSI Service Directory is shutdown as well (this should terminate when you Shutdown RSLinx). 4. From the computer desktop, double-click on the Batch Files shortcut. 5. Double-click on the Intro to EthernetIP.bat file and follow the prompts. 9/21/2004 Page 7 of 98
8 6. If the ControlLogix Processors are not already in Remote Program mode, use a keyswitch to change them to Remote Program. 7. Review the physical EtherNet/IP demo box on your table (single box). 8. Review the EtherNet/IP network diagram for the demo box: 9/21/2004 Page 8 of 98
9 9. Review the chart below for IP addresses you will use later in the lab: Note that initially you will have a network consisting of 7 nodes on your table. Document Conventions Throughout this workbook, we have used the following conventions to help guide you through the lab materials. This style or symbol: Words shown in bold italics (e.g., RSLogix 500 or OK) Words shown in Courier text, enclosed in single quotes (e.g., 'Controller1') FYI Indicates: Any item or button that you must click on, or a menu name from which you must choose an option or command. This will be an actual name of an item that you see on your screen or in an example. An item that you must type in the specified field. This is information that you must supply based on your application (e.g., a variable). Note: When you type the text in the field, remember that you do not need to type the quotes; simply type the words that are contained within them (e.g., Controller1). The text that is displayed as shown is supplemental information regarding the lab materials; it is not information that is required reading in order for you to complete the lab exercises but may provide you with helpful hints that can make it easier for you to use this product. Note: If the mouse button is not specified in the text, you should click on the left mouse button. 9/21/2004 Page 9 of 98
10 Reviewing the Application Story This lab has been created mostly around the ControlLogix L63 processor in slot 3 of the chassis in the upper left corner of the demo box. You may assume that most of your plant operations are through the L63 controller which includes the discrete control, analog control, PowerFlex drive, Electronic Operator Interface, and DeviceNet. Your management decided to add a remote controller (L55) for process interlocking at a later phase. Also, you decided to add a web interface module (EWEB) for providing easy access to maintenance department and remotely located system integrators to diagnose, troubleshoot, and predict maintenance issues on devices or machines in the plant. If this was a real project, prior to this point you should have taken the following steps to install your system: All Rockwell Automation modules including EtherNet/IP interfaces are installed and powered up. Control and network wiring are complete. Almost 90% of the start-up problems are due to either wiring or network architecture related. Your controllers are connected via EtherNet/IP network or other networks. You verified the system status by looking at the LEDs of the controller and EtherNet/IP interfaces. You are ready to configure the IP addresses and other network parameters for each EtherNet/IP devices. There are several ways to configure an IP address, Rockwell BOOTP utility is just one of them. Other tools are RSLinx software, RSLogix 5000 software, DHCP software and more. If you want to learn how to use BOOTP, refer to Appendix-A. To save time, all EtherNet/IP nodes have been pre-configured in this lab. 9/21/2004 Page 10 of 98
11 Lab 1: Configuring the Computer to Communicate to the PLC In this lab, we will introduce you to the RSLinx communications software. In this lab you will: Start RSLinx Configure an EtherNet/IP driver Launching RSLinx Communication Software and Configuring a Driver RSLinx is the communication software that allows a PLC to communicate with your computer. We must first configure how we want our computer to communicate with our PLC. 1. From the Windows start menu select Start > Programs > Rockwell Software > RSLinx > RSLinx. If this launches the software in the computer service tray (lower right corner of the computer desktop), click on the RSLinx icon to maximize the software. 2. Once RSLinx starts, from the toolbar menu select Communications > Configure Drivers as shown below: 9/21/2004 Page 11 of 98
12 3. When the Configure Drivers window appears, from the Available Driver Types pull-down menu, locate and choose the EtherNet/IP Driver and then click the Add New button. FYI In RSLinx you noticed 3 different Ethernet drivers listed: EtherNet/IP Driver, Ethernet devices, and Remote Devices via Linx Gateway. In general, you should use the new EtherNet/IP Driver. It will automatically scan for and find any EtherNet/IP compatible devices on the network. A few older Rockwell EtherNet/IP products cannot be found using this driver. The older drivers work with all Rockwell EtherNet/IP products, but will only scan for IP addresses that you manually tell them to search for. You can have combinations of drivers and/or multiple instances of each type active in RSLinx at the same time if needed. 4. Accept the default name of AB_ETHIP-1 by clicking OK. 5. When the Configure Driver: AB_ETHIP-1 dialog appears, ensure that the Browse Local Subnet radio button is checked and then click OK. This is selecting where the EtherNet/IP modules reside. The software locates valid IP addresses. 9/21/2004 Page 12 of 98
13 6. Verify that the driver is RUNNING as shown below: The driver is now available and you can select the EtherNet/IP port from Who Active in RSLogix5000 programming software. 7. Close the Configure Drivers dialog box and click on the RSWho icon. The RSWho Window appears as shown below: 9/21/2004 Page 13 of 98
14 8. Click on the + sign next to AB_ETHIP-1, EtherNet/IP. This enables the EtherNet/IP driver in RSLinx to browse your network and identify the nodes in your network. You should see the following IP addresses: 9. Close RSWho. 10. Close RSLinx. This completes configuring your computer using the RSLinx EtherNet/IP driver. Lab 1 Summary Did you notice that you did not have to define any IP addresses in RSLinx? Isn t this a cool feature!?! Also, RSLinx is a great tool to check out your network during start-up. 9/21/2004 Page 14 of 98
15 Lab 2: Adding FLEX I/O About This Lab The purpose of this lab is to add a 1794-AENT (FLEX adapter with an analog output module) to your network, configure that node and control the analog meter on the I/O panel. You will notice that two discrete I/O modules (1756-IB16D and 1756-OB16D) already exist under the Parent ENBT module in your I/O configuration list. The discrete input/output modules are required for controlling the push buttons on the I/O panel. Also, the Child ENBT already exists in the I/O configuration list. You will be adding a DeviceNet scanner to this Child ENBT in the DeviceNet lab. In this lab you will: Add an FLEX adapter (1794-AENT) and an analog output module(1794-oe4e) to the I/O tree in RSLogix 5000 Configure the modules (I/O tags are automatically created when you add an I/O module to the configuration tree) Write Logic in the controller Note that to save time you will not write any ladder code. The necessary ladder rungs are already there in your project. Launching a Project in RSLogix 5000 Programming Software In this section of the lab, you will launch the RSLogix 5000 software, which will allow you to program the project. 1. From the computer desktop, double-click on the Working Folder. 2. Double-click on the existing project called EIP_DEMO.ACD. This will launch the project in RSLogix The Controller Organizer appears on the left side of the RSLogix 5000 window, with a Controller folder called EIP_DEMO. Notice that the locally configured modules: Parent ENBT (IP address = ), discrete input, and discrete output. These modules are required for using the push buttons in the I/O panel. The Child ENBT (IP address= ) has also been configured. 9/21/2004 Page 15 of 98
16 If you want to learn how to add modules to I/O Configuration list, refer to Appendix C at the end of this document. 3. Right click on the Child ENBT > Properties to view the configuration parameters such as IP address, Slot number, etc.. 4. Click on Cancel when you have finished reviewing the Module Properties. Adding the1794-aent adapter module to the I/O configuration list 1. From the Controller Organizer I/O Configuration folder, right click on the Parent 1756-ENBT module, choose New Module, and then click on the 1794-AENT module as shown below: 9/21/2004 Page 16 of 98
17 2. Click on OK. 3. When the Select Major Revision window appears, select Major Rev 2 as shown below and click OK to accept your changes. 4. When the following dialog box appears, configure the 1794-AENT as shown below and then click Finish. If you want to learn more about Communication Formats, refer to Appendix B at the end of this document. 9/21/2004 Page 17 of 98
18 Adding a 1794-OE4 Module to AENT in RSLogix 5000 Project 1. From the Controller Organizer I/O Configuration folder, right click on the 1794-AENT and choose New Module. 2. When the following window appears, select the 1794-OE4 module from the list and then click OK. 3. When the Module Properties window appears, enter the parameters as follows and then click on the Next button. 9/21/2004 Page 18 of 98
19 4. The following screen shows the default RPI value of 50ms. Leave this value configured as shown below: 5. Click on Next 3 times so that you see the following configuration screen: 6. Use the pull-down menu for Channel 0 to select a range of (0 to 10V)/(0 to 20ms) since we will be using 0 to 10 VDC for the analog meter in the demo box. 7. Click on Finish. 9/21/2004 Page 19 of 98
20 Adding Alias tags to the Controller An alias tag lets you create one tag that represents another tag. Both tags share the same value. When the value of one tag changes, the other tag changes its value as well. Why we are using alias tag in this lab? As you have noticed, the ladder codes were written first, and we used general tag names in the ladder logic. The great advantages of alias tags are as follows: For each I/O device, you can create a descriptive name that describes the device, such as In_any_PB (Input signal from any push button) or Dout lites (outputs to the illuminated lamps). One can however, customize these tag names depending upon the type of applications. Test your logic without the I/O connected Later, when the I/O layouts are complete, add the I/O modules to the I/O configuration of the controller. Finally, convert the descriptive tags to aliases for their respective I/O connections. In this section you will connect three descriptive tags in the controller scope to their respective I/O points. 11. From the Controller Organizer, double-click on the Controller tags. You will see the following descriptive tags: The In_meter_up tag (input signal for forward movement of the meter) is for the upper right most push button. Similarly, the In_meter_down tag (input signal for reverse movement of the meter) is for the lower right most push button. The Out_meter tag is for analog output signal to the analog meter. 9/21/2004 Page 20 of 98
21 12. From the bottom of the Controller Tags window, click on the Edit Tags tab. 13. In the tag editor click in the Alias For column next to the In_meter_up tag and click on the down arrow. 14. Select Local:1.I.Data, and finally select the bit 3 from the bit table as shown below: 15. In the tag editor click in the Alias For column next to the In_meter_down tag and click on the down arrow. 16. Select Local:1.I.Data, and finally select the bit 7 from the bit table. Bit 7 is being used for analog meter down/reverse movement. 17. Verify that the tag editor appears as follows: 18. In the tag editor click in the Alias For column next to the Out_meter tag and click on the down arrow. 9/21/2004 Page 21 of 98
22 19. Connect this tag to analog channel output MyFlexAEN:0:O.Ch0Data as shown below: 20. Verify that your I/O Configuration and Controller Tags appear as follows before moving on: 21. From the toolbar menu, select File > Save As. 22. Save your project under the same name (EIP_Demo) in directory c:\rslogix 5000\Projects. 9/21/2004 Page 22 of 98
