Absorption. LG HVAC Solution.

Size: px
Start display at page:

Download "Absorption. LG HVAC Solution. www.lgeaircon.com"

Transcription

1 Ver. 1.0 LG HVAC Solution Absorption chiller LG Electronics, Air Conditioning & Energy Solution Company 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355 Seoul , Korea For continual product development, LG reserves the right to change specifications or designs without notice LG Electronics. Printed in Korea. May Distributed by

2 Nomenclature W: Water Chiller heater DH: Direct-fired double-effect H series DN: Direct-fired double-effect N series DS: Direct-fired double-effect S series DA: Direct-fired double-effect A series Chiller MW: - single-effect W series 2T: Double-lift, low-temperature, hot-, single-effect T series SS: Steam-fired double-effect S series Water working pressure: C: : 5kgf/cm 2 G : 5kgf/cm 2 G G: : 8kgf/cm 2 G : 8kgf/cm 2 G K: : 10kgf/cm 2 G : 10kgf/cm 2 G N: : 12kgf/cm 2 G : 12kgf/cm 2 G R: : 16kgf/cm 2 G : 16kgf/cm 2 G U: : 20kgf/cm 2 G : 20kgf/cm 2 G W c DH 024 S K 6 1 Features / Benefits LG has over 40 years of experience developing and building top-quality air conditioning solutions. With more than 13,000 Absorption Chillers sold, in overseas market, the company leads the industry in advanced user interface design and product reliability. World-class 1.51 COP C: Chiller Line up Nominal ton: 10RT RT RT 100 S: Standard A: 1 step-up heating capacity B: 2 step-up heating capacity C: 3 step-up heating capacity R: Other type 6: Leaving hot temperature 60 C 8: Leaving hot temperature 80 C N: Chiller Develop -ment sequence Direct fired absorption chiller heater Efficiency Highly efficient heat transfer tube The newly designed high performance tube enables a 29 percent increase in heat transfer rate and an improved LiBr concentration range at low temperatures. The special absorber also reduces heat loss at higher temperature settings. High performance heat exchanger Via plate-type heat exchanger, LG s chiller achieved 20 percent improved performance level of efficiency across its entire operation range in comparison with conventional unit. Model ,000 1,500 3,000 WCDH (H Series) WCDN (N Series) WCDS (S Series) WCDA (A Series) 50~80RT 100RT 1,500RT 3,000RT 100RT 700RT 3,000RT 100RT 1,500RT 3,000RT Absorption chiller PID (Proportional, Integral, Differential) control logic Through the ability to control cooling outlets and combustion simultaneously, LG s Absorption Chiller is able to reach the desired temperature in a minimal amount of time. It also minimizes temperature fluctuations, creating more operational stability and lowering energy consumption. World leading efficiency Resolving the double-effect, LG s Absorption Chiller boasts a COP ratio of COP 1.12 COP 1.51 Model ,000 1,500 4,000 WCSS 100RT 1,500RT 4,000RT 0.5 WCMW 30RT 1,020RT 3,000RT 0 WCDS032 WCDH032 WC2T 80RT 980RT 2,250RT * Available on request LG HVAC Solution 3

3 Features / Benefits Efficiency Reliability High part-load efficiency (Max. COP: 1.60) With HVAC solutions operating at less than full capacity the majority of the time, efficiency in part-load is essential. LG s absorption chiller achieves energy savings and increased part-load efficiency via an advanced absorbent pump featuring state-of-the-art inverter control. The optimized system also decreases capacity in accordance with the volume of absorbent in circulation. Fuel consumption ratio (%) COP Fuel consumpion (Standard H series) High performance purge system with strong vacuum hold structure Each heat exchanger piping connection has been simplified and strengthened in order to maintain an optimal vacuum state, thereby minimizing potential leakage points. Self-diagnosis / Maintenance-notice alarm The microprocessor also has a self-diagnosis function, capable of alerting system managers to any potential issue; preventing inefficient operation and averting inconvenient breakdown. Operational conditions - outlet maintains temperature at a steady 7 degrees Celsius inlet capacity (%) inlet (ºC ) 100% 75% 50% 25% 32ºC 30.75ºC 29.5ºC 28.25ºC (%) Automatic anti-crystallization safety operation Intelligent system prevents the crystallization of absorbent through a safety-control logic algorithm. LG s LiBr- solution function enables uninterrupted system monitoring, resulting in the following benefits: Absorbent Concentration control Low temperator Generator Condenser temperature Input-energy control Less than 30 Min. Process during Power failure Power failure Automatic dilution operation Automatic restart Operation cost savings Up to 27% savings on operational costs annually (in comparison with a conventional 320RT chiller - based on South Korean gas tariff standards). Reduced CO2 emissions CO2 emissions can be reduced by up to 44 tons annually (in comparison with a conventional 320RT chiller). The LiBr- solution s concentration level is maintained at an optimum level, thereby preventing crystallization. The chiller uses sensors to detect the status of absorbent and controls temperature distribution by adjusting combustion levels. Pressure (mmhg) Concentration 24% 34% 44% 54% 64% Maintain 54~64% LiBr crystallization curve Less than 1 hour More than 1 hour Automatic dilution operation Manual restart Manual dilution operation Manual restart % % 27% Saving 73% Ton % Reducing Temperature (ºC) Conventional (WCDS032) New (WCDH032) 0 Conventional (WCDS032) New (WCDH032) LG HVAC Solution 5

