HEPA Filters for Pharma Applications Cleanrooms & Safety Applications. Gordon Farquharson June 2012

Size: px
Start display at page:

Download "HEPA Filters for Pharma Applications Cleanrooms & Safety Applications. Gordon Farquharson June 2012"

Transcription

1 HEPA Filters for Pharma Applications Cleanrooms & Safety Applications Gordon Farquharson June

2 Air Filters at work Images courtesy of CamfilFarr 2

3 How filters work Sieving Effect Straining 3

4 Filter Test Methods 4

5 Filter Specifications 5

6 Some important filter considerations Correct pre-filters protect systems & prolong life of final filters HEPA filters are required in cleanroom & safety ventilation applications Designs and installation must allow for convenient & safe filter testing Make sure you know what filters are installed in the system 6

7 HEPA Filter Standards HEPA Filters are dealt with in 4 basic ways. Filter Construction standards Factory or manufacturer s tests In-situ testing of installations Some application standards include HEPA Filter specifications (e.g. EN for Biosafety Cabinets) 7

8 Filter Test Methods MPPS = 0.2 8

9 Some Test Equipment Thermo-Pneumatic Aerosol Generator 9

10 Some Test Equipment Laskin Nozzle Cold Generator 10

11 Some Test Equipment Aerosol Photometer 11

12 New Standards from CEN TC Air Filtration 2 HEPA & ULPA Filters EN Testing Planar Filter Medium to determine the MPPS -- Most Penetrating Particle size. The processes of Interception, Diffusion & Straining give the following v1 classic curve. Performance is velocity dependent. 12

13 HEPA & ULPA Filters EN Factory Test 13

14 EN 1822 compared with Eurovent 4/4 NaCl Eurovent 4/4 EN 1822 Filter Class Efficiency % Filter Class Efficiency % H H EU H EU EU H EU H EU 14 > U U U

15 EN Filter Classifications Local efficiency = 5x 0verall Overall Effic/Pen Local Effic/Pen H / 15 % na / na H11 95 / 5 na / na H / 0.5 na / na H / / 0.25 % H / / U / / U / / U / / To avoid problems with In-situ test, always specify a face scanned filter from the supplier! 15

16 Local & Overall Efficiency H 14 MPPS Local pen < % Local pen < % Local pen < % Local & Overall Pen % must pass Overall penetration < MPPS 16

17 Leak test In-situ PAO test Local pen < 0.01 % Local pen < 0.01 % Local pen < 0.01 % 17 Overall penetration < or MPPS

18 Local & Overall Efficiency H 14 example 18

19 How do we choose our HEPA filters?? From the requirements in a Cleanroom Standard or GMP rule/guideline. Because we have chosen a certain acceptance value for the In-Situ leak test e.g % or 0.01%. Because we have calculated the efficiency of filter we need from an evaluation of the particle challenge imposed upon the filters. Because the filter gives good Uni-Directional Flow. Compliance with some other requirement e.g. Corporate. 19

20 Choosing the Right HEPA Filter EU GMP Grade A Class At Rest E 0.5 ISO M3.5 Class In Operation E 0.5 ISO M3.5 Air flow regime and final filter configuration UDAF Terminal HEPA filter Final Filter specification to EN 1822 In situ test leak test method Test acceptance criteria = stated % U15 Face scan with % aerosol & H14 photometer 0.01 % B ISO M3.5 ISO 7 10,000 M5.5 N-UDAF Terminal HEPA filter H14 Face scan with aerosol & photometer 0.01 % C ISO 7 10,000 M5.5 ISO 8 100,000 M6.5 N-UDAF Terminal HEPA filter H14 Face scan with aerosol & photometer 0.01 % D ISO 8 100,000 M6.5 Not defined N-UDAF In plant final filter H13 Volumetric overall penetration % Refers to filter grades in accordance with EN 1822 ULPA, & HEPA 20

21 The Installed HEPA Filter 21

22 Typical Aseptic Facility Design (From ISPE HVAC GPG) Outside air treatment AHU 22

23 In-Situ Testing General Select test method, aerosol, and acceptance criteria Determine challenge up-stream Scan test final filter face for leaks Determine acceptance or rejection Carry out remedial work. Agree before repairing filters. Have a clear policy. ISO allows repair, subject to manufacturer s approved method. I don t know any manufacturers who encourage repairs. Re-test 23

