1 इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. ज न1 क अ+धक र, ज 1 क अ+धक र Mazdoor Kisan Shakti Sangathan The Right to Information, The Right to Live प0र 1 क छ ड न' 5 तरफ Jawaharlal Nehru Step Out From the Old to the New IS 8148 (2003): Packaged Air Conditioners [MED 3: Refrigeration and Air Conditioning]! न $ एक न' भ रत क +नम-ण Satyanarayan Gangaram Pitroda Invent a New India Using Knowledge! न एक ऐस खज न > ज कभ च0र य नहB ज सकत ह ह Bhartṛhari Nītiśatakam Knowledge is such a treasure which cannot be stolen

2

3

4 Indian Standard PACKAGED AIR CONDITIONERS SPECIFICATION (First Revision ) ICS BIS 2003 BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI Price Group 7

5 Refrigeration and Air Conditioning Sectional Committee, ME 03 FOREWORD This Indian Standard (First Revision) was adopted by the Bureau of Indian Standards, after the draft finalized by the Refrigeration and Air Conditioning Sectional Committee had been approved by the Mechanical Engineering Division Council. This standard was first published in The eperience gained in implementation of this standard necessitates this revision and certain changes that are necessary are incorporated in this revision. The methods of test for room air conditioners of capacity up to W1)(approimately 9000 kcal/h) specified in 1S 1391 (Part 1) : 1992 Room air conditioners Specification : Part 1 Unitary air conditioner (second revision) and IS 1391 (Part 2) : 1992 Room air conditioners : Part 2 Split air conditioners (second revision) are 1imitcd to those making use of room calorimeters. Such methods are considered cumbersome and not suitable for packaged air conditioners of capacity W and above covered in this standard. This standard has, therefore, been prepared to specify psychometric and other methods of test suitable for such units. The quantities have been epressed in International System of Units (S1). The basic units of measurement together \vith their symbols for the various quantities used in the tet have been listed in Anne A. For the purpose of deciding whether a particular requirement of this standard is complied with, the final value, observed or calculated, epressing the result of atestor analysis, shallbe rounded off in accordance with IS 2:1960 Rules for rounding off numerical values (revise~. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard. l] I kcai/h= W.

6 Indian Standard PACKAGED AIR CONDITIONERS (First Revision ) SPECIFICATION 1 SCOPE This standard prescribes constructional and performance requirements and methods for establishing rating of packaged air conditicmers of the nominal cooling capacity W (approimately 9000 kcallh) and above, which operate non-frosting when cooling and dehumidifying at standard rating conditions. 2 REFERENCES The following standards contain provisions, which through reference in this tet constitute provision of this standard. At the time of publication, the editions indicated were valid. All standards are subject to revision and parties to agreements based on this standard are encouraged to investigate the possibility of applying the most recent editions of the standards indicated below: 1S No. 101 (Part 6/ Secl) : : (Part 1) : : : (Part 1) : TERMINOLOGY Title Methods of sampling and test for paints, varnishes and related products : Part 6 Durability tests, Section 1 Resistance to humidity under conditions of condensation (third revision) Atmospheric conditions for testing (revised) General and safety requirements for household and similar electrical appliances (first revision) Three phase induction motors (fifih revision) Single phase small ac and universal electric motors (second revision) Room air conditioners Specification : Part 1 Unitary air conditioners (second revision~ For the purpose of this standard, the following definitions shall apply. 3.1 Packaged Air Conditioner An encased assembly as a self-contained unit primarily for floor mounting designed to provide free delivery of conditioned air to an enclosed space, room, or zone (conditioned space). It includes a prime source of refrigeration for cooling and dehumidification and means for the circulation and cleaning of air, with or without eternal air distribution ducting. It may also include means for heating, humidifying or ventilating air This definition shall also include split air conditioners consisting of an evaporating unit comprising an evaporator coil and a fan (which is located indoors) and a condensing unit comprising a condenser and acompressor [which is usually located outdoors) These machirms are equipped with either watercooled or air-cooled condenser. For the purpose of this definition, the unit for which the air-cooled condenser is built as a separate package for r-emote field installation and interconnection shall also be considered as a packaged air conditioner. 3.2 Standard Barometric Pressure Barometric pressure of kpa ). 3.3 Wet-Bulb Temperature Temperature indicated when the temperature-sensing element and wetted wick have reached a state of constant temperature (evaporative equilibrium) and when air is flowing over the cotton wick at a velocity of 5 to 10 mls, wick is wetted with constant.source of distilled water. 3.4 Discharge Air Flow of a Unit Rate of flow of air from the outlet of the unit. 3.5 Intake Ah Flow of a Unit Rate of flow of air into the unit from the conditioned space. 3.6 Nominal Water Flow Rate Rate of water flow through the condenser of watercooled unit under capacity rating test conditions. 3.7 Nominal Condenser Air Flow Rate Rate of air flow through condenser coil specified as m3/h of standard air at 27 C dry bulb, 65 percent 1)100kPa= 1bar.