23 Downloading and Testing the 1794-AENT AND 1794-OE4 1. Verify that your controller is in Remote Program mode by toggling the keyswitch to PROG then back to REM. 2. From the toolbar menu, select Communications > WhoActive. 3. When the Who Active window appears, browse to the 1756-L63 processor as shown below and then click Download. 4. Go into Remote Run mode on the processor by toggling the keyswitch to RUN then back to REM. 5. From the Controller Organizer I/O Configuration folder, examine all modules. There should be no yellow triangles visible on any of the modules. The Logix processor I/O LED should be solid green. If you see yellow triangles, right-click on any yellow triangle and then select the Connection tab to view status. If you need help, call a lab assistant. The analog output module will drive the voltmeter (in the demo box). You don t have to write any ladder code. Ladder code for 1794-OE4 Analog Module already exists in your Demo_Routine. 9/21/2004 Page 23 of 98
24 6. From the Controller Organizer, double-click on the Demo_Routine to open the ladder editor. 7. Notice the following 3 rungs of logic for the 1794-OE4 which drives the analog meter in the demo box. Verifying FLEX Ladder Logic Your ControlLogix 5563 processor is already in Remote Run mode. 1. In the demo box I/O panel, press and hold the METER UP pushbutton to make the AO0 meter goes up. 2. Press and hold the METER DOWN pushbutton to make the meter goes down. 3. If the meter does not go up or down, call a lab assistant. 9/21/2004 Page 24 of 98
25 Lab 2 Summary You learned how to add a FLEX adapter and an analog output module to the I/O list, and configure them to operate an analog meter in the I/O panel. You now have 1756 I/O, and FLEX I/O working! Congratulations!! 9/21/2004 Page 25 of 98
26 Lab 3: Processor Interlocking About This Lab The purpose of this lab is to understand how to Produce a tag and Consume a tag. This method enables you to interlock Logix processors without programming. Logix controllers can produce (multicast) and consume (receive) system- shared tags that are sent and received via the EtherNet/IP communication module. A produced tag allows a PLC processor to produce a tag out on the wire for consumption by 1 or more processors on the network. This is used most frequently for interlocking processors. The controller (5563) in the Parent rack will Produce a tag. The controller (5555) in the Child rack will Consume that tag. To produce a tag, you have to configure the produced tag in the RSLogix 5000 project for the 5563 controller. You have to also configure a consumed tag in the RSLogix 5000 project for the 5555 controller. Network Diagram IP= Panelview IP= Ethernet Switch Interlocking 1756-ENBT in Parent rack 1756-L63 controller IP= ENBT Parent IP= ENBT in Child rack 1756-L55 controller IP= PF 70 9/21/2004 Page 26 of 98
27 Verifying EtherNet/IP Connectivity 1. From the toolbar menu in RSLogix 5000, select Communications > Go Offline. 2. Maximize RSLinx by clicking the RSLinx icon in the computer service tray. 3. From the toolbar menu, select Comunications > RSWho. 4. Navigate through the AB_ETHIP-1 driver to ensure that you find both the controllers, one in the Parent rack and another in the Child rack. 5. When you have verified that your network appears as shown above, close RSWho and minimize RSLinx. Let us create a Produced tag in L63 controller now. Creating a Produced Tag in L63 Controller 1. Back in RSLogix 5000, right-click on the Controller Tags folder and select Edit Tags. 2. Scroll to the bottom of the tag list, right click on the asterisk, and select Edit Tag Properties. 9/21/2004 Page 27 of 98
28 3. When the Tag Properties window appears, enter the parameters as shown below: 4. Click on OK. 5. Verify that you see the Produce_tag in your controller s tag list and then Save your work by clicking on the Save icon. 6. From the toolbar menu, select Communications > Who Active. 9/21/2004 Page 28 of 98
29 7. When the Who Active window appears, select the 1756-L63 processor as shown below and click Download. 8. When prompted, select Yes to place the controller into Remote Run. 9. Examine the list of modules in your I/O configuration list. There will be no yellow triangles. At this point of time you will have a solid green I/O indication on your controller. 10. Minimize this session of RSLogix /21/2004 Page 29 of 98
30 Configuring the Consumer of the Produced Tag In this lab, you will open another RSLogix 5000 project where you will configure the consumer of the Produce_tag you created in the previous lab section. 1. From the computer desktop, double-click on the Working Folder. 2. Double-click on the existing project called Consumer55.ACD. This will launch the project in RSLogix RSLogix5000 is in Offline mode. Your I/O configuration and controller s tag list look like the following picture: Adding a Remote Controller in the L55 Project (Defining the Producer) You already have the Parent ENBT defined in your I/O configuration tree. In this section of the lab, you will add a Controller (L63) under that. Notice the digital input module in the configuration tree. We require this input module for using one push button (DI0) on the IO panel. 9/21/2004 Page 30 of 98
31 1. Right click on the Parent ENBT, click on New Module, and select L63 from the list of available devices. 2. Click on OK, choose Major Revision 13 when prompted, and click on OK once again. 3. Enter the parameters as shown below, then click on Finish. 9/21/2004 Page 31 of 98
32 4. Verify that EIP_Demo shows up under Parent ENBT in the I/O configuration list as shown below: Creating a Consumed Tag Now, create a consumed tag in the controller named ConsumerL In your Consumer55.ACD project, double-click on the Controller Tags and select the Edit Tags tab at the bottom left corner of the Tags window. 2. Create a new tag named Consume_tag as shown below and then click in the white space below the tag to accept your change. 3. Select the Consume_tag by clicking on the grey area to the left of the tag name. This will select the entire record as shown below: 4. Right click on the record and select Edit Tag Properties. 9/21/2004 Page 32 of 98
33 5. When the Tag Properties dialog box appears, ensure you re on the General tab and fill in the parameters as shown below: 6. Click on the Connection tab and configure the parameters as shown below: 7. Click on OK and verify that the newly created tag appears as follows: 9/21/2004 Page 33 of 98
34 Saving and Downloading the Consumer Project 1. Save your project. 2. From the toolbar menu, select Communication > Who Active. 3. Navigate through the Child node (IP address = ) to select 1756-L55 controller as shown below: 4. Click on the Download button. 5. When the following screen appears, click Download once again. 6. Change the controller mode back to Remote Run mode. 9/21/2004 Page 34 of 98
35 7. Verify that your Consumer55 project has all steady green LEDs and no yellow triangles as shown below: Initializing the Produced Tag 1. Verify that both the controllers L63 and L55 are in Remote Run mode. 2. In the EIP_Demo.ACD (producer) project, double-click on Controller Tags and ensure you re in Monitor Tags mode. 3. Locate the Produce_tag you created earlier in the lab exercise. 4. Initialize the 2 DINTs to some non-zero values such as 11, 111 as shown above. 9/21/2004 Page 35 of 98
36 Testing the Produced and Consumed Tags 1. In the Consumer55.ACD project, double-click on Controller Tags and ensure that you are in Monitor tags mode. 2. Locate the Consume_tag you just created and verify that the tag values (e.g., 11, 111) are the same as being produced. 3. To prove that the tags are being consumed, the students should left-click on either of the consumed tags and set the value to 0. The tag should immediately change back to the nonzero value (11). 4. Save your work. 5. In both projects, from the toolbar menu, select Communications > Go Offline. 6. In both projects, from the toolbar menu in both projects, choose File > Close. Lab 3 Summary Did you like the data exchange method using Produced tag and Consumed tag? You did not write any ladder code for exchanging data. Did you notice that the consumption rate is defined in the Consume tag!! 9/21/2004 Page 36 of 98
37 Lab 4: Using RSView ME and PanelView Plus 600 About This Lab This lab will provide a demonstration of EtherNet/IP communications to a PanelView Plus 600. The programs for the PanelView Plus 600 and the ControlLogix processor have already been constructed. The ControlLogix program was created using RSLogix The PanelView Plus 600 program was created using RSView Studio. We will use a PanelView Plus 600 Touch screen. Downloading to the 5563 Processor 1. From the RSLogix 5000 toolbar menu, select File > Open. 2. Open the program named EIP_DEMO_PVP.ACD. 3. Download this program to the L63 processor in slot 3 of the upper chassis of your lab station (IP address ) and go into Remote Run mode. 4. From the toolbar menu, select Communications > Go Offline. 5. From the toolbar menu, select File > Exit. Opening the Existing RSView ME Project 1. From the computer desktop, double-click on the RSView Studio icon. 2. Select and click on Continue. 3. When the following list appears, select the EIP_DM application as shown below and then click Open. 9/21/2004 Page 37 of 98
38 This will launch the development environment for RSView Studio as shown below:. Reviewing the HMI Communications Path An application display screen has already been created for this lab. What needs to be configured is the path to the controller tags that will be displayed on the PanelView Plus Expand the RSLinx Enterprise icon in the tree and double-click on the Communications Setup. This will display the communications setup window. 9/21/2004 Page 38 of 98
39 2. Verify that the communication shortcut EIP has already been created. 3. Click on the Local and Target tabs and verify that the communication path is directed to the 1756-L63 in slot 3 as shown above. 4. Select OK to close the Communications Setup window. Creating and Downloading a Runtime Application Now that the configuration is complete, the runtime application must be created. 1. From the toolbar menu, select Application > Create Runtime Application. 2. Type the filename EIP_DM.mer and select Save. Please be patient as the runtime image is created. 3. To download this image, select Tools > Transfer Utility from the toolbar menu. 4. Use the Browse key to select the file you just created. 9/21/2004 Page 39 of 98
40 5. Select the PanelView Plus 600 (IP Address ) for the Destination Terminal and select Download. 6. If asked if you want to overwrite the existing file, select Yes. 7. Once the download completes, select OK and exit the transfer utility. The application has been downloaded to the PanelView Plus Go to your PanelView Plus 600 screen. The RSView Station window should be displayed. 9. Load the image that was downloaded by selecting Load Application. 10. Choose the file that was downloaded (EIP_Demo.mer) and select Load. 11. Select Yes to replace the current configuration. It will take a few moments to load. 12. Once loaded, select Run Application. 9/21/2004 Page 40 of 98
41 13. The following screen will appear that looks similar to the demo box push buttons and gauge:. 14. In RSView Studio, select File > Exit from the toolbar menu. FYI While online in RSLogix5000, note that the PanelView Plus 600 does not appear in the I/O Configuration of the ControlLogix processor. In this demonstration, the PanelView Plus 600 is initiating the transfer of information (explicit messaging). So, the PanelView Plus 600 is not in the list. The RSLogix5000 program downloaded includes all functionality that you have observed through the completion of the previous labs. It also includes ladder logic that will provide parallel functionality for the PanelView Plus 600. Confirming the PanelView Plus 600 Operation Test the PanelView Plus 600 by doing the following: 1. On the PanelView Plus 600 screen, press and hold the DI03 button. The analog meter should start the move to the right. 2. On the PanelView Plus 600 screen, press and hold the DI07 button. The analog meter should start the move to the left. 3. Press the real pushbuttons on the demo box. Note the resultant action of the outputs and the analog meter on your PanelView Plus 600. It has been designed to mimic the same operation. 4. Press the pushbuttons on the PanelView Plus 600 screen and observe how the results on the hardwired I/O and the screen are the same (reference the LEDs 1756-IB16D and 1756-OB16D in slots 1 and 2 of the top chassis). 5. When you have finished exercising the PV+ 600, press the Goto Config button on the screen to return to the RSView ME Station. 9/21/2004 Page 41 of 98