24 Testing is application specific Filter testing in this Isolator is a different problem from the cleanroom. 24

25 Filter Systems for Potent, Toxic, Biohazard applications 25

26 Exposure Control Potent Compound Control Bands EH & S Call the shots! EXPOSURE CONTROL BAND Band OEL Range Design 1 >1000 ug/m3 General Ventilation, Conventional open Equipment with local exhaust (LEV) ug/m3 Semi-closed to closed materialo transfer laminar flow/directionalized laminar flow engineered LEV ug/m3 Transfers using direct couplings % closed systems selected use of unidirectionalized air flow booths ug/m3 Totally enclosed processes: Transfers using direct coupling barrier/isolator technology 5 <1 ug/m3 Isolator technology; remote operations fully auotmated 26

27 Typical OSD Facility Using Multiple Air handlers (From ISPE HVAC GPG) 27

28 BIBO (Bag-In, Bag-Out Housing Fully Self contained system with fan, integrated dampers & automatic scan section optional Cover Panel Access door for BT damper Scan section Hepa Section Pre filter section Air intake levelling feet 28

29 29

30 30 Filter Leak Test Procedure!

31 31

32 Duct mounted double exhaust housing Safety ventilation systems - typical contemporary BSL-3 exhaust system High Total Cost of Ownership Large Each system must be specifically oriented Costly to test 32

33 Typical BSL-3 HEPA Filter Exhaust System 33 High Efficiency Particulate Air 33 (HEPA) Filter

34 Field system leak testing manual scanning Potential Risk to Certifier Requires lab shutdown and system decontamination Slow process 34

35 Field system leak testing automated scanning 35 Control Unit

36 Conclusions Be aware of the Different Standards Understand the configuration Specify filters correctly (including leak testing) Install carefully Test In-situ Plan re-testing Keep records

37 37 Thanks for your attention Questions?

38 PharmOut Unit 20, 40 Montclair Avenue, Glen Waverley, Victoria, Australia, 3150 Tel +61 (0) Thanks for your attention Slid e 38

39 S Y S CRI T ICAL E M S Gordon J Farquharson Chair BSI LBI/030; Chair CEN TC243; Convenor ISO TC209 WG1. c/o Critical Systems Ltd 4, Greencroft, Guildford, Surrey, GU1 2SY, UK. tel +44 (0) mob +44 (0) gj.farquharson@gmail.com & gjf@critical-systems.co.uk 39

Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested

Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested DOP Solutions Technical Document: Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested Issue 1: Prepared by Neil Stephenson and Tim Triggs and edited by

More information

VALIDATION OF CLEAN ROOMS FOR ASEPTIC MANUFACTURING. F.R.Smal Pharmaceutical Director ICCE ICCE a member of SNC-Lavalin Group

VALIDATION OF CLEAN ROOMS FOR ASEPTIC MANUFACTURING. F.R.Smal Pharmaceutical Director ICCE ICCE a member of SNC-Lavalin Group VALIDATION OF CLEAN ROOMS FOR ASEPTIC MANUFACTURING F.R.Smal Pharmaceutical Director ICCE ICCE a member of SNC-Lavalin Group tel + 3226431600 E-Mail: francis.smal@be.snclavalin.com VALIDATION OF CLEAN

More information

Air and Water Balancing - Sound and Vibration Testing - Cleanroom Services - Building Commissioning Building Envelope Testing Thermal Imaging

Air and Water Balancing - Sound and Vibration Testing - Cleanroom Services - Building Commissioning Building Envelope Testing Thermal Imaging NEUDORFER ENGINEERS, INC. provides our customer with unbiased, professional, performance testing of Cleanrooms. We are committed to providing you, our customer, with value-added expertise in an effort

More information

Laminar Flow Cabinets

Laminar Flow Cabinets Laminar Flow Cabinets The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. 24 36 48 Simple, Effective Protection for Samples and Work Processes, Uncompromised Performance, Economical

More information

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory

More information

Environmental Monitoring

Environmental Monitoring Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is

More information

EACO DOP / PAO TESTING GUIDELINE 2013

EACO DOP / PAO TESTING GUIDELINE 2013 2013 Foreword The guideline promotes industry standards for training, equipment, and methodologies for HEPA filter integrity testing of negative air units, vacuums and any other HEPA filtered equipment