7 1S 8148:2003 relative humidity and a pressure of kpa as specified in IS Net Total Cooling Effect of a Unit Total available capacity of the unit for removing of sensible and latent heat from the space to be conditioned. 3.9 Net Dehumidifying Effect (Latent Cooling Effect) Total available capacity of the unit for removing latent heat from the space to be conditioned Net Sensible Cooling Effect Available capacity of the unit for removing of sensible heat from the space to be conditioned Net Sensible Heat Ratio Ratio of the net sensible cooling effect to the net total cooling effect Test Room Any room or space in which the unit is installed for test, with conditioning apparatus to ensure proper temperatures of air and water entering the unit, In case of water-cooled unit single room is required for the evaporator side atong with water handling equipment to feed water into the condenser at desired temperature and rate of flow. In case of air-cooled unit two rooms are required, one for evaporator side and the other for condenser side, each with appropriate conditioning apparatus Rated Voltage Voltage shown on the nameplate of the unit Rated Frequency Frequency shown on the nameplate of the unit. 4 CONSTRUCTION (GENERAL) 4.1 The unit shall be constructed with sufficient strength and rigidity to withstand normal manual and mechanical handling, transportation and usage without damage or failure and shall withstand mechanical strength test as given in 21 of IS 302 (Part 1). 4.2 All parts that require periodic cleaning or maintenance shall.be easily accessible when the unit is installed in accordance with manufacturer s instructions. These shall be resistant to corrosion and withstand neutral salt spray test for 72 hin accordance with 3 of IS 101 (Part 6/See 1). 4.3 Self-tapping screws shall not be used for any load bearing parts or any part that has to be removed for routine maintenance. 4.4 Units shall be free from undue noise and vibration. 4.5 All parts that constitute an accident hazard shall be effectively guarded. 4.6 An adequate.method of condensate removal shall be provided. There shall be condensate tray of adequate size so that no water overflows after 8 h continuous operation at rating conditions of indoor air. The tray and drain shall be made of corrosion-resistant material, or suitably treated with corrosion-resistant coating to withstand neutral salt spray test for 72 h in accordance with 3 of IS 101 (Part 6/See 1). The tray shall be adequately insulated to avoid condensation over its eternal surface. 4.7 Pipes and connections to moving or resiliently mounted parts shall be so arranged as not to foul, or to transmit undue vibrations to other parts and shall be so designed as to prevent failure due to fatigue. All other pipes and connections shall be securely anchored. 4.8 Suitable means shall be provided to prevent water condensed on cold parts of the refrigerating system from affecting the operation of the unit or its controls; Pipes shall be suitably insulated-wherever necessary. 4.9 Water-cooled condenser shall have cleanable water passages, either by mechanical means or chemical or both. An adequate opening shall be provided in the casing so as to have access to the passage: bearing water, from either end, for the design amenable to mechanical cleaning A suitable size refrigerant strainer shall be incorporated in the liquid line immediately before the epansion device All valves and refrigeration piping shall be properly clamped so as to avoid ecessive vibrations Air Filter The air filter shall be of the dry-air type or viscous-oil coated type. It may be of the throwaway type or washable and replaceable type. The filter may be made from synthetic or coconut fibre or any other suitable material, with proper bonding and impregnation to prevent fraying or loosening of fibres under its normal life. 5 DETERMINATION OF COOLING CAPACITY 5.1 Test Methods The following three test methods for total cooling capacity are covered in this standard: a) Psychometric method Evaporator side (see 5.3), 2

8 b) c) Psychometric method Condenser side (see 5.3), and Condenser water method (see 5.4). 5.2 Applicability of Test Methods Equipment within the scope of this standard shall be tested simultaneously by two test methods, one for evaporator side and the other for condenser side. The test results by these two methods shall agree within limits specified in Psychometric Methods General Description In psychometric methods, cooling capacities are determined from measurements of entering andleaving wet and dry bulb temperatures and the associated air flow rate. These methods shall be employed for the evaporator side tests of all equipment. Subject to the additional requirements of 5.3.6, this method may be used for condenser side tests of air-cooled equipment The test apparatus for psychometric methods consists of an air measuring device (see 12) attached to the equipment air discharge (evaporator or condenser as applicable). A conditioning apparatus is attached to the inlet of the unit. This may be done through suitable ducting. Alternatively the test room in which the unit is placed may be supplied with conditioned air through conditioning apparatus. In the latter method the air leaving the unit may be caused to flow completely out of the test room or part of it may be diverted to the conditioning apparatus, so asto create suitable temperature conditions. Suitable means for measuring the wet and dry-bulb temperatures of the air entering and leaving the unit shall be provided. Conditioning apparatus shall consist of arrangement for heating, cooling and humidifying air, along with fans or blowers. Figures 1 and 2 show the typical test arrangement for air-cooled and water-cooled units respectively. NOTE Figures1and 2 whichshowonly typicaltest arrangementare not to be construedas illustratingthe eact layout.suitablemodificationsmaykaveto bemadesoasto ensureminimumlosses Other means of handling the airflow measuring device and supply air at the proper conditions to the equipment inlet may be employed, provided that they do not interfere with the prescribed means of air flow rate, temperature and eternal resistance measurements nor create abnormal conditions surrounding the equipment. S.3.2 Test Room Requirements The test room or rooms shall meet the requirements prescribed in Air Flow Measurement The air flow measuring device shall be in accordance with the provisions of Eternal Resistance Measurement Eternal resistances shall be measured in accordance with the provisions of 13. Connections to equipment outlet shall comply with the provisions of Temperature Measurement Evaporator outlet temperature measurements EVAPORATOR SIDE CONDENSER SIDE \ L CONDITIONING CONDITIONING/ APPARATUS APPARATUS FIG. 1 TYPICALTEST ARRANGEMENTFORAIR-COOLED UNITS 3

