Report Number BTC 17755F
|
|
- Abraham Jared Ramsey
- 7 years ago
- Views:
Transcription
1 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Report Number BTC 77F A FIRE RESISTANCE TEST ON A LOADBEARING TIMBER JOIST FLOOR INCORPORATING 4mm x 7mm x 47mm SOLID JOISTS PROTECTED BY A DOUBLE LAYEROF.mmGYPROC FIRELINE INCORPORATINGNINEDOWNLIGHTERS, CONDUCTEDINACCORDANCEWITH BS 47: PART : 87: CLAUSE 7. Test Date: 8 March th Customer: KSR Lighting Ltd Unit 4 The Nelson Centre Portfield Road Portsmouth Hampshire PO SF BTC 77F: Page of
2 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com A FIRE RESISTANCE TEST ON A LOADBEARING TIMBER JOIST FLOOR INCORPORATING 4mm x 7mm x 47mm SOLID JOISTS PROTECTED BY A DOUBLE LAYER OF.mm GYPROC FIRELINE INCORPORATING NINE DOWNLIGHTERS, CONDUCTED IN ACCORDANCE WITH BS 47: PART : 87: CLAUSE 7. TABLE OF CONTENTS FOREWORD 4 REPORT AUTHORISATION 4 TEST REPORT AMENDMENTS TEST CONSTRUCTION Description of Construction Test Construction Drawings 7 Horizontal Cross Section 7 Exposed Face Elevation 8. TEST MATERIALS Gyproc FireLine Joists Chipboard Tongue and Groove Flooring Fasteners Miscellaneous Components Downlighters TEST PROCEDURE TEST RESULTS LIMITATIONS TEST DATA....4 Observations Furnace Temperature Graph Furnace Pressure Graph 7 Unexposed Face Temperature Graph 8 BTC 77F: Page of
3 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Unexposed Face Layout Unexposed Face Downlighter Layout Unexposed Face Standard Five Temperature Data Additional Unexposed Face Temperature Data Internal Temperature Data 7 Specimen Vertical Deflection PHOTOGRAPHS Downlighter KSRFRD prior to installation...4 Exposed face prior to test 7 Unexposed face prior to test 8 Unexposed face at hour, minutes BTC 77F: Page of
4 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. FOREWORD This test report details a fire resistance test conducted on a full scale horizontal loaded timber joist floor. The test specimen was installed by Alltone Limited. The construction of the specimen took place on the and 7 March. The Building Test Centre played no role in the design or selection of materials comprising the test specimen. The test was conducted on the 8 March. th Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.. REPORT AUTHORISATION Report Author Authorised by P.P. Liam Woodford Technologist Paul Miller BSc. (Hons.) Fire Test Manager The Building Test Centre will not discuss the content of this report without written permission from the test sponsor. The Building Test Centre retains ownership of the test report content but authorises the test sponsor to reproduce the report as necessary in its entirety only. BTC 77F: Page 4 of
5 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. TEST REPORT AMENDMENTS Page Amendments Date BTC 77F: Page of
6 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com 4. TEST CONSTRUCTION 4. Description of Construction The specimen was constructed in a refractory concrete lined steel restraint frame having an opening of 4mm long x mm wide. 7mm x 47mm C grade softwood joists were placed, nominally, at mm centres, spanning 4mm length of the test frame. Fulldepth noggings were fixed at each end of the joists (within the test aperture) with inch nails. 8mm x 8mm noggings were fixed between the joists to coincide with the outer layer board joints using inch nails. The tops of the joists were covered with a walking surface of mm tongue and groove chipboard flooring (nominally mm long x mm wide) which was fixed using mm drywall timber screws at mm centres. The underside of the floor was lined with a double layer of.mm Gyproc FireLine, (nominally mm long x mm wide). The inner layer was fixed using mm Drywall timber screws at mm centres. The outer layer was fixed using mm Drywall timber screws at mm centres. All board joints were staggered between layers. All joints were finished using Gyproc Joint Tape and Joint Filler. All screw heads were spotted using Gyproc Joint Filler. Nine downlighters were incorporated into the ceiling. A mm diameter hole was cut into the plasterboards to accommodate all of the downlighters. Downlighters KSRFRD were positioned at F, G, H, I and J. Four additional downlighters were positioned at A, B, C and D. See figure 7 for the positions of each downlighter. BTC 77F: Page of
7 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com 4. Test Construction Drawings 4.. Horizontal Cross Section mm Drywall Timber Screws (mm centres) mm T&G Chipboard Flooring (nominally mm x mm) Timber Joist 7mm x 47mm C grade softwood joist mm Drywall Timber Screws (mm centres) Gyproc.mm TE FireLine mm Drywall Timber Screws (mm centres) Figure Horizontal cross section BTC 77F: Page 7 of