4 Features / Benefits Convenience Convenient maintenance Operational management function State-of-the-art controller A high quality 7-inch display and a variety of communication ports make system operation and maintenance far more convenient. 7-inch color LCD screen with high resolution (800 x 480) Operation scheduling function Real time trend display Automatic anti-crystallization Advanced algorithm for highly effective temperature and safety control Running acquisition Graphic display of operational Certified EMC Communication supported: RS485 (standard) and Ethernet (optional) Communication protocol supported: Modbus (standard), BACnet Direct control of pumps and cooling tower Language: English / Chinese / Korean Auto-printing function (optional) Installation flexibility and ease of transport. The three-section design and smaller size of the product enhances convenience. LG s absorption chiller offers better performance than parallel-flow models as it absorbs a smaller amount of liquid. User-friendly positioning of valves and instruments results in more convenient operation and maintenance. Various interface solutions The onboard microprocessor boasts an impressive memory, enabling the chiller to store 20-years worth of operational settings, 301 error reports, and temperature from the last 10.6 days. This wealth of accumulated information is employed by LG s Absorption Chiller to guarantee efficient performance. Using industrial standard protocol converters, the chiller can be interfaced with the BMS (Building Management System). The reomote monitoring and control of the chillers is possible via BACnet/Eternet, BACnet/IP, Modbus, Modem or RS485. TCP/IP RS485 Multi-Drop 7 Color LCD with high resolution Real time operation status Time schedule Serial to LAN Converter RS485 Converter Procontrol Converter Connecting to max 8 units Evaporator & absorber Low temperature generator High temperature generator The chillers can be managed up to 255 units when using communication of RS485 or TCP/IP LG HVAC Solution 7

5 Direct fired absorption chiller heater (H series COP 1.51) Direct fired absorption chiller heater (H series COP 1.51) Model name (WCDH) 010S 012S 015S 018S 021S 024S 028S 032S 036S 040S 045S 050S Model name (WCDH) 056S 063S 070S 080S 090S 100S 110S 120S 130S 140S 150S RT kw ,125 1,266 1,407 1,582 1,758 RT ,000 1,100 1,200 1,300 1,400 1,500 kw 1,969 2,215 2,461 2,813 3,165 3,516 3,868 4,220 4,571 4,923 5,274 Heating capacity kcal/h 253, , , , , , , , , ,800 1,012,000 1,138,500 kw ,059 1,177 1,324 Heating capacity kcal/h 1,265,000 1,416,800 1,593,900 1,771,000 2,024,000 2,277,000 2,530,000 2,783,000 3,036,000 3,289,000 3,542,000 kw 1,471 1,647 1,853 2,059 2,353 2,648 2,942 3,236 3,530 3,824 4,119 Water flow rate m 3 /h Water flow rate m 3 /h Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Water flow rate m 3 /h Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Water flow rate m 3 /h ,000 1,100 1,200 1,300 1,400 1,500 Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Fuel A(mm) 40 (at 4,000mmAq) 50 (at 4,000mmAq) Nozzle size B(inch) 1 1/2 (at 4,000mmAq) 2 (at 4,000mmAq) Fuel (Gas) A(mm) 50 (at 4,000mmAq) 65 (at 4,000mmAq) Nozzle size B(inch) 2 (at 4,000mmAq) 2 1/2 (at 4,000mmAq) (Gas) Nm 3 /h Nm 3 /h Heating Nm 3 /h Heating Nm 3 /h Total current A Total current A Wire size mm Wire size mm Power kva Absorbent pump no.1 kw(a) 1.5(5.43) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) Absorbent pump no.2 kw(a) 0.4(1.8) 0.4(1.8) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.5(5.5) 1.5(5.5) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2) Power kva Absorbent pump no.1 kw(a) 6.6(16.2) 6.6(16.2) 6.6(16.2) 5.5(20.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) Absorbent pump no.2 kw(a) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) Refrigerant pump kw(a) 0.2(1.1) Refrigerant pump kw(a) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) Burner blower (gas) kw(a) 0.72(2.1) 1.5(3.3) 1.5(3.3) 1.5(3.3) 2.2(4.7) 2.2(4.7) 2.2(4.7) 3.0(7.7) 5.5(10.6) 5.5(10.6) 5.5(10.6) 5.5(10.6) Burner blower (gas) kw(a) 5.5(10.6) 7.5(14.0) 7.5(14.0) 7.5(14.0) 7.5(14.0) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5) 11.0(20.5) Length mm 2,840 2,840 3,860 3,860 3,860 3,860 4,880 4,880 4,900 4,900 4,900 4,900 Length mm 4,940 5,480 5,940 5,740 6,240 6,760 6,170 6,690 7,190 6,850 7,350 Width mm 1,940 2,010 2,015 2,110 2,250 2,250 2,235 2,335 2,480 2,646 2,720 3,080 Width mm 3,280 3,280 3,570 3,670 3,670 3,670 4,340 4,340 4,340 4,750 4,750 Height mm 2,120 2,120 2,120 2,120 2,380 2,380 2,380 2,380 2,725 2,725 2,895 2,895 Height mm 3,360 3,360 3,360 3,800 3,800 3,800 3,900 3,900 3,900 4,000 4,000 Operating ton Total shipping ton Operating ton Total shipping ton Flue connection size mm 340x x x x x x x x x x x x550 Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500 Flue connection size mm 650x x x x x x x x x x x400 Clearance for tube removal mm 4,500 5,200 5,700 5,200 5,700 6,200 5,700 6,200 6,700 6,200 6, Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office. 2. Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9,360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office LG HVAC Solution 9

