1 SIMADYN D Digital Control System User Manual Interface module SE21.2 Edition DK-Nr
2 User Manual, Interface module SE21.2 Edition Edition status 1 Interface module SE Interface module SE Copying of this document and giving it to others and the use or communication of the contents thereof is forbidden without express authority. Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design. We have checked the contents of this Manual to ensure that they coincide with the described hardware and software. However, deviations cannot be completely ruled-out, so we cannot guarantee complete conformance. However, the information in this document is regularly checked and the necessary corrections included in subsequent editions. We are thankful for any recommendations or suggestions.
3 Contents Contents Warning information Function Description Board Design Application Notes Technical Specification Pin Allocation of the SE X1: Actual values X2: Actual values X3: Frequency outputs and Binary inputs X4: Diagnostics outputs X5: Binary outputs (Limit values), Frequency outputs (Absolute values) and the SIMADYN D power supply X6: Power supply converter side and binary inputs for polarity switching X9: Power supply and Signals Appendices Block Diagram Scale Drawing and Table of the plug connector Allocation Plan SE ECB instructions Siemens AG Dk-Nr Edition 05.95
4 Warning information Edition Siemens AG Dk-Nr
5 Warning information N O T E! The information in this Manual does not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, please contact your local Siemens office. Further, the contents of this Manual shall not become a part of or modify any prior or existing agreement, committment or relationship. The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements contained herein do not create new warranties nor modify the existing warranty. Warning information W A R N I N G! Electrical equipment has components which are at dangerous voltage levels. If these instructions are not strictly adhered to, severe bodily injury and material damage can result. Only appropriately qualified personnel may work on this equipment or in its vicinity. This personnel must be completely knowledgeable about all the warnings and service measures according to this User Manual. The successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance. Siemens AG Dk-Nr Edition
6 Warning information Definitions * QUALIFIED PERSONNEL For the purpose of this User Manual and product labels, a Qualified person is someone who is familiar with the installation, mounting, start-up and operation of the equipment and the hazards involved. He or she must have the following qualifications: 1. Trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety procedures. 2. Trained in the proper care and use of protective equipment in accordance with established safety procedures. 3. Trained in rendering first aid. * DANGER For the purpose of this User Manual and product labels, Danger indicates death, severe personal injury and/or substantial property damage will result if proper precautions are not taken. * WARNING For the purpose of this User Manual and product labels, Warning indicates death, severe personal injury or property damage can result if proper precautions are not taken. * CAUTION For the purpose of this User Manual and product labels, Caution indicates that minor personal injury or material damage can result if proper precautions are not taken. * NOTE For the purpose of this User Manual, Note indicates information about the product or the respective part of the User Manual which is essential to highlight. C A U T I O N! This board contains components which can be destroyed by electrostatic discharge. Prior to touching any electronics board, your body must be electrically discharged. This can be simply done by touching a conductive, grounded object immediately beforehand (e.g. bare metal cabinet components, socket protective conductor contact). W A R N I N G! Hazardous voltages are present in this electrical equipment during operation. Non-observance of the safety instructions can result in severe personal injury or property damage. It is especially important that the warning information in all of the relevant Operating Instructions are strictly observed. 2 Edition Siemens AG Dk-Nr
