Re: Wildwood, 2-6 High Street, Kingston, KT1 1EY - Proposed Restaurant - External Plant Noise Assessment - Revised

Size: px
Start display at page:

Download "Re: Wildwood, 2-6 High Street, Kingston, KT1 1EY - Proposed Restaurant - External Plant Noise Assessment - Revised"

Transcription

1 Ref: MDR/J2553b 7 th September 2015 Extracair Installations Ltd Endeavour House Sterte Avenue West Poole Dorset BH15 2AJ For the attention of Mr J Emery Dear Sirs Re: Wildwood, 2-6 High Street, Kingston, KT1 1EY - Proposed Restaurant - External Plant Noise Assessment - Revised Further to your recent instruction, we are pleased to forward a revised external plant noise assessment, incorporating additional background noise data as follows:- Proposed Plant Installation The external plant noise sources are assumed to be located on the rear flat roof area. The external plant noise sources will be the supply air fan and intake, the extract air fan and discharge and 4No. heat pump A/C outdoor units, a normal installation format for Extracair Installations Ltd. We have assumed the plant would be controlled to operate from typically 09.00hrs to no later than 24.00hrs. RandTech Consulting 90 Park Avenue North Northampton NN3 2JD Tel

2 Ref: MDR/J2553b Noise Design Criterion The Royal Borough of Kingston upon Thames planning permission ref: 14/12520/FUL planning condition 4 requires the cumulative external plant noise to be at least 5dBA lower than the existing background noise level, measured or predicted 1m externally to any window at the nearest residential facade. The background noise level is assumed to be a measured LA90 value and the nearest residential windows will be those of the proposed flats on the floors above the restaurant within the same building. The assessment methodology would be to BS4142:2014 and the criteria adopted for the assessment will be to achieve a cumulative plant noise level at least 5dBA below the LA90 background noise level 1m outside the nearest residential windows. During our site inspection visit of 10/2/15 we measured the typical background noise level at the rear of the building on the flat roof area where the external plant will be located and below the windows of the proposed flats on the floors above. The background noise level measured for 1 hour, starting at 11.32hrs was 54dB LA90. This measured background level was a combination of traffic noise in the locality and some existing mechanical plant in operation. Given the enclosed nature of the location it would be reasonable to assume that the measure background noise level would be representative of the background noise level outside the nearest residential windows. Applying planning condition 4 gives a design criterion for the cumulative plant noise of no more than 49dBA 1m outside the nearest residential window. The instrumentation used for the noise measurement was a Casella CEL 63x precision grade real time analyser/sound level meter, serial number , calibration checked before and after using a Casella CEL 110 acoustic calibrator, calibration seen to be correct and unchanged. A copy of the current calibration certificate for the instrument is available upon request. The weather conditions prevailing during the noise measurement were satisfactory with no significant wind and no precipitation. Additional Background Noise Measurement The Royal Borough of Kingston upon Thames requested a further measurement of the prevailing background noise, outside the rear façade windows of the proposed 2 nd floor flats, over a longer time period, to determine a more accurate value for the background noise that would prevail throughout the operational period of the restaurant external plant noise sources. RandTech Consulting 90 Park Avenue North Northampton NN3 2JD Tel

3 Ref: MDR/J2553b An additional noise measurement was undertaken from 15.00hrs 5/10/15 to 15.00hrs 6/10/15, measuring the background LA90 1hr level 1m outside the living room window of Flat 1 on the second floor, directly above the proposed external plant location; please see the attached 2nd floor plan. The instrumentation used was a Rion NL52 precision grade real time analyser/sound level meter, serial number , calibration checked before and after the measurement period and seen to be correct. We attach a copy of the instrument calibration certificate for your reference. The weather conditions prevailing during the measurement period were variable with some periods of rain. The set of 1hour period LA90 values are detailed on an attached graph. For the survey period on 5/10/15 from 15.00hrs up to 23.00hrs there was no significant site construction noise and what was recorded was what could be considered as normal background noise. The average value for this first set of values was 56.2dB and the minimum value was 55.1dB. During the night period the background level decreased slightly and after 07.00hrs on 6/10/15 the background level significantly increased due to construction site activity. In conclusion we would advise that the daytime measurements taken on 5/10/15 are representative of the background level in question. The minimum LA90 level measured was 55.1dB and this compares reasonably with our original measurement of 54.0dB. The External Plant Noise Assessment For the noise assessment design calculations can be undertaken to predict the radiated noise from the two fan systems and 4No. heat pump outdoor units operating at maximum noise output, radiating noise within a reverberant location to a distance of 6m. Where required mitigation is required this is included within the plant noise assessment. The Calculated External Plant Noise We have attached standard design calculations on three design sheets, to predict the radiated noise at 6m distance. For simplicity we have assumed no acoustic screen enclosing the plant and all the plant sources are at 6m distance; source within the flat roof area are assumed to be in a reverberant location. The 4No. Toshiba RAV-SP1104AT-E heat pump outdoor units would create a maximum noise level of 46dBA at 6m distance. RandTech Consulting 90 Park Avenue North Northampton NN3 2JD Tel

