Test Report: ICL/H11/979. BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures.
|
|
- Kerry Townsend
- 8 years ago
- Views:
Transcription
1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) Fax.: +44 (0) firetesting@intersciencecomms.co.uk Test Report: ICL/H11/979 BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures. Sponsored By RHI tents 28 Boulevard Way Capricorn Park Muizenburg Cape Town 7945 South Africa Registered Office: West Yard House, Guildford Grove, Greenwich, London SE10 8JT, UK firetesting@intersciencecomms.co.uk; Web: intersciencecomms.co.uk Company Registration VAT No. GB Page 1 of 5
2 Test Report: ICL/H11/979 Sponsored By BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures. RHI tents 28 Boulevard Way Capricorn Park Muizenburg Cape Town 7945 South Africa 1 Purpose of Test 2 Scope To assess the performance of a fabric when it is tested in accordance with the procedures called up in BS 7837:1996. BS 7837:1996 specifies requirements for flammability of fabrics and fabric assemblies for use in the construction of textile structures such as marquees, large tents, temporary buildings, awnings and other textile structures utilizing large areas of a flexible textile membrane other than air-supported structures, when tested in accordance with test 2B (bottom edge ignition) of BS 5438 : Description of Test Specimen The description of the specimen given above has been prepared from information provided by the sponsor of the test and Interscience Communications Ltd was not involved in any selection or sampling procedure. The product was a cream coloured nominally 1mm thick FR treated coated fabric referenced RHI ALLWEATHER MK4 having a mass of 806g/m 2. A photograph showing two faces of the fabric is given in Appendix 1. The sponsor of the test did not provide further details relating to the composition of the material from which the tape was produced. 4 Water soaking treatment In accordance with the requirements given in Clause 5 of BS 7837: 1996 the samples were subjected to the water soaking procedure described in clause 3 of BS 5651: Page 2 of 5
3 5 Conditioning of Test Specimens The specimens were received on 21 September The test specimens were conditioned at 20 ± 2 o C and 65 ± 5% relative humidity for a minimum period of 24 hours prior to testing. 6 Date of Test The test was performed on 7 October Test Procedure Test was carried out in accordance with the procedure specified in BS 5438: 1989 Incorporating Amendment 1 and 2 in clause 10 Test 2B Limited flame spread: bottom edge ignition. 8 Test Results The test results relate only to the behaviour of the specimens of the product under the particular conditions of test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use. The test results relate only to the specimens of the product in the form in which they were tested. Small differences in the composition or thickness of the product may significantly affect the performance during the test and may therefore invalidate the test results. Flame application time: 10s Warp direction Weft direction Parameters Run 1 Run 2 Run 3 Run 4 Run 5 Run 6 Duration of flaming (s) Duration of afterglow (s) N/A N/A N/A N/A N/A N/A Flaming debris None None None None None None Flame to edge N/A N/A N/A N/A N/A N/A Hole to edge N/A N/A N/A N/A N/A N/A Glow to edge N/A N/A N/A N/A N/A N/A Max. extent of hole (mm) Max. damaged length (mm) Page 3 of 5
4 9 Requirements: The following requirements are given in clause 8 of BS 7837:1996. The sample shall be deemed to perform satisfactorily (pass), if, for at least five of the six test specimens: a) the duration of flaming does not exceed 5 s after removal of the igniting flame; and b) the lowest boundary of any flame does not reach the upper edge or either vertical edge; and c) the filter paper does not smoulder or flame. The sample shall be deemed not to conform to this British Standard (fail) if more than two test specimens show any of the effects listed in items a) to c) If two test specimens show any of the above effects, then a further six specimens shall be tested. In this case, the sample shall be deemed to `pass' if five of the second set of six specimens perform satisfactorily. 10 Conclusion The fabric satisfies the requirements of the standard. Prepared by C. Chong S. Kumar Fire Scientist Technical Manager Date of Issue: 31 October Page 4 of 5