6 Direct fired absorption chiller heater (N series COP 1.34) Direct fired absorption chiller heater (N series COP 1.34) Model name (WCDN) 010S 012S 015S 018S 021S 024S 028S 032S Model name (WCDN) 036S 040S 045S 050S 056S 063S 070S RT kw ,125 RT kw 1,266 1,407 1,583 1,758 1,969 2,216 2,462 Heating capacity kcal/h 253, , , , , , , ,600 kw Heating capacity kcal/h 910,800 1,012,000 1,138,500 1,265,000 1,416,800 1,593,900 1,771,000 kw 1,059 1,177 1,324 1,471 1,647 1,853 2,059 Water flow rate m 3 /h Water flow rate m 3 /h Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Water flow rate m 3 /h Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Water flow rate m 3 /h Pressure drop maq Pressure drop maq A(mm) B(inch) A(mm) B(inch) Fuel Nozzle size A(mm) B(inch) 40 (at 4,000mmAq) 1 1/2 (at 4,000mmAq) Fuel Nozzle size A(mm) 40 (at 4,000mmAq) 50 (at 4,000mmAq) B(inch) 1 1/2 (at 4,000mmAq) 2 (at 4,000mmAq) (Gas) Nm 3 /h (Gas) Nm 3 /h Heating Nm 3 /h Heating Nm 3 /h Total current A Total current A Wire size mm Wire size mm Power kva Absorbent pump no.1 kw(a) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) Absorbent pump no.2 kw(a) 0.4(1.8) 0.4(1.8) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.2(4.0) 1.5(5.5) 1.5(5.5) Power kva Absorbent pump no.1 kw(a) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 6.6(16.2) 6.6(16.2) 6.6(16.2) Absorbent pump no.2 kw(a) 1.5(5.5) 1.5(5.5) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) Refrigerant pump kw(a) 0.4(1.4) Burner blower (Gas) kw(a) 0.72(2.1) 0.72(2.1) 0.72(2.1) 1.1(4.0) 1.5(4.0) 1.5(4.0) 1.8(4.4) 2.2(5.0) Burner blower (Gas) kw(a) 2.2(5.0) 3.0(6.5) 3.0(6.5) 3.0(6.5) 5.5(13.0) 5.5(13.0) 5.5(13.0) Length mm 2,870 3,070 3,740 3,740 3,770 3,845 4,790 4,790 Length mm 4,915 4,915 4,915 4,915 4,975 5,520 6,015 Width mm 1,910 1,910 2,015 2,015 2,200 2,200 2,235 2,235 Width mm 2,480 2,480 2,720 2,720 3,280 3,280 3,280 Height mm 2,130 2,130 2,130 2,130 2,280 2,280 2,280 2,280 Height mm 2,535 2,535 2,790 2,790 3,240 3,240 3,240 Operating Ton Total shipping Ton Operating Ton Total shipping Ton Flue connection size mm 280x x x x x x x x310 Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 Flue connection size mm 360x x x x x x x350 Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,600 5,200 5, Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9,360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office. 2. Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9,360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office LG HVAC Solution 11

7 Direct fired absorption chiller heater (S series COP 1.12) Direct fired absorption chiller heater (S series COP 1.12) Model name (WCDS) 010S 12S 015S 018S 021S 024S 028S 032S 036S 040S 045S 050S RT kw Model name (WCDS) 056S 063S 070S 080S 090S 100S 110S 120S 130S 140S 150S RT ,000 1,100 1,200 1,300 1,400 1,500 kw 1,969 2,216 2,462 2,813 3,165 3,517 3,869 4,220 4,572 4,924 5,275 Heating capacity kcal/h 253, , , , , , , , ,800 1,012,000 1,138,500 1,265,000 kw Heating capacity kcal/h 1,416,800 1,593,900 1,771,000 2,024,000 2,277,000 2,530,000 2,783,000 3,036,000 3,289,000 3,542,000 3,795,000 kw 1,647 1,852 2,058 2,352 2,646 2,940 3,234 3,529 3,823 4,117 4,411 Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h ,000 1,100 1,200 1,300 1,400 1,500 Pressure drop maq A(mm) B(inch) Fuel (gas) Nm 3 /h Heating Nm 3 /h Fuel (gas) Nm 3 /h Heating Nm 3 /h Total current A Total current A Wire size mm Wire size mm Power kva Absorbent pump no.1 kw(a) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.7(12.0) 3.7(12.0) Absorbent pump no.2 kw(a) n/a Power kva Absorbent pump no.1 kw(a) 6.6(16.2) 6.6(16.2) 6.6(16.2) 5.5(20.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) Absorbent pump no.2 kw(a) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) Refrigerant pump kw(a) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) 0.75(2.5) Burner blower (gas) kw(a) 0.72(2.1) 0.72(2.1) 0.72(2.1) 1.1(4.0) 1.5(4.0) 1.5(4.0) 1.8(4.4) 2.2(5.0) 2.2(5.0) 3.0(6.5) 3.0(6.5) 3.0(6.5) Burner blower (gas) kw(a) 5.5(13.0) 5.5(13.0) 5.5(13.0) 7.5(15.8) 7.5(15.8) 7.5(15.8) 11.0(22.7) 11.0(22.7) 11.0(22.7) 11.0(22.7) 11.0(22.7) Length mm ,720 3,740 3,740 4,780 4,780 4,890 4,890 4,870 4,870 Length mm 5,060 5,600 6,100 5,740 6,240 6,760 6,170 6,690 7,190 6,850 7,350 Width mm 1,990 1,990 1,990 2,010 2,190 2,210 2,170 2,170 2,310 2,350 2,570 2,570 Width mm 3,080 3,080 3,080 3,400 3,400 3,400 4,180 4,180 4,180 4,590 4,590 Height mm 2,030 2,030 2,030 2,030 2,300 2,300 2,300 2,300 2,540 2,540 2,765 2,765 Height mm 3,066 3,066 3,066 3,600 3,600 3,600 3,600 3,600 3,600 3,800 3,800 Operating ton Total shipping ton Operating ton Total shipping ton Flue connection size mm 280x x x x x x x x x x x x310 Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500 Flue connection size mm 500x x x x x x x x x x x400 Clearance for tube removal mm 4,600 5,200 5,700 5,200 5,700 6,200 5,700 6,200 6,700 6,200 6, Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9,360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office. 2. Standard side pressure (chilled & hot & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard gas pressure: 4,000mmAq 4. Standard gas low calorific value: 9,360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40ºC ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office LG HVAC Solution 13