4 Ref: MDR/J2553b The supply air ventilation system based on a Nicotra 9-9 external fan in an acoustic box with a connecting duct to an intake louvre The silenced noise level would be 37dBA at 6m distance, from the air intake louvre, and fitted with a 1200mm long rectangular splitter silencer, 38% free area design. The extract air ventilation system based on a Systemair MUB 630 DV4-K2 external fan in an acoustic box with connecting ductwork to a vertical discharge, on the discharge side of the fan a rectangular silencer would be fitted, typically a 44% free area splitter design, 1800mm long located in the ductwork. The silenced noise level would be 36dBA at 6m distance, assuming free-field spherical radiation. In addition there would be some fan casing break-out noise requiring acoustic cladding to be applied to the fan casing and a short length of connecting ductwork. Typically an acoustic cladding nominally 10kg/m2, (1.2mm sheet mild steel and 50mm mineral wool insulation), would reduce the break-out noise to 26dBA at 6m. In addition to reduce fan break-out noise from the inlet side ductwork will require an inlet silencer to be fitted, typically a 44% free area splitter design, 900mm long, reducing inlet ductwork break-out to 32dBA at 6m. The summated noise level of all the external plant in operation at a distance of 6m, typically outside the nearest flat window would be 47dBA, which would be 7dBA less than the measured background noise level 54dB LA90 1hr assumed to be outside the nearest residential windows. For the purposes of BS4142:2014, the plant rating level would be 47dBA, with no tonal correction required for the silenced noise sources, the background level for comparison is 54dB LA90 1hr, and the rating level has been calculated to be 7dBA less than the background level. Please see the attached design sheets and supporting information. Conclusion The initial noise assessment for the proposed external plant to be located at the rear of the building predicts a very reasonable operating noise level at typically 6m distance, assumed to be the distance from the plant location to the nearest residential windows. This complies with planning condition 4. The subsequent background noise measurements taken outside the living room window of Flat 1 on the 2nd floor over a 24 hour period have confirmed the original background noise level of 54.0dB as being valid for the original noise assement. RandTech Consulting 90 Park Avenue North Northampton NN3 2JD Tel

5 Ref: MDR/J2553b We trust the revised noise assessment meets with your approval and we remain. Yours faithfully M D Randall BSc(Eng) CEng MCIBSE MIOA RandTech Consulting 90 Park Avenue North Northampton NN3 2JD Tel

6

7

8

9

10

11

12

13

14

15

16

17

18

19

NOISE CONTROL REVIEW FOR 4 db NOISE REDUCTION SCENARIO FOR WAGERUP 3 EXPANSION PROJECT FOR ALCOA OF AUSTRALIA

NOISE CONTROL REVIEW FOR 4 db NOISE REDUCTION SCENARIO FOR WAGERUP 3 EXPANSION PROJECT FOR ALCOA OF AUSTRALIA ENGINEERING CONSULTANTS A.C.N. 009387393 433 Vincent St West Leederville, Western Australia, 6007 P.O. Box 48, Leederville, 6902 PH: (08) 9381 3566 FAX: (08) 9381 3588 NOISE CONTROL REVIEW FOR 4 db NOISE

More information

Noise Assessment For Proposed EfW & IBA Facility. Paving Way North Hykeham Lincolnshire. For. Fichtner Consulting Engineers. Acting on Behalf of

Noise Assessment For Proposed EfW & IBA Facility. Paving Way North Hykeham Lincolnshire. For. Fichtner Consulting Engineers. Acting on Behalf of 56a Leabrooks Road Somercotes Derbyshire DE55 4HB Tel No: 01773 607483 Fax No: 01773 603331 E-mail: nvc.acoustics@btopenworld.com Noise Assessment For Proposed EfW & IBA Facility At Paving Way North Hykeham

More information

Data Centres A complete solution to noise control and acoustic packages

Data Centres A complete solution to noise control and acoustic packages Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions

More information

Planning Statement. Project Prince William School, Oundle. Prepared for Lend Lease

Planning Statement. Project Prince William School, Oundle. Prepared for Lend Lease Planning Statement Project Prince William School, Oundle Prepared for Lend Lease Published 7 September 2015 Telephone +44(0)1787 247595 Website www.srltsl.com London, Birmingham, Manchester, Sudbury Quality

More information

SOUND INSULATION FOR AIR CONDITIONERS AND OTHER EXTERNAL MECHANICAL PLANT. Installing and Maintaining Air Conditioning Units

SOUND INSULATION FOR AIR CONDITIONERS AND OTHER EXTERNAL MECHANICAL PLANT. Installing and Maintaining Air Conditioning Units SOUND INSULATION FOR AIR CONDITIONERS AND OTHER EXTERNAL MECHANICAL PLANT Excessive noise from the operation of machines and external mechanical plant can disturb neighbours, disrupt sleep, interfere with

More information

Noise Design Advice. Noise can be a major factor to consider in any new development.