5 Appendix 1 Photograph 1. Showing the front coated surface and rear face of the material. Page 5 of 5
BS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Eco-Sol Ltd. Document Reference: 304043
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationBS 476: Part 7: 1997. Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Gurit (UK) Ltd. Document Reference: 312304
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 7: 1997 Method For Classification
More informationOur ref: AMR/AMR Date: 20 December 2012. Report 194799 Page 1 of 9
Our ref: AMR/AMR Date: 20 December 2012 Report 194799 Page 1 of 9 Chimney Sheep P O Box 80 Cockermouth Cumbria CA13 0HE Attention: Sally Phillips DATE RECEIVED: 19 NOVEMBER 2012 QUALITY/REFERENCE: 15 CIRCULAR
More informationTest report No. 2013-1650
Exova Warringtonfire, Frankfurt Industriepark Höchst, C369 Frankfurt am Main D-65926 Germany T : +49 (0) 69 305 3476 F : +49 (0) 69 305 17071 E : EBH@exova.com W: www.exova.com Exova Warringtonfire, Frankfurt
More informationBRE Global Test Report
BRE Global Test Report IMO 2010 FTP Code Part 5 - Test For Surface Flammability MSC.307(88) on PVC film ORAJET 3951-010, printed with solvent based inks in colour Orange. Laminated with ORAGUARD 290 and
More informationEUROPEAN STANDARDS PERSONAL PROTECTIVE CLOTHING FOR FLAME RESISTANT. Alexander Gstettner, Lenzing AG Austria
EUROPEAN STANDARDS FOR FLAME RESISTANT PERSONAL PROTECTIVE CLOTHING Alexander Gstettner, Lenzing AG Austria W a t e r How are the standards organized? A 1 Testing Methods Standards specifiying performance
More informationHow To Test For Premer Retardant
TEST REPORT NEBS COMPLIANCE CHOMERICS PREMIER CONDUCTIVE PLASTIC Prepared by: CHOMERICS R&D 84 DRAGON COURT WOBURN, MA 01801 Test Report Number: TR 1007 EN 0206 Chomerics Approved Signatory: This report
More informationReport Number BTC 17755F
Leics. LE NP Tel () 4 Fax () 4 Email btc.testing@saintgobain.com Report Number BTC 77F A FIRE RESISTANCE TEST ON A LOADBEARING TIMBER JOIST FLOOR INCORPORATING 4mm x 7mm x 47mm SOLID JOISTS PROTECTED BY
More informationNightwear Advisory Note
NEW REQUIREMENTS FOR THE FIRE SAFETY OF CHILDREN'S NIGHTWEAR Nightwear Advisory Note OCTOBER 2008 NEW REQUIREMENTS FOR THE FIRE SAFETY OF CHILDREN'S NIGHTWEAR This is an advisory note regarding new flammability
More informationfurnishings flammability characteristics
Technical Bulletin 110104 New Options for Textiles The performance of Ingeo fibers in the standard flammability tests described below confirm that Ingeo fibers, without any flame retardant (FR) treatment,
More informationNIGHTWEAR AND FIRE. A Guide to Nightwear (Safety) Regulations. Contents
NIGHTWEAR AND FIRE A Guide to Nightwear (Safety) Regulations Contents The Regulations Labelling Requirements Requirements For Advertisments The Test Enforcement THE REGULATIONS Nightwear can burn rapidly,
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009
P.O. Box 1090 - NL-2280 CB Rijswijk Lange Kleiweg 5 - NL-2288 GH Rijswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification
More informationRequirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by Avenue de Catalogne 11300 LIMOUX Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:007 Sponsor Prepared by Qualyline Srl Gewerbezone Reifenstein 18 - Sadrobre I-39040- Freienfeld(BZ), Italy and Stefano Mardegan
More informationCHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
More informationCLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN 13501-1:2007
ERA YÖNETİM DANIŞMANLIĞI HİZMETLERİ A.Ş. ERA Fire Test Laboratory Accredited Body tified Body : AB-00-T : 2184 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN 1501-1:2007 Sponsor Prepared by Product
More informationPRODUCTS. Ten 47 Ltd 2B Frances Industrial Park Kirkcaldy Fife. UK KY1 2XZ
+ Ten 47 CABLEGUARD PRODUCTS Ten 47 Ltd 2B Frances Industrial Park Kirkcaldy Fife UK KY1 2XZ Tel: +44 (0) 1592 655725 Fax: +44 (0) 1592 651049 Email: sales@cableguardeu Web: wwwcableguardeu Index Black
More informationREPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012
TEST REPORT REPORT NUMBER: 100758576MID-001 ORIGINAL ISSUE DATE: JUNE 27, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Fire Door Caulk LLC.
More informationCERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
More informationLABORATORY REPORT: Assessment of Ikadan, IKA Floor Sports, to the Performance Requirements of EN 14877 (2006): Multi-sports
LABORATORY REPORT: Assessment of Ikadan, IKA Floor Sports, to the Performance Requirements of (2006): Multi-sports Report Number LSUK.12-0256 Client Ikadan Højris Alle 89 7430 Ikast Date(s) 17/09/2012
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1581: Issue 2.1 Requirements and tests for LPCB approval of nonload This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information
More informationColonnade Security Pipe
Description: Round & Square downpipe formed from extruded 6060 T4 aluminium in various sizes (Ø83mm, Ø108mm, 83x83 mm & 108x108mm*) & supplied with a complete range of accessories i.e. Offsets, bends,
More informationDubai Municipality Standard DMS 1: Part 5: 2004
Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue
More informationINTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
More informationFlying imposes considerable physiological demand
Technical Communication Heat Release Characteristics of the basic materials used for flying clothing Wg Cdr V S Sachdev *, TM Kotresh +, MK Vyawahare #, GP Agrawal ** ABSTRACT The fabrics used for overalls
More informationCavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
More informationFire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
More informationSede: Via Antica, 24/3 33048 S. Giovanni al Nat. UD Tel. 0432.747211 r.a. Fax 0432.747250 http://www.catas.com e-mail: lab@catas.
centro ricerche-sviluppo e laboratori prove Date received: 12-11-13 Date of issue: 02-12-13 33048 S. Giovanni al at. UD OMP S.R.L. VIA CA' LEOCIO, 2 31030 CASTELLO DI GODEGO (TV) Report consists of 6 test
More informationQBE European Operations Suttons Electrical Contractors Insurance Schedule
QBE European Operations Suttons Electrical Contractors Insurance Schedule Policy Number: Y025641QBE0115A Policy Wording Reference: PSEC011114 Period of Insurance: From: 18 February 2015 To: 17 February
More informationStudy on flame retardant properties of poly(lactic acid) fibre fabrics
Indian Journal of Fibre & Textile Research Vol. 39, September 2014, pp. 268-273 Study on flame retardant properties of poly(lactic acid) fibre fabrics M S Parmar a, Maheshwar Singh, Rajiv Kumar Tiwari
More informationLAMINAR FLOW CABINETS
LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2007
CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1: 2007 Sponsor Prepared by Fiboveien 2 NO-4580 Lyngdal Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB RIJSWIJK
More informationPRODUCT SHEET 1 MIDLAND LEAD MANUFACTURERS LTD S CAST LEAD SHEET
CI/SfB (49) Mh8 Midland Lead Manufacturers Ltd Kiln Way Woodville Swadlincote Derbyshire DE11 8ED Tel: 01283 224555 Fax: 01283 550284 e-mail: sales@midlandlead.co.uk website: www.midlandlead.co.uk Agrément
More informationFURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
More information(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
More informationSkirt 1 / 4. The Skirt. The skirt patterns were downloaded from Mark's site but they need expanding before they can be used.