More information

HEPA FILTER DEFECTS ARE COMMON

HEPA FILTER DEFECTS ARE COMMON HEPA FILTER DEFECTS ARE COMMON Kenneth F. Cherry 1 and Kenneth A. Smigielski 2 1 NCEC Inc. 2 First Solar LLC. ABSTRACT HEPA filters (High Efficiency Particulate Air) filters are claimed by vendors to have

More information

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class

More information

Biosafety Program University of Colorado. BSL-1 Audit Checklist

Biosafety Program University of Colorado. BSL-1 Audit Checklist PI first name: PI last name: username: IBC application #: Inspection Date: Lab Location: Department: email: best lab contact lab contact email Inspected by: Time BSL-1 Yes BSL-2 Yes A. Contamination Control

More information

LAMINAR FLOW CABINETS

LAMINAR FLOW CABINETS LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different

More information

Testing HEPA/ULPA filters at the manufacturer s facility and in situ on the user s premises

Testing HEPA/ULPA filters at the manufacturer s facility and in situ on the user s premises Publication Series Viledon Testing HEPA/ULPA filters at the manufacturer s facility and in situ on the user s premises Dipl.-Ing. Thomas Schroth Dr.-Ing. Thomas Caesar Lecture at 4th CLEANROOMS Europe

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

DATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS

DATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS DATA CENTERS Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS COSTLY FAN ENERGY REDUCED BY CAMFIL PREMIUM PRODUCTS = COST SAVINGS Power Usage Effectiveness (PUE) is an important metric

More information

Risk Assessment: Biosafety Cabinet

Risk Assessment: Biosafety Cabinet Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.

More information

Viledon HEPA and ULPA Filters The Patented Solution for Sterile Air and Clean Rooms. Product Overview

Viledon HEPA and ULPA Filters The Patented Solution for Sterile Air and Clean Rooms. Product Overview Viledon HEPA and ULPA Filters The Patented Solution for Sterile Air and Clean Rooms Product Overview In a class of their own for technology and performance While the performance qualities of air filters

More information

Revision of ISO 14644-1:1999 A progress report and explanation of some of the key issues and principles June 2012

Revision of ISO 14644-1:1999 A progress report and explanation of some of the key issues and principles June 2012 Revision of ISO 14644-1:1999 A progress report and explanation of some of the key issues and principles June 2012 Gordon J Farquharson Convenor ISO TC209 WG1, Critical Systems Ltd, 4 Greencroft, Guildford,

More information

CLASSIFICATION OF CLEANROOMS

CLASSIFICATION OF CLEANROOMS CLASSIFICATION OF CLEANROOMS Cleanrooms are classified by the cleanliness of their air. The method most easily understood and most universally applied is the one suggested in the earlier versions (A to

More information

ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS

ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS PRESENTATION TO RACI 20 TH APRIL 2016 PAUL MORGAN DIRECTOR CRITICAL CERTIFICATION PTY LTD CHANGES TO ISO14644 PART 1 CHANGES

More information

Laminar Flow Cabinets and Workstations

Laminar Flow Cabinets and Workstations VERTICAL AND HORIZONTAL HEPA FILTERED SYSTEMS FOR PROCESS OR OPERATOR PROTECTION Laminar Flow Cabinets and Workstations For procedures requiring protection from particulate contamination and for aseptic

More information

HVAC Air Systems. Recirculation Air System Types

HVAC Air Systems. Recirculation Air System Types HVAC Air Systems Recirculation Air System Types Summary Recirculation air handler fan energy can account for 10 to 30% of total cleanroom energy use. There are three fundamental recirculation system configurations:

More information

Cleanroom. For. Sterile Manufacturing Facilities

Cleanroom. For. Sterile Manufacturing Facilities Cleanroom For Sterile Manufacturing Facilities Praphon Angtrakool Food and Drug Administration 1 WHO TRS No. 823 Annex 1, 1992 (1) General 17.1 The production of sterile preparations should be carried

More information

G U I D E L CERTIFICATION EDUCATION TRAINING. Procurement Guideline. National Air Filtration Association Recommended Practice

G U I D E L CERTIFICATION EDUCATION TRAINING. Procurement Guideline. National Air Filtration Association Recommended Practice G U National Air Filtration Association Recommended Practice I D E L I N E Procurement Guideline TRAINING EDUCATION CERTIFICATION HVAC Air Filter Purchasing Specification Guideline 1.0 Purpose To provide

More information

Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade

Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial

More information

White Paper. Life Sciences Industry Solution Blueprint for Environmental Monitoring Systems (EMS) ISPE Guidance and Best Practices.