8 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com 4.. Exposed Face Elevation Figure Exposed Face Elevation The descriptions of individual components making up the test specimen were provided by the customer and were checked for accuracy wherever possible. BTC 77F: Page 8 of
9 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. TEST MATERIALS. Gyproc FireLine i) Nominally, mm (long) x mm (wide) x.mm (thick), Gyproc FireLine manufactured and supplied by. Measured surface density: Measured thickness: Board identification numbers: Measured moisture content:.kg/m.mm 7: 7: 7:7.4% The surface density and board thickness were calculated using a selection of boards used in the test specimen. The moisture content of plasterboard was determined using samples dried to constant weight in an oven at C. Material dimensions were measured by The Building Test Centre.. Joists ii) Nominally, 4mm (long) x 7mm (deep) x 47mm (wide), C grade softwood joists, supplied by The Building Test Centre. (8mm x 8mm noggings were also made from the same grade softwood) Measured dimensions: Mass per joist: Measured moisture content: 48mm x 7mm x 47mm.kg.4% The surface density and thickness were calculated using a selection of timber used in the test specimen. The moisture content of the timber joists and flooring was determined using samples dried to constant weight in an oven at C. All joists supplied by Alltone. BTC 77F: Page of
10 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Chipboard Tongue and Groove Flooring iii) Nominally mm (long) x mm (wide) x mm (thick), supplied by Alltone. Measured surface density: Measured thickness: Measure moisture content:. kg/m mm 7.4% The surface density and thickness were calculated using a selection of timber used in the test specimen. The moisture content of the timber joists and flooring was determined using samples dried to constant weight in an oven at C. All chipboard tongue and groove flooring supplied by Alltone..4 Fasteners iv) v) vi) mm Gyproc Drywall Timber Screws mm Gyproc Drywall Timber Screws inch nails All fasteners supplied by The Building Test Centre.. Miscellaneous Components vii) viii) ix) Gyproc Joint Filler Gyproc Paper Tape Gyproc Bonding Coat All miscellaneous components supplied by The Building Test Centre.. Downlighters x) xi) KSR FRD (five included) Four additional downlighters were positioned into the specimen BTC 77F: Page of
11 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. TEST PROCEDURE The test was conducted fully in accordance with BS 47: Part : 87: Clause 7. The asymmetrical specimen was subjected to fire from the underside (plasterboard side) this being the required direction of fire resistance as specified in BS 47: Part : 87: Clause 7. Where areas of the test specification are ambiguous, or open to interpretation, the Fire Test Study Group Resolutions 4, 47,,,, 7, 7, 7, 77, 7 and 8 have been followed (where appropriate). These Resolutions provide the basis of common agreements between the fire test laboratories, which are members of this group. The test procedure used was 47//7, issue. The ambient temperature at the commencement of the test was 7 C. o The furnace pressure was set to control at 8 ± Pa positive with respect to atmosphere, at the top of the specimen. Furnace pressure data is shown in figure 4. A total load of 8kN (.kn/m ) was applied to equally distributed loading points. Loading requirements were supplied by the sponsor. BTC 77F: Page of
12 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com 7. TEST RESULTS The requirements of the standard were satisfied for the following periods: Loadbearing Capacity: minutes Integrity: minutes By virtue of loadbearing capacity failure Insulation: minutes By virtue of loadbearing capacity failure The test was terminated at minutes at the request of the laboratory. 8. LIMITATIONS The results only relate to the behaviour of the specimen of the element of construction under the particular conditions of test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they reflect the actual behaviour in fires. The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. BTC 77F: Page of
13 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. TEST DATA. Observations Observers: Unexposed face Exposed face L Cooper, S Potter L Woodford Time Hrs mins Observations All observations refer to the exposed face unless otherwise stated. Test started. Jointing material was flaking away. Board face papers charred. All downlighters had darkened. Glass had fallen into furnace from downlighters C, F, G and J. Glass had fallen into furnace from all downlighters. Bezel on downlighters F, I and J had fallen into furnace. Flaming from downlighter G. Crack running parallel to meter edge on lefthand side board nearest to viewing platform. All board joints had opened to approximately mm. 4 Bezel on downlighters B, C and D had fallen into furnace. All board joints had opened to approximately 8mm. 4 Bezel on downlighter A had fallen into furnace. Bezel on all downlighters had fallen into furnace. Boards bowing into furnace between screw heads adjacent to all board joints. Flaming from downlighter F. Boards bowing into furnace between all screw heads. BTC 77F: Page of
