Controlling a 2-phase CO 2 loop using a 2-phase accumulator

Size: px
Start display at page:

Download "Controlling a 2-phase CO 2 loop using a 2-phase accumulator"

Transcription

1 ICR07-B2-6 Controlling a CO 2 loop using a accumulator Bart VERLAAT National Institute for Nuclear Physics and High Energy Physics (NIKHEF) P.O. Box 42, 009 DB, Amsterdam, the Netherlands bverlaat@nikhef.nl Telephone: / Fax: ABSTRACT Mechanically pumped fluid loops often have the problem of insufficient sub-cooling to operate the pumps without cavitation. This paper describes the use of accumulators for controlling CO 2 loops to obtain forced sub-cooling and accurate evaporator control. The technique of using accumulators for loop control was first applied in satellite cooling. Two accumulator controlled loops have been successfully developed at NIKHEF. One CO 2 loop for cooling the AMS particle detector which will study cosmic radiation onboard the International Space Station and a second CO 2 loop is developed for cooling the LHCb-VELO particle detector which will study CP-violation at the CERN laboratory in Geneva (Switzerland). A accumulator has the advantage of controlling the evaporator and condenser pressures independent of the primary cooler temperature. It is therefore possible to create as much sub-cooling for the pump as desired. It is even possible to operate the loop in single phase, a feature which turns out to be very convenient during start-up and cooling-down procedures. A accumulator for evaporator pressure control in combination with an internal heat exchanger between the liquid feed and the return line creates a very stable evaporator with a guaranteed evaporation at low vapor qualities. In this way the evaporator heat transfer can be tuned and evaporator dry-out is prevented.. INTRODUCTION The semiconductor silicon tracking detectors of the Alpha Magnetic Spectrometer (AMS) (Borgia, 200) on the International Space Station (ISS) and the LHCb-VErtex LOcator Experiment (VELO) (LHCb collaboration, 200) at the CERN s Large Hadron Collider (LHC) require accurate thermal control of the silicon sensors. The readout electronics of the sensors produce the heat which a cooling system should remove. Construction material used inside silicon detectors must be of low mass and tolerant to ionizing radiation. To suppress radiation damage of the silicon detectors, the silicon must be kept cold to sub-zero temperatures at all times (Rose collaboration, 999). A silicon tracking detector consists of multiple silicon sensors which are uniformly spread over the detector volume. All the silicon sensors need to have equal temperatures within or 2 degrees to avoid thermal stresses. The discussed requirements for a silicon detector cooling system such as: low mass, multiple heat sources, small temperature gradients and radiation resistance, give design constraints to the cooling system which are different from conventional cooling systems.

2 The requirements of the cooling system for the Figure.: The AMS experiment on the ISS LHCb VELO detector have led to the use of CO 2 as evaporative cooling fluid (Boer Rookhuizen et al. 999). CO 2 was selected as coolant because of the radiation hardness and the proper temperature range. Feasibility tests have shown excellent thermal performance of CO 2 in small diameter evaporators, which is a welcome feature for a cooling system were low mass is required. The development of CO 2 evaporative cooling at NIKHEF was simultaneous to the developments of CO 2 cooling in the commercial refrigeration industry. The AMS Silicon Tracker required a cooling system which can keep the evaporator section at a constant temperature. In space the background temperature is around 4 Kelvin, heat can be rejected to space from radiator panels. These radiators have a fluctuating temperature due to the changing exposure to the sun and earth. At NIKHEF a mechanically pumped CO 2 loop was developed for the cooling of the AMS Silicon Tracker. This cooling system is named AMS-Tracker Thermal Control System (AMS-TTCS), (Verlaat et al., 2002). The temperature in the evaporator is controlled by a accumulator control mechanism which is used in capillary pumped loop systems, which were under development for satellite cooling (TPX Space Shuttle experiment), (Delil, et al. 997). The accumulator keeps the pumped loop at a constant system pressure. The evaporator temperature is therefore fixed, as long as saturated liquid is flowing through it. The temperature variation in the sub-cooled liquid from the condenser is heated by the internal heat exchanger. In this way it is possible to keep the evaporator constant at a fluctuating heat sink, without additional heating or mechanical control. This is important in space, because power is limited and mechanical actuators have a too large risk of failure. The method of controlling a loop with a accumulator as it was done in the AMS-TTCS is well suited for the use in the cooling cycle of the LHCb-VELO detector. This cooling system is named VELO Thermal Control System (VTCS) (Verlaat, 200). The cold radiator of the AMS-TTCS is replaced by a conventional refrigeration system. This combination allows temperature control of the VELO detector at a large distance (~0m), without any control actuators in the radiation area, resulting in a complete passive evaporator system. This paper describes the design and testing of a accumulator controlled loop (2PACL) developed for the VELO Thermal Control System. Evaporator with 27 parallel connections Figure.2: The LHCb VErtex LOcator Beam-pipe 27 VELO modules