White Paper. Life Sciences Industry Solution Blueprint for Environmental Monitoring Systems (EMS) ISPE Guidance and Best Practices. White Paper Life Sciences Industry Solution Blueprint for Environmental Monitoring Systems (EMS) Author: Roberto Zerbi, Global Industries Solutions Life Sciences, Invensys What s Inside: 1. Introduction

More information

HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests Bulletin: PB2007-0504

HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests Bulletin: PB2007-0504 HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests Bulletin: PB2007-0504 Introduction HEPA filters, once known as absolute filters, were originally developed as the particulate

More information

Fume Hood Questions and Answers

Fume Hood Questions and Answers Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or

More information

HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests

HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests FOREMOST IN AIR FILTRATION HEPA Filters and Filter Testing PB-2007-1203 HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests A Wholly Owned Subsidiary of Flanders Corporation

More information

Procedures for the Effective Use of Biological Safety Cabinets

Procedures for the Effective Use of Biological Safety Cabinets Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum

More information

Particle Monitoring Requirements in Pharmaceutical Cleanrooms

Particle Monitoring Requirements in Pharmaceutical Cleanrooms Particle Monitoring Requirements in Pharmaceutical Cleanrooms All drugs must be manufactured in accordance with the current Good Manufacturing Practice (cgmp) regulations. Pharmaceutical manufacturers

More information

ANNEXURE I SERVICE LEVEL AGREEMENT BETWEEN. The Client. and. The Contractor/Service Provider. HVAC Systems Maintenance Service

ANNEXURE I SERVICE LEVEL AGREEMENT BETWEEN. The Client. and. The Contractor/Service Provider. HVAC Systems Maintenance Service ANNEXURE I SERVICE LEVEL AGREEMENT BETWEEN The Client and The Contractor/Service Provider HVAC Systems Maintenance Service Page 1 of 11 Version Number Originator Status Date Signature Page 2 of 11 Table

More information

ISPE is pleased to provide comments using the supplied WHO template on the above document, as requested.

ISPE is pleased to provide comments using the supplied WHO template on the above document, as requested. 16 August 2010 World ealth Organization 1211 Geneva 27 Switzerland SUBMISSION OF COMMENTS ON QAS/10.342: WO Supplementary guidelines on good manufacturing practices for heating ventilation and air conditioning

More information

Indoor air quality monitoring made easy

Indoor air quality monitoring made easy Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor

More information

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC USP Cleanroom Design and Environmental Monitoring Andrew King, USP Specialist CETA Member RCCP-SC Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how

More information

GUIDELINE TO THE INSPECTION OF HORMONE PRODUCT MANUFACTURING FACILITIES

GUIDELINE TO THE INSPECTION OF HORMONE PRODUCT MANUFACTURING FACILITIES February 2008 RESTRICTED GUIDELINE TO THE INSPECTION OF HORMONE PRODUCT MANUFACTURING FACILITIES Please address comments on this proposal, by 13 May 2008, to Dr S. Kopp, Quality Assurance and Safety: Medicines,

More information

Howorth Air Technology. Healthcare Air Management Services

Howorth Air Technology. Healthcare Air Management Services Howorth Air Technology Healthcare Air Management Services Howorth - Pure Protection For more than 150 years, the Howorth name has represented technical creativity and expertise in air engineering and its

More information

Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity

Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity Best Products. Best Performance. Best Protection. NuAire, Inc. 2100 Fernbrook Lane Plymouth, MN 55447 U.S.A ph: 763.553.1270 fx:

More information

EU GMP Annex 1 Update 2008: Airborne Particle Counting

EU GMP Annex 1 Update 2008: Airborne Particle Counting EU GMP Annex 1 Update 2008: Airborne Particle Counting Airborne Particle Counting for Pharmaceutical Facilities: Update 2008, EU GMP Annex 1 Morgan Polen - VP of Applications Technology, Lighthouse Worldwide

More information

cleanroom validation Cleanroom Validation

cleanroom validation Cleanroom Validation Cleanroom Validation cleanroom applications laboratories production environments laminar flow boxes cleanroom concepts microelectronics pharmaceutical industry, food industry nuclear industry, aerospace

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Particle testing in cleanroom high-pressure gas lines to ISO 14644 made easy with the MET ONE 3400 gas calibrations