9 COOLING TOWER AND CONDITIONING APPARATUS (HEATING AND COOLING) FOR WATER \ WATER FLOW RATE MEASURING DEVICE AIR FLOW MEASURING DEVICE --f / / / / / P MP / \ CONDITIONING WATER TEMPERATURE APPARATUS MEASUREMENTS FIG. 2 TYPICALTEST ARRANGEMENTFORWATER-C OLEDUNITS shal! be made using an air sampiing device as shown in Fig. 3. Thesampling device shall belocatedbeyond the minimum static pressure duct length (see ) to avoid introducing any additional resistance. Ductwork connecting the evaporator outlet to the air flow measuring device shall be insulated between the place of temperature measurement and the evaporator outlet so that heat leakage through the ductwork does not cause a wet bulb temperature rise of more than i).l c Evaporator inlet temperatures shallbe measured using suitable sampling devices covering the inlet area and located approimately 150 mm from the unit inlet or inlets For air cooled units, condenser inlet temperature shall be measured using suitable sampling devices covering the inlet area and located approimately 150 mm from the condenser air inlet or inlets. Condenser outlet temperature shall be measured in the ductwork connecting the unit to airflow measuring device in the same manner as described in For water-cooled units, condenser inlet and outlet temperatures shall be measured with suitable instruments located as close to the unit as possible, Additional Requirements for Condenser Side Use When the psychometric method is employed for condenser or high temperature side tests, it is necessary to ascertain whether the attachment of the airflowmeasuring device changes the performance of the equipment being tested and if so, it should be suitably corrected. 5.4 Condenser Water Method In this method, total cooling capacity is determined from measurements of the condenser water temperature-rise and flow rate. This method may be used for the condenser side tests of water-cooled equipment Water Flow Rate and Temperatures Measurement The condenser water flow rate shall be measured with a suitable liquid quantity or flow meter. Entering and leaving condenser water temperatures shall be measured with suitable instmments located at the equipment water connections. Data shall be taken at 1 minute intervals until seven consecutive sets of 4

10 a 0 a e... DRY BULB THERMOMETER d WET BULB THERMOMETER BLOWER MOTOR FIG. 3 SAMPLINGDEVICE reading agree with the tolerances prescribed in CALCULATIONS 6.1 Psychometric Method Total, sensible and latent cooling capacities (see Note) on the evaporator or low side are calculated by the following equations: where 9, = Qv(h,, - h~,)/vn 9, = Qv(t,, t~z)/vn 9, = Q, (we, Wc2)/~n 9, = evaporator side total cooling capacity, in w; 9, = 9, = Qv = v,, = h= c1 h=.1 t= cl t= C2 we, = evaporator side sensible cooling capacity in W; evaporator side latent cooling capacity, in w; measured evaporator airflow rate, in m3/s; specific volume of air at place of air flow measurement, in m3/kg dry ai~ enthalpy of air entering equipment, in J/kg dry ai~ enthalpy of air leaving equipment, in J/kg dry ai~ dry-bulb temperature of air entering equipment, in C; dry-bulb temperature of air leaving equipment, in C; humidity ratio of air entering equipment, in kg, water per kg dry ai~ and we2 = humidity ratio of air leaving equipment, in.kg, water per kg dry air. NOTE These are the capacities delivered to the ductwork by the equipment under test. They do not take into account heat transfer through equipment casings, which normally are less than 2 percent of the capacity, nor evaporator fin motor heat when a fan is not fumiahed with the equipment. Where desired, casing transfer may be measured with the calorimeter method arrangement Total cooling capacity based on condenser side data is calculated by one of the following equations: 9,, = Qm (hc,-ac,) / Vn- E, or for air-cooled equipment which does not reevaporate condensate only where 9,. = Q., = v = hc, = hc2 = t= cl t= C2 E, = 9,C = 1.02 X103QV(tc,- t,,) /Vm- Et condenser side total cooling capacity, w; measured condenser air flow rate, in m3/s (see 12); specific volume of air at place of air flow measurement, in m3/kg dry aih enthalpy of air entering equipment, in J/kg dry ai~ enthalpy of air leaving equipment, in J/kg dry ai~ dry-bulb temperature of air entering equipment, in C; dry-bulb temperature of air leaving equipment, in C; and total power input to equipment, in W. in 5

11 6.2 Condenser Water Method Total cooling capacity based on condenser side data is calculated by the following equation: where 9,, = w= = c= t= W2 t= WI E, = 9,, = WCC (tw2- tw,) Et condenser side total cooling capacity, in w; condenser water flow rate, in kgls; specific heat of water, in J/kg C; temperature of water leaving equipment, in C; temperature of water entering equipment, in C; and total power input to equipment, in W. 7 RATING REQUIREMENTS 7.1 Tolerances To comply with this standard, published or reported ratings shall be based on conditions specified in 7.2 to 7.6 and shall be such that the performance of any production unit shall have a capacity not less than 90 percent of the stated capacity. 7.2 Cooling Capacity R-stings Cooling capacity ratings shall be based on tests conducted under condhions specified in 9.1 and with apparatus described in 12 and 13. Ratings shall include the total cooling capacity and the latent cooling capacity. 7.3 Discharge Alr Flow 12atings Discharge air flow ratings shall be stated.in cubic metres per hour of standard air at 27 C dry bulb, 65 percent relative humidity and a pressure of kpa as specified in IS 196 with the controls set for maimum cooling and with the fresh air properly closed and with eternal resistance adjusted in accordance with manufacturer s instructions. 7.4 Eternal Static Pressure Rating This is the static pressure rating eternal to the unit, against which the specified discharge of airflow occurs. This pressure is a necessary requisite to overcome friction losses in field conditions such as those produced, for eample ducting. 7.5 Condenser Cooling Medium Flow Rating The flow rating of cooling medium for condenser shall be specified by the manufacturer, in kg/s. Rated flow rate of cooling water shall be maintained for the condensel during capacity rating test. In other tests the flow rate of cooling medium shall be maintained as per test conditions described in Electrical Heating Capacity Rating An air conditioner equipped with an electrical heating element or elements shall have its electrical heating capacity ratings determined by measurement of the total electrical power consumed by the unit. 7.7 Electrical Ratings Ratings, in watts, for packaged air conditioner shall be based on rated voltage. The units, however, shall be capable of working at any voltage within +10 percent of the rated voltage. 7.8 Rated air quantities shall not eceed 64 m3/h per 300 W of rated cooling capacity. The minimum eternal resistance for the range of cooling capacity shall be specified by the manufacturer and shall not be less than the values given below: Cooling Capacity w Eternal Resistance, A4in Pa In interpreting the requirements, it is understood that the filters, heating coils and other equipment recommended as part of the unit be in place and that the net eternal resistance specified above are available for the duct system. 7.9 All standard ratings for the air-cooled units shall be determined at condenser air quantity specified by the manufacturer, where the speed of the fan is adjustable. However, the manufacturer need not necessarily speci~ the condenser air quantity where the fm speed is nonadjustable, in which case, the ratings shall be determined at the condenser air quantity inherent in the unit when operated with alltheresistance elements associated with the inlet louvers, ductwork and other attachments considered by the manufacturer asnormal in installation practice. Once established, the condenser air circuit of the unit shall remain unchanged throughout all the tests prescribed in this standard. 8 BASIS OF RATINGS 8.1 For the purpose of rating, information shall be provided regarding the functions, which the unit performs under rating conditions as per capacity rating test given in 9.1, namely: a) b) c) d) e) Cooling; Dehumidifyin& Heating, if provided; Air circulating; and Filtering. 6