3 2. THE 2-PHASE ACCUMULATOR CONTROLLED LOOP FOR THE VTCS 2. PRINCIPLE OF A 2-PHASE ACCUMULATOR CONTROLLED LOOP (2PACL) 4 Heater Accumulator gas R404a chiller gas Condenser Transfer lines Cooling plant area (Ca. 0m) VELO area Inside VELO 0 Pump 2 2 liquid 4 6 Concentric tube Restriction Evaporator 9 7 liquid Figure 2.: Schematic of the VELO Thermal Control System Figure 2. shows the schematic diagram of the 2PACL as it is applied in the VELO. A mechanically pumped CO 2 loop is cooling the VELO detector by evaporating low quality CO 2 (9-0). The vapor is condensed by a chiller with R404a as refrigerant (-). The condensed liquid is pumped by a liquid pump back towards the detector (2--). The evaporator and condenser work at the same pressure, because the pressure drop of the vapor return line is low. The CO 2 pressure is controlled by the accumulator (4) which is parallel connected between the condenser and the pump (). The accumulator contains a saturated CO 2 liquid-vapor mixture. The temperature of the saturated mixture in the accumulator is regulated, controlling the accumulator pressure hence the condenser and evaporator pressure. The pressure regulation of the accumulator is a combination of heating and cooling. An electrical heater is evaporating liquid CO 2 causing the pressure to increase, an evaporator branch of the primary R404a chiller is condensing CO 2 vapor causing the pressure to decrease. 2x 0 4 Internal heat exchanger brings evaporator pre-expansion 0 4 per definition right above saturation (-)=-(0-) P [kpa] Accumulator pressure = detector temperature Pump is sub cooled Capillary expansion brings evaporator in saturation Te rtia ry VTCS in P-H dia gr am Saturation line 0 C 2 0 C -0 C 4-20 C C 0-40 C Detector load (9-0) x h [kj/kg] Figure 2.2: Operation of a 2PACL in the P-h diagram of CO 2 In order to ensure sub-cooling of the CO 2 before the liquid pump, the accumulator temperature must be above the condenser temperature. The sub-cooled state will prevent the pump from cavitation, a common problem in mechanically pumped loops. The sub-cooled liquid is however too cold to be injected into the evaporator, because evaporators require saturated liquid. To heat the liquid up to saturation, a heat exchanger between the liquid inlet (4-) and vapor outlet (-2) of the evaporator is used. The absorbed heat in the evaporator is used to heat the sub-cooled flow so no extra heat is needed. Figure 2.2 shows the schematic of figure