14 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time Hrs mins Observations All observations refer to the exposed face unless otherwise stated. Board joint parallel to meter edge nearest to viewing platform had opened to approximately mm. Outer layer board fall, second full board in from the viewing platform, piece approximately mm (wide) x mm (long). 7% of outer layer boards had fallen into the furnace. Inner layer board joints had opened to approximately mm. Cracking noises heard from inside the furnace. Downlighters A, C and G still in position, all other downlighters had fallen into the furnace. Unexposed face Cracking noises heard from the specimen. Inner layer board joints had opened to approximately mm. Flaming inside furnace, visibility poor. Unexposed face Specimen visibly bowed into the furnace in centre. 7 Second layer board fall around downlighter G. Unexposed face Smoke emissions increased from joints in walking surface. Unexposed face Black smoke issued from specimen (closer door end). Unexposed face LOAD BEARING CAPACITY FAILURE Rate of deflection was greater then 7.mm per minute after mm deflection. BTC 77F: Page 4 of
15 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time Hrs mins Observations All observations refer to the exposed face unless otherwise stated. Unexposed face Deflection in centre greatly increased. Deflection limit exceeded mm. Unexposed face Gap visible approximately mm wide. Flaming on walking surface in excess of seconds. TEST TERMINATED at the request of the laboratory. BTC 77F: Page of
16 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Furnace Temperature Graph 8 Temperat ure ( C) Mean Furnace Figure Furnace temperature graph Time (minutes) Standard Furnace BTC 77F: Page of
17 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Furnace Pressure Graph Pressure (Pa) 4 8 Time (minutes) Figure 4 Furnace pressure graph The furnace pressure was set to control at 8 ± Pa positive with respect to atmosphere, at the top of the specimen. BTC 77F: Page 7 of
18 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com.4 Unexposed Face Temperature Graph 4 Temperat ure Rise ( C) Time (minutes) Mean Standard Five Maximum Unexposed Figure Unexposed face temperature graph BTC 77F: Page 8 of
19 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Unexposed Face Layout A B C Standard Five TC's Additional Unexposed TC's Placed in line with D, E, F, & G Internal TC's (see below) Positions A, B, C, D, E, F, G, H, I and J D/ E/ F/7 G/ With pad Downlighter H I J mm T&G Chipboard Flooring (nominally x ) Figure Unexposed face thermocouple layout BTC 77F: Page of
20 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Unexposed Face Downlighter Layout A B C D F G H J K Figure 7 Unexposed face downlighter layout BTC 77F: Page of
21 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com.7 Unexposed Face Standard Five Temperature Data Time (mins) Temperature Rise (ºC) No. No. No. No. No. Mean Standard BTC 77F: Page of
22 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Temperature Rise (ºC) No. No. No. No. No. Mean Standard BTC 77F: Page of
23 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Temperature Rise (ºC) No. No. No. No. No. Mean Standard See Figure for thermocouple layout. BTC 77F: Page of
24 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com.8 Additional Unexposed Face Temperature Data Time (mins) Temperature Rise (ºC) No. No. No. 7 No BTC 77F: Page of
25 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Temperature Rise (ºC) No. No. No. 7 No BTC 77F: Page of
26 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Temperature Rise (ºC) No. No. No. 7 No See Figure for thermocouple layout. BTC 77F: Page of
27 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Internal Temperature Data Time (mins) Actual Temperature (ºC) Position AAB B C C D D F F BTC 77F: Page 7 of
28 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Actual Temperature (ºC) Position AAB B C C D D F F BTC 77F: Page of
29 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Actual Temperature (ºC) Position AAB B C C D D F F See Figure for thermocouple layout. BTC 77F: Page of