12 8.2 In addition to the above, the following information shall be furnished by the manufacturer as and when desired: a) b) c) d) e) f) g) h) j) k) m) Manufacturer s name and address; Model, size or type; Net total cooling effect; Total air capacity and eternal static pressure; Required rate of water/air flow and its pressure drop across condenser; Name of refrigerant; Weight of the refrigerant charged into the unit Power input of each motor separately; Total power:input; Nameplate ratings of each motor; and Manufacturer s installation and operatirtg instructions. NOTE All capacity ratings and power input shall be under the same conditions as for capacity rating test. 9 RATING AND TEST CONDITIONS 9.1 Capacity Rating Test Condition The package air conditioner shall have nameplate rating determined by test conducted at the standard rating condition specified below: Evaporator side inlet air temperature: a) Dry bulb 27 C b) Wet bulb 19 C Condenser side inlet air temperature: a) Dry bulb 35 c b) Condenser water inlet 30 c temperature c) Condenser water outlet 35*C, Min temperature Test voltage ) Rated voltage Test frequency Rated frequency 9.2 Maimum Operating Test Condition The maimum operating tests shall be conducted under the conditions specified below: Evaporator side inlet air temperature: a) Dry bulb 35 c b) Wet bulb.24 C Condenser side inlet air temperature: a) Dry bulb 46 C b) Condenser water inlet 34 C temperature c) Water flow rate Same as in 9.1 Test voltage: a) For units with a single 90 and 110 percent voltage rating b) For units with a dual 90 percent, Min. voltage rating 110 percent, Ma Test frequency Rated frequency 9.3 Freeze-up Test Conditions Freeze-up tests shall be conducted under the conditions specified below: Evaporator side inlet air temperature: a) Dry bulb 21 C b) Wet bulb 16 C Condenser side inlet air temperature: a) Dry bulb 21 c b) Condenser water inlet 19 C temperature c) Water flow rate Same as in 9.1 Test voltage ) Rated voltage Test frequency Rated frequency 9.4 Enclosure Sweat Test Conditions The enclosure sweat test shall be conducted under the conditions given below: Evaporator side inlet air temperature: a) Dry bulb 27 C b) Wet bulb 24 C Condenser side inlet air temperature: a) Dry bulb 27 C b) Condenser water inlet 27 C temperature c) Water flow rate Same as in 9.1 Test voltagei) Rated voltage Test frequency Rated ffequency 9.5 Condensate Disposal Test Conditions Condensate disposal test shall be conducted under the same conditions as those specified for enclosure sweat tests (see 9.4). 10 PERFORMANCE REQUIREMENTS 1O.1 Capacity Rating Test Purpose The purpose of the capacity rating testis to determrne the magnitude of the following functions: a) Net total cooling effect, b) Net dehumidifying effect, c) Net sensible cooling effect, I)unlt~withdualratedvoltages shall be tested at the iower vohage. I)Unit5 with dual mted voltages shall be tested at higher voltage. 7