8 Direct fired absorption chiller heater (A series COP 1.06) Model name (WCDA) RT kw Steam fired absorption chiller Model name (WCSS) RT kw ,125 1,266 1,407 1,582 1,758 sata 103kcal/h Heating capacity kw Water flow rate m 3 /h Pressure drop maq A(mm) 80 B(inch) 3 Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) 80 B(inch) 3 Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Total current A Temperature ºC Wire size mm 2 4 Water flow rate m 3 /h Pressure drop maq A(mm) 100 B(inch) 4 Power kva Absorbent pump no.1 kw(a) 1.5(5.43) 1.5(5.43) 2.4(6.4) 2.4(6.4) 2.4(6.4) 2.4(6.4) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.4(10.3) 3.7(12.0) 3.7(12.0) Absorbent pump no.2 kw(a) n/a Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) Fuel (gas) Nm 3 /h Heating Nm 3 /h (1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) Length mm 2,650 2,650 3,670 3,670 3,730 3,730 4,750 4,750 4,850 4,850 4,850 4,850 Width mm 1,775 1,775 1,775 1,775 1,880 1,880 1,880 1,880 2,110 2,110 2,250 2,250 Absorbent pump kw(a) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) Height mm 2,030 2,030 2,030 2,030 2,300 2,300 2,300 2,300 2,550 2,550 2,780 2,780 Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.45) 0.4(1.45) 0.4(1.45) Burner blower (gas) kw(a) 0.37(1.0) 0.37(1.0) 0.74(2.3) 0.74(2.3) Control kw(a) 0.3(0.5) Total current A Operating ton Total shipping ton Steam flow rate kg/h ,060 1,230 1,410 1,580 1,760 1,980 2,200 Steam inlet A(mm) B(inch) /2 2 1/2 2 1/2 2 1/ Wire size mm 2 4 Power kva Fuel Drain outlet A(mm) B(inch) /2 1 1/2 1 1/2 1 1/2 Length mm 1,976 1,976 2,480 2,480 Width mm 1,875 1,875 1,875 1,875 Steam control valve A(mm) B(inch) 1 1 1/2 1 1/2 1 1/2 1 1/2 1 1/ /2 2 1/2 Height mm 1,852 1,852 1,852 1,852 Operating ton Total shipping ton Flue connection size mm 190x x x x150 Clearance for tube removal mm 1,700 1,700 2,200 2,200 Note: 1.1RT = 3,024kcal/h, 1kW = 860kcal/h 2. Standard side pressure (chilled & hot & cooling ): 5kgf/cm 2 G (490kPa) 3. Standard gas pressure: 200mmAq 4. Standard gas low calorific value: 9360kcal/Nm 3 5. The currents and electricity consumptions are based on 3Ph/380V/50Hz (60Hz). 6. The power supply wire size is based on the metal conduit and on 40 C ambient temperature. 7. Due to our policy of innovation some specifications may be changed without notification. 8. For information other than those in the above table, contact the nearest LG Electronics office. Clearance for tube removal mm 2,400 2,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4, Standard side pressure (chilled & cooling ): 8kgf/cm 2 G (785kPa) 3. Standard steam pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 15

9 Steam fired absorption chiller Model name (WCSS) RT ,000 1,100 1,120 1,300 1,400 1,500 kw 1,969 2,215 2,461 2,813 3,165 3,516 3,868 3,938 4,571 4,923 5,274 fired absorption chiller Model name (WCMW) RT kw Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/ Temperature ºC Water flow rate m 3 /h ,000 1,100 1,200 1,300 1,400 1,500 Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Total current A Water flow rate ton/h Wire size mm Power kva Absorbent pump no.1 kw(a) 6.6(16.2) 6.6(16.2) 6.6(16.2) 6.6(16.2) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) 7.5(25.0) Pressure drop maq A(mm) B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 Absorbent pump no.2 kw(a) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) 5.5(21.0) Refrigerant pump kw(a) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) of A(mm) B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/ /2 2 1/2 2 1/2 2 1/2 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.2) 0.75(2.2) 0.75(2.2) 0.75(2.2) 0.75(2.2) Length mm 5,060 5,600 6,100 5,710 6,210 6,730 6,170 6,690 7,180 6,830 7,330 Total current A Width mm 2,480 2,480 2,480 2,825 2,825 2,825 3,000 3,000 3,000 3,250 3,250 Wire size mm 2 4 Height mm 3,000 3,000 3,000 3,400 3,400 3,400 3,600 3,600 3,600 3,650 3,650 Operating ton Total shipping ton Power kva Absorbent pump no.1 kw(a) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 1.2(4.1) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) Absorbent pump no.2 kw(a) n/a Steam flow rate kg/h 2,470 2,780 3,080 3,520 3,960 4,400 4,840 5,280 5,720 6,160 6,600 Refrigerant pump kw(a) 0.2(1.1) Steam inlet A(mm) B(inch) Length mm 2,020 2,020 2,020 2,020 2,520 2,520 2,547 2,547 2,547 2,547 3,567 3,567 Fuel Drain outlet A(mm) B(inch) /2 2 1/2 2 1/ Width mm 1,394 1,394 1,396 1,396 1,396 1,396 1,355 1,355 1,355 1,355 1,355 1,355 Height mm 1,952 1,952 1,965 1,965 1,965 1,965 2,150 2,150 2,150 2,150 2,150 2,150 Steam control valve A(mm) B(inch) 2 1/2 2 1/ Operating ton Total shipping ton Clearance for tube removal mm 4,600 5,200 5,700 5,200 5,700 6,200 5,800 6,300 6,800 6,300 6,800 Clearance for tube removal mm 2,000 2,000 2,000 2,000 2,400 2,400 2,400 2,400 2, ,400 3, Standard side pressure (chilled & cooling ): 8kgf/cm 2 G (785kPa) 3. Standard steam pressure: 8kgf/cm 2 G (785kPa) 2. Standard side pressure (chilled & cooling ): 8kgf/cm 2 G (785kPa, RT), 5kgf/cm 2 G (490kPa, 30-50RT) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 17