Skirt 1 / 4 The Patterns The Skirt The skirt patterns were downloaded from Mark's site but they need expanding before they can be used. I used Corel Draw's real world dimensions to expand the patterns
More information1-085 Fire safety performance of materials
Transport for London London Underground Category 1 Standard 1-085 Fire safety performance of materials! Please read the Written Notices attached to this standard Issue: A3 MAYOR OF LONDON Contents 1 Purpose
More informationNATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA GB 12014-200x Replaces GB 12014 1989. Anti-static protective clothing
ICS 13.340.10 C 73 GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA GB 12014-200x Replaces GB 12014 1989 Anti-static protective clothing (Draft Submitted for Approval) Announced XX-XX-200X Effective
More informationGlobal Hybrid Roofing Solutions (Delaware) LLC
Global Hybrid Roofing Solutions (Delaware) LLC Product ing Summary Distributed by: BEST MATERIALS LLC Ph: 800-474-7570, 602-272-8128 Fax: 602-272-8014 Email: sales@bestmaterials.com www.bestmaterials.com
More informationINTERNATIONAL TECHNO 293 CLASS RULES
INTERNATIONAL TECHNO 293 CLASS RULES INDEX INTRODUCTION... 3 C.9 Sails...8 PART I ADMINISTRATION Section A General A.1 Language... 4 A.2 Abbreviations... 4 A.3 Authorities and Responsibilities4 A.4 ISAF
More informationFIRE SAFETY RISK ASSESSMENT
FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory
More informationHigh Visibility Clothing
GORT3279 Iss 7 on 07/12/2013 Railway Group Standard Date December 2013 High Visibility Clothing Synopsis This document sets out the minimum specification for high visibility clothing. Copyright in the
More informationCode of Practice for fire resisting metal doorsets
COP 1005 Code of Practice for fire resisting metal doorsets Scope The aim of this document is to provide guidance on the best practice for, and a better understanding of, hinged or pivoted fire resisting
More informationFloodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
More informationCI/SfB (31.5) Xn (U46) 07/05. A complete range of
CI/SfB (31.5) Xn (U46) 07/05 A complete range of Hygienic GRP Doors Applications: Pharmaceutical Facilities Food Industries Hospitals/Health Care Sector Retail Leisure Industry Manufacturing Education
More informationREACTION TO FIRE CLASSIFICATION REPORT No. RA11-0178 ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1
SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to fire REACTION TO FIRE CLASSIFICATION REPORT No. RA078 ACCORDING TO THE EUROPEAN STANDARD NF EN 350 Notification by the French Government to the European
More informationHIGHWAYS ASSET MANAGEMENT STRUCTURES TEAM GUIDANCE NOTE SMT/GN/03/10 TECHNICAL APPROVAL
HIGHWAYS ASSET MANAGEMENT STRUCTURES TEAM GUIDANCE NOTE SMT/GN/03/10 TECHNICAL APPROVAL Rev Purpose of Issue Originated Reviewed Authorised Date 0 First issue Anil Kumar Ken Duguid Stephen Pottle 21-07-2010
More informationPower chip resistor size 2512 PRC221 5%; 2% FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability.
FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability. APPLICATIONS Power supplies Printers Computers Battery chargers Automotive Converters CD-ROM. QUICK
More informationCaribeanCommunity EDICTOFGOVERNMENT±
CaribeanCommunity EDICTOFGOVERNMENT± Inordertopromotepubliceducationandpublicsafety,equaljustice foral,abeterinformedcitizenry,theruleoflaw,worldtradeand worldpeace,thislegaldocumentisherebymadeavailableona
More informationThe dangers of cellulose nitrate film
The dangers of cellulose nitrate film This leaflet is aimed at private individuals and voluntary groups who have or find old film in domestic or other non-workplace premises. It gives advice on: why cellulose
More informationHow To Build A Two Hour Firewall In Calgary
BUILDING CODE INTERPRETATION February 2008 06-BCI-005-R1 Page 1 of 6 TWO-HOUR FIREWALLS BACKGROUND Historically, firewalls used to subdivide buildings into smaller units have been built using one of two
More informationThis test may be carried out with the IGT printability testers A1-3, A2-3 and AIC2-5 with the accompanying inking unit AE.