13 d) Net total air capacity for cooling, e) Eternal resistance to evaporator airflow, and f) Total power input to equipment (see 10.6) or power inputs to all equipment components. 10.1,2 Test Condition Capacity rating test shall be conducted under the conditions specified in 9.1. The air conditioners shall be in the condition as normally intended for use. Filters and grills where supplied shall be in position Test results shall be used to determine capacities without adjustment for permissible variations in test conditions ecept as specified for deviations from standard barometric pressure Capacities may be increased by 2.4 percent for each 10 kpa of barometric reading below kpa at which the tests were conducted Procedure Two simultaneous methods for determining capacities shall be used. One method shall determine capacity on the evaporator side and the other shall determine the capacity on the condenser side. The total cooling capacity will be the average of the two simultaneous y conducted methods of test, which shall agree within 6 percent. Sensible and latent cooling capacities shall be those determined from the evaporator side test multiplied by the ratio of the average total cooling capacity to the evaporator side total cooling capacity. The air conditioner shall be tested in test room complying with 12. Room discharge airflow measurement shall be in accordance with Test conditions shall be maintained until equilibrium has been reached and maintained for not less than one hour, before recording data for the capacity test. The test shall then be run for 2 h recording data every 15 min. lfj The data to be recorded for this test is given in Table 1. This table shows general information required, but is not intended to limit the data to be obtained. Items required for different test methods are indicated by an under the test method columns. Table 1 Data to be Recorded (Clauses and ) s] Hem Units PsychromaticMethod Condenser A No. f. WaterMethod Evaporator Condenser Side Side (1) (2) (3) (4) (5) (6) i) ii) iii) iv) v) vi) vii) viii) i) ) i) ii) iii) iv) v) vi) vii) viii) i) ) i) ii) Date and time Observers Barometric pressure Equipment nameplate data Eternal resistance to evaporator air tlow Power input to equipment (see Note l) Applied Frequency Fan speed(s), voltage(s) if adjustable Dry-bulb temperature of air entering equipment Hot-bulb temperature of air entering equipment Dry-bulb temperature of air leaving equipment Wet-bulb temperature of air leaving equipment Throat diameter of nozzle(s) Velocity pressure at nozzle throat or static pressure difference across nozzle(s) Temperature Pressure at nozzle at nozzle throat Condensing pressure or temperature Evaporator pressure or temperature Condenser water flow rate Temperature of condenser water entering equipment Temperature of condenser water leaving equipment kpa Pa w v Hz Rev/rein c c DC Oc m Pa c Pa Pa, C Pa, C kgk Oc OC (see Note2) (see Note2) NOTES I Total power input and, where-required, input to equipment components. 2 Required for evaporative-cooled equipment and equipment which re-evaporates condensate. 8

14 Test Tolerances All test observations shall be within the variations allowed as specified in Table 2, as appropriate to the test methods and type of equipment The maimum permissible variation of any observation during the capacity test is listed under maimum variation of individual reading from rating conditions in Table 2. This represents the greatest permissible difference between maimum and minimum instrument observations during the test. When epressed as a percentage, the maimum allowable variation is the specified percentage of the arithmetical average of the observations Variations greater than those prescribed shall invalidate the test Maimum Operating Conditions Test Purpose The purpose of this test is to prove that the air conditioner is capable of operating satisfactorily under maimum operating conditions Test Conditions The maimum operating conditions test shall be conducted under the conditions specified in 9.2. The unit s controls should be set for maimum cooling Voltage Adjustment Test voltage shall be.as specifiedin 9.2. These voltages shall be maintained at the rated voltages *2 percent under running conditions. The electrical service supplied to the unit service connection shall be such that the voltage will not rise more than 3 percent when the unit is stopped Procedure The packaged air conditioner shall be operated continuously for 2 h atler the specified air temperatures and equilibrium condensate level have been established. All power to the packaged air conditioner shall then be cut off for 3 min and then restored for 1 h Requirements During one entire test, the packaged air conditioner should operate without visible or audible indication of damage The packaged air conditioner motors should operate continuously for the first 2 h of the test without tripping of the motor overload protective devices The motor overload protective device may trip only during the first 5 min after the shut-down period of 3 min. During the remainder of that 1 h test period, no motor overload device shall trip For the models so designed that resumption of operation does not occur afier initial trip within the first 5 rein, the unit may remain out of operation for not longer than 30 min. It shall then operate continuously for 1 h Freeze-Up Tests Purpose The air blockage test and drip test shall -be conducted to determine the ability of the air conditioner to operate Table 2 Test Tolerances (Clauses and ) SI Reading VariationofArithmeticalMean Values Maimum Variation of Individual No. from Specified Test Conditions Reading from Rating Conditions (1) (2) (3) (4) i) ii) iii) iv) v) vi) vii) viii) i) Temperature of air entering indoor side : a) Dry-bulb b) Wet-bulb Temperature of air leaving indoor side Temperature of air entering outdoor side : a) Dry-bulb b) Wet-bulb Temperature of air leaving outdoor side Dry-bulb Air volume Voltage flow rate Water temperature : a) Inlet b) Outlet Water volume flow rate Eternal resistance to airflow * 0.3 C * 0.2 C * 0.3 C * 0.2 C * 1.O c * 5%0 i 1 A *0. I C * O.l c * 1 /0 +5Pa * I.ow.* 0.5 C * 1.Ow * 1.Wc 0.5T i.t.wc * 1o% 2% * 0.2V 0.2T * 2% * 10 Pa 9