Particle testing in cleanroom high-pressure gas lines to ISO 14644 made easy with the MET ONE 3400 gas calibrations Particle testing in cleanroom high-pressure gas lines to ISO 14644 made easy with the MET ONE 3400 gas calibrations B e c k m a n C o u l t e r L i f e S c i e n c e s 2 5 0 S. K r a e m e r B o u l e

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

LAMINAR FLOW FOR ALL YOUR NEEDS

LAMINAR FLOW FOR ALL YOUR NEEDS LAMINAR FLOW FOR ALL YOUR NEEDS 2 LAMINAR FLOW FOR ALL YOUR NEEDS EXPLORE TECNIPLAST COMPLETE RANGE OF LAMINAR FLOW SOLUTIONS: OUR CUTTING-EDGE TECNOLOGY IS AT YOUR SERVICE, TO ASSURE TOP ENVIRONMENTAL,

More information

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS Introduction Heating, Ventilation and Air-Conditioning (HVAC) plays

More information

SUPPLEMENTARY GUIDELINES ON

SUPPLEMENTARY GUIDELINES ON August 2015 Draft document for comment 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES

More information

WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems

WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems WIBOjekt and WIBObarrier Air Curtain Systems. The perfect protection for person, product and environment. Filling Weighing Sampling Research Safe handling with high potent products / API WIBObarrier OCS

More information

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus

More information

Environmental Monitoring of Clean Rooms

Environmental Monitoring of Clean Rooms Environmental Monitoring of Raul Duarte President DDK Scientific, Corp. Copyright DDK Scientific, Corp. 2008, 2009, DDK Scientific, Corp. Proprietary A manufacturing facility for pharmaceutical products

More information

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)

PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No

More information

NEBB Cleanroom Performance Testing Certified Professional Seminar and Exams

NEBB Cleanroom Performance Testing Certified Professional Seminar and Exams NEBB Cleanroom Performance Testing Certified Professional Seminar and Exams October 20-22, 2014 Orlando, FL Introduction Cleanroom testing must be performed to ensure that cleanrooms comply with design

More information

Chemical Fume Hoods. Environmental Health and Safety 974-5084

Chemical Fume Hoods. Environmental Health and Safety 974-5084 Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods

More information

General Purpose Laminar Flow Cabinets, Horizontal and Vertical

General Purpose Laminar Flow Cabinets, Horizontal and Vertical 24 36 48 60 72 96 The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. VLF-48 Provides reliable protection for samples and work processes for a multitude of applications. p:2 Product

More information

Whitepaper Cross-Contamination

Whitepaper Cross-Contamination Whitepaper Cross-Contamination Protection in HVAC I N D U S T R Y I N S I G H T S Norman A. Goldschmidt September 30, 2011 Principal, Engineering www.geieng.com I N D U S T R Y I N S I G H T S Genesis

More information

SAFE USE OF MICROBIOLOGICAL SAFETY CABINETS

SAFE USE OF MICROBIOLOGICAL SAFETY CABINETS SAFE USE OF MICROBIOLOGICAL SAFETY CABINETS Microbiological Safety Cabinets are designed to protect users and the environment (which includes other people in the laboratory) from aerosol risks arising

More information

Fire safety in buildings and implementation of European fire test standards

Fire safety in buildings and implementation of European fire test standards Fire safety in buildings and implementation of European fire test standards Dr Debbie Smith OBE Chair of CEN TC127 Fire Safety BRE Global Ltd, UK 18 th June 2014 Part of the BRE Trust Construction Products

More information

MOHD NASRUL MOHAMAD NOOR

MOHD NASRUL MOHAMAD NOOR QUALITY ASSURANCE IN ASEPTIC WHO Collaborating Centre For Regulatory Control of Pharmaceuticals DISPENSING : MAINTENANCE OF CLEAN ROOM & EQUIPMENT Member of Pharmaceutical Inspection Cooperation Scheme

More information

Working document QAS/10.342/Rev.1 June 2010 RESTRICTED

Working document QAS/10.342/Rev.1 June 2010 RESTRICTED June 2010 RESTRICTED SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES FOR HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS FOR NON-STERILE PHARMACEUTICAL DOSAGE FORMS PROPOSAL FOR REVISION Please

More information

Benjamin Fontes, Geoffrey Lyon and Maryjo Lanzillotta Yale University

Benjamin Fontes, Geoffrey Lyon and Maryjo Lanzillotta Yale University Benjamin Fontes, Geoffrey Lyon and Maryjo Lanzillotta Yale University Yale Cell Sorting Biosafety Cross Training Learning phase Program Collaboration Setting up a program Partnership Maintaining the program