This test may be carried out with the IGT printability testers A1-3, A2-3 and AIC2-5 with the accompanying inking unit AE. INTRODUCTION With absorption the speed is meant with which the ink penetrates
More informationDOCUMENT CAESAS/1: SCHEME DESCRIPTION AND BENEFITS
CONFORMITY ASSESSMENT FOR THE EXECUTION OF STEEL & ALUMINIUM STRUCTURES DOCUMENT CAESAS/1: SCHEME DESCRIPTION AND BENEFITS 2nd Edition July 2012 Issued under the authority of the Governing Board for Certification
More informationTechnical Regulations 2015-2016
F1 in Schools - 2014 World Finals Technical Regulations Technical Regulations 2015-2016 2013 - F1 in Schools Ltd. Page 1 of 27 3 September 2015 CONTENTS PREFACE SUMMARY OF MAIN REVISIONS FROM 2013 REGULATIONS...
More informationCERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
More informationUser Manual. Studio Rail. Size 60. www.doughty-engineering.co.uk. Version 11.0. www.doughty-engineering.co.uk
User Manual Studio Rail Size 60 Version 11.0 Contents Contents: Introduction... 2 Exclusion of Liability... 2 Safety Instructions... 2 Rail Loading Charts...3-4 Operating Data...5-10 1. Selecting the correct
More informationWATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
More informationF1 in Schools - 2015 World Finals Technical Regulations
2013 - F1 in Schools Ltd. Page 1 of 24 25 March 2015 Front Cover Colossus F1 2014 World Champions F1 Car, Robert May's School, Hampshire, England Amendments made on [Date] are indicated thus (using red
More informationBuilt-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
More informationConstruction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
More informationFire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
More informationM J Spearpoint & J N Smithies Fire Research Station, Building Research Establishment, Garston, Watford, WD6 7JR, UK
Reference: Spearpoint M J, Smithies J N. Practical comparison of domestic smoke alarm sensitivity standards. Proc. 11 th International Conference on Fire Detection, AUBE '99, pp. 576-587, Duisburg, Germany,
More informationFINAL DRAFT FprEN 13381-2
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM FINAL DRAFT FprEN 13381-2 April 2014 ICS 13.220.50 Will supersede ENV 13381-2:2002 English Version Test methods for determining the contribution to the
More informationUnderstanding BS EN 771-3: Aggregate concrete masonry units
60 Charles Street, Leicester LE1 1FB Tel: 0116 253 6161 Fax: 0116 251 4568 Email: enquiries@cba-blocks.org.uk Website: www.cba-blocks.org.uk February 2006 Understanding BS EN 771-3: Aggregate concrete
More informationSeawater corrosion resistant piping systems for large diameters up to 100 / 2.5 metres O.D.