15 1S 8148:2003 satisfactorily under conditions with the maimum tendency to frost or ice the evaporator Test Conditions Freeze-up test shall be conducted under the conditions given in 9.3. The unit s controls, fan speeds, dampers and grills should be set to produce the maimum tendency to frost or ice the evaporator, provided such settings are not contrary to the manufacturer s operating instructions Air Blockage Test Procedure The test should be continuous, with the unit on the cooling cycle for 12 h after establishment of the specified temperature conditions Requirements At the end of 12 h, the accumulation of ice or frost on the evaporator shall not obstruct the air passing through the evaporator coil Drip Test Procedure The units should be operated for 6 h with the room side air inlet covered to completely block the passage of air so as to attempt to achieve complete blockage of the evaporator coil by frost. After the 6 h operating period, the unit shall be stopped and the air-inlet covering removed until the accumulation of ice or frost has melted. The unit shall then be turned on again, with the fan operating at the highest speed, for 5 min Requirements During the test no ice shall drop from the unit, and no water shall drip or blow off the unit on the room side Enclosure Sweat Test Purpose The purpose of this testis to determine the resistance to sweating of the air-conditioner when operating under conditions of high humidity Test Conditions An enclosure sweat test shall be conducted under the conditions specified in 9.4. The unit s controls, fans, dampers and grillers shall be set to produce the maimum tendency to sweat, provided such settings are not contrary to manufacturer s operating instructions Procedure After establishment of the specified temperature conditions, the unit shall be operated continuously for a period of 4 h Requirements During the test, no condensed water shall drip, run or blow off the unit Condensate Disposal Test Purpose The purpose of this testis to determine the capability of the air condhioner to dispose off condensate. This test may be conducted concurrently with the-enclosure sweat test (see 10.4) Test Conditions A condensate disposal test shall be conducted under the conditions specified in 9.5. The unit s controls, fans, dampers and grillers shall be set to produce the maimum tendency to sweat, provided such settings are not contrary to manufacturer s operating instructions Procedure After establishment of the specified temperature conditions, the packagedair conditioner shall be started with its condensate collection pan filled to the overflowing point, and shall be operated continuously for 4 h after the condensate level has reached equilibrium Requirement During thistest, the packaged air conditioner shallhave the ability to dispose of all condensate and there shall be no dripping or blowing off of water from the unit such that the building or surroundings may become wet Power Consumption Test Purpose The purpose of the power consumption test is to determine the power consumption, in watts Test Condition m,..,.,,,--,.-..-,,-.. i ne power consurnpuon snail De aetermmea aurmg the capacity rating test (see 10.1) under the condition given in Test Procedure The power consumption shall be the average power consumption in watts measured during the capacity rating test (see 10.1 and Table 1) The maimum power consumption when measured during thecapacity rating test (see 10.1) under the conditions given in 9.1 shall be as given below:

16 Cooling Capacip Watts Tons of Refrigeration INSTRUMENTS r Maimum P@wer Consumption in Watts w Water Air Cooled Cooled Temperature Measuring Instruments Temperature measurements shall be made with one or more of the following instruments: a) Mercury-in-glass thermometers, b) Thermocouples, and c) Electric resistance thermometers Instrument accuracy shall be within+ O.1 C In no case shall be smallest scale division of the temperature-measuring instrument eceeding twice the specified accuracy In all measurements of wet bulb temperatures, sufficient wetting of the wick with distilled water shall be provided and sufficient time shall be allowed for the state of evaporative equilibrium to be attained. Air velocities over the wet bulb temperature measuring instruments shall be 5 to 10 mk. The same air velocity shall be maintained for the inlet and outlet temperature measurements. Figure 4 shallbe used to correct wetbulb temperature readings at air velocities below 5 m/s Wherever possible, temperature measuring instruments used to measure the change in temperature shall be arranged so that they can be readily interchanged between inlet and outlet positions to improve accuracy Temperature of fluids within conduits shall be 15.6 C O\O II 18 /, II 26.7 r -6.7 C WET BULB TEMP(UNSHIELDED) C VELOCITY. m/s FIG. 4 THE EFFECTOF AIR STREAMVELOCITYON THEWET-BULB PSYCHROMETER 11

17 1S 8148:2003 measured by inserting temperature measuring instrument directly within the fluid or within a well inserted into the fluid. Ifaglass thermometer is to be inserted directly into the fluid, it shall be calibrated for the effect of pressure Temperature measuring instruments shall be adequately shielded from radiation from any adjacent heat source Pressure Measuring Instruments Accuracy of pressure measuring instruments for measuring air pressure shall permit measurements within + 5 Pa In no case shall the smallest scale division of the temperature-measuring instrument eceeding twice the specified accuracy Barometric pressure shall be measured by a barometer having scale markings permitting readings with an accuracy within percent An evaporator or low side test room is always required. This may be any room or space in which the desired test conditions can be maintained within the permissible tolerances. It is recommended that air velocities in the vicinity of the equipment under test do not eceed 2.5 mls An adjacent condenser or high side test room or space is required for tests of air-cooled equipment. This test room shall be of sufficient volume and shall circulate air in a manner such that it does not change the normal air-circulating pattern of the equipment under test. Dimensions shall be such that the distance from any room surface to any equipment surface from which air is discharged is not less than 2 m and the distance from any other room surface to any other equipment surface is not less than 1 m ecept for floor or wall relationships required for normal equipment installation. The room conditioning apparatus shall handle air at a rate not less than the condenser airflow rate Electrical Instruments Electrical measurements shall be made with either indicating type or integrating type of instruments Instruments used for measuring all electrical inputs to the calorimeter compartments shall be accurate to percent of the quantity measured Water Flow Measuring Instruments Volume measurements shall be made with either of the following instruments having an accuracy of * 1 percent of the quantity measured: a) Liquid quantity meter, measuring either mass or volume; and b) Liquid-flow-rate meter Liquid quantity meter shall employ a tank having sufficient capacity to accumulate the flow for at least 2 min Other Instruments ] Time interval measurements shall be made with instruments whose accuracy is +0.2 percent of the quantity measured Mass measurement should be made with apparatus whose accuracy is+ 1percent of the quantity measured. 12 TEST PREPARATION 12.1 Test Room Requirements Either one or two adjacent test rooms are required, depending upon the type of equipment to be tested and the manufacturer s installation instruments Equipment Installation 12.2;1 The equipment to be-tested shall be installed in the test room or rooms in accordance with the manufacturer s installation instructions using recommended installation procedures and accessories. Self-contained water-cooled equipment shall be located entirely within the evaporator side test room; air-cooled self contained equipment shall be located in or adjacent to an opening in the wall or partition separating the test rooms in accordance with the normal or primary recommendations of the manufacturer. In all cases, the manufacturer s recommendations with respect to distances from adjacent walls, amount of etension through walls, etc, shall be followed No alterations to the equipment shall be made ecept the attachment of required test apparatus and instruments in the prescribed manner Where necessary, equipment shall be evacuated and charged with the type and amount of refrigerant specified on the nameplate or as prescribed in the manufacturer s instructions When required, pressure gauges shall be connected to the equipment only through short lengths of small diameter tubing and shall be located so that the readings are not influenced by fluid head in the tubing No changes shall be made in fan speed or system resistance to correct for barometric variations. 13 AIR FLOW MEASUREMENT 13.1 Air Flow Determination The following air quantities may be measured