7 Function Description 1. Function Description The interface board SE21.2 is designed in the SIMADYN D system as an interface between the PS16 digital control and the converter power section of a SIMOVERT S or SIMOVERT D drive (inverter motor or cyclo-converter). It converts and prepares the current and voltage actual values from the converter to SIMADYN D signals or signal groups. The board can process a maximum of 6 actual value signals. The three phase actual value systems U1, U2, U3 and I1, I2, I3 measured from operation of a cyclo-converter are supplied via X1. The two phase actual value systems U1, U2 and I11, I12, measured in connection with a inverter motor, is fed via X1 as well as for 12 pulse operation I21 and I22 via X2. The set-up of the corresponding mode of operation is implemented via the coding plug X250 as well as via solder bridges. The actual value transducer signals are matched via plug-in burden modules (SE24.1) and subsequently V/F converted (V/F converters = voltage to frequency converters). Three phase absolute values are used for the individual actual value systems, whereby the third phase, for SIMOVERT S, is calculated from both the measured phases. Overcurrent and overvoltage signals are derived from monitoring these values for their limits and frequency signals generated through V/F conversion (only for both current systems for SIMOVERT S). If, in the case of cyclo-converters, the currents are acquired as absolute values, then the absolute values are inverted via binary inputs and made available to the control system with the correct polarity. There is complete galvanic isolation between the SIMADYN D side and the converter side. The binary signals are isolated via opto-couplers and the frequency signals by trigger pulse transmitters. All actual values and binary signals as well as the supply voltages are short circuit protected and decoupled. They are available at the connector X4 for diagnostics, display and monitoring purposes (actual values in analog form and not as frequency signals). The released version of the board is upwards compatible to the previous board version SE21.1 (6DD1681-0CB1) with the following restrictions: a) The pins 3 and 4 on the burden module are no longer connected to 2M. Application with single pin sources, where this is necessary, require the corresponding connector pins X1: Z4, Z8, Z12, Z20, Z24 or X2: Z16, Z20 to be connected to 2M. 2M is connected to X1: b6, b10, b14, b18, b22, b26 and X2: b18, b22. b) The designations of the components on the board have been changed. Replacement of a SE21.1 with a SE21.2 requires the equipment documentation to be updated. c) If un-used terminal or connector pins on the SE21.1 board have been used as common points, then they must be compared with the pin allocation on the SE21.2. (Several terminals and connector pins have been additionally used on the SE21.2 for new functions). Siemens AG Dk-Nr Edition
8 Board Design 2. Board Design - 6 Analog inputs for actual values with differential amplifiers - 3 binary inputs for polarity switching - Summation for calculation of the third phase for two phase measured systems - Limit value generation for determining the overcurrent and overvoltage - 8 Frequency outputs for actual values (galvanic isolation) - 3 binary outputs for limit values (galvanic isolation) - 21 Diagnostic outputs, short circuit proof, decoupled (non isolated) - Actual value adaptation via the plug-in burden modules SE24 - Set-up for SIMOVERT D or SIMOVERT S via coded plug and solder bridges - For SIMOVERT S: overcurrent message via binary input switchable limit values - For SIMOVERT D: Selection input with voltage divider, differential amplifier and frequency actual value. Calibration circuit for V/F channels as a sub-module. 3. Application Notes - Default Setting The board set-up is implemented for the required application by cutting connections in the coding plug X250. The connection between the following pins in the plug are to be cut: - Cyclo-converter application Pin 2 - Pin 15 Pin 3 - Pin 14 Pin 6 - Pin 11 - Inverter motor application Pin 1 - Pin 16 Pin 4 - Pin 13 Pin 5 - Pin 12 - Power Supply The board power supply can either be fed via the connector X5 and X6 on the front panel or via the back plane connector X9. - Burden module 6DD CE1 (Circuit diagram in the equipment block diagram) The burden module can be implemented as a voltage divider for actual value transducers with constant voltage output or as a simple burden for transducers with constant current output. The resistor R1 must be jumpered when transducers with constant current output are used.! WARNING: maximum permissible power loss per load resistor is 2W when resistors of type G204 are used! 4 Edition Siemens AG Dk-Nr