42 6. From the Main Menu, select Terminal Settings > File Management > Delete Files > Delete Applications. 7. Select the file you downloaded and press the Delete button. 8. When finished, continue to press the Close button until you reach the Main Menu. Lab 4 Summary What you learned from this lab: Applications can be developed for the PanelView Plus 600 that can monitor tags within a controller as well as modify the tags via the touch screen. You can create a PanelView Plus 600 application and download it over EtherNet/IP to the PanelView Plus 600 device. 9/21/2004 Page 42 of 98
43 Lab 5: Add Remote I/O on DeviceNet About This Lab The purpose of this lab is to demonstrate access to a remote DeviceNet I/O over EtherNet/IP. By adding a 1756-DNB in your Child (remote) chassis, you will verify that the DeviceNet photoeye (in the demo box) can control the discrete output lights in the demo box. Add 1756-DNB to RSLogix5000 Project 1. From the computer desktop, double-click on the Working Folder. 2. Double-click on EIP_Demo.ACD to launch the project in RSLogix From the I/O Configuration folder in the Controller Organizer, right click on the Child ENBT and select New Module. 4. When the Select Module Type window appears, select the 1756-DNB and click OK. 5. When prompted, choose Major Revision 4 and select OK to accept your changes. 9/21/2004 Page 43 of 98
44 6. When the Module Properties dialog box appears, enter the parameters as shown below: The Input Size is 1 because the photoeye has only 1 byte of input data, so single DINT is adequate. The Status Size of 32 is the default size provided by the DNB and RSLogix Click on Next and change the RPI to 10 ms as follows and then click on Finish. 9/21/2004 Page 44 of 98
45 Connecting Alias tags to their I/O Points 1. From the Controller Organizer, double-click on Controller Tags. You still have two descriptive tags which are not connected to their I/O points: In_photo tag is an input tag to the 1756-DNB Out_DNB_Run tag is for the Command Register Run mode bit 2. In the tag editor, click in the Alias For column next to the In_photo tag. Then click on the down arrow. When the tag browser opens, double-click on Child3:I.Data[0] as shown below: 3. Verify that your tag editor now appears as follows: 4. Repeat step 2 above for the tag Out_DNB_Run and connect it to the Child:3:O.CommandRegister.Run by clicking on the + sign next to Child:3:O.CommandRegister and choosing the Run bit from the pre-defined structure. 5. From the toolbar menu, select Communications > Download and download to the L63 ControlLogix controller in slot 3 of the top chassis. 6. Go into Remote Run mode. 7. Verify that all modules in the I/O list do not have yellow triangles on any modules in the I/O Configuration. 9/21/2004 Page 45 of 98
46 If you have a yellow triangle(s), click on the module and select the Connection tab to view the status and call a lab assistant for help. Reviewing the Ladder Logic for the DNB 1. From the Controller Organizer, double-click on Demo_Routine under the Main Task. This will launch the ladder editor where you can view and edit ladder logic. 2. Review rungs 1 and 2. Rung 1 puts the DNB in Run mode. Rung 2 writes data to the output LEDs on the demo box when you place an object in from of the photoeye.look at the rungs. Photo eye senses object in front of it 3. Verify that the LED display on the DNB indicates RUN mode. 4. If all LEDs in the demo box are on, press any push button on the panel to switch off the lights except the light you press. 5. Now, put your hand in front of the photoeye switch and verify that all the LEDs illuminate. Lab 5 Summary We demonstrated the access to a remote DeviceNet I/O over EtherNet/IP. This is how DeviceNet equipment at the plant floor level communicates with the remote Controller over EthernNet/IP. Optional Lab Exercise: If you wish to learn more about creating a scanlist for the 1756-DNB, go to Appendix D. 9/21/2004 Page 46 of 98
47 Lab 6: Adding a PowerFlex70 drive About This Lab The purpose of this lab is to add a PowerFlex70 drive to your network, configure that node and control it over EtherNet/IP. The PowerFlex 70 demo box is a stand alone device. Ensure that the drive is physically connected to the switch located in the EIP demo box and single phase A/C power is available to the drive. If you want to learn about Drive Explorer for configuring and monitoring drive parameters, go to Appendix E. Drive Explorer is RSLogix5000 independent tool, which comes free with the drive. Adding the PowerFlex70 Drive to the I/O Configuration 1. From the toolbar menu, select Communications > Go Offline. 2. In the I/O Configuration folder, right click on the Parent 1756-ENBT and choose New Module. 3. When the list of available devices appears, select the PowerFlex 70E as shown below and click OK to accept your change. 9/21/2004 Page 47 of 98
48 4. When the following window appears, select Major Revision 2 as shown below and click OK. 5. When the Module Properties window appears, configure the PowerFlex 70E drives as follows: FYI Datalinks A Datalink is a type of pointer used by PowerFlex drives to transfer data to and from the controller. Datalinks allow specified parameter value(s) to be accessed or changed without using explicit messages. When enabled, each Datalink consumes either four bytes or eight bytes in both input and output image table of the controller. The drive determines the size of Datalinks. 9/21/2004 Page 48 of 98
49 6. Click the Next button. 7. Leave the Requested Packet Interval set at the default value of 5 ms as shown below and click on Finish. FYI Requested Packet Interval (RPI) In the RPI value determines the maximum interval that a controller would move data to and from the adapter. To conserve bandwidth, it is wiser to use higher values with the lower priority devices 8. Verify that the PowerFlex 70E drive is now listed to the I/O configuration as shown below: 9/21/2004 Page 49 of 98
50 Viewing the Pre-Defined Data Structure for the PowerFlex 70E 1. From the Controller Organizer, double-click on Controller Tags. 2. Change the scope from Main_Routine to EIP_Demo (controller).. 3. Locate and expand the PF_70:I data structure to view the tags that were automatically created when you added the PowerFlex 70 E drive to the I/O Configuration. Notice that the tag names correlate to the Logic Status bits and Feedback word. These status/feedback bits can be used in the ladder code for monitoring your drive status. 9/21/2004 Page 50 of 98
51 4. Locate and expand the PF_70:O data structure to view Logic Command Bits and Reference word, which were created automatically by adding the PowerFlex 70E to the I/O Configuration. We will use an extra step to add few alias tags. In the Flex IO lab you have already used alias tags and you are aware of its advantages. Creating Alias Tags for Use with the PowerFlex 70 Drive In order to save time in the lab, the controller tags and the ladder program already exist in the Main_Routine. You have to associate the alias tags to its actual I/O addresses. Let us look at the Controller tags first. These are the logic command tags being used for operating various drive functions. You will be using these bits in the ladder code to operate the drive. 1. From the Controller Organizer, locate the tag Start Command. 2. Click on the Alias For column next to the tag Start Command, browse through the tag list under PF_70:O, and double-click on PF_70:O.Start as shown below: 9/21/2004 Page 51 of 98
52 3. Left click to accept the tag change. 4. Verify that the tag now appears as follows: 5. Use this same procedure to alias the following tags: Stop_Command > PF_70:O.Stop Reverse_Command > PF_70:O.Reverse Jog_Command > PF_70:O.Jog Forward Command > PF_70:O.Forward ClearFault_Command > PF_70:O.ClearFault 6. When you have finished aliasing the tags into the PowerFlex 70E data structure, the controller tag editor should appear as follows: 9/21/2004 Page 52 of 98
53 Downloading the RSLogix 5000 Project and Verifying Successful Communication 1. From the toolbar menu, select Communications > Who Active. 2. When the Who Active window appears, browse to the 1756-L63 processor as shown below and then click Download. 3. Go into Remote Run mode on the processor by toggling the keyswitch to RUN then back to REM. 4. Verify that your I/O Configuration appears as shown below (no yellow triangles should be visible). 9/21/2004 Page 53 of 98
54 5. On the controller faceplate, verify that the I/O OK LED is solid green as shown below: 6. On the PowerFlex drive (20-COMM-D), the PORT, MOD and NET A LED s should also be solid green. Now you are ready to start and stop the drive. Reviewing the Ladder Code and Operating the Drive This section demonstrates PowerFlex70 operation. 1. From the Controller Organizer, double-click on Demo_Routine to open the routine in the ladder editor. 2. Review rungs 6 10 which are meant for operating the drive. The respective output bits are called Logic Command Bits. 9/21/2004 Page 54 of 98
55 3. Right click on the Start and select Toggle Bit to energize this tag. The drive will start running in the forward direction. 4. Right click on the Start again and select Toggle Bit to de-energize this tag. Notice that the drive started on an OFF > ON transition of the Start_Command and will continue to run until a Stop_Command is initiated. 5. Right click on the Stop and select Toggle Bit to energize this tag. The STS LED on the PowerFlex 70 will flash yellow to indicate that a Stop command has been initiated. The drive will stop. 6. Right-click on the Stop again and select Toggle Bit to de-energize this tag. The yellow flashing changes to green flashing. Try this same procedure for the direction (Forward and Reverse) bits: 7. Toggle the Reverse bit on. Notice that the drive motor doesn t move; you must now enable the drive by toggling the Jog bit. 8. Toggle the Jog bit off and try the same thing with the Forward bit. 9. When finished exercising the drive, ensure that all bits are de-energized. Changing the Speed Reference In real life application, the commanded frequency (Hz) value entered in floating point format (xx.xx) is converted to engineering units before delivering that to the drive as speed reference. The drive will accelerate or decelerate to the command provided Start_Command is initiated. To keep it simple, we will avoid the scaling part, and directly manipulate the speed reference value from the Controller Tags 1. Make sure that the drive motor is not running. 2. From the Controller Organizer, double-click on the Controller Tags. 9/21/2004 Page 55 of 98
56 3. Expand the PF_70:O data structure to view the PF_70:O.CommandedFreq tag as shown below: You can enter any values between 0 32, 767. The PowerFlex drive s default Maximum frequency is 130 Hz. Once you have set a value for the CommandFrequency tag, and started the drive from the ladder code, you can monitor the frequency of the drive from its front panel. 4. If the STS Led on the front of the drive is red (indicating a fault), enter a 1 into the ClearFault tag and press Enter; then clear the tag by entering a Change the value for the Command Frequency and then press Enter. Notice that the drive motor is not spinning. 6. Enter a value of 1 in the PF70:O.Start tag. The drive should start to turn the motor at the commanded frequency. 7. Enter a value of 0 in the PF70:O.Start tag and a value of 1 in the PF70:O.Stop tag. 8. Verify that the motor slows to a stop before proceeding. 9. Minimize your RSLogix 5000 session. Lab 6 Summary You learned how easy it is to add a PowerFlex70 drive to the I/O list, configure the drive, and operate it on EtherNet/IP. Optional Lab Exercise: If you wish to learn more about Drive Explorer, an independent tool that can be used to configure and monitor PowerFlex drives, go to Appendix E. 9/21/2004 Page 56 of 98
57 Lab 7: Web Server and Traffic Monitoring About this Lab In this lab, you will learn how to use web diagnostic pages to check out the health of your network system, including both connections and I/O messages (Packets). You will view the CPU utilization counter and also learn how to compare the RPI (Requested Packet Interval) and API (Actual Packet Interval). Start Web Browser The following labs refer to Internet Explorer but you can use either Internet Explorer or Netscape. You are working with L63 controller. 1. From the computer desktop, double-click on the Internet Explorer icon. 2. Enter the IP address in the browser s address field. The following page appears: You are now viewing web page diagnostic information for the 1756-ENBT in the top chassis of the demo box. 9/21/2004 Page 57 of 98