18 using the apparatus and testing procedures described in 13 of IS 1391 (Part 1): a) Room discharge airflow, and b) Ventilation airflow Specified eternal static pressure shall be maintained inside adischarge duct attached to the outlet of the unit under test (UUT) and having cross-sectional dimensions equal to the dimensions of the UUT outlet as shown in Fig. 5. This static pressure measurement duct shall discharge into air measuring device, either directly or through suitable connecting ducting. Minimum straight length of the static pressure duct shall be 2.5 times the equivalent diameters [that is, 2.5 1(A B) for rectangular ducts] and static r 7r pressure measurement shall be done at a distance of 2~~ from the UUT outlet, where A and B are the cross-sectional dimensions of the unit outlet. The static pressure measuring duct shall be proceeded by a flow straightening section, of equivalent diameter length to prevent cross flow at the pressure tap, which is to be set perpendicular to the flow A static pressure measurement tap shall be provided at the center of each face and all the taps shall be manifolded eternally for averaging. One side of a manometer (or differential pressure transducer) shall be connected to this manifold and the other side shall be open-to the surrounding atmosphere. 14 NOISE LEVEL OF PACKAGED AIR CONDITIONERS The noise level for packaged air conditioners shall be as low as possible. f STATIC PRESSURE TAPS I TO AIRFLOW MEASURING APPARATUS f > MANOMETER PLENUM NOTE A and B are outlet dimensions. FIG. 5 EXTERNALSTATICPRESSUREMEASUREMENT 13

19 NOTE It is recognized, that packaged air conditioners are usually located away from the conditioned space and the supply air as well as return air is handled through ducting. In some instances the packaged air conditioner is located directly in the conditioned space and conditioned air is supplied through a plenum chamber placed on the outlet(s) of the unit. It is recommended that the internal surfaces of the ducting, plenum chamber, as well as the packaged air conditioner should be acoustically treated so as to create suitably low noise level in conditioned space. The acceptable noise level and the corresponding acoustic treatment will naturally vary from establishment to establishment. With the intention ofprovidkrg general guidelines, it may be stated that in applications where supply and return airis handled by ducting, the noise level in conditioned space should beoftheorderof55 to66db when measured on A scale. For applications-where packaged air conditioner is located within the conditioned space, noise level of65 to70dbon A scale maybe permitted. 15 TESTS 15.1 Classification of Tests Tests shall be classified into the following three groups: a) Production routine tests, b) Type tests, and c) Acceptance tests Production Routine Tests These shall consist of routine tests that would be conducted on each and every unit after completion at the manufacturer s works (see 15.3) Type Tests The type tests shall consist of the tests that would be necessary to check up the performance and characteristics of the units and components, and shall be carried out by a recognized testing authority that may be the manufacturer if approved by thepurchaser. Once a packaged air conditioner has undergone type tests, any minor or essential alterations, which the manufacturer intends to make, shall be reported to the testing authority (see 1 5.4) Acceptance Tests lf the purchaser desires any of the production routine tests to be repeated at the time of purchase, then, where agreed to between the purchaser and the manufacturer, the tests may be carried out at the manufacturer s works; alternatively the tests may be repeated at the place specified by the purchaser provided that all the arrangements for tests are made by the purchaser at the specified place Sample for Tests Type Tests Two packaged air conditioners of each size shall be sent-along with manufacturer s detailed specifications to the recognized testing authority for purposes of type tests. The samples shall be picked up at random from stock or routine factory production Acceptance Tests The number of samples shall be as agreed to between the manufacturer and the purchaser Production Routine Tests General Running Test Each unit shall be given a run to ensure vibration-free and thorough running of mechanical parts Pressure Test or Leakage Test No part of the assembly under test shall show signs of refrigerant leakage greater than 3 g/year under normal working pressure when tested with a leak detector. This shall be in addition to the manufacturer s production test on each unit at the appropriate pressure corresponding to the refrigerant used Insulation Resistance Test The insulation resistance between all electric circuits and the metal parts when measured at normal room temperature with a voltage of not less than 500 Vdc shall be not less than one meghom, High Voltage Test The electrical insulation of all circuits shall be such as to withstand a test voltage of 2000 V rms applied for not less than 2s between circuits and accessible metal parts atnormal room temperature. The testvoltage shall be alternating approimately sine wave form and of any convenient frequency between 25 Hz and 100 Hz Performance Test Measurement shall be made of the following under the prevailing ambient conditions and the performance figures from (a) to (e) shall be compared with the unit, which has already passed the type test: a) b) c) d) e) o Temperature of air entering the unit, Temperature of the air leaving the unit, Air flow, Current consumption, Voltage, and Wattage. A vane type anemometer maybe used for comparing the airflow of the production unit and the type tested unit. NOTE The tests at and 15.3,2 may be carried out separately on each indoor and condensing unit by interconnecting. These tests on the interconnected units may be carried out as per sampling plan as agreed between manufacturer and purchaser. 14