30 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Actual Temperature (ºC) Position GGH H I I J J E E BTC 77F: Page of
31 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Actual Temperature (ºC) Position GGH H I I J J E E BTC 77F: Page of
32 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Actual Temperature (ºC) Position GGH H I I J J E E Indicates a broken thermocouple. See Figure for thermocouple layout. BTC 77F: Page of
33 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Specimen Vertical Deflection Time (mins) Centre Deflection (mm) Centre Deflection (mm) Maximum Rate of deflection (mm/minute) BTC 77F: Page of
34 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Centre Deflection (mm) 7 7 Centre Deflection (mm) 4 7 Maximum Rate of deflection (mm/minute) BTC 77F: Page 4 of
35 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com Time (mins) Centre Deflection (mm) Centre Deflection (mm) Maximum Rate of deflection (mm/minute) The two centre deflections were recorded at the approximate centre of the specimen. Positive readings indicate deflection into the furnace. BTC 77F: Page of
36
37 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Exposed face prior to test BTC 77F: Page 7 of
38 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com. Unexposed face prior to test BTC 77F: Page 8 of
39 Leics. LE NP Tel () 4 Fax () 4 btc.testing@saintgobain.com.4 Unexposed face at hour, minutes BTC 77F: Page of
Rockwool Flexi Insulation Application Guide
Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed
More informationTECHNICAL RECOMMENDATION
TECHNICAL RECOMMENDATION NO: 9 DESIGN OF LIGHT TIMBER FRAMED WALLS AND FLOORS FOR FIRE RESISTANCE Peter Collier Contents Design of Light Timber Framed Walls and Floors for Fire Resistance Relevance Acceptance
More informationCERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
More informationENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available.
APR 1200 Acoustic Partition Roll CI/Sfb Ref: APR002 Glass mineral wool roll designed to provide high levels of sound insulation in walls and floors to meet Part E (England & Wales) and Section 5 (Scotland)
More informationINTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
More informationFire-resistance test on fire collars protecting a concrete slab penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1614 Date: 14 February 2014 Client:
More informationBS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Eco-Sol Ltd. Document Reference: 304043
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationSMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION
SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC #100-2949-1 TESTED: MAY 23, 2008 REVISION 2.0: OCTOBER 14, 2008 October 14, 2008 Client: Attn: Subject:
More informationFire safety in timber buildings
Fire safety in timber buildings Introduction Fire spread in buildings is a risk to life safety for which the Building Regulations (for England and Wales 1,2, Scotland 3 and Northern Ireland 4 ) aims to
More informationRequirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
More informationFIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS
INFORMATION PAPER IP 21/10 FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS Tom Lennon and Danny Hopkin The use of Structural Insulated Panel (SIP) systems in construction in the UK has increased
More informationBS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Gurit (UK) Ltd. Document Reference: 312304
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationMezzanine. Technical manual
TechNICAL MANUAL 1 Mezzanine Technical manual 2 Varnished (optional) Product class P6 Melamined (optional) Tongue and groove Structural applications STANDARD FEATURE additional options - Chipboard - Varnished
More informationStructural fire design Eurocode 5-1.2 Timber structures
Background and Applications Brussels, 18-20 February 2008 Dissemination of information workshop 1 Structural fire design Eurocode 5-1.2 Timber structures Jochen Fornather Austrian Standards Institute jochen.fornather@on-norm.at
More informationCONTENTS 1. INTRODUCTION...1 2. METHODOLOGY...2 3. RESULTS & FINDINGS...9 APPENDIX
Load Testing of Balustrade Systems Test Report No. S365 CONTENTS 1. INTRODUCTION...1 2. METHODOLOGY...2 2.1 BALUSTRADE LOAD ASSESSMENTS... 2 2.2 TEST SYSTEMS... 3 2.3 TEST PROCEDURE... 8 3. RESULTS & FINDINGS...9
More informationFINAL DRAFT FprEN 13381-2
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM FINAL DRAFT FprEN 13381-2 April 2014 ICS 13.220.50 Will supersede ENV 13381-2:2002 English Version Test methods for determining the contribution to the
More informationFire Preventive and Fireproof Performance Test and Evaluation Procedure Manual
BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building
More informationFire 2This Technical Bulletin has been commissioned by the UK SIP Association in
REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory
More informationTimber Decks. Technical Note. March 2007
Timber Decks Technical Note. March 2007 This Technical Note contains general information for residential timber decks and floor frame structures for veranda s, patios etc which are exposed to the weather.
More informationREPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1181: PART 1: ISSUE 1.1 Series of Fire Growth Tests for LPCB Approval and Listing of Construction Product Systems Part One: Requirements and Tests for Built-up Cladding and
More informationCERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
More informationFireWall. High performance fireresistant. FireWall. www.british-gypsum.com
FireWall FireWall High performance fireresistant wall system FireWall is a non-loadbearing wall which provides up to 240 minutes fire resistance. It is used in certain ground floor basement situations
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationKnauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap
Tile Backing Will not deteriorate in water Easy to score and snap Resistant to mould and mildew Knauf Aquapanel Interior Cement board for wet areas Knauf Aquapanel Interior Cement Board Drywall for Wet
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationPASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors
PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors For distribution in Asia Pacific PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: Ceilings & Floors Contents
More informationDecember 2013. J-Ply Roofing, Flooring and Decking
December 2013 J-Ply Roofing, Flooring and Decking Introduction J-Ply plywood is manufactured in New Zealand by Juken New Zealand Limited (JNL) and marketed by New Zealand Wood Products Limited. The J-Ply
More informationManual lifting and handling
Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details
More informationSection 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with
Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and
More information(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationInstallation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details
D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls
More informationFire-resistant barriers: background on requirements and determination method. Reading guide for test reports.
Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports. Report number C 1395-1E-RA-003 d.d. May 14, 2014 Fire-resistant barriers: background on requirements
More informationHow to Install Hardwood Flooring Over a Sub Floor
How to Install Hardwood Flooring Over a Sub Floor Installation Preparation Instructions Read the entire instructions before starting your project. 1) INSPECT EACH PLANK (see fig. a) Wood is a natural product
More informationTest Report: ICL/H11/979. BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures.
Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk
More informationCardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com
CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information
More informationIRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION
IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION Bill Robinson BSc. C. Eng. M. I. Struct. E. Timber Design Services 1 IS440 Timber frame
More informationCERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES
CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,
More informationTEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
More informationFire testing procedure for concrete tunnel linings
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com Ministry of Infrastructure and the Environment (Rijkswaterstaat) Report no.
More informationSquash Court Design general points
Squash Court Design general points Contents: Contents:... 1 1. Squash Court Dimensions... 2 2. CourtTech Walls... 3 3. Dimensional requirements for courts with CourtTech Walls... 3 4. Loading of CT System
More informationSchlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing
Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight
More informationC05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction
C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05 Specialist partitions Introduction Specialist partitions This section details specialist lightweight systems where high-security,
More informationChapter 36 - STRAW BALE CONSTRUCTION SECTION 3601 - PURPOSE. SECTION 3602 - SCOPE. SECTION 3603 - DEFINITIONS.