9 Application Notes The potentiometer R7 can be used for fine calibration when activated by the series resistor R6.! WARNING: The potentiometer current must not exceed 20mA! The influence of the potentiometer on the divider resistance should be kept as small as possible because of it's relatively high temperature coefficient of ±100ppm/deg.C. - Actual Values Three contacts with +24V, -24V and the corresponding reference (ground) potential M are allocated to each actual value channel on the connectors X1 and X2. Therefore it is possible to supply the transducers via these connectors. The addition current requirement is therefore to be taken into account when configuring the SE21.2. The 6 burden modules are allocated the following actual values: SIMOVERT S SIMOVERT D Burden module in Plug Designation U1 U1 X122 and X269 A1 U2 U2 X10 and X141 A2 I11 I1 X72 and X175 A4 I12 I2 X170 and X280 A5 I21 I3 X294 and X392 A6 I22 U3 X427 and X523 A3 The following is valid for the signal Ua at the burden module and the output frequency: Ua = V corresponds to f = khz The input of the corresponding burden module must be shorted when the actual value is not used (i.e. by a jumper via R2 of the burden module). - Switching Polarity The absolute values of currents I1, I2 and I3, measured through the installed SE21.2 and in connection with a cyclo-converter, can be inverted through three binary inputs via the X6 connector when these values are required in the correct polarity by the control system. The following is valid for these inputs, which are at SIMADYN D potential level: Inputs 'Low' or open - Current actual value unchanged Inputs 'High' - Current actual value inverted - Overcurrent or Overvoltage Signals The comparator thresholds for detecting overcurrent or overvoltage in the two (three) three phase systems are set, in matched burden modules, to 1.38% ± 7% of the signal rated value (signal rated value corresponds to 5 Veff).! WARNING: The maximum permissible input voltage range for AC voltage is 10 V / 2 = 7.07 V(eff). The limit value indicator board reacts to peak values and not to average values. This results in pulsed signals on the threshold boundary. he hysteresis gap is approximately 2 %. Siemens AG Dk-Nr Edition
10 Application Notes The overcurrent thresholds can be commonly switched via a binary input for SIMOVERT S applications. The thresholds can be altered between 0 V and +15 V via the following voltage divider. The resistance values set in parentheses are the default installed values. SIMOVERT S SIMOVERT D Resistance Resistance on +15 V on 0 V U1,U2,U3 U1,U2,U3 R 502 (11 K) R 499 (10 K) I11,I12,I13 I1,I2,I3 R 506 (11 K) R 509 (10 K) I21,I22,I R 448 (11 K) R 513 (10 K)! WARNING: The supply tolerance of the +15 V is ±5 %. This should be taken into account when setting the threshold values. - Diagnostic Outputs X4 The diagnostic outputs can be accessed by installing a 40 pin ribbon cable and the SE23 terminal block. - Frequency Signals for Absolute Values: The absolute signals are scaled like the input signals. This signifies that when the actual values are loaded at 5 V(eff) = 100 %, then the absolute signals 5 V = 100 % average value. - Connection of the SE21.2 The front panel contains: X1: Plug connector 48 pin Actual values Type F to DIN from power section X2: Plug connector 48 pin Actual values Type F to DIN from power section X3: Plug connector 40 pin Interface to to DIN the PS16 board X4: Plug connector 40 pin Diagnostics to DIN X5: Terminal block 8 pin Power supply Plug - Screw - terminals and Signals X6: Terminal block 10 pin Power supply Plug - Screw - terminals and Signals 6 Edition Siemens AG Dk-Nr