58 3. From the menu on the left, expand the Diagnostics folder. 4. Click on Diagnostic Overview. The following screen appears: 9/21/2004 Page 58 of 98
59 FYI Reference the window on the previous page to review the following information: Ethernet Link Speed - The module is passing data over the EtherNet/IP network. Rockwell Automation EtherNet/IP interface modules support both 10Mbps and 100Mbps speeds. Duplex - The mode of communication module, full-duplex meaning transmission and reception of data simultaneously. Half-duplex means either transmission or reception of data. Auto negotiate Status Rockwell Automation EtherNet/IP interface modules auto negotiate with the switch for the 100 Mbps and full duplex mode. System Resource Utilization (CPU) This is an indicator of how loaded is your EtherNet/IP interface module at any point of time. CIP Connection Statistics Common Information Protocol (CIP) based connections are used for I/O controls and produce consume tags. I/O Packet / Second Statistics Actual class1 packets per second the module is currently receiving and transmitting over EtherNet/IP network. Actually, using a simple formula, you can calculate the number of packets / sec Packets per second = [C * 2] / RPI Where: RPI = Requested Packet Intervals i.e data update rate C = Number of connections For example, analog output module in the AENT adapter is a single Direct Connection (C=1) and it is using a RPI of 50 msec. Therefore, using the above formula, Packets per second = [1*2] / = 40. Can you verify this with the AENT module s web server page! Sent This field represents number of class1 packets sent each second to the controller 9/21/2004 Page 59 of 98
60 Receive This field represents number of class1 packets received each second from the controller Capacity Each ENBT module is capable of handling 5000 packets / sec. Each AENT module can handle 9500 packets / sec. Actual Reserve = Packet capacity (5000 or 9500 Actual class1 packets per sec) TCP Connections TCP connections are meant for EtherNet/IP communication. An EtherNet/IP interface device uses TCP connection for each IP address to which the device is connected. Multiple CIP connections can go through a TCP connection. For example TCP connections are: HMI (Human Machine Interface) to a controller that supports EtherNet/IP Logix MSG instruction to a controller OPC or DDE accessing a controller Produce-Consume tag 5. Click on Network Setting. The following screen appears: 6. Review the details under Network Interface and Ethernet Link. 9/21/2004 Page 60 of 98
61 7. Click on Message Connection. Message Connection tells you about the explicit message related connections or connections for non I/O control. For example, the above connection is between your computer running RSLogix5000 and L63 (IP address ). This is also called as Class 3 type connection. 8. Click on the I/O Connections. I/O Connections (also known as Class 1connections) are used for the most time critical data for I/O and produce consume tags. Notice the Source and Destination addresses in the above picture. RPI (Requested Packet Interval) is the update rate specified for a particular piece of data on the network. RPI can be defined for an entire rack or for a specific module. Notice the various RPIs above for different modules and rack. 9/21/2004 Page 61 of 98
62 9. Click on the Ethernet Statistics. The following screen appears: 10. Take some time to review the different types of errors under Media Counters. 11. When finished, close Internet Explorer by clicking on File > Close from the toolbar menu. Lab 7 Summary What should you remember from this lab? The packets/second capacity of 1756-ENBT is The packets/second capacity of AENT is Did you find the web server page helpful for monitoring and troubleshooting your EtherNet/IP network? Isn t this a great tool to diagnose the health of your network and performance of the individual EtherNet/IP interfaces? Extra Task For the Flex adapter module (1794-AENT), can you change Packets/Sec from 40 to 200? Answer: Packets /sec = (Connection * 2)/ RPI, RPI was 50 msec. New RPI = C * 2 / (Packets/sec) = 2 / 200 = 10 msec Therefore, change the RPI from 50 msec to 10 msec, packets /sec would be 200. How would you verify that? Answer: Check with the AENT web server page (IP = ). 9/21/2004 Page 62 of 98
63 Lab 8: Reviewing Features of the EWEB Module- More than Web services About this Lab In this lab we will explore the 1756-EWEB module. You are a production supervisor of Lacme Tool and Machine Company. Upper management has asked for easier access to production statistics in their office. You ve been manually publishing them once a day and it s been quite a pain. Now management says they want statistics at the end of each shift. Your task here will be to implement a web interface to allow access to production data from anyone who asks for permissions through your company intranet. Your Objectives as a Production Manager Make it simple for upper management to get production related data without your assistance from any office location to any plant location into the business system. Provide easy access to maintenance department and remotely located system integrators to diagnose, troubleshoot, and predict maintenance issues on devices or machines in the plant. Key Topics Covered in this Lab Routing and Explicit Messaging (no I/O) Creating and Using Data Views (convenient off-site access to control data) Sending s Modifying and Downloading Web Pages Data Collection with XML Background The EWEB module allows the user to host web pages from the ControlLogix rack. This enables Lacme s employees to view data from their control systems on any computer using Internet browser. (If the viewing computer is outside of the company network, the user will have to bridge the firewall). The EWEB also offers storing space for user documentation and help files. It offers 5.5MB worth of storage memory. Lacme is especially interested in remotely accessing its machines in the field and potentially correct problems without traveling to the site. Opening an Existing RSLogix 5000 Project and Downloading to the ControlLogix Processor 1. From the computer desktop, double-click on the Working Folder. 2. Double-click on the existing project called Consumer55.ACD. 3. From the toolbar menu, select Communications > Who Active and download the project to the ControlLogix L55 processor in slot 0 of the bottom chassis. 4. Go Online with the processor and go into Remote Run mode. 9/21/2004 Page 63 of 98
64 5. Minimize the RSLogix 5000 project. Notice the 1756-EWEB is in slot 2. The IP address of the EWEB module is You can also download the project using the EWEB module. The EWEB has all of the CIP Explicit Messaging capabilities of the 1756-ENBT. It can do everything the 1756-ENBT can do, except controlling I/O. Accessing the 1756-EWEB 1. From the computer desktop, double-click on Internet Explorer. 2. In the address field type and press Enter. This is the IP address of the EWEB module in slot 2 and will open the default EWEB web page as shown below: 3. From the menu on the left side of the web page, select Administrative Settings > User Management > Edit Users as shown below: 9/21/2004 Page 64 of 98
65 4. When the login screen appears, enter the following User Name and click OK. NOTE: This is the out-of-the-box login account. The password would need to be changed in any application that requires security. You are now on the Edit Users page. This is where you would set up an account to differentiate the amount of access to EWEB functionality by various users. We will use the default administrator s account. Access could be three types: Read: read only access to tags in the Data Views; Write: write and read access to tags in the Data Views; Administrator: complete access to all Web server functionality; Creating and Using Data Views (and Remote Custom Data Monitor) 1. From the menu on the left side of the web page, select Data Views > Data Views. 2. Click the New Data View tab at the top of the right-hand screen. 3. Fill out all the fields as shown below and then click on the Add icon (this will add the tag to a new data view). 9/21/2004 Page 65 of 98
66 MyDint is a tag that resides in the Consumer.ACD project running the L55 controller. 4. Name the Data View as MyView and then click the Create View button. Note: A data view may contain more than one tag of various types. Once the data view is created, you can see a list of all the data views. 5. Click on the Data Views tab. 6. Click on MyView.XML link under View Filename to see the data view you just created. The following screen appears: The EWEB module data views cannot retrieve data directly from I/O. If we wish to access this data, we must reference the data through an alias tag in the controller. Writing Data to the L55 Processor from the EWEB Module In addition to reading data from the Logix controller, the EWEB can also write data to the controller for diagnostics and limited troubleshooting. 1. Change the number in the Value window and click on the Update button. 9/21/2004 Page 66 of 98
67 2. Maximize the RSlogix 5000 project so you can verify the change you just made. 3. Double-click on Controller Tags and click on the Monitor Tags tab. 4. Locate the MyDint tag and verify that the value of the tag changed to reflect what you entered in the EWEB module. 5. Minimize the RSLogix 5000 project. Setting up the EWEB to Send s For this lab we have installed SMTP mail server software on your computer. Typically this server would be provided and running from your office IT staff. 1. From the computer desktop, double-click on the ArGoSoft Mail Server Icon. 2. From the menu on the EWEB module web page, click Administrative Settings > Device Configuration > Configuration. Your computer is the SMTP mail server for this lab. 3. Ensure that your computer s IP address is in the line for SMTP server ( ), the SMTP Authentication checkbox is empty, and then click Apply Changes. 9/21/2004 Page 67 of 98
68 SMTP Authentication is usually used with servers on the Internet, so only authorized users are allowed to "relay" mail through them. In this case, the ability to use the server successfully is based on authentication, and not at all on IP address. The idea is to prevent spammers from misusing server on the Internet. Sending Controller Generated s The EWEB has an interface that is good for testing the mail server and may, from time to time, prevent a user from having to open a separate client. However, the greatest benefit of the embedded client is that it allows the control system to send messages. 1. Maximize the RSLogix 5000 project and ensure that you are Online with the controller. In the file, there are three tags that we will be using to send an message. is sent using the MSG instruction, and there are three tags that we will be using to send a message: _text tag will contain our message _status tag will serve as a buffer for any status information returned by the MSG instruction _message tag controls the message (MSG) instruction. The _text and _status tags are of the pre-defined STRING type with a maximum length of 82 characters. This presents a problem since an message can easily exceed 82 characters. However, the content of messages sent from the controller to the EWEB may not exceed 474 characters (The message instruction must attach four characters as overhead making the maximum message length 478 characters). We, therefore, have aliased to strings of a user-defined string type with a maximum length of 474 characters. 2. In the Tag Editor, click on the Edit Tags tab. 3. Notice that the aliased_ _status tag is the alias for the _status tag. Similarly, aliased_ _text has been entered in the Alias For column for the _text tag. 4. Click on the Monitor Tags tab at the lower left corner of the tag editor. 5. Click on the Value column for the _text tag. 9/21/2004 Page 68 of 98