10 fired absorption chiller Model name (WCMW) RT kw Temperature ºC fired absorption chiller Model name (WCMW) RT kw ,027 1,090 1,125 1,196 1,259 1,336 1,424 1,512 1,589 1,688 Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate ton/h Water flow rate ton/h Pressure drop maq A(mm) B(inch) Pressure drop maq A(mm) B(inch) of A(mm) B(inch) of A(mm) B(inch) Total current A Total current A Wire size mm 2 4 Wire size mm Power kva Absorbent pump no.1 kw(a) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) Power kva Absorbent pump no.1 kw(a) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 2.2(5.5) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) Absorbent pump no.2 kw(a) n/a Absorbent pump no.2 kw(a) n/a n/a n/a n/a n/a n/a 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.0(5.2) 2.2(6.7) 2.2(6.7) Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) Refrigerant pump kw(a) 0.4(1.4) Length mm 3,567 3,567 3,627 3,627 3,627 3,627 4,630 4,630 4,630 4,630 4,784 4,784 Length mm 4,784 4,784 4,789 4,789 4,789 4,789 4,931 4,931 5,473 5,473 5,971 5,971 Width mm 1,355 1,355 1,526 1,526 1,526 1,526 1,526 1,526 1,526 1,526 1,575 1,575 Width mm 1,575 1,575 1,702 1,702 1,702 1,702 2,015 2,015 2,015 2,015 2,015 2,015 Height mm 2,150 2,150 2,330 2,330 2,330 2,330 2,330 2,330 2,330 2,330 2,630 2,630 Height mm 2,630 2,630 2,886 2,886 2,886 2,886 3,260 3,260 3,260 3,260 3,260 3,260 Operating ton Total shipping ton Operating ton Total shipping ton Clearance for tube removal mm 3,400 3,400 3,400 3,400 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500 Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,500 4,500 4,600 4,600 5,200 5,200 5,700 5, Standard side pressure (chilled & cooling ): 8kgf/cm 2 G (785kPa, RT), 5kgf/cm 2 G (490kPa, 30-50RT) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) 2. Standard side pressure (chilled & cooling ): 8kgf/cm 2 G (785kPa, RT), 5kgf/cm 2 G (490kPa, 30-50RT) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 19

11 fired absorption chiller Model name (WCMW) RT kw 1,790 1,899 1,987 2,110 2,219 2,356 2,451 2,602 Temperature ºC fired absorption chiller Model name (WCMW) RT ,020 kw 2,683 2,848 2,915 3,094 3,147 3,340 3,379 3,587 Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) 400 B(inch) 16 Temperature ºC Temperature ºC Water flow rate ton/h Water flow rate ton/h Pressure drop maq A(mm) B(inch) Pressure drop maq A(mm) 200 B(inch) 8 of A(mm) B(inch) of A(mm) 200 B(inch) 8 Total current A Total current A 44.2 Wire size mm Wire size mm 2 16 Power kva Absorbent pump no.1 kw(a) 3.0(11.0) 3.0(11.0) 3.0(11.0) 3.0(11.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) 4.5(16.0) Power kva 29.1 Absorbent pump no.1 kw(a) 4.5(16.0) Absorbent pump no.2 kw(a) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7) 2.2(6.7) 5.5(21.0) 5.5(21.0) Absorbent pump no.2 kw(a) 5.5(21.0) Refrigerant pump kw(a) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) Refrigerant pump kw(a) 1.5(3.9) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.5) 0.75(2.5) Purge pump kw(a) 0.75(2.5) Length mm 5,616 5,616 6, ,346 6,346 Length mm 6,871 6,871 7,371 7,371 7,070 7,070 7,570 7,570 Width mm 2,195 2,195 2,195 2,195 2,195 2,195 2,680 2,680 Width mm 2,680 2,680 2,680 2,680 2,910 2,910 2,910 2,910 Height mm 3,680 3,680 3,680 3,680 3,680 3,680 3,920 3,920 Height mm 3,920 3,920 3,920 3,920 4,040 4,040 4,040 4,040 Operating ton Total shipping ton Operating ton Total shipping ton Clearance for tube removal mm 5,200 5,200 5,700 5,700 6,200 6,200 5,800 5,800 Clearance for tube removal mm 6,300 6,300 6,800 6,800 6,300 6,300 6,800 6, Standard side pressure (chilled & cooling ): 8 kgf/cm 2 G (785kPa, 70-1,020 RT), 5kgf/cm 2 G (490kPa, 30-50RT) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) 2. Standard side pressure (chilled & cooling ): 8 kgf/cm 2 G (785kPa, 70-1,020 RT), 5kgf/cm 2 G (490kPa, 30-50RT) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 21

12 fired absorption chiller Model name (WC2T) RT kw Temperature ºC fired absorption chiller Model name (WC2T) RT kw ,030 1,054 Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate ton/h Water flow rate ton/h Pressure drop maq Pressure drop maq Pressure drop maq A(mm) B(inch) 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 3 3 Pressure drop maq A(mm) B(inch) of A(mm) B(inch) 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/ of A(mm) B(inch) /2 2 1/ /2 2 1/2 3 3 Total current A Total current A Wire size mm 2 4 Wire size mm Power kva Absorbent pump no.1 kw(a) 2.8(6.3) 2.8(6.3) 2.8(6.3) 2.8(6.3) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) 3.7(9.6) Power kva Absorbent pump no.1 kw(a) 3.7(9.6) 3.7(9.6) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) 5.4(17.4) Absorbent pump no.2 kw(a) 0.6(2.4) 0.6(2.4) 0.6(2.4) 0.6(2.4) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) 0.8(2.8) Absorbent pump no.2 kw(a) 0.8(2.8) 0.8(2.8) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) 0.8(3.2) Refrigerant pump kw(a) 0.2(1.1) Refrigerant pump kw(a) 0.2(1.1) 0.2(1.1) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) Length mm 2,600 2,600 2,600 2,600 3,650 3,650 3,650 3,650 3,712 3,712 Length mm ,850 Width mm 1,900 1,900 1,900 1,900 1,900 1,900 1,900 1,900 2,265 2,265 Width mm ,380 Height mm 2,260 2,260 2,260 2,260 2,260 2,260 2,260 2,260 2,290 2,290 Height mm ,540 Operating ton Total shipping ton Operating ton Total shipping ton Clearance for tube removal mm 2,400 2,400 2,400 2,400 3,400 3,400 3,400 3,400 3,400 3,400 Clearance for tube removal mm 3,400 3,400 4,500 4,500 4,500 4,500 4,500 4,500 4,500 4, Standard side pressure (chilled & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) 2. Standard side pressure (chilled & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 23