4 2. in the P-h diagram of CO 2. The indices of the diagram correspond to the nodes in figure 2.. The exchanged heat in the internal heat exchanger is the enthalpy difference of node and. As a minimum this heat must have been absorbed in the evaporator (9-0). If the evaporated heat is sufficient to overcome the sub-cooling, the evaporator inlet (Node 9) is and close to the saturated liquid curve, otherwise the inlet of evaporator remains sub-cooled causing degraded heat transfer. A 2PACL does only require a controlled accumulator. The 2PACL condenser temperature may vary, as long as the maximum temperature is lower than the accumulator set-point. The chiller may therefore run maximal cold, without any chiller evaporator regulation. The 2PACL pump flow may be constant as well; a sufficient overflow of the pump will make the system heat load independent and prevent the 2PACL against evaporator dry-out. A useful feature of the 2PACL is the ability of turning the loop into a single phase loop. Significantly increasing the accumulator s pressure will suppress any formation of vapor anywhere in the loop. This feature is very useful at start-up. It is used as start-up procedure in both the AMS-TTCS and the LHCb-VTCS systems. 2.2 VELO THERMAL CONTROL SYSTEM DESIGN. The cooling plant contains the chillers, the pumps, the accumulators and valves. The detector with evaporator is away from the cooling plant and situated in a hostile radiation environment which makes it inaccessible. The transfer of cooling fluid from the plant to the evaporator is via a concentric transfer tube. The liquid feed line is inside the vapor return line and bridges the 0 meter distance from the plant to the evaporator. The transfer tube is concentric so the environmental heat will only affect the return flow. The concentric tube is the necessary internal heat exchanger to overcome liquid sub-cooling. The silicon wafers in the detector need to be kept cold at all times. This is also required even if the detector is switched off. In paragraph 2. it was discussed that a heat load is needed in the evaporator to overcome the sub-cooling. If no sufficient heat load is available, sub-cooled liquid will enter the evaporator and the accumulator is no longer able to control the temperature of evaporator. The evaporator can become colder than the Figure 2.:VTCS CO 2 plant accumulator set-point leading to an uncontrolled and too cold detector. The transfer tube s isolation is tuned such that enough heat from the environment is entering the loop at all time to overcome the sub-cooling, the evaporator does not need a heat load in this case. The concept of environmental heat leak is chosen over electrical heating, because of reliability issues. Figure 2.4: VTCS Evaporator Assembly The evaporator has flow restrictions to distribute the flow evenly over the 27 parallel cooling connections. At start-up these restrictions can cause large pressure drops in the system when vapor has to pass through. At start-up it is also not guaranteed that the pumps are primed with liquid. The pumps are not self priming and they will not start up if there is no

5 liquid inside. A nice feature of the accumulator control is that the loop can be turned into a single phase liquid loop by heating-up the accumulator. The VTCS-accumulator will be heated to 27ºC prior to start-up. The pressure in the loop is above the saturation pressure of the environment, causing the CO 2 in the loop to be liquefied. The pump can now start-up without problems and the restrictors are fed with liquid, keeping the pump head pressure low. 2. VTCS SIMULATION RESULTS. A simulation model of the VTCS loop has been made to study the thermal equilibriums of the different operational states in transient modes. Figure 2. shows the simulation results of several situations from start-up to cold operation. The model calculates the energy and pressure balance of the nodes of figure 2.. Environmental heat leak is included and calculated between each node. Prior to start-up, the whole loop is at room temperature. It is not defined where the liquid or vapor is situated. The start-up situation (A) in the P-h diagram is somewhere along the 20ºC isotherm in the region. At start up the accumulator is heated to 27ºC and the system pressure increases to the corresponding saturation pressure of 67 bar. The loop is still at room temperature and will be filled with liquid. Once the loop is filled, the pump can be switched on. Sub-cooled liquid of 20ºC is now circulated and cooling from the primary R404a chiller is not yet needed. The loop operates as situation B in the P-h diagram. Once liquid circulation is achieved the primary chiller can be switched on. The accumulator is kept at high pressure so all the liquid will stay sub-cooled. In paragraph 2. it was discussed that the primary R404a chiller does not need any temperature regulation, therefore it will cool the liquid flow to its minimum temperature. After cooling down in liquid mode the situation of C has been reached. The pump flow will be about -40ºC, the evaporator (with liquid only!) is about -22ºC. The thermal gradient is due to the heat leak of the transfer tube. After having cooled down the loop in liquid mode, the accumulator can be cooled down by the primary chiller to the desired set-point of -0ºC. The system is now at situation D, which is indicated by the small squares in figure 2.. The unloaded evaporator (node 9-0) is now in the region, so its temperature is now controlled by the accumulator. P [bar] 2 x C 9,0, D E 9 0 9,0 VTCS start -up and operating cycles 40 C 20 C x h [kj/kg] Figure 2.: Simulation results of the VTCS model in the P-h diagram, B 0, A 0 C -20 C -40 C Once the situation of D is stabilized, the detector power is switched on. In the diagram this means that node 0 is moved away from node 9, ending up in situation E. The circuit of E also shows a change of the sub-cooled temperature of node with respect to situation D. This increase is due to the behavior of the primary R404a chiller. An increased heat load causes the compressor suction pressure to increase, and hence the primary evaporator pressure and temperature. The simulation clearly shows the independence of a varying sub-cooling. As long as node is on the left of the saturation line, the system works properly. The inlet of the evaporator (node 9) is controlled to stay and near the saturation line, assuring the evaporator being fed with a low quality flow.