69 6. Click on the ellipsis and review the text in the string browser that will be ed from the controller: 7. Click Cancel when you have finished reviewing the string information. 8. From the Controller Organizer, double-click on the MainRoutine to open the ladder editor. The following rungs of code appear: 9. Open the Message Configuration dialog by clicking the ellipsis button in the MSG instruction. 9/21/2004 Page 69 of 98
70 10. Ensure all fields of the Configuration tab appear as shown below: 11. Click on the Communication tab and ensure that the path appears as 1, Click on Apply and OK to accept your changes. Examining the path, the 1 tells us to go to the back plane from the controller, and the 2 tells us to go to the EWEB module in slot Press the DIO button on the demo box. This should send an message from the controller to the computer. 14. Minimize the RSLogix 5000 project. 15. From the computer desktop, double-click on MS Outlook Express. 16. Double-click on the Inbox and verify that you received incoming . You should see the message you sent from the controller. This could also just as easily gone to a text pager or cell phone with text paging capability. 17. Delete all messages in the inbox and then Exit MS Outlook Express. 18. Turn off the ArgoSoft Mail Server by right clicking on the icon in the computer service tray and choosing Exit. 9/21/2004 Page 70 of 98
71 Modifying and Downloading Web Pages Management is thrilled with the new web interface and their ability to gather this data up to at will. In fact, your supervisor has been using it very extensively and has an issue with third shift production. It appears to fall off significantly over the other shifts. You get the new intern in the department to put together a web page so you can get even more data in a much easier to readable format. We will be using FTP to move files from your computer to the EWEB module. FTP stands for File Transport Protocol, and it is a standard technology, used for managing files on remote servers. 1. In the browser s address bar, type ftp://administrator@ which is the IP address for your EWEB module. FYI The password is transmitted over the network in plain text, so it is visible to anyone using a network Sniffer. It is recommended that you create a temporary Administrator account for when you use FTP to access the web server module. Also, leave FTP disabled except for when actively copying files to or from the web server module. 2. From the computer desktop, double-click on the Working Folder. 3. Copy the data.asp and main.html files and Paste them in the Internet Explorer window you just opened for FTP use. This will transfer them to the EWEB. Let s look at the web page we downloaded. 9/21/2004 Page 71 of 98
72 4. In the browser s address bar, type /user/web/main.html. The following screen appears: 5. Browse the different links on the web page to see if you can figure out why production on Line 7 is so low. Please be patient as the live camera images may take a minute to load. 6. Close Internet Explorer. Data Collection through XML One of the great benefits of the EWEB module is that it Queries and stores data in XML, a widely supported, platform independent file format. In this section, you will see some examples of how we can extract data from our XML data views. Let s see how management can easily pull this data from DataView on our web interface into an excel spreadsheet that gets fresh data on command. 1. Launch MS Excel. 2. From the toolbar menu, select Data > XML > Import. 9/21/2004 Page 72 of 98
73 3. In the File Name field, enter /user/system/dataviews/ProductionData.xml as shown below: 4. Click the Import button. 5. If the Login screen appears, enter a User Name of Administrator and click Enter. 6. When the following window appears, click OK. 7. If prompted to enable macros, say Yes. The excel sheet now collects live data as defined from the data view. Okay, this is sort of a success but the data is ugly with lots of fields that your management doesn t want to see. Lets customize this XML data in excel so that only the relevant production data is displayed. 9/21/2004 Page 73 of 98
74 8. From the toolbar menu, select Data > XML > XML Source. This provides a dialog to allow you to select which XML data fields you want and don t want in your excel data sheet. 9. Highlight all the data columns we just imported into the excel sheet and right click select Delete so the spread sheet is empty again. 10. Now drag elements from the XML Source dialog that you want displayed on your screen (we dragged Name, Path, and ns1: value on to our sheet below): 11. Now with one of the items you just dragged to the screen selected, from the toolbar menu select Data > XML > Refresh XML Data. The data you requested should be updated on your excel spread sheet. Now to generate shift reports, all that needs to be done is this excel spread sheet opened, the data refreshed and whatever excel functions need to be performed on the data can take place. 9/21/2004 Page 74 of 98
75 Lab 8 Summary In this lab, you explored the following features of the EWEB Module: Easy and simple access to plant floor data using Data Views Routing and Explicit Messaging (no I/O) Sending s Modifying and Downloading Web Pages Data Collection with XML 9/21/2004 Page 75 of 98
76 Appendix A: Adding Devices to the Network This Appendix if for informational purposes only and should not be treated as part of the lab exercise. Read this document to learn what BOOTP is and how it works. All the Rockwell Automation EtherNet/IP nodes have been configured using this tool. The IP addresses used in this lab are part of standard TCP / IP EtherNet/IP. What is BOOTP? In order for a host to exchange data with other hosts, each host must have its own distinct IP address. BOOTP is a simple way to provide IP addresses to hosts. BOOTP uses IP to provide IP configuration and boot service, hence the name BOOTP, for bootstrapping protocol. The requesting host sends a BOOTP request, which is answered by a BOOTP server that has a configuration for the requesting station. The way of assigning IP addresses varies depending upon the product. All the devices will be configured using a method called BOOTP as default. The table below describes different ways of configuring IP addresses: Devices Default 1756-ENBT BOOTP BOOTP RS232 through the 5555 / 5563 using RSLogix5000 ControlNet (CNB) Using RSLinx Gateway functionality or RSLogix5000 DH+ Using RSLinx Gateway functionality or RSLogix5000 EtherNet/IP Using RSLinx Gateway functionality or RSLogix5000 (through another, already configured, 1756-ENBT module in the same chassis as the un- initialized ENBT module). PanelView Plus 600 BOOTP DHCP / Manually from touch screen 1794-AENT BOOTP BOOTP / RSLinx Gateway PowerFlex70 Drive BOOTP DriveExplorer / PF70 HIM / Drive Executive 9/21/2004 Page 76 of 98
77 This method requires a computer to examine the list of hardware addresses for the devices connected to your network and assign corresponding IP addresses to them. General procedure: First, verify that your Rockwell EtherNet/IP nodes are not configured: 1756-ENBT modules (2) The OK LED is blinking green, the NET LED is OFF, and the MAC address is being displayed on the module AENT The Network Status LED is off (not illuminated), and the Module status LED is blinking green. There are several tools to configure PowerFlex 70 drive: PoweFlex HIM, BOOTP Server, DriveExplorer (Version 2.01 or higher) software, Drive Executive (Version 1.01 or higher). Panel View Plus 600 See touch screen Terminal setting on the RSView ME Station. Select Networks and Communication, then Network Connections, then Network Adapters, and finally select IP address. Check for the absence of IP address, and that DHCP OK is enabled. Also, in this screen, you can see the EtherNet/IP hardware address. 1. For each of your RA EtherNet/IP nodes, record the EtherNet/IP hardware address below (the labels are located on each device or PanelView Plus 600 setup screen): MAC Addresses IP adddresses 1756-ENBT (in BC chassis) 1756-ENBT (in BC chassis) 1794-AENT BC PanelView Plus BC EWEB 00 00BC PowerFlex BC On your desktop, double-click the BOOTP Server application.. 9/21/2004 Page 77 of 98
78 As shown below, the Address Relationship windows should both be empty. The Request History may be empty or have boot requests in it. 3. From the Tools menu, choose Network Settings. 4. When the Network Settings dialog appears, enter the following: This convenience will keep you from entering the same mask and gateway for each of the IP addresses you are about to assign. 5. Click on OK. 9/21/2004 Page 78 of 98
79 When BOOTP server software is open, any BOOTP enabled module will show up in the Request History as shown below. Here is an example: 6. Double-click on the MAC address. The New Entry dialog appears. 7. Enter your desired IP address. In this case, we are using the Parent ENBT 8. Click on OK. We are not using DNS (Domain Name Service) in this lab. We will be using IP addresses instead. 9/21/2004 Page 79 of 98
80 DNS provides the function of translating the IP address of a host / node into meaningful human understandable names. DNS uses a tree-like naming structure to provide a naming hierarchy. The newly entered IP address appears in the Relation List. This allows the BOOTP server to configure that module the next time it receives a BOOTP request. Wait until the next request is received (in the Request History window) from the module confirming the IP address was assigned to it. 9. Select the IP address from the Relation List and click on Disable BOOTP/DHCP; the status changes to Command Successful. This enables the EtherNet/IP interface devices to retain their IP addresses. 10. Repeat the steps above for the remaining nodes 1756-ENBT in the remote chassis (child) 9/21/2004 Page 80 of 98
81 1794-AENT FLEX adapter PowerFlex 70 drive Once you have completed these steps, your BOOTP Server screen should have multiple entries in the Relation List. Note: Your EtherNet/IP hardware addresses will differ from the above screen 11. PanelView Plus 600 (manually configure from the PV terminal) Navigation tips Terminal setting Networks and communications-network connections- Network adapters IP address. 12. Select Disable the DHCP button. Select IP address and type in the IP address for your PanelView Plus600. Now, select the Subnet Mask and type in Select OK and select Close until you get to the RSView Station window. 14. Reset the device. IP addresses PC ENBT/B Parent ENBT/B Child AENT Pview Plus EWEB PowerFlex70 drive Verify your EtherNet/IP interfaces are configured. The OK LED on all nodes should be as follows: 1756-ENBT OK and NET LEDs solid green 1794-AENT Network Status and Module Status LEDs Solid green 15. PanelView Plus 600 Refer to the navigation tips in step 11 above and verify that the PanelView Plus 600 has the correct IP address. 16. Select File > Save. 9/21/2004 Page 81 of 98
82 17. Save your BOOTP configuration in C:/RSLogix 5000/Projects folder, using your first and last name. 18. Exit/Close the BOOTP server. Now, it is time to verify that the modules are configured properly. We will use a utility called ping. 19. When all the EIP interfaces have been configured, open a DOS prompt (Start > Programs > Accessories > Command Prompt) and ping all the nodes, one at a time (for example, at the DOS prompt, type: Ping ) FYI Ping is an EtherNet/IP utility that verifies connectivity at the lowest level. You will use it for troubleshooting. After the class, if you want to read about ping, open a DOS prompt, type PING and press Enter. To do this, your PC will need to have TCP/IP installed. In the DOS prompt, you should see multiple Replies from the device you are pinging. 16. Also, ping your own PC s IP address. This demonstrates that you can ping all EtherNet/IP nodes. You will use this many times in the future. 17. Close the DOS prompt. 9/21/2004 Page 82 of 98