More information

PERFORMANCE QUALIFICATION OF A CLEAN ROOM FROM A QUALITY PERSPECTIVE

PERFORMANCE QUALIFICATION OF A CLEAN ROOM FROM A QUALITY PERSPECTIVE PERFORMANCE QUALIFICATION OF A CLEAN ROOM FROM A QUALITY PERSPECTIVE Every facility design is unique for its specific needs, and validation programs must be customized to meet these challenges. While there

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

ASALAIR BIOHAZARD CABINET MODEL ATLANTIC CYTOCABINET 1200 CLASS II TYPE A2 COD. 29940086 MICROBIOLOGICAL SAFETY CABINET CLASS II TYPE A2

ASALAIR BIOHAZARD CABINET MODEL ATLANTIC CYTOCABINET 1200 CLASS II TYPE A2 COD. 29940086 MICROBIOLOGICAL SAFETY CABINET CLASS II TYPE A2 ASAL S.R.L. - APPARECCHI SCIENTIFICI ATTREZZATURE LABORATORI Quality System comply with requirements of UNI EN ISO 9001:2008. Certificate TÜV Italia n 50 100 3290 Rev. 02 ASALAIR BIOHAZARD CABINET MODEL

More information

Manufacturing. Environmental Monitoring Particle Counts Are Easy B IOP ROCESSTECHNICAL. Scott E. Mackler

Manufacturing. Environmental Monitoring Particle Counts Are Easy B IOP ROCESSTECHNICAL. Scott E. Mackler B IOP ROCESSTECHNICAL Environmental Monitoring Particle Counts Are Easy Scott E. Mackler Manufacturing pharmaceutical and biotechnology products requires that the appropriate level of quality be designed

More information

MAC 10. Original & IQ FAMILY OF FAN FILTER UNITS

MAC 10. Original & IQ FAMILY OF FAN FILTER UNITS MAC 10 Original & IQ FAMILY OF FAN FILTER UNITS used in: microelectronics medical device semiconductor disk drive laboratory pharmaceutical markets hospitals clean rooms Table of Contents MAC 10 Original

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

GUIDELINES ON TEST METHODS FOR ENVIRONMENTAL MONITORING FOR ASEPTIC DISPENSING FACILITIES

GUIDELINES ON TEST METHODS FOR ENVIRONMENTAL MONITORING FOR ASEPTIC DISPENSING FACILITIES GUIDELINES ON TEST METHODS FOR ENVIRONMENTAL MONITORING FOR ASEPTIC DISPENSING FACILITIES PRODUCED BY A WORKING GROUP OF THE SCOTTISH QUALITY ASSURANCE SPECIALIST INTEREST GROUP SECOND EDITION FEBRUARY

More information

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?

More information

Biosafety Level 2 (BSL-2) Safety Guidelines

Biosafety Level 2 (BSL-2) Safety Guidelines BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff

More information

Biosafety Level 2 Criteria

Biosafety Level 2 Criteria Biosafety Level 2 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Biosafety Level 2 (BSL-2): Biosafety Level 2 builds upon BSL-1. BSL-2 is suitable for work involving

More information

Filter Fan Unit SILENT. Type SILENT AC Type SILENT EC

Filter Fan Unit SILENT. Type SILENT AC Type SILENT EC Technical Concept Filter Fan Unit SILENT Type SILENT AC Type SILENT EC Filter Fan Unit SILENT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide clean

More information

Laboratory Biosafety Level 3 Criteria

Laboratory Biosafety Level 3 Criteria Laboratory Biosafety Level 3 Criteria Biosafety in Microbiological and Biomedical Laboratories (BMBL) 5th Edition Section IV Biosafety Level 3 (BSL-3): Biosafety Level 3 is applicable to clinical, diagnostic,

More information

Laminar Flow Hoods and Booths

Laminar Flow Hoods and Booths Laminar Flow Hoods and Booths ... we go further... to absolutely clean air! Klimaoprema Cleanroom Technology is a leading Croatian manufacturer of equipment for cleanrooms. We offer complete engineering

More information

All Processes Dr. Paul Ruffieux Consultant

All Processes Dr. Paul Ruffieux Consultant PSI-L Isolator Platform All Processes Dr. Paul Ruffieux Consultant 1 Requirements Is it possible to have one Isolator for Filling under aseptic conditions (Grade A) Use of isolator technology in ISO8 room