13 fired absorption chiller Model name (WC2T) RT kw 1,167 1,195 1,288 1,318 1,442 1,476 1,614 1,652 1,803 1,845 Temperature ºC fired absorption chiller Model name (WC2T) RT kw 2,060 2,109 2,318 2,372 2,573 2,636 2,833 2,900 3,090 3,163 3,344 3,427 Temperature ºC Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h Pressure drop maq A(mm) B(inch) Water flow rate m 3 /h ,048 1, , , , , ,363 1,383 Pressure drop maq A(mm) B(inch) Temperature ºC Temperature ºC Water flow rate ton/h Water flow rate ton/h Pressure drop maq Pressure drop maq Pressure drop maq A(mm) B(inch) Pressure drop maq A(mm) 125 B(inch) 5 of A(mm) B(inch) of A(mm) B(inch) Total current A Total current A Wire size mm Wire size mm Power kva Absorbent pump no.1 kw(a) 6.4(19.0) 6.4(19.0) 6.4(19.0) 6.4(19.0) 6.7(20.0) 6.7(20.0) 6.7(20.0) 6.7(20.0) 8.7(27.0) 8.7(27.0) Power kva Absorbent pump no.1 kw(a) 8.7(27.0) 8.7(27.0) 10.5(33.5) 10.5(33.5) 10.5(33.5) 10.5(33.5) 11.5(37.5) 11.5(37.5) 11.5(37.5) 11.5(37.5) 11.5(37.5) 11.5(37.5) Absorbent pump no.2 kw(a) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 1.2(4.8) 3.0(10.0) 3.0(10.0) Absorbent pump no.2 kw(a) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 3.0(10.0) 4.0(12.0) 4.0(12.0) 4.0(12.0) 4.0(12.0) 4.0(12.0) 4.0(12.0) Refrigerant pump kw(a) 0.4(1.4) Refrigerant pump kw(a) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 0.4(1.4) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 1.5(3.9) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.4(1.45) 0.75(2.2) 0.75(2.2) 0.75(2.2) 0.75(2.2) 0.75(2.2) 0.75(2.2) Length mm 4,910 4,910 4,910 4,910 4,995 4,995 5,540 5,540 6,035 6,035 Length mm 5,680 5,680 6,180 6,180 6,705 6,705 6,340 6,340 6,865 6,865 7,365 7,365 Width mm 2,550 2,550 2,550 2,550 2,745 2,745 2,745 2,745 2,745 2,745 Width mm 3,235 3,235 3,235 3,235 3,235 3,235 3,800 3,800 3,800 3,800 3,800 3,800 Height mm 2,815 2,815 2, ,140 3,140 3,140 3,140 Height mm 3,575 3,575 3,575 3,575 3,575 3,575 4,050 4,050 4,050 4,050 4,050 4,050 Operating ton Total shipping ton Operating ton Total shipping ton Clearance for tube removal mm 4,500 4,500 4,500 4,500 4,600 4,600 5,200 5,200 5,700 5,700 Clearance for tube removal mm 5,200 5,200 5,700 5,700 6,200 6,200 5,800 5,800 6,300 6,300 6,800 6, Standard side pressure (chilled & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) 2. Standard side pressure (chilled & cooling ): 10kgf/cm 2 G (981kPa) 3. Standard hot- pressure: 8kgf/cm 2 G (785kPa) LG HVAC Solution 25

14 Note Note LG HVAC Solution 27

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control... Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply

More information

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124 Appendix 2B: Chiller Test Results...119 2B.1 Chilled-Water Return (and Supply) Temperature...119 2B.2 Chilled-Water Flow... 122 2B.3 Cooling-Water Supply Temperature / Flow... 124 2B.4 Pressure/Temperature...

More information

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com. Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

GLOBACON 05 HVAC Systems for Cogen

GLOBACON 05 HVAC Systems for Cogen GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity

More information

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

High-efficient gas boiler CompactGas

High-efficient gas boiler CompactGas High-efficient gas boiler CompactGas Patented alufer for a high efficiency and low emission. 1 CompactGas (1000-2800). Advantages at a glance. The Hoval CompactGas fulfils all expectations with regard

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of

More information

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in

More information

Metering for today s systems

Metering for today s systems Metering for today s systems The sub-meter gathers data on the building side of the utility company meter. This allows us to break out usage so data can be collected from individual circuits, a single

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

Product Data. 16DNH 20% Energy Saving Model, Direct-Fired, Double Effect, Hermetic Absorption Liquid Chiller/Heater

Product Data. 16DNH 20% Energy Saving Model, Direct-Fired, Double Effect, Hermetic Absorption Liquid Chiller/Heater Product Data 6DNH 0% Energy Saving Model, Direct-Fired, Double Effect, Hermetic Absorption Liquid Chiller/Heater 50 to 650 minal Tons (57 to 580 kw) Copyright 009 Carrier China Operations 6DNH Carrier

More information

Silicagel-water adsorption cooling prototype system for mobile air conditioning

Silicagel-water adsorption cooling prototype system for mobile air conditioning Silicagel-water adsorption cooling prototype system for mobile air conditioning R. de Boer S.F. Smeding S. Mola Paper to be presented at the Heat Powered Cycles Conference 09 Berlin, 7 to 9 September 2009

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

Chilled Water Precision Air Conditioner For Critical Application

Chilled Water Precision Air Conditioner For Critical Application AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.