83 Appendix B: Communication Formats Read this document to learn about communication formats. Communication format When you configure an I/O module, you select a communication format for the module. The communication format determines the data structure for the tags that are associated with the module. Direct connection or rack-optimized connections are the most commonly used ones. Rack Optimization The Logix5000 controller uses connections to transmit and receive I/O data. For digital I/O modules, rack-optimized communication is selected. A rack-optimized connection consolidates connection usage between the controller and all the digital I/O modules in the chassis (or DIN rail). Rather than having individual, direct connections for each I/O module, there is one connection for the entire chassis (or DIN rail). None Is a real-time, direct connection used for data transfer between the controller and an I/O module. The controller maintains and monitors the connection with the I/O module. Any break in the connection, such as module fault, or the removal of a module while under power, sets fault bits in the data area associated with the module. This type of communication format is also used for peer- to- peer scheduled communication. Input Data In Logix5000 system, modules generate multicast data. This means that multiple modules can receive the same data at the same time from a single module. While selecting a communication format, you have to choose whether to establish an owner or listen only relation with the module. The controller that creates the primary configuration and communication connection to a module is called an owner controller. The owner controller writes configuration data and can establish a connection to the module. An owner connection is any connection that does not include Listen- Only in its Communication Format. Listen-Only connection This is an I/O connection where another controller owns/provides the configuration data for the I/O module. A controller using a listen-only connection only monitors the module. It does not write configuration data and can only maintain a connection to the I/O module when the owner controller is actively controlling the I/O module. Output Data Only one controller is the owner of outputs to a device. An output data connection to a device is the only connection that determines the mode (Program or Run) of that particular device. 9/21/2004 Page 83 of 98
84 Appendix C: Adding Modules to I/O Configuration List This Appendix if for informational purposes only and should not be treated as part of the lab exercise. Read this document to learn how to add modules to I/O configuration list in RSLogix5000. Adding an Input Module to the Parent Rack 1. First, make sure you are Offline with your RSLogix Right click on I/O Configuration and choose New Module. 3. Find the 1756-IB16D in the module list as shown below and click on OK. 4. Select Major Rev 2 and Click OK. 9/21/2004 Page 84 of 98
85 5. Configure the input module as shown below: 6. Click on Next, the following screen appears. 7. Make RPI = 10 ms and click on Next to advance through the configuration screens to view COS (Change Of State) and input filter settings. 9/21/2004 Page 85 of 98
86 8. Verify that the selections match with the picture below: 9. Click on Finish. Adding an Output Module to the Parent Rack 1. Right-click on I/O Configuration, choose New Module, and select the 1756-OB16D as shown below. 9/21/2004 Page 86 of 98
87 2. Click on OK. 3. When the following screen appears, select Major Revision 2 and click OK 4. Enter the configuration parameters as shown below: and click Finish. 9/21/2004 Page 87 of 98
88 Adding EtherNet/IP Module to the I/O Configuration 1. To add a 1756-ENBT bridge to the I/O list, right click on I/O Configuration, select New Module, and select 1756-ENBT as shown below: 2. Select OK. 3. When the following window appears, select Major Revision 3 and click OK. 9/21/2004 Page 88 of 98
89 4. Configure the module as follows and then click Finish. Configuring a Remote Ethernet Node 1. Right click on the Parent 1756-ENBT and select New Module. 2. Select the 1756-ENBT from the list and then click OK. 9/21/2004 Page 89 of 98
90 3. When the following window appears, choose Major Revision 3 and then click OK. 4. Configure the module as follows and then click the Next button. To learn more about Communication Formats, refer to Appendix B. 9/21/2004 Page 90 of 98
91 5. When the following window appears, change RPI from 10 to 20 and then click Finish. When you configure an I/O module, you define the Requested Packet Interval (RPI) for that module. The RPI specifies the period at which data updates occur. For example, an input module sends data to a controller at the RPI you assign to the module or the rack. You configure the RPI in milliseconds. When finished, your I/O configuration tree in RSLogix5000 will appear as follows: 9/21/2004 Page 91 of 98
92 Appendix D: Verifying the DeviceNet Scanlist using RSNetworx for DeviceNet This Appendix if for informational purposes only and should not be treated as part of the lab exercise. The steps below generate a scanlist for the DNB. A scanlist has already been loaded into your DNB. You can verify or create a scanlist as follows: 1. From the computer desktop, double-click on RSNetworx for DeviceNet to launch the software. 2. From the toolbar menu, select Network > Online to browse the DeviceNet network. 3. From your PC, bridge to the 1756-DNB and out onto the DeviceNet network via the 1756-ENBT in your remote 1756 (Child) chassis as shown below and then click OK. 4. If you see the following message, click on OK. 9/21/2004 Page 92 of 98
93 5. When the 1756-DNB and photoeye appear in the graphics view as shown below, click Cancel to stop the browse. 7. Double-click on the 1756-DNB and select the Scanlist tab. 9. Verify that there is a scanlist downloaded in the 1756-DNB. 10. Verify that the scanlist has a photoeye and that the Automap box is selected. 12. Verify the Photoeye configuration (default of COS is OK). 13. Close RSNetworx for DeviceNet. 9/21/2004 Page 93 of 98
94 Appendix E: Drive Explorer This Appendix if for informational purposes only and should not be treated as part of the lab exercise. Configuring / monitoring Drive Parameters Using DriveExplorer 1. From the computer desktop, double-click on the DriveExplorer icon. 2. From the toolbar menu, select Explore > Connect > Ethernet. 3. Click OK. 4. Highlight the IP Address as shown below and click on the Connect button. 9/21/2004 Page 94 of 98
95 DriveExplorer connects on-line with the drive: 5. Click on the 20-COMM-E EtherNet/IP under PowerFlex 70 to display its parameters. 6. Click on the Device Properties icon for displaying 20- COMM-E s properties. 9/21/2004 Page 95 of 98
96 7. Spend few moments to familiarize yourself with the information available under various tabs. The User Text allows you a more descriptive name for the device. 8. Click on the Diagnostics tab to see actual data in the 20-COMM-E adapter. The Diagnostics tab provides the ability from the drive side without knowing the controller or the ladder program. 9. Click on the Close button. Verifying Parameters in the 20-COMM-E 1. Verify the following parameters: Pr. 23 [DPI I/O Cfg] set to x01 to allow Logic Command / Reference to transfer data between the 20 COMM-E and the drive Pr. 35 [M-S Input] set to x01 to allow Logic Command / Reference to transfer data between the 20- COMM- E and the controller. 9/21/2004 Page 96 of 98
97 Pr. 36 [M-S output] set to x01 to allow Logic Status/Feedback to transfer data between the 20- COMM- E and the controller. Pr. 20 [Reset Module] - If any parameter is modified reset the adapter via Prameter20 for the setting to take place. Note that M-S Input and M-S output determines the 20-COMM-E s I/O size on the network. Because of the I/O size mismatch between 20-COMM-E, and ENBT, you will see a warning icon in the RSLogix5000 I/O configuration menu and there would not be any access to the drive through ladder program. 2. Click on the PowerFlex70 drive to display its parameters. 3. Scroll down to Parameter 90 for [Speed Ref A Sel]. Notice that DPI Port 5 is selected. 4. Scroll down to Parameter 276 for [Logix Mask]. Notice that DPI Port 5 is selected. 5. Scroll down to Parameter 300 to display the Datalinks. This tells drive which parameter to use with the Datalinks. Parameters 140 and 142 contain Accel time and Decel time for the drive. 6. Close DriveExplorer. 9/21/2004 Page 97 of 98
98 Accessing the Adapter s Main Web Page 1. Type the IP address in your internet explorer s address location and press Enter. 2. When the following screen appears, navigate through different pages. 9/21/2004 Page 98 of 98
Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description... 3. 1.1 Objective... 3 1.2 Goals...
Moxa MGate 5105-MB-EIP Contents Moxa Technical Support Team [email protected] 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements...
ControlLogix Remote I/O Communication Module
User Manual ControlLogix Remote I/O Communication Module Catalog Number 1756-RIO Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
1769 CompactLogix Packaged Controllers
1769 CompactLogix Packaged Controllers Quick Start and User Manual (Catalog Numbers 1769-L23E-QB1B, 1769-L23E-QBFC1B, and 1769-L23-QBFC1B) Important User Information Solid state equipment has operational
User Manual. DeviceNet Network Configuration
User Manual DeviceNet Network Configuration Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the
Global Common Controls Software Design (GCCS-2) Course (Version 6.0)
Global Common Controls Software Design (GCCS-2) Course (Version 6.0) Course No. GCCS8029, (CTIS: 33544) Duration 4 days Recommended RS Logix 5000 Basic Ladder Logic Programming experience Objectives Upon
User Manual. ControlNet Network Configuration
User Manual ControlNet Network Configuration Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for
Building a groov HMI for Allen-Bradley Logix Systems. About groov. Building a groov HMI for Allen-Bradley Logix. A-B Systems and groov
About groov Opto 22 s groov makes it easy to build and deploy simple, effective operator interfaces for your system. groov is browser-based and uses only Internet standards (HTML5, CSS3, SVG, SSL). That
EtherNet/IP Modules in Logix5000 Control Systems
EtherNet/IP Modules in Logix5000 Control Systems Catalog Numbers 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN2TXT, 1768-ENBT, 1769-L23E-QB1B, 1769-L23E-QBFC1B, 1769- L32E, 1769-L35E, 1783-ETAP,
Application about Communication
Application about Communication Integration of a MicroMaster Drive with Rockwell ControlLogix using DeviceNet Third-Party Integration Warranty, liability and support Note The application examples are not
for both the Verbatim Gateway and Catalyst Autodialer EtherNet Options
RSLogix 5000 Configuration for both the Verbatim Gateway and Catalyst Autodialer EtherNet Options Addendum 1.0 Revision History Rev # Description Author/Editor Date 1.0 Original Davey Hudson 05/01/2015
DeviceNet Motor Control
Quick-Start Guide for the DN65 DeviceNet I/O Module using Rockwell RSNetWorx version 2.22 or later This Quick-Start Guide provides instructions for configuring a Cutler-Hammer Freedom full voltage, non-reversing
EtherNet/IP Web Server Module
EtherNet/IP Web Server Module 1756-EWEB, 1768-EWEB User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
EtherNet/IP Adapter. 22-COMM-E FRN 1.xxx. User Manual
EtherNet/IP Adapter 22-COMM-E FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
RSLinx Enterprise GETTING RESULTS GUIDE. PUBLICATION LNXENT-GR001K-EN-E August 2014 Supersedes Publication LNXENT-GR001J-EN-E
RSLinx Enterprise GETTING RESULTS GUIDE PUBLICATION LNXENT-GR001K-EN-E August 2014 Supersedes Publication LNXENT-GR001J-EN-E Contact Rockwell Customer Support Telephone 1.440.646.3434 Online Support http://www.rockwellautomation.com/support/
Module 1 Overview ControlLogix5000
Module 1 Overview ControlLogix5000 Module Overview This module takes a fundamental approach to a ControlLogix system. It begins with an overview of the architecture and migrates into an introduction of
Logix5000 Controllers
Logix5000 Controllers Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 CompactLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix Quick Start Important
EZ-ZONE RMA & EtherNet/IP Configuration & Startup Using an Allen-Bradley CompactLogix PLC EtherNet/IP Fundamentals
EtherNet/IP Fundamentals EtherNet/IP is built on the Common Industrial Protocol (CIP) at a foundational level. When communicating using CIP there are two ways to communicate to/from the Master and Slave
Premier Integration with ControlLogix, PowerFlex Drives, and FactoryTalk View
Premier Integration with ControlLogix, PowerFlex Drives, and FactoryTalk View Premier Integration with ControlLogix, PowerFlex Drives, and FactoryTalk View Contents About this lab... 4 About Integrated
1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3
Contents Moxa Technical Support Team [email protected] 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...