More information

Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC

Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC Technical Concept Filter Fan Unit COMPACT Type COMPACT AC Type COMPACT EC Ultra Filter Fan Unit COMPACT Technical Concept Product Description Filter Fan Units (FFUs) from M+W Products are designed to provide

More information

GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS

GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE OF STERILE MEDICINAL PRODUCTS PHARMACEUTICAL INSPECTION CONVENTION PHARMACEUTICAL INSPECTION CO-OPERATION SCHEME PI 032-2 8 January 2010 RECOMMENDATION GMP ANNEX 1 REVISION 2008, INTERPRETATION OF MOST IMPORTANT CHANGES FOR THE MANUFACTURE

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

CLEANROOMS IN PHARMACEUTICAL PRODUCTION

CLEANROOMS IN PHARMACEUTICAL PRODUCTION Mikhail Kitain CLEANROOMS IN PHARMACEUTICAL PRODUCTION Bachelor s thesis Building Services March 2010 DESCRIPTION Date of the bachelor's thesis 14.03.2010 Author(s) Mikhail Kitain Degree programme and

More information

Laminar Flow Clean Benches, Horizontal and Vertical The Leading Solution for Research Laboratories

Laminar Flow Clean Benches, Horizontal and Vertical The Leading Solution for Research Laboratories Esco Labculture Laminar Flow Clean Bench Model LHC-4A_ AS 1386.5, EN12469 (Microbiological Testing Method) Laminar Flow Clean Benches, Horizontal and Vertical The Leading Solution for Research Laboratories

More information

What to Know When Considering a Cleanroom. by Simplex Technical Staff

What to Know When Considering a Cleanroom. by Simplex Technical Staff What to Know When Considering a Cleanroom by Simplex Technical Staff What to Know When Considering a Cleanroom by Simplex Technical Staff Does your business plan include the development of an area in your

More information

Barrier and isolation systems

Barrier and isolation systems VOLUME 21, NO. 04, APRIL 2007 T H E M A G A Z I N E O F C O N T A M I N A T I O N C O N T R O L T E C H N O L O G Y Barrier and isolation systems INTERPHEX 2007 Showguide Ventilation and exhaust systems

More information

MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard

MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard Advances in testing procedures, coupled with greater pressure for better IAQ, leads to a new standard By Ron Wilkinson, P.E.

More information

PROCEDURAL STANDARDS FOR CERTIFIED TESTING OF CLEANROOMS

PROCEDURAL STANDARDS FOR CERTIFIED TESTING OF CLEANROOMS PROCEDURAL STANDARDS FOR CERTIFIED TESTING OF CLEANROOMS 2009 THIRD EDITION National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 301-977-3698 301-977-9589 FAX www.nebb.org

More information

Bill Mixon, RPh, MS Senior Associate Gates Healthcare Associates

Bill Mixon, RPh, MS Senior Associate Gates Healthcare Associates Bill Mixon, RPh, MS Senior Associate Gates Healthcare Associates 14 pharmacists and 1 epidemiologist make up the committee USP staff FDA and CDC representatives have input but do not vote Call for Candidates

More information

Effectiveness of Engineering controls (LEVs)

Effectiveness of Engineering controls (LEVs) Carlos Fito López Responsable A.T. Seguridad & Coordinador de Proyectos de Nanoseguridad cfito@itene.com Sevilla 3 de Diciembre de 2014 Jornada de Nanotecnología y prevención de riesgos Nuevos desarrollos

More information

Qualification of Cleanrooms and Environmental Monitoring - Practical Approaches in Europe

Qualification of Cleanrooms and Environmental Monitoring - Practical Approaches in Europe Qualification of Cleanrooms and Environmental Monitoring - Practical Approaches in Europe 1 Dr. Doris Herrmann Zum Eselsbachtal 20 67657 Kaiserslautern Doris.Herrmann@GMP-unlimited.de www.gmp-unlimited.com

More information

THE EFFECTS OF LAMINAR AIRFLOW IN SEMICONDUCTOR FABS ON THE VENTILATION DESIGN FOR EXHAUSTED ENCLOSURES

THE EFFECTS OF LAMINAR AIRFLOW IN SEMICONDUCTOR FABS ON THE VENTILATION DESIGN FOR EXHAUSTED ENCLOSURES THE EFFECTS OF LAMINAR AIRFLOW IN SEMICONDUCTOR FABS ON THE VENTILATION DESIGN FOR EXHAUSTED ENCLOSURES Presented By: John Hatfield, CIH John O Hehir Global Semiconductor Safety Services 1365 Adams Court