More information

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Hot Water. Heat pump water heaters. Residential and Commercial R410a Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

BB-18 Black Body High Vacuum System Technical Description

BB-18 Black Body High Vacuum System Technical Description BB-18 Black Body High Vacuum System Technical Description The BB-18 Black Body is versatile and is programmed for use as a fixed cold target at 80 K or variable target, at 80 K- 350 K no extra cost. The

More information

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Online Infrared Flue Gas Analyzer Gasboard 3000

Online Infrared Flue Gas Analyzer Gasboard 3000 Online Infrared Flue Gas Analyzer Gasboard 3000 O 2 CO CO2 SO 2 NO NO x Use of measurement methods Proprietary Infrared NDIR Detectors - Micro-flow in ppm range: CO, NO, SO2, CO2 - Dual beam in % volume

More information

The Best Selling Domestic Stainless Steel Oil Boiler

The Best Selling Domestic Stainless Steel Oil Boiler The Best Selling Domestic Stainless Steel Oil Boiler Stainless Steel Oil Boiler / Standard Oil Boiler Convenience By using the prograed timer, you can control the HEATING / OFF functions inside your room

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Vacuum drying oven for non-flammable solvents

Vacuum drying oven for non-flammable solvents VD series 53 Vacuum drying ovens Vacuum drying oven for non-flammable solvents A BINDER vacuum drying oven of the VD series is impressive while gently drying with its homogeneous temperature distribution.

More information

NOW 6 STAR EFFICIENT. factor RHEEM CONTINUOUS FLOW GAS HOT WATER HOT WATER THAT NEVER RUNS OUT YEAR WARRANTY L/MIN ENERGY GAS

NOW 6 STAR EFFICIENT. factor RHEEM CONTINUOUS FLOW GAS HOT WATER HOT WATER THAT NEVER RUNS OUT YEAR WARRANTY L/MIN ENERGY GAS RHEEM CONTINUOUS FLOW GAS HOT WATER REVISED MAY 2013 GAS 6 ENERGY RATING 1-6 PERSONS 12-54 L/MIN CAPACITY 10 YEAR WARRANTY 3 NOW 6 STAR EFFICIENT HOT WATER THAT NEVER RUNS OUT factor COMES ON STEADY, HOT

More information

Desiccant Air Dryers Heatless, Heated and Heated Blower

Desiccant Air Dryers Heatless, Heated and Heated Blower Desiccant Air Dryers Heatless, Heated and Heated Blower Desiccant Dryers... Desiccant Our reliable high strength, non-acidic desiccant provides maximum performance and is easily stored and handled. Environmentally

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device

ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR The heat transfer innovators. THE RELIANCE COPPER FINNED TUBE HYDRONIC BOILER FEATURES Copper Fin-Tube Heat Exchanger Up to 88% Thermal

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

Enclosed Football Stadium Design History and Lessons Learned

Enclosed Football Stadium Design History and Lessons Learned Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention

More information

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Dr. Nguyen Nguyen An, HUST CONTENTS Energy consumption to produce hot water in residential

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

GTS Gas-to-Steam Humidification System

GTS Gas-to-Steam Humidification System GTS Gas-to-Steam Humidification System Gas has lowest energy operating costs The industry s first and best-selling gas-to-steam (GTS ) humidifier continues to be your best choice for reducing energy costs

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

AdSORPTION CHILLER NAK

AdSORPTION CHILLER NAK AdSORPTION CHILLER NAK Chilling Capacity from 50 to 430 kw Usage of Surplus Heat from 50 C Ã*%8ÃPE+Ã TECHNICAL DESCRIPTION ADSORPTION CHILLER NAK 1 INTRODUCTION... 2 2 THE PRINCIPLE OF ADSORPTION... 2

More information

TWE+TTA TWE+TWA 6.25-20 T.R.

TWE+TTA TWE+TWA 6.25-20 T.R. TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.

More information

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM organization / project coordinator (address, telephone, email) Solel Solar Systems Ltd./ Mr. Avi Brenmiller 3, Hac'shara St, Industrial Zone

More information

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 CONTENTS 1.MODELS LIST... 3 2.NOMENCLATURE... 3 3.FEATURES... 3 4.PRODUCT

More information

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Drives and motors. A guide to using variable-speed drives and motors in retail environments Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

HOT WATER SYSTEMS. www.thermann.com.au

HOT WATER SYSTEMS. www.thermann.com.au HOT WTER SYSTEMS www.thermann.com.au GS HOT WTER SYSTEM The Thermann 4 star Gas hot water heater can suit almost any family type. With an adjustable thermostat for safety and efficiency it allows you to

More information

HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3

HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3 HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- BY MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3 SYNOPSIS JP Steel Plantech Co. has developed Hybrid system for EAF off-gas heat recovery, with EAF

More information

ThermoSorb Desiccant Dryers

ThermoSorb Desiccant Dryers ThermoSorb Desiccant Dryers Sierra Why dry compressed air? Contamination reduces efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. During the compression

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

G234X-55 Conventional Gas Boiler

G234X-55 Conventional Gas Boiler Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus G234X-55 fl oor standing hot water boiler(s), suitable with natural

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems F ox W hi t e Paper Reduce Energy Costs and Enhance Emissions Monitoring Systems A Technical White Paper from Fox Thermal Instruments Rich Cada, VP Sales & Marketing, Fox Thermal Instruments, Inc. 399