11 Technical Specification Supplementary components for the SE21.2: a) Cable 40 pin 1,2 m SC6 6DD1684-0AG0 2 m SC18 6DD1684-0BJ0 b) Terminal block SE23 6DD1681-0CD0 40 pin ribbon cable connector on 40 terminals 1:1 c) Burden sub-module SE24.1 Burden sub-modul 6DD1681-0CE1 Note : The SE21.2 is delivered with installed burden modules. The cables to X1 and X2 are to be made according to equipment requirements. 4. Technical Specification INSULATION GROUP Isolated to VDE 0160 for small function voltages with protection separation to VDE 0109 or (Degree of contamination 2, overvoltage category II) Rated insulation DC voltage 60 V. PROTECTION CLASS IP00 to DIN HUMIDITY CLASS F to DIN ALTITUDE RATING S to DIN AMBIENT TEMPERATURE 0 to 55 deg. C STORAGE TEMPERATURE -40 to +70 deg. C PACKAGING SYSTEM DIMENSIONS BOARD WIDTH WEIGHT ES 902 C x mm 4 SEP = 3 Slot = mm 0.7 kg Supply Designat Reference Rated Permiss. Permiss. voltages potential value ripple range 1P24 1M +24 V 3.6 V V 2P24 2M +24 V 3.6 V V 2N24 2M -24 V 3.6 V V Current consumption 1P A Reference potential 1M 2P A _ without external output 2N A (i.e. Actual value transducers), Ref. potential 2M max. 2 A binary inputs Polarity switching signals 1, 2, 3 'H'-Signal Rated value +24 V permissible voltage range +10 V V 'L'-Signal Rated value 0 V; or binary inputs open permissible voltage range 0 V V Input current for 'H'-Signal TYP. 1.5 ma Siemens AG Dk-Nr Edition
12 Technical Specification 8 Edition Siemens AG Dk-Nr
13 Technical Specification binary outputs 'H'-Signal 'L'-Signal analog inputs Limit Value indicator GW1, GW2, GW3 Rated Value 24 V permissible voltage range +19 V V OPEN-Collector Outputs Ri = 1.8 K Voltage range V maximum current in the 'L' state 50 ma Actual values 6 Act.val.: Impressed current: - 1 A A Impressed voltage: - 60 V V DC Matching via burden modules 6DD1681-0CE1 Series connected differential amplifier 1 Selector input (only for SIMOVERT D) Impressed voltage: - 60 V V DC Matching via voltage divider Series connected differential amplifier Frequency outputs Number 8 (I/(ACT) / U(ACT) / Absolute value signals) Mean frequency 60 KHZ (for Input signal = 0 V) -10 % / +20 % Band width for matched Input signal ± 10 V = ± 30 khz (-10 % / +20 %) Level as with the binary outputs Temperature coefficient: without burden, without calibration circuits = ± 260 ppm/deg. C Diagnostic outputs Number analog diagnostic outputs binary diagnostic outputs 21 short circuit proof Supply voltages: Ri = 10 K Actual values : ± 10 V max. output current 5 ma Voltage level and output currents as other binary outputs Tolerance specification of the thresholds: The threshold values for the overcurrent or overvoltage indicators are derived from 2P15 (= +15 V). The threshold values drift slightly since the power supply tolerance is ± 5 %. (The voltage dividers are set at delivery to V ± 5 %). Siemens AG Dk-Nr Edition
14 Pin Allocation of the SE Pin Allocation of the SE21.2 ( ) Signals for operation with inverter motor [ ] Signals for operation with cyclo-converter 5.1.X1: Actual values 1 Actual value inputs - for cyclo-converter : all actual values - for inverter motor : Actual values motor inverter 1 (or 6 pulse operation) Pin Signal Pin Signal 2 d d 2P24 b --- b 2 M z 3S9 (Shield) z 2N24 4 d d --- b + Act.val 1 (U1) ; [U1] b + Act.val 5 (I12) ; [I2] z - Act.val 1 z - Act.val 5 6 d 2P24 22 d 2P24 b 2M b 2M z 2N24 z 2N24 8 d d --- b + Act.val 2 (U2) ; [U2] b + Act.val 6 ( - ) ; [I3] z - Act.val 2 z - Act.val 6 10 d 2P24 26 d 2P24 b 2M b 2M z 2N24 z 2N24 12 d d --- b + Act.val 3 ( - ) ; [U3] b --- z - Act.val 3 z d 2P24 30 d --- b 2M b --- z 2N24 z d d --- b + Act.val 4 (I11) ; [I1] b --- z - Act.val 4 z --- Note: The power supply to the contacts 6, 10, 14, 18, 22 and 26 can be used, for example, to power actual value transducers. 10 Edition Siemens AG Dk-Nr
15 Pin Allocation of the SE X2: Actual values 2 Actual value inputs - for cyclo-converter : not used - for inverter motor : Actual values motor inverter 2 Pin Signal Pin Signal 2 d d 2P24 b --- b 2 M z 3S9 (Shield) z 2N24 4 d d --- b --- b + Act.val 8 (I22) ; [-] z --- z - Act.val 8 6 d d 2P24 b --- b 2M z --- z 2N24 8 d d --- b --- b --- z --- z d d --- b --- b --- z --- z d d --- b --- b --- z --- z d d --- b --- b --- z --- z d d --- b + Act.val 7 (I21) ; [-] b --- z - Act.val 7 z --- Note: The power supply to the contacts 18 and 26 can be used, for example, to power actual value transducers. Siemens AG Dk-Nr Edition
16 Pin Allocation of the SE X3: Frequency outputs and Binary inputs Pin No. Signal 1 3S9 (Shield) (U1) ; [U1] (U2) ; [U2] Binary input Bit ( I21,I22,I23 ) ; [ U1,U2,U3 ] ( I11,I12,I13 ) ; [ I1,I2,I3 ] Binary input Bit (I11) ; [I1] (I12) ; [I2] Binary input Bit (I21) ; [I3] (I22) ; [U3] Binary input Bit M 12 Edition Siemens AG Dk-Nr