6 2.4 VTCS ACCUMULATOR DESIGN The accumulator must be partially filled with liquid at all operational situations. Figure 2.6 show the simulation results of different liquid fillings in the accumulator as a function of accumulator volume for several fill ratios of the accumulator and loop together. It shows that the 2 extreme accumulator liquid levels appear at the single phase cold (C) for the minimum level and the loaded evaporator (E) for the maximum level (C and E are the situations of figure 2.). The chosen VTCS design parameters are indicated in the 2 nd graph by a vertical dashed line; for a VTCS loop volume of. liter a fill ratio of 7 gram per liter with an accumulator volume of.6 liter are sufficient to comply with all the operational scenarios. Liquid level (%). Liquid level (%). Loop fill ratio: 00 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0% Accumulator Volume (L) Loop fill ratio: 60 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0% Accumulator Volume (L) Liquid level (%). Liquid level (%). Loop fill ratio: 7 gram/liter 00% 90% VTCS Design 0% 70% 60% 0% 40% 0% 20% 0% 0% Accumulator Volume (L) Loop fill ratio: 72 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0% Accumulator Volume (L) Figure 2.6: Accumulator liquid levels as a function of accumulator volume and fill ratios for a loop volume of. liter. Figure 2.7: Accumulators in the VTCS plant Figure 2.: Thermo siphon heater Figure 2.9: Accumulator cooling coils

7 Figure 2.0 shows the mechanical design of the VTCS accumulator. The heater must be submerged in the liquid to avoid partial dry-out. In practice this means that the heater needs to stay below the minimum level of situation C at the design parameter line of figure 2.6. The capacity of the heater is driven by the required speed of pressurizing. A rod element heater of kw was chosen. The heater is at the bottom of the accumulator in a concentric thermo-siphon lay-out. The evaporated CO 2 on the heater surface is going up, sucking new liquid via the outer annulus to the heater. Care must be taken at heating near the critical point of CO 2. The difference in the density of liquid and vapor becomes small, decreasing the liquid flow. The decreased liquid flow causes a dry-out with high heater temperatures as a result. Figure 2.0: VTCS Accumulator mechanical design A lowering of the system pressure is achieved by condensing the vapor content in the accumulator. In the VTCS accumulator this is achieved with a coiled tube inside the accumulator volume (figure 2.9). The coil is cooled with R404a by the primary chiller. This coil is situated at the upper part of the accumulator. A large part of the coil needs to be above the maximum level of situation E at the design parameter line of figure 2.6. A submerged part of the spiral is no problem, it only decreases the condensation surface and hence the cooling down speed. At the VTCS the liquid level is monitored using a dielectric probe. 2. VTCS TEST RESULTS. Figure 2. shows some test results of the VTCS test system. The loop was started up from stand still to cold operation. Time A was the start-up time. The loop was still cold from earlier tests. The saturation temperature of the loop was 0ºC, while the pump was at room temperature. The pump was filled with vapor only and could not start-up. The accumulator was heated to pressurize the system such that the saturation temperature of the system became above room temperature. At time B the accumulator heater was reduced to avoid heater dry-out; pressurization is now going slower. At time C the system was sufficiently filled with Temperature (ºC), Pump flow (g/s) :2:6 6:0:24 7:9:2 7:4:00 :6:4 :4:6 9:4:24-0 A B C Figure 2.: VTCS Test results Pump liquid (ºC) Evaporator Saturation Temperature (ºC) Evaporator Temperature (ºC) Massflow (g/s) Accu Pressure (Bar) Evaporator Pressure (Bar) F G H D E Time (hh:mm:ss) Pressure (Bar)