OSNA -10 Copper-Nickel Lined Pipes Seawater corrosion resistant piping systems for large diameters up to 100 / 2.5 metres O.D. KME Germany AG & Co. KG Copper-Nickel Lined Pipes [GB] Member of the KME Group
More informationOffice of the State Fire Marshal. Fire Rated Doors
Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow
More informationEN 14904. Export Manager Pulastic Sports Surfaces The Netherlands www.descol.nl
Introduction by : Peter Minnée Export Manager Pulastic Sports Surfaces The Netherlands www.descol.nl Co-operation between European test institutes and standardization institutes formalized in 1961 Construction
More informationAPPLICATION FOR FACILITY HIRE
APPLICATION FOR FACILITY HIRE Facility: Date: Club/Organisation/Committee Responsible Person (Name): Address: Telephone: Driver s Licence No. I of hereby make application for the premises set out in the
More informationSection 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01
Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal
More informationTEST REPORT N 125543
centro ricerche-sviluppo Date received: 15-02-11 Date of issue: 14-03-11 33048 S. Giovanni al at. UD VIA CA' LEOCIO, 2 Report consists of 8 attached sheets. Defects before testing: one Sample name: DROP
More informationUPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
More informationRecommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems
Technical Bulletin Gas & Air Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems 1. Introduction Norit GL 50 is a powdered activated carbon widely used for the removal of
More informationOut - Ecrano / 002010 White Charcoal
Out - Ecrano / 002010 White Charcoal front: back: Widths 270 cm TECHNICAL SPECIFICATION STANDARD RESULT composition Glassfibre 42% - PVC 58% openness factor NBN EN 410 2.00% weight NF EN 12127 650.00g/m²
More informationInsulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW
Insulated Roof & Wall Panels Trapezoidal Insulated Roof Panels KS1000 RW Overview Kingspan roof panel systems present a superior system compared to conventional multi-part site assembled systems. They
More informationDA / hpypkong Page 1 Of 5
REPORT NUMBER: 天 祥 集 团 中 国 广 州 经 济 开 发 区 开 发 大 道 235 号 恒 运 大 厦 3 楼 (510730) 3/F.,Hengyun Building,235 Kaifa Ave.,Guangzhou Economic & Technological Development District,Guangzhou,P.R.C.(510730) Tel:(8620)8396
More informationSOLDERING PROCEDURE SPECIFICATIONS PROCEDURE QUALIFICATION RECORDS. and SOLDERER PERFORMANCE QUALIFICATION RECORDS
SOLDERING PROCEDURE SPECIFICATIONS PROCEDURE QUALIFICATION RECORDS and SOLDERER PERFORMANCE QUALIFICATION RECORDS COPPER DEVELOPMENT ASSOCIATION INC. 260 Madison Avenue New York, NY 10016 (212) 251-7200
More informationSAFETY FENCES, SAFETY BARRIERS AND PEDESTRIAN GUARDRAILS
SERIES NG 400 SAFETY FENCES, SAFETY BARRIERS AND PEDESTRIAN GUARDRAILS Contents Clause Title Page NG 401 Performance Criteria for Safety Fences and Safety Barriers 2 NG 402 Components for Safety Fences
More informationHome Product Testing
Intertek s global reach is our major strength linking suppliers in one part of the world with buyers in another. We independently inspect factories and goods in the countries of origin across the whole
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1181: PART 1: ISSUE 1.1 Series of Fire Growth Tests for LPCB Approval and Listing of Construction Product Systems Part One: Requirements and Tests for Built-up Cladding and
More informationINTERNATIONAL HOCKEY FEDERATION PERFORMANCE REQUIREMENTS AND TEST PROCEDURES FOR HOCKEY BALLS. Published: April 1999
INTERNATIONAL HOCKEY FEDERATION PERFORMANCE REQUIREMENTS AND TEST PROCEDURES FOR HOCKEY BALLS Published: April 1999 CONTENTS 1 Introduction 2 Test Procedures General 3 Standards and Specific Test Procedures
More informationICH Topic Q4B Annex 5 Disintegration Test General Chapter. Step 3
European Medicines Agency June 2008 EMEA/CHMP/ICH/308895/2008 ICH Topic Q4B Annex 5 Disintegration Test General Chapter Step 3 ANNEX 5 TO NOTE FOR EVALUATION AND RECOMMENDATION OF PHARMACOPOEIAL TEXTS
More informationEXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
More informationGuidance on the use of Marquees, Tents and other Temporary Structures
Guidance on the use of arquees, Tents and other Temporary Structures Guidance on the use of arquees, Tents and other Temporary Structures arquees, tents or temporary structures (s) are often leased or