More information

Current state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours:

Current state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours: Current state of plant Functioning as a peak and emergency centre Statistics Accumulated operating hours: D1-2-3-6-7: 43000 to 48000 hrs D4-5: 53000 to 57000 hrs D8: 33000 hrs Layout of the plant Index:

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Daikin Altherma hybrid heat pump. The natural combination

Daikin Altherma hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient

More information

The natural ombination

The natural ombination The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80 FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80 List of symbols T f average temperature at the flow header, C T r average temperature at the return header, C f average water

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment Larry Zanko Project Manager STERIS Corporation Agenda Brief overview of multiple-effect water stills (MWS) Lean advancements

More information

CHAPTER 9: WATER HEATING

CHAPTER 9: WATER HEATING Chapter 9: Water Heating 145 CHAPTER 9: WATER HEATING Energy costs for water heating can be as great as the costs for heating, for an energy efficient house, in a mild climate. Estimating hot water usage

More information

Y-200 Multi-Stage Sequencer

Y-200 Multi-Stage Sequencer Y-200 Multi-Stage Sequencer Designed for use with single or multiple space heating or hot water supply systems, the Y-200 is offered in 4- and 8-stage configurations and is available loose or factory-mounted

More information

Refrigeration Compressed Air Dryer Buran Ultrapulse

Refrigeration Compressed Air Dryer Buran Ultrapulse Refrigeration Compressed Air Dryer Buran Ultrapulse There is more to compressed air than just compressing air Compressed air is an indispensable source of operating and processing power in all areas of

More information

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Air-sourced 90 Hot Water Supplying Heat Pump HEM-90A Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced

More information

Efficiency on a large scale CFB Steam Boilers

Efficiency on a large scale CFB Steam Boilers Efficiency on a large scale CFB Steam Boilers Circulating Fluidized Bed Steam Boiler The Circulating Fluidized Bed Steam Boiler is an offering from Bosch Thermotechnology a member of the worldwide Bosch

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents

More information

Condensate water pump with neutralisation system

Condensate water pump with neutralisation system Pumps for fuel oil and gas boiler Condensate water pump with neutralisation system SK9E/FP8E débit obtenu (l/h) caractéristriques selon la fréquence réglée performances avec une hauteur d aspiration de

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes

More information

Waste Incineration Plants

Waste Incineration Plants Waste Incineration Plants Modern Technology for a better Environmental Welcome at Hafner! We Manufacture Systems for Energy Recovery from Wastes and Biomass as well as for Treatment of Hazardous Wastes.

More information

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE Satish Joshi Managing Director CONTENTS 1. INTRODUCTION, APPLICATIONS 2. TECHNOLOGY, PROJECTS DONE, COST COMPARISION 3. HEAT PUMPS IN THE RENEWABLES DIRECTIVE,

More information

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin

Drying of Woody Biomass. Process Engineering / GEA Barr-Rosin Drying of Woody Biomass BioPro Expo & Marketplace / Atlanta, GA / March 14-16, 2011 Drying of Woody Biomass Conventional Direct Fired Dryer Technology Proprietary work of the Copyright Owner Issues with

More information

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our

More information

VDL 53 - Vacuum drying oven for flammable solvents

VDL 53 - Vacuum drying oven for flammable solvents Vacuum drying ovens VDL 53 - Vacuum drying oven for flammable solvents The VDL series ensures maximum safety when drying organic solvents in accordance with TÜV/GS guidelines. The interior chamber is designed

More information

Defining Quality. Building Comfort. Heating and Cooling Coils

Defining Quality. Building Comfort. Heating and Cooling Coils Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.

More information

With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS

With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS SAWAI Tsuneji *1 TAKAHASHI Hiroshi *1 INOUE Ken-ichi *2 We have developed the Econo-Pilot energy-saving system for water pumps, which reduces the power

More information

BorsodChem MCHZ, Czech Republic. 6,000 Nm 3 /h HTCR Topsøe Hydrogen Plant A Case Story: 18 Months from Engineering to Operation

BorsodChem MCHZ, Czech Republic. 6,000 Nm 3 /h HTCR Topsøe Hydrogen Plant A Case Story: 18 Months from Engineering to Operation 6,000 Nm 3 /h HTCR Topsøe Hydrogen Plant 2 1. Introduction... 3 2. The BorsodChem MCHZ Company... 3 3. HTCR Process and Reformer Principle...4 4. Engineering of the BorsodChem MCHZ HTCR Plant... 6 5. Workshop

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Heating oven with mechanical control

Heating oven with mechanical control ED series 53 Drying ovens / Heating ovens Heating oven with mechanical control The strength of the BINDER ED series heating oven: routine drying and sterilization applications up to 300 C (572 F). Thanks

More information

Laboratory Autoclave SN210/310/510,SQ510/810

Laboratory Autoclave SN210/310/510,SQ510/810 1/5 Laboratory Autoclave SN210/310/510,SQ510/810 SN210/310/510,SQ510/810 The highest temperature of 135deg.C Upwards opening lid SN210 SN310 SN510 Effective Capacity : 20LEffective Capacity : 32L Effective

More information

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM. Answers for infrastructure.

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM. Answers for infrastructure. The product segments Heating, ventilation, air conditioning Control Products & Systems OEM Answers for infrastructure. The right product for every application Siemens specializes in the development, production

More information

In-Line Electronic Flow Switches

In-Line Electronic Flow Switches In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

Using waste heat. with gas-fired steam humidifiers Condair GS. Humidification and evaporative cooling

Using waste heat. with gas-fired steam humidifiers Condair GS. Humidification and evaporative cooling Using waste heat with gas-fired steam humidifiers Condair GS Humidification and evaporative cooling Economical and ecological steam production with gas as primary energy. Gas-operated steam humidification

More information

In-Line Electronic Flow Switches

In-Line Electronic Flow Switches In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information