20 15.4 Type Tests Besides all the production routine tests outlined in 15.3, thetype tests shall comprise the following: a) Capacity rating andothertests specified in9. b) Room discharge air flow rating test in accordance with.procedure given in 13 and under conditions in 7.3; c) Electrical rating (that is, measurement of current in.amperes and power input and energy consumption at rated voltage and frequency of the blower fan motor and compressor motor) under conditions specified in 7.7; and d) Test for fan or blower motor to determine the conformity to the requirements specified in IS 996 and IS 325. NOTE The BIS Certification Mark on motors for fan and compressors guarantees conformity of the motors to IS 996 and IS 325. If the purchaser so desires, type test certificate maybe obtained from the manufacturer The type test repmt shall also contain the nameplate particulars of the packaged air conditioners for purposes of identification. 16 MANUFACTURER S GUARANTEE The manufacturer shall give a guarantee for the soundness of construction and performance of the air conditioner, and shall be responsible for putting right any manufacturing defects free of charge for a period of 12 months right from the date of sale to the original purchaser or date of inspection or approval in the case of government or semi-government institutions. Such repairs or replacements of defective parts shall be carried out as per the manufacturers guarantee policy agreed upon by the manufacturer and the purchaser. 17 MARKING 17.1 The packaged air conditioner shall have the following information marked in a nameplate in a permanent and legible manner in a location where it is accessible and visible: a) Name and address of the manufacture~ b) Type of model number and serial number of the unit; c) Power supply in...v... phase...hz. d) FuII load amperage; -e) Name and quantity of refrigerant charge; f) Nominal capacity, in W, under temperature conditions specified in this standard; g) Power consumption, in W, at the normal operating conditions specified in =this standard; and h) Locked rotor amperage BIS Certification Marking Each unit may alsobe marked with the Standard Mark The use of the Standard Mark is governed by the provisions of the Bureau of Indian Standard Act, 1986 and the Rules and Regulations made thereunder. The details of conditions under which a licence for the useof Standard Mark maybe granted to manufacturers or producers may be obtained from the Bureau of Indian Standards. 15

21 ANNEX A (Forewor~ BASIC UNITS OF MEASUREMENT AND THEIR SYMBOLS sl No. Quantity International System (S1) Units Metric Units Name of Unit Symbol Name of unit Symbol i) Air mass flow rate Air volume flow rate Kilogram per second Cubic metre per kgls m31s Kilogram per hour Cubic metre per kgih m ih ii) Air specific humidity second Kilogram per kilogram kg/kg hour Kilogram per kilogram kglkg iii) Air specific volume Cubic metre per kilogram m3/kg Cubic metre per kilogram m3/kg iv) Air static pressure or dynamic pressure Pascal 1) Pa Millimeter of water mm H20 v) Air velocity Metre per second ds Metre per second In/s vi) Air volume Cubic metre m Cubic metre m3 vii) Area Square metre m Square metre m viii) Barometric pressure Pascal Pa Bar Millibar Millimetre of mercury (torr) bar mbar mmhg i) ) Cooling effect Dehumidifying effect Watt Watt w w Kilocalorie per hour Kilocalorie per hou?) kcallh keal/h i) Electric current input Ampere A Ampere A ii) Electric frequency Hertz Hz Hertz Hz iii) Electric power input Watt w Watt w iv) Specific enthalpy Joule per kilogram J/kg Kilocalorie per Kilogram2) kcallkg v) Rotating speed Radian per second rad/s Turn per second Turn per minute trfs tr/min vi) Heat flow rate Watt w Kilocalorie per hour kcallh vii) Heat leakage rate Watt w Kilocalorie per hour kcal/b viii) Linear measurements Metre Millimetre m mm Metre Millimetre m mm i) Temperature Interval of temperature Kelvin Kelvin K K Degree celsuis Degree celsuis c c ) Water mass flow rate Kilogram per second kgfs Kilogram per hour kg/h i) Acceleration Metre per square rn/s2 Metre per square second m/s2 1) I Pa= 1 N.m2= 10-5bar. 21 Kilocalorie 15 C = kj. 16

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Schedule 3(A) Room Air Conditioners

Schedule 3(A) Room Air Conditioners Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To nformation Whereas the Parliament of ndia has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC & hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998

Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 ABC FOUR CORNERS Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 Reverse Cycle, High Wall Mounted, Non-Ducted, Single Phase, Single Split System Air Conditioner OPTICAL ACC-25V2 Report No. 30W-07-0038-TRP-221466-0

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

AIR CONDITIONING TECHNOLOGY

AIR CONDITIONING TECHNOLOGY AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

MEMBRANE VACUUM MINI PUMPS

MEMBRANE VACUUM MINI PUMPS MEMBRANE VACUUM MINI PUMPS The mini pumps described in this page are membrane-type. They can be used both as vacuum pumps and compressors. In the latter version they can supply compressed air 100% oil-free

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None 1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

A Guide to Trouble-Free Cooling Towers

A Guide to Trouble-Free Cooling Towers A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Evaporative Cooling for Residential and Light-Commercial

Evaporative Cooling for Residential and Light-Commercial EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Environment-Laboratory Ambient Conditions

Environment-Laboratory Ambient Conditions ISSUE 3.0: MADE MINOR CLARIFICATION CHANGES. FOR CLIENT LABS Purpose To assure laboratory conditions are stable during the performance of testing and data collection. Why this requirement is important?

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

Operating Instructions Air Conditioner

Operating Instructions Air Conditioner F566272 Operating Instructions Air Conditioner CS-C18FFH CS-C28FFH CU-C18FFH CU-C28FFH ENGLISH Before operating the unit, read these operating instructions thoroughly and keep them for future reference.

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010 Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the

More information

Disclosure to Promote the Right To Information

Disclosure to Promote the Right To Information इ टरन ट म नक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information

More information