8 liquid so the pump could start-up. The pump was rapidly cooling down while the evaporator temperature was staying behind. The accumulator was maintained on pressure making the system cooling down in sub-cooled liquid state. At time D the accumulator cooling started at a set-point of -2ºC. At time E, the evaporator was no longer sub-cooled; the accumulator had taken over control of the evaporator s temperature. At time F, the evaporator had reached the set-point temperature of -2ºC and the detector power was switched on. At time G the accumulator set-point was lowered to -0ºC, reaching the -0ºC evaporator temperature at time H. This was the minimum reachable evaporator temperature with the VTCS test system, because the pump sub-cooling had become marginal. Note that the accumulator and evaporator pressures were the same during the entire test.. CONCLUSION AND DISCUSSION The accumulator controlled loop (2PACL) method is a good solution for controlling mechanically pumped loops. It can operate at a large dynamic evaporator pressure range and is virtually independent of heat load and condenser temperature. The accumulator pressure is the only accurate controlled parameter in the system. This makes the system robust, stable and easy to operate. The 2PACL method is a good alternative for controlling the current secondary pumped loops. The accumulator method can also be used for loop systems which do not need controlled evaporators but only need to transfer heat from A to B. One can think of an accumulator maintaining a slight over-pressure with respect to the pump sub-cooling, just enough to avoid pump cavitation. Different types of accumulators can be considered, such as a spring acted bellow accumulator with secondary loading at the loop temperature, or an accumulator with a secondary fluid mixture having slight over pressure properties to the loops working fluid. An active pneumatic controlled accumulator is also an option. The LHCb-VTCS and the AMS-TTCS both use CO 2 as working fluid, but the principle is expected to work for any fluid pumped systems. 4. REFERENCES. B.Borgia, 200, The Alpha Magnetic Spectrometer on the International Space Station, IEEE Transactions on Nuclear Science, Vol. 2, No. 6, p The LHCb Collaboration, 200, The LHCb VELO Technical Design Report, CERN/LHCC note, The ROSE Collaboration, 999, R&D On Silicon for future Experiments, CERN/LHCC note, Boer Rookhuizen H. et al, 999, Preliminary Studies for the LHCb Vertex Detector Cooling System, LHCb note, /VELO. Verlaat, B., Krijger, E., 200, Performance Testing of the AMS TTCS CO 2 Evaporator., NIKHEF note, ASR-T- 00/MT Verlaat, B. et al. 2002, Feasibility Demonstration of a Mechanically Pumped Two-Phase CO 2 Cooling Loop for the AMS-2 Tracker Experiment, Conference on Thermophysics in Microgravity, in the Space Technology & Applications International Forum (STAIF-2002), Albuquerque, NM, USA 7. Delil, A.A.M. et al., 997, In-orbit demonstration of two-phase heat transport technology - TPX II reflight, European Space Agency, SP-400, p.. Verlaat, B., Woering, A., Pauw, A., Delil, A.A.M., 200, AMS-2 Tracker Thermal Control System: design and thermal modeling of the mechanically pumped two-phase CO 2 loop, AIAA Aerospace Sciences Meeting & Exhibit, Reno, NV, USA, (AIAA ) 9. Verlaat, B., 200, Thermal Performance Testing of the VTCS Evaporator and VELO Module, NIKHEF note, MT 0-0.

Thermal Modeling Issues Concerning the Mechanically Pumped Two-Phase CO 2 Cooling for the AMS-2 2 Tracker

Thermal Modeling Issues Concerning the Mechanically Pumped Two-Phase CO 2 Cooling for the AMS-2 2 Tracker Thermal Modeling Issues Concerning the Mechanically Pumped Two-Phase CO 2 Cooling for the AMS-2 2 Tracker A.A.Woering, A.Pauw, A.W.G. de Vries, A.A.M. Delil, The Netherlands B. Verlaat National Institute

More information

UNIT 2 REFRIGERATION CYCLE

UNIT 2 REFRIGERATION CYCLE UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression

More information

How To Calculate The Performance Of A Refrigerator And Heat Pump

How To Calculate The Performance Of A Refrigerator And Heat Pump THERMODYNAMICS TUTORIAL 5 HEAT PUMPS AND REFRIGERATION On completion of this tutorial you should be able to do the following. Discuss the merits of different refrigerants. Use thermodynamic tables for

More information

16. Heat Pipes in Electronics Cooling (2)

16. Heat Pipes in Electronics Cooling (2) 16. Heat Pipes in Electronics Cooling (2) 16.1 Pulsating Heat Pipes 16.1.1Introduction Conventional heat pipe technology has been successfully applied in the last thirty years for the thermal management

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

How To Clean Up A Reactor Water Cleanup

How To Clean Up A Reactor Water Cleanup General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component

More information

Waste Heat Recovery through Air Conditioning System

Waste Heat Recovery through Air Conditioning System International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning

More information

Two-Phase Evaporative Precision Cooling Systems

Two-Phase Evaporative Precision Cooling Systems Two-Phase Evaporative Precision Cooling Systems For heat loads from 3 to 300kW Using non-conductive refrigerant fluid, our patented Next-generation, two-phase evaporative precision cooling systems enable

More information

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P2.6.3.2. Thermodynamic cycle Heat pump

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P2.6.3.2. Thermodynamic cycle Heat pump Heat Thermodynamic cycle Heat pump LD Physics Leaflets P2.6.3.2 Investigating the function of the expansion valve of the heat pump Objects of the experiment g To study the operational components of the

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: Frank.@UniSA.edu.au Abstract The high efficiency

More information

How Ground/Water Source Heat Pumps Work

How Ground/Water Source Heat Pumps Work How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy

More information

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1 Lesson Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications Version ME, IIT Kharagpur The objectives of this lecture are to discuss. Performance aspects of SSS cycle and

More information

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

A/C refrigerant system, overview

A/C refrigerant system, overview Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -

More information

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL Master of Science Thesis Stockholm, Sweden 2011 What is not measured does not exist; What

More information

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION

More information

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil Answer: (1) Condenser coil See the video. A.R.E. Building Systems Study Guide

More information

Fundamentals of Mass Flow Control

Fundamentals of Mass Flow Control Fundamentals of Mass Flow Control Critical Terminology and Operation Principles for Gas and Liquid MFCs A mass flow controller (MFC) is a closed-loop device that sets, measures, and controls the flow of

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low GWP Replacements for R404A in Commercial Refrigeration Applications Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract

More information

How To Know If A Refrigeration System Is Efficient

How To Know If A Refrigeration System Is Efficient Universitatea de Ştiinţe Agricole şi Medicină Veterinară Iaşi ASSESSMENT OF E SUBCOOLING CAPABILITIES OF A ERMOELECTRIC DEVICE IN A VAPOR COMPRESSION REFRIGERATION SYSTEM R. ROŞCA 1, I. ŢENU 1, P. CÂRLESCU

More information

C. starting positive displacement pumps with the discharge valve closed.

C. starting positive displacement pumps with the discharge valve closed. KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

FEDSM2014-21213. Flow Boiling Heat Transfer Enhancement in Subcooled and Saturated Refrigerants in Minichannel Heat Sinks

FEDSM2014-21213. Flow Boiling Heat Transfer Enhancement in Subcooled and Saturated Refrigerants in Minichannel Heat Sinks Proceedings of the ASME 2014 4th Joint US-European Fluids Engineering Division Summer Meeting and 12th International Conference on Nanochannels, Microchannels, and Minichannels FEDSM2014 August 3-7, 2014,

More information

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3

More information

CGC s Hybrid System Loop Control

CGC s Hybrid System Loop Control verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system

More information

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com. Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment

More information

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not

More information

Heat Pipe Cooling of Concentrating Photovoltaic (CPV) Systems

Heat Pipe Cooling of Concentrating Photovoltaic (CPV) Systems Heat Pipe Cooling of Concentrating Photovoltaic (CPV) Systems William G. Anderson 1, Sanjida Tamanna 2, David B. Sarraf 3, and Peter M. Dussinger 4 Advanced Cooling Technologies, Inc., Lancaster, PA, 17601