More information

Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated

Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated Duct Leakage Testing Ken Helfers, TSI Inc. Agenda Need for duct leakage testing Duct leakage testing standards and regulations Performing duct leakage testing Why Test Ducts for Leakage? Conserve energy

More information

DATA CENTER & TELECOM APPLICATIONS. Purafil 2012 VMB-DCTC-01

DATA CENTER & TELECOM APPLICATIONS. Purafil 2012 VMB-DCTC-01 1 2 3 Er Wc Cc EQUIPMENT WARRANTY CORROSION RELIABILITY COMPLIANCE CONTROL DATA CENTER & TELECOM APPLICATIONS 1 2 3 Er Wc Cc EQUIPMENT WARRANTY CORROSION RELIABILITY COMPLIANCE CONTROL CLEAN AIR SOLUTIONS

More information

Pharmagraph. GMP/GLP Monitoring System

Pharmagraph. GMP/GLP Monitoring System Pharmagraph GMP/GLP Monitoring System Pharmagraph GMP/GLP Monitoring System Demonstrates GMP/GLP compliance for cleanrooms and laboratories Monitors, Alarms, Logs and Reports Airborne particle counts,

More information

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

6 MECHANICAL HVAC SYSTEMS

6 MECHANICAL HVAC SYSTEMS Conventional Facilities Chapter 6: HVAC Systems 6-1 6 MECHANICAL HVAC SYSTEMS 6.1 Design Criteria 6.1.1 Codes and Standards The latest edition of the codes, standards, orders, and guides referred to in

More information

Range Equipment HVAC Design & Supply Modular Ranges

Range Equipment HVAC Design & Supply Modular Ranges Range Equipment HVAC Design & Supply Modular Ranges SRI Shooting Range Industries LLC, SRI is a premier design and manufacturing company of quality and innovative live fire Modular Containerized Small

More information

Commercial Coil Cleaning:

Commercial Coil Cleaning: 18 Commercial Coil Cleaning: by Barry Harris, PH.D., ASCS 1, Lindell F. Killian, ASCS 2, and Nicolaus P. Neumann, P.E. 3 A Case History Facility managers and HVAC engineering supervisors have limited budgets

More information

DATA CENTRES. Camfil Farr Segment Brochure Data Centres Camfil Farr - Clean Air solutions

DATA CENTRES. Camfil Farr Segment Brochure Data Centres Camfil Farr - Clean Air solutions DATA CENTRES Camfil Farr Segment Brochure Data Centres Camfil Farr - Clean Air solutions Camfil Farr Leading the way in clean air Technology About Camfil Farr Camfil Farr is a world Leader in clean air

More information

World Health Organization WHO Technical Report Series, No. 961, 2011

World Health Organization WHO Technical Report Series, No. 961, 2011 World Health Organization WHO Technical Report Series, No. 961, 2011 Annex 5 Supplementary guidelines on good manufacturing practices for heating, ventilation and airconditioning systems for non-sterile

More information

Grilles & Diffusers Series LFP Incorporating

Grilles & Diffusers Series LFP Incorporating Grilles & Diffusers Incorporating Series LFP Produce a stable linear throw, creating an area of clean air with minimal diffusion Perfect for areas like clean rooms and operating theatres Tile replacer

More information

CLEAN ROOM MONITORING REGULATORY STANDARDS

CLEAN ROOM MONITORING REGULATORY STANDARDS CLEAN ROOM MONITORING REGULATORY STANDARDS Air Classification as per Schedule M Maximum permitted number of particles / m3 equal or above at rest in operation 0.5µm 5.0µm 0.5µm 5.0µm A 3,520 29 3,500 29

More information

BIOLOGICAL SAFETY CABINET PROGRAM

BIOLOGICAL SAFETY CABINET PROGRAM BIOLOGICAL SAFETY CABINET PROGRAM TABLE OF CONTENTS: 1. INTRODUCTION 2. PURPOSE AND SCOPE 3. SELECTION AND INSTALLATION 4. USE OF BIOLOGICAL SAFETY CABINETS 5. CERTIFICATION OF BIOLOGICAL SAFETY CABINETS

More information

SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.

SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799. SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information