CompactLogix 5370 L1 Controllers
Quick Start CompactLogix 5370 L1 Controllers Catalog Numbers 1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B Important User Information Read this document and the documents listed in the additional
RSLinx Classic Getting Results Guide
Performance and Visibility RSLinx Classic Getting Results Guide Getting Results Guide Table of contents Chapter 1 Introduction Purpose of the document... 7 Intended audience... 7 How does the getting
2011, The McGraw-Hill Companies, Inc. Chapter 5
Chapter 5 5.1 Processor Memory Organization The memory structure for a PLC processor consists of several areas, some of these having specific roles. With rack-based memory structures addresses are derived
IGSS. Interactive Graphical SCADA System. Quick Start Guide
IGSS Interactive Graphical SCADA System Quick Start Guide Page 2 of 26 Quick Start Guide Introduction This guide is intended to get you up and running with the IGSS FREE50 license as fast as possible.
TestManager Administration Guide
TestManager Administration Guide RedRat Ltd July 2015 For TestManager Version 4.57-1 - Contents 1. Introduction... 3 2. TestManager Setup Overview... 3 3. TestManager Roles... 4 4. Connection to the TestManager
Logix5000 Controllers Nonvolatile Memory Card
Programming Manual Logix5000 Controllers Nonvolatile Memory Card Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 CompactLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex
Introduction to LogixPro - Lab
Programmable Logic and Automation Controllers Industrial Control Systems I Introduction to LogixPro - Lab Purpose This is a self-paced lab that will introduce the student to the LogixPro PLC Simulator
FactoryTalk Gateway Getting Results Guide
Performance and Visibility FactoryTalk Gateway Getting Results Guide Getting Results Guide Table of contents Chapter 1 Introduction Intended audience... 7 Where to find additional information... 7 Help...
Application Note Connect to a Rockwell PLC over Netbiter Remote Access
Application Note Connect to a Rockwell PLC over Netbiter Remote Access Doc: HMSI 27-239 Rev: 1.0 Connecting Devices TM HALMSTAD CHICAGO KARLSRUHE TOKYO BEIJING MILANO MULHOUSE COVENTRY PUNE COPENHAGEN
Accessing EtherNet/IP Network Variables in a WAGO 750-841 with a ControlLogix PLC Application note
Accessing EtherNet/IP Network Variables in a WAGO 750-841 with a ControlLogix PLC, English Version 1.0.0 2 General Copyright 2002 by WAGO Kontakttechnik GmbH All rights reserved. WAGO Kontakttechnik GmbH
USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6
KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly
Using SSH Secure Shell Client for FTP
Using SSH Secure Shell Client for FTP The SSH Secure Shell for Workstations Windows client application features this secure file transfer protocol that s easy to use. Access the SSH Secure FTP by double-clicking
Legal Notes. Regarding Trademarks. 2012 KYOCERA Document Solutions Inc.
Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable for any problems arising from
NETWORK PRINT MONITOR User Guide
NETWORK PRINT MONITOR User Guide Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable
SHORT TRAINING COURSES
Post Office Box SR 95, Spintex Road, Ghana Tel: +233 302 812680, Fax: +233 302 814709 E mail: [email protected] Website: www.automationghana.com SHORT TRAINING COURSES Equipping industries with
IMPORTANT PRODUCT INFORMATION
January 2010 IMPORTANT PRODUCT INFORMATION READ THIS INFORMATION FIRST Product: Max-ON Hot-Backup Redundancy Software, Release 2.05 Introduction Max-ON is a trademark of GE Intelligent Platforms, Inc.
Configuring RSLinx as an OPC Server for PanelMate epro
Configuring RSLinx as an OPC Server for PanelMate epro RSLinx includes OPC Server functionality in all versions except RSLinx Lite. This means that if a user purchases a license for RSLinx OEM, Standard,
User s Guide for version 5 Page
Network Management Interface Catalog VPi 32.15E For use with these ATS products: 7000 & 4000 Series (Group 5 Controller) Series 300 (Group 1 Controller), and 940, 962, 436, 434, 447, 448 (Group 6A/7A Control
TOSHIBA GA-1310. Printing from Windows
TOSHIBA GA-1310 Printing from Windows 2009 Electronics for Imaging, Inc. The information in this publication is covered under Legal Notices for this product. 45081979 04 February 2009 CONTENTS 3 CONTENTS
BIGPOND ONLINE STORAGE USER GUIDE Issue 1.1.0-18 August 2005
BIGPOND ONLINE STORAGE USER GUIDE Issue 1.1.0-18 August 2005 PLEASE NOTE: The contents of this publication, and any associated documentation provided to you, must not be disclosed to any third party without
EtherNet/IP Network Configuration
User Manual EtherNet/IP Network Configuration EtherNet/IP Communication Modules 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN2TXT, 1756-EN3TR, 1756-EN2TSC, 1756-EN2TRXT, 1756-EWEB, 1768-ENBT CompactLogix
RSLinx-Lite PLC Programming software communication interface. RSLinx-OEM Provides DDE capability for Rockwell DDE capable software.
H 1 H. RSLinx is a windows based communication software package developed by Rockwell Software to interface to all of the Rockwell and A-B industrial control and automation hardware. RSLinx comes in a
QUICK START GUIDE. SG2 Client - Programming Software SG2 Series Programmable Logic Relay
QUICK START GUIDE SG2 Client - Programming Software SG2 Series Programmable Logic Relay SG2 Client Programming Software T he SG2 Client software is the program editor for the SG2 Series Programmable Logic
Using Logix5000 Controllers as Masters or Slaves on Modbus
Application Solution Using Logix5000 Controllers as Masters or Slaves on Modbus Purpose of the Document This application solution, and the associated RSLogix 5000 project files, help you use Logix5000
USER MANUAL SlimComputer
USER MANUAL SlimComputer 1 Contents Contents...2 What is SlimComputer?...2 Introduction...3 The Rating System...3 Buttons on the Main Interface...5 Running the Main Scan...8 Restore...11 Optimizer...14
138 Configuration Wizards
9 Configuration Wizards 9.1 Introduction to Wizards ACP ThinManager uses wizards for configuration. Wizards take two forms. List Wizards associate Terminal Servers and ThinManager Servers with their IP
Practice Fusion API Client Installation Guide for Windows
Practice Fusion API Client Installation Guide for Windows Quickly and easily connect your Results Information System with Practice Fusion s Electronic Health Record (EHR) System Table of Contents Introduction
FreeAgent DockStar Network Adapter User Guide
FreeAgent DockStar Network Adapter User Guide FreeAgent DockStar Network Adapter User Guide 2010 Seagate Technology LLC. All rights reserved. Seagate, Seagate Technology, the Wave logo, and FreeAgent are
IntelliCENTER Software
User Manual IntelliCENTER Software Catalog Number 2101A-INTLCNTR Important User Information Read this document and the documents listed in the additional resources section about installation, configuration,
Avaya Wireless AP Device Manager User Guide
Avaya Wireless AP Device Manager User Guide February 2003 Avaya Wireless AP Device Manager User Guide Copyright Avaya Inc. 2003 ALL RIGHTS RESERVED The products, specifications, and other technical information
SecureAssess Local. Install Guide. www.btl.com. Release 9.0
SecureAssess Local Install Guide Release 9.0 Document 1.0 15.11.10 www.btl.com Disclaimer Whilst every effort has been made to ensure that the information and content within this user manual is accurate,
R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement
I/Q Modulation Generator Supplement The following description relates to the Operating Manuals, version 03 of R&S AFQ100A, and version 01 of R&S AFQ100B. It encloses the following topics: LXI features,
How to test and debug an ASP.NET application
Chapter 4 How to test and debug an ASP.NET application 113 4 How to test and debug an ASP.NET application If you ve done much programming, you know that testing and debugging are often the most difficult
GUARD1 PLUS SE Administrator's Manual
GUARD1 PLUS SE Administrator's Manual Version 4.4 30700 Bainbridge Road Solon, Ohio 44139 Phone 216-595-0890 Fax 216-595-0991 [email protected] www.guard1.com i 2010 TimeKeeping Systems, Inc. GUARD1 PLUS
Getting Started with Vision 6
Getting Started with Vision 6 Version 6.9 Notice Copyright 1981-2009 Netop Business Solutions A/S. All Rights Reserved. Portions used under license from third parties. Please send any comments to: Netop
Citrix EdgeSight for Load Testing User s Guide. Citrix EdgeSight for Load Testing 3.8
Citrix EdgeSight for Load Testing User s Guide Citrix EdgeSight for Load Testing 3.8 Copyright Use of the product documented in this guide is subject to your prior acceptance of the End User License Agreement.
Service Bulletin [2014 02]
How do you know if you have a PanelView Plus or a Panelview Plus 6? The quickest way is to look at the type of memory slot the unit has on the back. If it accepts and SD Card, it s a PanelView Plus 6.