Austin City Code - Volume II TITLE 25 LAND DEVELOPMENT\CHAPTER 25-12 TECHNICAL CODES\ARTICLE 1: UNIFORM BUILDING CODE\25-12-3 LOCAL AMENDMENTS TO THE BUILDING CODE Chapter 36 - STRAW BALE CONSTRUCTION
More informationSection 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining
Section Timber Frame Walls Single layer between studs Product: Earthwool FrameTherm Rolls and Slabs Tf01 Single layer between studs with service void Product: Earthwool FrameTherm Rolls and Slabs Tf02
More informationINTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.
INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal
More informationFIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England
FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England Fire is a life-threatening and destructive force, which if unchecked, can spread rapidly through a building. Every year,
More informationCity of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures
City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards
More informationDubai Municipality Standard DMS 1: Part 5: 2004
Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue
More informationMulti-layer Insulation Blanket for Roofs
Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof
More informationTECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE
TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE TECHNICAL SPECIFICATION PART 8000 - PRECAST CONCRETE TABLE OF CONTENTS Item Number Page 8100 PRECAST CONCRETE CONSTRUCTION - GENERAL 8-3 8101 General
More informationSteel-framed Walls. Insulation
Insulation A4/8 SF AW1192 Issue 4 Nov 2012 Steel-framed Walls Insulation guide Helps achieve a 6-star house energy rating Rigid and flexible Kingspan AIR-CELL solutions available Vapour barrier or vapourpermeable
More informationSection 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.
Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice
More informationH:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
More informationConnection Solutions
Connection Solutions DESIGN BUILD SYSTEM Connection Solutions for Cold formed Steel Construction Complies with; AS/NZS 4600:2005 AISI S100:2007 AS/NZ 1397 ASTM A653 DESIGN & BUILD SYSTEM FRAMECAD Construction
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationFire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No.
BULLETIN No. 28 (a) Fire Protection CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8 Floor Assembly No. NRC764-FF22 Fire Endurance Period 1 74 minutes Sound
More informationApproval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
More informationEuropean Organisation for Technical Approvals
Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive
More informationChapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
More informationTPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER
Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)
More informationLinea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1
Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.
More informationFiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationCompression load testing straw bale walls. Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY.
Compression load testing straw bale walls Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY May 2004 1. Introduction Over the last 10 years a growing number of loadbearing
More informationVA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
More informationFire Resistance of Brick Masonry
TECHNICAL NOTES on Brick Construction 1850 Centennial Park Drive, Reston, Virginia 20191 www.gobrick.com 703-620-0010 Fire Resistance of Brick Masonry 16 March 2008 Abstract: This Technical Note presents
More informationWHI TEST REPORT #630-104800 FIRE RATED DOORS
8000 Whitepine Rd. Richmond, VA 23237 Tel: 800-446-7325 Fax: 800-448-2908 E-mail: weatherseal@sealeze.com WHI TEST REPORT #630-104800 FIRE RATED DOORS REPORT OF TEST OF GASKETING FOR RESISTANCE TO AIR
More informationGypsum Board Systems Manual
CertainTeed Gypsum Board Systems Manual Fire Resistance and Sound Control Design Manual Division 09 GYPSUM BOARD SYSTEMS MANUAL TABLE OF CONTENTS Introduction General Fire Resistance...1 Sound Control...3
More informationBETONYP building boards. The modern way of living.
BETONYP building boards The modern way of living. Tough for 30 years. Healthy, debarked pine wood and cement: the raw materials used to produce one of our most successful products for more than three decades.