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

BB-18 Black Body High Vacuum System Technical Description

BB-18 Black Body High Vacuum System Technical Description BB-18 Black Body High Vacuum System Technical Description The BB-18 Black Body is versatile and is programmed for use as a fixed cold target at 80 K or variable target, at 80 K- 350 K no extra cost. The

More information

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE Roulette, T., J. Roulette, and S. Pons. Results of ICARUS 9 Experiments Run at IMRA Europe. in Sixth International Conference on Cold Fusion, Progress in New Hydrogen Energy. 1996. Lake Toya, Hokkaido,

More information

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 00 Measurement And Application of Performance Characteristics Of A Free Piston

More information

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS 1 HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS Jørn Stene SINTEF Energy Research, 7465 Trondheim, Norway Jorn.Stene@sintef.no In hotels, hospitals,

More information

Optimization of Natural Gas Processing Plants Including Business Aspects

Optimization of Natural Gas Processing Plants Including Business Aspects Page 1 of 12 Optimization of Natural Gas Processing Plants Including Business Aspects KEITH A. BULLIN, Bryan Research & Engineering, Inc., Bryan, Texas KENNETH R. HALL, Texas A&M University, College Station,

More information

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology Energy and Climate Refrigeration and Heat Pump Technology Energy Efficient Ammonia Heat Pump PSO no. 342-059 Claus Madsen Bastiaan Pijnenburg Henning Schumann Grindorf Rolf Christensen Bjarne D. Rasmussen

More information

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here. COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

Advances in Gas Cooler Design and the New Gas Cooler Product Selector

Advances in Gas Cooler Design and the New Gas Cooler Product Selector Advances in Gas Cooler Design and the New Gas Cooler Product Selector Simon Jones Engineering Manager Sean Armitage Sales Manager Introduction GEA Searle Over 90 years experience in the design and manufacture

More information

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements Stuart Self 1, Marc Rosen 1, and Bale Reddy 1 1 University of Ontario Institute of Technology, Oshawa, Ontario Abstract

More information

APPLICATIONS AND DEFINITIONS

APPLICATIONS AND DEFINITIONS HEAT PUMP APPLICATIONS AND DEFINITIONS Per Fahlén SP Energy Technology APPLICATIONS OF HEAT PUMPS 900s: Refrigeration, need to chill food; Survival: very large application; chilled food comprises Turnover:

More information

WHITE PAPER #: CLIMATEMASTER KNOWLEDGE SERIES: HEAT PUMP DESIGN FOR 100% OUTSIDE AIR SYSTEMS THE SMART SOLUTION FOR ENERGY EFFICIENCY

WHITE PAPER #: CLIMATEMASTER KNOWLEDGE SERIES: HEAT PUMP DESIGN FOR 100% OUTSIDE AIR SYSTEMS THE SMART SOLUTION FOR ENERGY EFFICIENCY WHTE PPE #: 5 THE SMT SUTN F ENEGY EFFENY MTEMSTE KNWEDGE SEES: HET PUMP DESGN F 100% UTSDE SYSTEMS WTE-SUE HET PUMP SYSTEMS Table of ontents: ntroduction... 2 Background on oops... 2 Heat Pump Principles...

More information

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS FUNDAMENTALS OF ENGINEERING THERMODYNAMICS System: Quantity of matter (constant mass) or region in space (constant volume) chosen for study. Closed system: Can exchange energy but not mass; mass is constant

More information

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control... Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply

More information

5.2. Vaporizers - Types and Usage

5.2. Vaporizers - Types and Usage 5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS J J Brasz, Carrier Corporation, Syracuse, NY, 13221, USA joost.j.brasz@carrier.utc.com I K Smith and N Stosic

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

جامعة البلقاء التطبيقية

جامعة البلقاء التطبيقية AlBalqa Applied University تا سست عام 997 The curriculum of associate degree in Air Conditioning, Refrigeration and Heating Systems consists of (7 credit hours) as follows: Serial No. Requirements First

More information

How does solar air conditioning work?

How does solar air conditioning work? How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze

More information

A Design and Performance Test of the Visualization within a Capillary Pumped Loop (*).