17 Pin Allocation of the SE X4: Diagnostics outputs Pin No. Signal 1 1P24 D 2 1 M 3 3S9 (Shield) 4 2P24 D 5 2M 6 2N24 D 7 2 M 8 2P15 D 9 2 M 10 2N15 D 11 2 M 12 2P10 D 13 2 M 14 (U1) ; [U1] D 15 2 M 16 (U2) ; [U2] D 17 2 M 18 (I11) ; [I1] D 19 2 M 20 (I12) ; [I2] D 21 2M 22 (I21) ; [I3] D 23 2 M 24 (I22) ; [U3] D 25 2 M 26 ( U1,U2,U3 ) ; [ U1,U2,U3 ] D 27 2 M 28 ( I11,I12,I13 ) ; [ I1,I2,I3 ] D 29 2 M 30 ( I21,I22,I23 ) ; [-] D 31 2 M 32 Overvoltage ( U1,U2,U3 >) ; [ U1,U2,U3 >] D 33 Overcurrent ( I11,I12,I13 >) ; [ I1,I2,I3 >] D 34 Overcurrent ( I21,I22,I23 >) ; [-] D 35 Polarity switch I1 D 36 Polarity switch I2 D 37 Polarity switch I3 D M Siemens AG Dk-Nr Edition
18 Pin Allocation of the SE X5: Binary outputs (Limit values), Frequency outputs (Absolute values) and the SIMADYN D power supply Pin Signal 1 Overvoltage ( U1,U2,U3 >) ; [ U1,U2,U3 >] 2 Overcurrent ( I11,I12,I13 >) ; [ I1,I2,I3 >] 3 Overcurrent ( I21,I22,I23 >) ; [-] 4 ( I11,I12,I13 ) ; [ I1,I2,I3 ] 5 ( I21,I22,I23 ) ; [ U1,U2,U3 ] 6 3S9 7 1 M 8 1P24 Pins 1, 2, 3 - Binary signals Pins 4, 5 - Frequency signals Pins 7, 8 - SIMADYN D power supply Note: The power supply can also be selected to be fed via X X6: Power supply converter side and binary inputs for polarity switching Pin Signal 1 2P24 D 2 2 M 3 2N S9 7 1 M 8 Switch I1 9 Switch I2 10 Switch I3 Pins 1, 2, 3 - Power supply, converter side Pins 8, 9, 10 - Binary signals Note: The power supply can also be selected to be fed via X9. 14 Edition Siemens AG Dk-Nr
19 Pin Allocation of the SE X9: Power supply and Signals Pin Signal Pin Signal 2 d - Act.val 9 * 18 d + Act.val 2 b 1 P24 b - Act.val 2 z 1 P24 z d + Act.val 9 * 20 d + Act.val 3 b 1 M b - Act.val 3 z 1 M z d - Act.val 10 * 22 d + Act.val 4 b Switch 1 b - Act.val 4 z --- z d + Act.val 10 * 24 d + Act.val 5 b --- b - Act.val 5 z --- z d d + Act.val 6 b 2 P24 b - Act.val 6 z 2 P24 z d d --- b 2 M b --- z 2 M z d d --- b 2 N24 b --- z 2 N24 z d + Act.val 1 32 d 3S9 b - Act.val 1 b 3S9 z --- z 3S9 Pins 2b, 4b - Power supply SIMADYN D side Pins 10b, 12b, 14b - Power supply, Converter side Note: The power supply may be selected to be fed via the connectors X5 and X6. * Select inputs, only available with SIMOVERT D Actual value 10 only available when the V/F calibration not used Siemens AG Dk-Nr Edition
20 Appendices 6. Appendices 6.1.Block Diagram Block Diagram 3GE SU 6.2. Scale Drawing and Table of the plug connector Scale Drawing and Table of the plug connector 3GE MB 6.3. Allocation Plan SE21.2 Allocation Plan SE21.2 3GE AO 16 Edition Siemens AG Dk-Nr
21 ECB instructions 7. ECB instructions Components which can be destroyed by electrostatic discharge (ECB) Generally, electronic boards should only be touched when absolutely necessary. The human body must be electrically discharged before touching an electronic board. This can be simply done by touching a conductive, grounded object directly beforehand (e.g. bare metal cubicle components, socket outlet protective conductor contact. Boards must not come into contact with highly-insulating materials - e.g. plastic foils, insulated desktops, articles of clothing manufactured from man-made fibers. Boards must only be placed on conductive surfaces. When soldering, the soldering iron tip must be grounded. Boards and components should only be stored and transported in conductive packaging (e.g. metalized plastic boxes, metal containers). If the packing material is not conductive, the boards must be wrapped with a conductive packing material, e.g. conductive foam rubber or household aluminum foil. The necessary ECB protective measures are clearly shown in the following diagram. a = Conductive floor surface b = ECB table c = ECB shoes d = ECB overall e = ECB chain f = Cubicle ground connection Seated Standing Standing/sitting Siemens AG Dk-Nr Edition
22 ECB instructions 18 Edition Siemens AG Dk-Nr
23 ECB instructions Drives and Standard Products Motors and Drives Systems Group Postfach 3269, D Erlangen System-Based Technology Siemens AG Dk-Nr Edition
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
More informationDigital Pressure Measuring Instrument MDR480
Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm
More informationSIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
More informationBrake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!
Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8
More informationABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationMCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
More informationIsolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationContents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationDMX2PWM 9 Channel Dimmer Setup Manual
DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationPhysical Specifications (Custom design available.)
Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given
More informationOperation Manual. Plasma torch height controller. Model: Compact THC Controller 150
Operation Manual Plasma torch height controller. Model: Compact THC Controller 150 Notes on safety WHEN THE DEVICE IS IN OPERATION, VOLTAGE HAZARDOUS TO HEALTH AND HUMAN LIFE IS PRESENT INSIDE THE HOUSING
More informationDigital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationSINAMICS G130. Braking Module / braking resistor. Operating Instructions 05/2010 SINAMICS
SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Operating Instructions Mechanical installation 3 Connection 4 Maintenance and servicing 5
More informationTM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
More informationOption field bus: without bus with profibus DP. Design-Index (Subject to change)
Amplifier / controller cards ED1 Digital amplifier / controller card ED1 for 1 or 2 proportional solenoids 4 analogue inputs, of which 2 for differential inputs 8 digital inputs Card setting via PC, multi-function
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationGAE953 Electrical Alarm Unit 19" with Indicator
Master Instruction 08.95 MI EIO2211 A-(en) GAE953 Electrical Alarm Unit 19" with Indicator The electrical alarm unit GAE953 gives a signal when one or two set alarm values have been exceeded. Input signals
More informationProduct Datasheet P1110 915 MHz RF Powerharvester Receiver
DESCRIPTION The Powercast P1110 Powerharvester receiver is an RF energy harvesting device that converts RF to DC. Housed in a compact SMD package, the P1110 receiver provides RF energy harvesting and power
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationFrequency Converter Fv
2 Bosch Rexroth AG Electric Drives and Controls Documentation Brake chopper with up to 30 kw continuous braking power Easy to operate and service (detachable fan, LCD operating panel with copy function)
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationSIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01
SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal
More informationHEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
More informationHP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationJUMPFLEX 857 Series. 0...20 ma 2...10 V. 4...20 ma. Transducers / Relay and Optocoupler Modules
0888-0172/0002-3601 JUMPFLEX 857 Series 2.0 E 12/08 Printed in Germany Subject to design changes 2...10 V 0...20 ma 4...20 ma WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 32385 Minden Hansastraße 27
More informationVoltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationSIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
More informationProcess modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
More informationWhale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
More informationT0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
More informationINSTRUCTION MANUAL. Universal sensor switching module 230 V version with Housing
Technical changes reserved Fon +49 771 83160 Fax +49 771 831650 info@bb-sensors.com bb-sensors.com 1 / 17 Contents 1. General dangers and precautions 3 1.1. Instructions regarding documentation 3 1.2.
More informationBroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationSAFETY MANUAL SIL Switch Amplifier
PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General
More informationMPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card
Machinery Protection Card Type FEATURES Continuous on-line Machinery Protection Card Real-time measurement and monitoring using state-of-the-art DSP techniques Fully VME-compatible slave interface Fully
More informationMAC-8. Technical Documentation AC Voltage Input Submodule. Please keep for further use!
MAC-8 Technical Documentation AC Voltage Input Submodule Please keep for further use! Edition date/rev. date: 16.12.1998 Document no./rev. no.: TRS - V - BA - GB - 0029-00 Software version: 1.0 File name:
More informationDATA SHEET. TDA1518BQ 24 W BTL or 2 x 12 watt stereo car radio power amplifier INTEGRATED CIRCUITS
INTEGRATED CIRCUITS DATA SHEET File under Integrated Circuits, IC01 July 1994 GENERAL DESCRIPTION The is an integrated class-b output amplifier in a 13-lead single-in-line (SIL) plastic power package.