More informationThe dangers of cellulose nitrate film
The dangers of cellulose nitrate film This leaflet is aimed at private individuals and voluntary groups who have or find old film in domestic or other non-workplace premises. It gives advice on: how to
More informationCompliant Terminal Technology Summary Test Report
Engineering Report ER04100 October 5th, 2004 Revision A Copyright Autosplice Inc., September 2004 Table of Contents Summary Overview 3 Compliant Terminal Specifications 3 Test Plan 4 Test Conditions 4
More informationImproving fire safety through engineering (rational designs)
Improving fire safety through engineering (rational designs) Johan van den Heever Fire Safety Indaba, Cape Town 2013 'Promoting responsible fire safety in Southern Africa' 1 Introduction What is fire safety
More informationIntertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17. Report issued by: S64604 Issue 1
Intertek Research & Performance Testing Technical Report S64604 Issue 1 Page 1 of 17 TECHNICAL REPORT Client: Stephen Curtler Electrical Safety Council 18 Buckingham Gate London SW1E 6LB Report issued
More informationIntroduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)
1 Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS) Introduction The new harmonised system for the classification of reaction to fire in EU member states is using the SBI test
More informationEUROPEAN STANDARDS AND MARKINGS FOR HAND AND ARM PROTECTION
APPENDIX 5 EUROPEAN STANDARDS AND MARKINGS FOR HAND AND ARM PROTECTION ISSUE 8: January 2013 This information is extracted from British Standards with the permission of BSI under licence number PD\1998
More informationFire Resistant Systems
Fire Resistant Systems A R C H I T E C T U R A L A L U M I N I U M G L A Z I N G S Y S T E M S Fire Resistant Systems Introduction Kawneer are pleased to introduce two new comprehensive Fire Resistant
More informationFlammability testing is arguably one of the most important testing procedures within the textile industry
Flammability testing is arguably one of the most important testing procedures within the textile industry because it has crucial safety implications in the event of a fire. It has been statistically shown
More informationTECHNICAL BULLETIN 117-2013
State of California Department of Consumer Affairs BUREAU OF ELECTRONIC & APPLIANCE REPAIR HOME FURNISHINGS & THERMAL INSULATION 4244 SOUTH MARKET COURT, SUITE D SACRAMENTO, CA 95834-1243 TECHNICAL BULLETIN
More informationAppendix B. Property Owner Questionnaire
Appendix B Property Owner Questionnaire WEST WINDSOR TOWNSHIP DEPARTMENT OF COMMUNITY DEVELOPMENT PROPERTY QUESTIONNAIRE DIVISION OF ENGINEERING As someone who owns and lives and/or works on a property
More informationC1.2 CONTRACT DATA PROVIDED BY EMPLOYER (ECC3)
C1.2 CONTRACT DATA PROVIDED BY EMPLOYER (ECC3) The conditions of contract are the NEC3 Engineering and Construction Contract (June 2005), copies of which may be obtained from the South African Institution
More informationDiscipline: Structural Issued 04-26-06
California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This
More informationF1 in Schools - 2014 World Finals Technical Regulations. 2014 WORLD FINALS Technical Regulations
2014 WORLD FINALS Technical Regulations Refer also to the 2014 World Finals Competition Regulations. For World Finals use only. 2013 - F1 in Schools Ltd. Page 1 of 23 13 August 2014 Front Cover A1 Racing
More informationFire Preventive and Fireproof Performance Test and Evaluation Procedure Manual
BR BO-01-02 Effective from June 1, 2000 Revision: March 26, 2002 Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual (Unofficial Manual) Technical Appraisal Department, Building
More informationW1T 1HQ mark.waples@royalmail.com Copied for information to: Nigel Woods & Cem Suleyman Consumer Focus 4 th floor, Artillery House Artillery Row
29 th October 2010 Philip Groves Postcomm Hercules House 6 Hercules Road LONDON SE1 7DB Mark Waples 1 st Floor Royal Mail Letters Centre 35-50 Rathbone Place LONDON W1T 1HQ mark.waples@royalmail.com Copied
More informationFLAMMABILITY REQUIREMENTS FOR 25.853-1 AIRCRAFT SEAT CUSHIONS
FLAMMABILITY REQUIREMENTS FOR 25.853-1 AIRCRAFT SEAT CUSHIONS ANM-110 1. PURPOSE. This Advisory Circular (AC) provides guidance material for demonstrating compliance with the Federal Aviation Regulations
More information