A Design and Performance Test of the Visualization within a Capillary Pumped Loop (*). IL NUOVO CIMENTO VOL. 16 D, N. 7 Luglio 1994 A Design and Performance Test of the Visualization within a Capillary Pumped Loop (*). W. K. LIN (1), p. L. WONG(1), P. C. WONG(1) P. C. CHENG(1) and H. PAUL

More information

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling Computers and Chemical Engineering 31 (2007) 712 721 Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling Jørgen Bauck Jensen, Sigurd Skogestad Department

More information

Automobile Air Conditioning Primer

Automobile Air Conditioning Primer Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the

More information

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) The Concept Maximum Heat Load Temperature Testing is a powerful air-conditioning diagnostic and evaluation technique. It is also

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump? KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge

More information

Thermodynamics - Example Problems Problems and Solutions

Thermodynamics - Example Problems Problems and Solutions Thermodynamics - Example Problems Problems and Solutions 1 Examining a Power Plant Consider a power plant. At point 1 the working gas has a temperature of T = 25 C. The pressure is 1bar and the mass flow

More information

Thermo Siphon Solar Systems

Thermo Siphon Solar Systems Thermo Siphon Solar Systems Thermo Siphon Solar Systems are a very cost effective way of producing hot water due to their simplicity in design and installation requirements. Usually more common in hotter

More information

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Air-sourced 90 Hot Water Supplying Heat Pump HEM-90A Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced

More information

Alcatel-Lucent Modular Cooling Solution

Alcatel-Lucent Modular Cooling Solution T E C H N O L O G Y W H I T E P A P E R Alcatel-Lucent Modular Cooling Solution Redundancy test results for pumped, two-phase modular cooling system Current heat exchange methods for cooling data centers

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Open Cycle Refrigeration System

Open Cycle Refrigeration System Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.

More information

SOLVING REACTOR WATER CLEAN-UP SYSTEM ANOMALIES USING RELAP5 MOD3.3

SOLVING REACTOR WATER CLEAN-UP SYSTEM ANOMALIES USING RELAP5 MOD3.3 11 th International Conference on Nuclear Engineering Tokyo, JAPAN, April 20-23, 2003 ICONE11-36149 SOLVING REACTOR WATER CLEAN-UP SYSTEM ANOMALIES USING RELAP5 MOD3.3 Joseph S. Miller EDA, Inc 6397 True

More information

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Simulation of a small size solar assisted adsorption air conditioning system for residential applications Heat Powered Cycles Conference 2009 2009 Simulation of a small size solar assisted adsorption air conditioning system for residential applications Salvatore Vasta, Andrea Frazzica, Gaetano Maggio, Alessio

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard

More information

HOW HVAC WORKS. How HVAC. Works PAGE 1

HOW HVAC WORKS. How HVAC. Works PAGE 1 How HVAC Works PAGE 1 Heat - What is it? Heat is more than a physical concept - it is a feeling. Heat is taught to us at a very young age as a danger to be avoided. Yet, have you ever stopped and thought

More information

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES INTRODUCTION This tutorial is designed for students wishing to extend their knowledge of thermodynamics to a more

More information

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances. C4. Heat Pump I. OBJECTIVE OF THE EXPERIMENT We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances. II. INTRODUCTION II.1. Thermodynamic

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Soil Suction. Total Suction

Soil Suction. Total Suction Soil Suction Total Suction Total soil suction is defined in terms of the free energy or the relative vapor pressure (relative humidity) of the soil moisture. Ψ = v RT ln v w 0ω v u v 0 ( u ) u = partial

More information

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Dr. Nguyen Nguyen An, HUST CONTENTS Energy consumption to produce hot water in residential

More information

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015 International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 EXPERIMENTAL STUDY

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

GEOTHERMAL HEATING AND COOLING INTRODUCTION

GEOTHERMAL HEATING AND COOLING INTRODUCTION GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

Improving Data Center Efficiency with Rack or Row Cooling Devices:

Improving Data Center Efficiency with Rack or Row Cooling Devices: Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities

More information

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit

More information

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7 Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator

More information

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort

More information