More informationActuator-Sensor-Interface
Selection and ordering data Design Order No. Price Pack 3RX9 307-0AA00 3RX9 307-1AA00 4FD5 213-0AA10-1A 3RX9 305-1AA00 3RX9 306-1AA00 Single output IP 65 current 2.4 A Rated input voltage DC 24 V current
More informationTechnical Note Series
Technical Note Series SKIN CONDUCTANCE SENSOR (SA9309M) S TN0 0 0 8-0 0 S k i n C o n d u c t a n c e S e n s o r Page 2 IMPORTANT OPERATION INFORMATION WARNING Type BF Equipment Internally powered equipment
More informationPower Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration
More informationLOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
More informationNTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter
NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter Description: The NTE2053 is a CMOS 8 bit successive approximation Analog to Digital converter in a 20 Lead DIP type package which uses a differential
More informationSafety Relays ESM/ESM-F
Safety Relays ESM/ESM-F More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in
More informationTIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
More informationThermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
More informationDS 600. A contact free flux gate based current measurement sensor 600A rms
DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum
More informationDATA SHEET. TDA8560Q 2 40 W/2 Ω stereo BTL car radio power amplifier with diagnostic facility INTEGRATED CIRCUITS. 1996 Jan 08
INTEGRATED CIRCUITS DATA SHEET power amplifier with diagnostic facility Supersedes data of March 1994 File under Integrated Circuits, IC01 1996 Jan 08 FEATURES Requires very few external components High
More informationCONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
More informationR4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
More informationAnalog Command Value Card Type VT-SWKA-1
RE 0 55/.0 Replaces: 05.00 Analog Command Value Card Type VT-SWKA- Series X Table of contents H/A/D 658/00 Typ VT-SWKA--X/ Features Contents Page Features Ordering code Functional description Block circuit
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationDifferential-Hall-Effect based Sensors Series A5S
Speed and Frequency Seite 1 von 6 Differential-Hall-Effect based Sensors Series A5S Outstanding Characteristics Speed range covering most demands: from close to zero up to 25,000 pulses/second (response
More informationDocumentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20
Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation
More informationBITMAIN. APW3-12-1600 PSU Series User Guide
BITMAIN APW3-12-1600 PSU Series User Guide Contents 1 Overview... 3 2 Features... 3 3 Specifications... 4 4 Switching On/Off Remotely... 5 5 Order Information & Wire Type... 6 5.1 Order Information...
More informationAnalog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
More informationCross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
More informationFiber Optics. Integrated Photo Detector Receiver for Plastic Fiber Plastic Connector Housing SFH551/1-1 SFH551/1-1V
Fiber Optics Integrated Photo Detector Receiver for Plastic Fiber Plastic Connector Housing SFH551/1-1 Features Bipolar IC with open-collector output Digital output, TTL compatible Sensitive in visible
More informationSilvertel. Ag5200. 1 Features. 2 Description. Power-over-Ethernet Plus Module. IEEE802.3at and IEEE802.3af compliant. Maximum 30W output power
Silvertel V1.1 November 2012 Datasheet Pb 1 Features IEEE802.3at and IEEE802.3af compliant Maximum 30W output power Dual In-Line (DIL) package size 50.6mm (L) x 30mm (W) Overload, short-circuit and thermal
More informationMINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
More informationKNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184
EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49
More informationOptions for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface
Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................
More informationCommunication Interface for SMA Inverters SMA BLUETOOTH PIGGY-BACK
Communication Interface for SMA Inverters SMA BLUETOOTH PIGGY-BACK Installation Guide BTPB-IEN112112 98-0014212 Version 1.2 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this
More informationSIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.
SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Manual 04/2007 A5E01077385-01 Safety Guidelines
More informationPower Management & Supply. Design Note. Version 1.0, Nov. 2001 DN-EVALMF2ICE2A265-1. CoolSET 35W DVD Power Supply with ICE2A265.