13 Managing Devices. Your computer is an assembly of many components from different manufacturers. LESSON OBJECTIVES
LESSON 13 Managing Devices OBJECTIVES After completing this lesson, you will be able to: 1. Open System Properties. 2. Use Device Manager. 3. Understand hardware profiles. 4. Set performance options. Estimated
Windows XP Pro: Basics 1
NORTHWEST MISSOURI STATE UNIVERSITY ONLINE USER S GUIDE 2004 Windows XP Pro: Basics 1 Getting on the Northwest Network Getting on the Northwest network is easy with a university-provided PC, which has
1. Installing The Monitoring Software
SD7000 Digital Microphone Monitor Software manual Table of Contents 1. Installing The Monitor Software 1.1 Setting Up Receivers For Monitoring 1.2 Running The Application 1.3 Shutdown 2. The Detail Monitoring
L5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
User Manual. Onsight Management Suite Version 5.1. Another Innovation by Librestream
User Manual Onsight Management Suite Version 5.1 Another Innovation by Librestream Doc #: 400075-06 May 2012 Information in this document is subject to change without notice. Reproduction in any manner
Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements
Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements - Two (2) MiCOM Px4x IEDs with Version 2 implementation of IEC 61850 - Two (2) Cat 5E Ethernet cable - An Ethernet switch 10/100 Mbps - MiCOM
Lab - Using Wireshark to View Network Traffic
Topology Objectives Part 1: (Optional) Download and Install Wireshark Part 2: Capture and Analyze Local ICMP Data in Wireshark Start and stop data capture of ping traffic to local hosts. Locate the IP
FactoryTalk View Site Edition V5.0 (CPR9) Server Redundancy Guidelines
FactoryTalk View Site Edition V5.0 (CPR9) Server Redundancy Guidelines This page left intentionally blank. FTView SE 5.0 (CPR9) Server Redundancy Guidelines.doc 8/19/2008 Page 2 of 27 Table of Contents
Personal Call Manager User Guide. BCM Business Communications Manager
Personal Call Manager User Guide BCM Business Communications Manager Document Status: Standard Document Version: 04.01 Document Number: NN40010-104 Date: August 2008 Copyright Nortel Networks 2005 2008
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
Wireless-N. User Guide. PCI Adapter WMP300N (EU) WIRELESS. Model No.
2,4 GHz WIRELESS Wireless-N PCI Adapter User Guide Model No. WMP300N (EU) Copyright and Trademarks Specifications are subject to change without notice. Linksys is a registered trademark or trademark of
FactoryTalk ViewPoint Quick Start Guide
FactoryTalk ViewPoint Quick Start Guide Publication FTVP-QS002F-EN-E - September 2015 Supersedes Publication FTVP-QS002E-EN-E Important user information Read this document and the documents listed in the
L06 - FactoryTalk View Site Edition - Building Applications Lab. For Classroom Use Only!
L06 - FactoryTalk View Site Edition - Building Applications Lab For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter
WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01
WinCC Communication Manual Manual 2 This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 Release: September 1999 WinCC, SIMATIC, SINEC, STEP are trademarks of Siemens.
STATISTICA VERSION 10 STATISTICA ENTERPRISE SERVER INSTALLATION INSTRUCTIONS
Notes: STATISTICA VERSION 10 STATISTICA ENTERPRISE SERVER INSTALLATION INSTRUCTIONS 1. The installation of the STATISTICA Enterprise Server entails two parts: a) a server installation, and b) workstation
ControlFLASH Firmware Upgrade Software
User Manual ControlFLASH Firmware Upgrade Software Catalog Numbers ControlFLASH 12.00.00 Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
Introduction to Kinetix Integrated Motion with CompactLogix and the Kinetix 2000 Drive
Introduction to Kinetix Integrated Motion with CompactLogix and the Kinetix 2000 Drive Introduction to Kinetix Integrated Motion with CompactLogix and the Kinetix 2000 Drive: Hands-On Lab Traiiniing Lab
AXIS Camera Station Quick Installation Guide
AXIS Camera Station Quick Installation Guide Copyright Axis Communications AB April 2005 Rev. 3.5 Part Number 23997 1 Table of Contents Regulatory Information.................................. 3 AXIS Camera
How to Obtain an OPC License--5. Creating a System Code 5 Entering an Authorization Code 6. Getting Started with SNMP Editor--7
Contents Introduction--1 Product definition 1 Implementing SNMP 2 Integrating SNMP into the user interface 3 Components of OPC SNMP Gateway 4 How to Obtain an OPC License--5 Creating a System Code 5 Entering
genie app and genie mobile app
genie app and genie mobile app User Manual 350 East Plumeria Drive San Jose, CA 95134 USA June 2012 202-10933-02 v1.0 2012 NETGEAR, Inc. All rights reserved No part of this publication may be reproduced,
OPERATION MANUAL. MV-410RGB Layout Editor. Version 2.1- higher
OPERATION MANUAL MV-410RGB Layout Editor Version 2.1- higher Table of Contents 1. Setup... 1 1-1. Overview... 1 1-2. System Requirements... 1 1-3. Operation Flow... 1 1-4. Installing MV-410RGB Layout
Technical Note. Monitoring Ethernet Traffic with Tolomatic ACS & Managed Switch. Contents
Monitoring Ethernet Traffic with Tolomatic ACS & Managed Switch Contents 1. Introduction...2 2. Equipment...2 3. Software...3 4. Definitions...3 5. Procedure...3 6. Change PC IP Address...3 7. Network
DeviceNet Configurator User Guide
DeviceNet Configurator User Guide Doc. No. MAN-1070B Copyright 2000 Control Technology Corporation All Rights Reserved. Printed in USA The information in this document is subject to change without notice.
ControlNet PLC-5 Hot Backup System
ControlNet PLC-5 Hot Backup System Cat. No. 1785-CHBM User Manual Important User Information Because of the variety of uses for the products described in this publication, those responsible for the application
Control Technology Corporation CTC Monitor User Guide Doc. No. MAN-1030A Copyright 2001 Control Technology Corporation All Rights Reserved Printed in USA The information in this document is subject to
C-more Remote HMI App
Topic: CM630 C-more Remote HMI App SAFETY NOTICE: The C-more Remote HMI App allows the user to connect to remote C-more panels from Ethernet, Wi-Fi, or cellular network connections. The Remote user can
PigCHAMP Knowledge Software. Enterprise Edition Installation Guide
PigCHAMP Knowledge Software Enterprise Edition Installation Guide Enterprise Edition Installation Guide MARCH 2012 EDITION PigCHAMP Knowledge Software 1531 Airport Rd Suite 101 Ames, IA 50010 Phone (515)
Network Scanner Tool R3.1. User s Guide Version 3.0.04
Network Scanner Tool R3.1 User s Guide Version 3.0.04 Copyright 2000-2004 by Sharp Corporation. All rights reserved. Reproduction, adaptation or translation without prior written permission is prohibited,
MONITORING PERFORMANCE IN WINDOWS 7
MONITORING PERFORMANCE IN WINDOWS 7 Performance Monitor In this demo we will take a look at how we can use the Performance Monitor to capture information about our machine performance. We can access Performance
User Manual. PowerFlex 525 Embedded EtherNet/IP Adapter
User Manual PowerFlex 525 Embedded EtherNet/IP Adapter Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
Setting up VPN Access for Remote Diagnostics Support
Setting up VPN Access for Remote Diagnostics Support D. R. Joseph, Inc. supports both dial-up and Internet access for remote support of 3GIBC1 and LF-Sizer control systems. This document describes how
Hands-on Practice. Hands-on Practice. Learning Topics
Using Microsoft PowerPoint Software on a SMART Board Interactive Whiteboard You make presentations for a reason to communicate a message. With a SMART Board interactive whiteboard, you can focus the attention
User Guide. SysMan Utilities. By Sysgem AG
SysMan Utilities User Guide By Sysgem AG Sysgem is a trademark of Sysgem AG. Other brands and products are registered trademarks of their respective holders. 2013 Sysgem AG, Lavaterstr. 45, CH-8002 Zürich,
Installation Instructions
Installation Instructions Use these installation instructions to set up the lab for the DeviceNet seminar. The DeviceNet lab exercises require the following components. Advanced Programming Software (APS)
SECTION 16926 CONTROL SOFTWARE
SECTION 16926 CONTROL SOFTWARE PART 1 GENERAL 1.01 SUMMARY: A. Contractor shall furnish a complete control software package for the Red River Wastewater Treatment Plant and the Northeast Wastewater Treatment
Installing GFI MailEssentials
Installing GFI MailEssentials Introduction to installing GFI MailEssentials This chapter shows you how to install and configure GFI MailEssentials. GFI MailEssentials can be installed in two ways: Installation
UNICORN 7.0. Administration and Technical Manual
UNICORN 7.0 Administration and Technical Manual Page intentionally left blank Table of Contents Table of Contents 1 Introduction... 1.1 Administrator functions overview... 1.2 Network terms and concepts...
Xerox EX Print Server, Powered by Fiery, for the Xerox 700 Digital Color Press. Printing from Windows
Xerox EX Print Server, Powered by Fiery, for the Xerox 700 Digital Color Press Printing from Windows 2008 Electronics for Imaging, Inc. The information in this publication is covered under Legal Notices
CompactLogix 5370 L3 Controllers
Quick Start CompactLogix 5370 L3 Controllers Catalog Numbers 1769-L30ER, 1769-L30ERM, 1769-L30ER-NSE, 1769-L33ER, 1769-L33ERM, 1769-L36ERM Important User Information Solid-state equipment has operational
SQL Server 2005: Report Builder
SQL Server 2005: Report Builder Table of Contents SQL Server 2005: Report Builder...3 Lab Setup...4 Exercise 1 Report Model Projects...5 Exercise 2 Create a Report using Report Builder...9 SQL Server 2005:
L26 - FactoryTalk AssetCentre: Self-Paced Lab. For Classroom Use Only!
L26 - FactoryTalk AssetCentre: Self-Paced Lab For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is
CentreWare Internet Services Setup and User Guide. Version 2.0
CentreWare Internet Services Setup and User Guide Version 2.0 Xerox Corporation Copyright 1999 by Xerox Corporation. All rights reserved. XEROX, The Document Company, the digital X logo, CentreWare, and
USER GUIDE WEB-BASED SYSTEM CONTROL APPLICATION. www.pesa.com August 2014 Phone: 256.726.9200. Publication: 81-9059-0703-0, Rev. C
USER GUIDE WEB-BASED SYSTEM CONTROL APPLICATION Publication: 81-9059-0703-0, Rev. C www.pesa.com Phone: 256.726.9200 Thank You for Choosing PESA!! We appreciate your confidence in our products. PESA produces
ABB solar inverters. User s manual ABB Remote monitoring portal
ABB solar inverters User s manual ABB Remote monitoring portal List of related manuals Title ABB Remote monitoring portal User s manual NETA-01 Ethernet adapter module User s manual Code (English) 3AUA0000098904