More informationModule 3.7. Thermal bridging
Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More informationPlanet Frameless Glazing. Planet 20 frameless glass swing door
Planet Frameless Glazing Planet 20 frameless glass swing door Contents Introduction Pg 2 Planet 20 - Single Glazing Pg 3-7 Planet 100 - Double Glazing Pg 8-12 Joint Options Pg13 Sectional Drawings for
More informationINTERNATIONAL HOCKEY FEDERATION PERFORMANCE REQUIREMENTS AND TEST PROCEDURES FOR HOCKEY BALLS. Published: April 1999
INTERNATIONAL HOCKEY FEDERATION PERFORMANCE REQUIREMENTS AND TEST PROCEDURES FOR HOCKEY BALLS Published: April 1999 CONTENTS 1 Introduction 2 Test Procedures General 3 Standards and Specific Test Procedures
More informationDE Frame with C Series Sidelight
TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder
More informationPost and Beam Construction
Post and Beam Construction A Presentation By the Canadian Wood Council Canadian Conseil Wood canadien Council du bois Early settlers introduced the concept of post and beam construction in North America
More informationProperty Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT
Property Inspection 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT March 2013 This document has been prepared for the benefit of Clint Marston. No liability is accepted by this company
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
More informationR=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES
IEC SYSTEM FO CONFOMITY TESTING AND CETIFICATION OF ELECTICAL EQUIPMENT COMMITTEE OF TESTING LABOATOIES TESTING AND MEASUING EQUIPMENT/ALLOWED SUBCONTACTING Power cables with extruded insulation and their
More informationComposite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
More informationCHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
More informationHow to secure your property after a disaster
How to secure your property after a disaster The Red Guide to Recovery HOuse secured properly Board-Up of Windows, Doors and Roof Hole. Lot secured with Perimeter Fencing. Fires, floods, tornadoes, hurricanes,
More informationResidential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
More informationIMPACT DAMAGE RESISTANT WALL SYSTEMS
IMPACT DAMAGE RESISTANT WALL SYSTEMS CONTENTS Introduction 2 Advantages 2 2 Material Specifications 2 Design Considerations 3 Framing 5 Plasterboard Installation 5 Health, Safety & Warranty 6 Contact Details
More informationsound reduction systems for commercial, educational and industrial environments
sound reduction systems for commercial, educational and industrial environments Tel: +44 ()14 3874 Fax: +44 ()14 38957 E-mail: info@soundreduction.co.uk Web: www.soundreduction.co.uk soundblocker Acoustic
More informationThe University of Birmingham (Live System)
The University of Birmingham (Live System) Behaviour of Structural Insulated Panels (SIPs) under both short-term and long-term loadings Yang, Jian; Rungthonkit, Prathan Document Version Author final version
More informationUnderstanding BS EN 771-3: Aggregate concrete masonry units
60 Charles Street, Leicester LE1 1FB Tel: 0116 253 6161 Fax: 0116 251 4568 Email: enquiries@cba-blocks.org.uk Website: www.cba-blocks.org.uk February 2006 Understanding BS EN 771-3: Aggregate concrete
More informationGordon Cooke BSc PhD CEng MICE MIMechE FIFireE
International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, April 6-7, 2003 Upgrading the fire resistance of floors and doors in heritage buildings Gordon Cooke BSc PhD CEng
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009
P.O. Box 1090 - NL-2280 CB Rijswijk Lange Kleiweg 5 - NL-2288 GH Rijswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationwww.gaylordhardwoodflooring.com
Chapter 16 Problems, Causes, and Cures Problem: Cupping Cause: Flooring absorbing excessive moisture on underside, causing expansion with raised edges. / Not leaving enough expansion space around perimeter.
More informationH-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
More informationEuropean Technical Approval ETA-12/0500
ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 10 of the Council Directive 89/106/EEC
More informationMold Preventing I nterior System
interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal
More informationInstallation information. METTLER TOLEDO MultiRange DW150 / DW150T wall scale
Installation information METTLER TOLEDO MultiRange DW150 / DW150T wall scale DW150 / DW150T wall scale Contents Contents Page 1. Installation... 2 1.1 Preparatory work... 2 1.2 Installing the wall plates
More informationInterior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer
More informationPolicy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
More informationGuidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
More informationEuropean Technical Assessment ETA-10/0153 of 10/06/2015
ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet ww.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011 of
More information