Version 1.0, Nov. 2001 Design Note DN-EVALMF2ICE2A265-1 CoolSET 35W DVD Power Supply with ICE2A265 Author: Harald Zöllinger Published by Infineon Technologies AG http://www.infineon.com Power Management
More informationDATA SHEET. TDA1543 Dual 16-bit DAC (economy version) (I 2 S input format) INTEGRATED CIRCUITS
INTEGRATED CIRCUITS DATA SHEET File under Integrated Circuits, IC01 February 1991 FEATURES Low distortion 16-bit dynamic range 4 oversampling possible Single 5 V power supply No external components required
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
More informationAutoRanging Digital MultiMeter
Owner's Manual AutoRanging Digital MultiMeter Model No. 82139 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance
More informationUSB-AD14f Data Acquisition System (USB)
Data Acquisition System (USB) Measurement & Control. Super-Low Priced. Record and output signals with the USB-AD14f. The USB data acquisition system accomodated in a stable aluminum housing is ideal for
More informationUSB-AD16f Data acquisition system (USB)
Data acquisition system (USB) Measurement & Control. Extremely powerful. Precisely record and output signals with the USB-AD16f: The high-performance USB data acquisition system accomodated in a stable
More informationSwitch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111
, GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,
More informationFLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
More informationIR Receiver Module for Light Barrier Systems
Not for New Design - Alternative Available: New TSSP4038 (#82458) www.vishay.com IR Receiver Module for Light Barrier Systems TSOP4038 2 3 MECHANICAL DATA Pinning: = OUT, 2 = GND., 3 = V S 6672 FEATURES
More informationEFC 3600. Frequency converters
2 Bosch Rexroth AG Electric Drives and Controls Documentation Compact and complete: space saving side-by-side assembly, plug-in I/O terminals, with brake chopper and mains filter for ultra-simple installation
More informationIO-RM3 3-Stage Relay Module
Page 1 of 6 IO-RM3 3-Stage Relay Module Features: Benefits: Link selectable modes binary, heat/cool, staged or sequenced On/Off/Auto links for ease of commissioning DIN Rail mounting Fault finding LED
More informationTDA4605 CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS
CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS Fold-Back Characteristic provides Overload Protection for External Diodes Burst Operation under Short-Circuit and no Load Conditions
More informationSiemens AG 2011 SINAMICS V60. The perfect solution for basic servo applications. Brochure May 2011 SINAMICS. Answers for industry.
The perfect solution for basic servo applications Brochure May 2011 SINAMICS Answers for industry. with 1FL5 servomotors The solution for basic servo applications There is a requirement to automate motion
More informationRS - SPM. Serial parallel translator module
ReSatron GmbH Boisheimer Str. 162 D-41751 Viersen Telefon (+49) 02162-45 06 80 Telefax (+49) 02162-45 03 04 email: info@resatron.de RS - SPM Serial parallel translator module RSSPM000215SPM-021 - Subject
More informationInstallation manual. Generator Paralleling Controller GPC multi-line 2 4189340225C
Installation manual Generator Paralleling Controller GPC multi-line 2 Software ver. 1.3X Compact system in one unit - dynamic synchronisation - load sharing - generator protection DEIF A/S 3-phase AC RMS
More informationPrecision, Unity-Gain Differential Amplifier AMP03
a FEATURES High CMRR: db Typ Low Nonlinearity:.% Max Low Distortion:.% Typ Wide Bandwidth: MHz Typ Fast Slew Rate: 9.5 V/ s Typ Fast Settling (.%): s Typ Low Cost APPLICATIONS Summing Amplifiers Instrumentation
More informationAnalog Servo Drive 25A8
Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit
More informationCAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008
CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand
More informationIn regard to calculating system power requirements, refer to DBK Basics located near the front of this manual.
DBK42 16-Slot 5B Signal Conditioning Module Overview 1 Hardware Setup 2 DBK42 Connection 2 DBK42 Configuration 2 5B Module Connection 2 Power Considerations 2 Terminal Block Connections 3 DaqBoard/2000
More informationPower Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
More informationAAV003-10E Current Sensor
Datasheet AAV003-10E Current Sensor Key Features For Low Current Detection On-Chip Current Strap for Precise Operation 80 ma to +80 ma Linear Range Sensitivity up to 2 mv/ma AC or DC Measurement Ultraminiature
More informationSIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M
SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M Compact Operating Instructions Legal information Qualified Personnel The product/system described in this documentation
More informationElectronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
More information