Noise Design Advice. Noise can be a major factor to consider in any new development. Noise Design Advice Noise can be a major factor to consider in any new development. This design advice is to help those involved in development in Leeds achieve an acceptable noise environment for people

More information

TOP 10 NOISE CONTROL TECHNIQUES

TOP 10 NOISE CONTROL TECHNIQUES TOP 10 NOISE CONTROL TECHNIQUES The following are 10 simple noise control techniques that have wide application across the whole of industry. In many cases, they will produce substantial noise reductions

More information

TFSR & TFSK Roof Fans

TFSR & TFSK Roof Fans Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans TFSR & TFSK Roof Fans With swing-out function 2 I TFSR/TFSK TFSR & TFSK Roof

More information

115 NEW CAVENDISH STREET 5 TH FLOOR EXTENSION

115 NEW CAVENDISH STREET 5 TH FLOOR EXTENSION 115 NEW CAVENDISH STREET 5 TH FLOOR EXTENSION Acoustic Design Report University of Westminster 11 August 2009 QM Issue/revision Issue 1 Issue 2 Remarks Draft - Date 07 August 2007 11 August 2007 Prepared

More information

Permanent Ventilators (for the Supply of Combustion

Permanent Ventilators (for the Supply of Combustion Part - Installation, Safety & Maintenance Permanent Ventilators (for the Supply of Combustion Air) Introduction All heating appliances that produce heat from the combustion of carbon based fuels such as

More information

Sample Trigger Action Plan (TAP)

Sample Trigger Action Plan (TAP) Thames Tideway Tunnel Thames Water Utilities Limited Application for Development Consent Application Reference Number: WWO10001 Sample Trigger Action Plan (TAP) Doc Ref: APP113 Folder 183 3 February 2014

More information

Contents BB93 Acoustic Design for Schools

Contents BB93 Acoustic Design for Schools Contents BB93 Acoustic Design for Schools BB93 Background Noise Sound Insulation Rooms Acoustics - Reverberation times Internal Noise Level Example Llwynu School Internal Background Noise BB93 Internal

More information

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01 Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal

More information

SECTION 15936 AIR INLETS AND OUTLETS

SECTION 15936 AIR INLETS AND OUTLETS SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer Fundamentals of Acoustics & Practical HVAC Design Considerations Demir Doken Acoustic Engineer What is sound? Sound is a mechanical wave that is an oscillation of pressure transmitted through some medium

More information

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898 NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report

More information

Relationship between Sound Pressure and Sound Power Levels

Relationship between Sound Pressure and Sound Power Levels Relationship between Sound Pressure and Sound Power Levels 4 W. T. W. CORY Chairman of the Eurovent WG 1 Fans If we wish to know the sound power transmitted through a fan and ducting system, it is preferable

More information

Mistrale. Fusion Terminal

Mistrale. Fusion Terminal Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant

More information

Attended Noise Monitoring - Quarter Ending December 2013

Attended Noise Monitoring - Quarter Ending December 2013 Big Island Mining Pty Ltd Majors Creek Road Majors Creek Version: Page 2 PREPARED BY: ABN 29 001 584 612 Units 7-8, 26-28 Napier Close Deakin ACT 2600 Australia (PO Box 9344 Deakin ACT 2600 Australia)

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

Under sill units. Type FSL-B-ZAS

Under sill units. Type FSL-B-ZAS .1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract

More information

Façade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn

Façade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn strategy Proposed residential development Report Number: 1420.1 Version: A Date: 13 th October 2008 Prepared by: Checked by: Andrew Gibson Jack Harvie-Clark Apex Acoustics Limited Design Works William

More information

General Thoughts on Generator Set - Acoustic Solutions & Noise Control

General Thoughts on Generator Set - Acoustic Solutions & Noise Control t: 023 81 290160 www.excelpowerltd.co.uk f: 023 81 290260 info@excelpowerltd.co.uk General Thoughts on Generator Set - Acoustic Solutions & Noise Control Written By Steve Delaney A.M.I.O.A. of TAS Ltd

More information

Airline. small air handlers and extract fan units. VES Airline part of a complete range of innovative, flexible products from the HVAC experts

Airline. small air handlers and extract fan units. VES Airline part of a complete range of innovative, flexible products from the HVAC experts Lo w p r o f i l e small air handlers and extract fan units Duties to 0.55m 3 /sec Available with the Electroline fitted control panel Ceiling void friendly - unit heights from 190mm to 350mm Airline VES

More information

sound reduction systems for commercial, educational and industrial environments

sound reduction systems for commercial, educational and industrial environments sound reduction systems for commercial, educational and industrial environments Tel: +44 ()14 3874 Fax: +44 ()14 38957 E-mail: info@soundreduction.co.uk Web: www.soundreduction.co.uk soundblocker Acoustic

More information

UDSA - UDSBD unit heater

UDSA - UDSBD unit heater APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the

More information

MICRO HYDRO FOR THE FARM AND HOME

MICRO HYDRO FOR THE FARM AND HOME MICRO HYDRO FOR THE FARM AND HOME How much can I expect to save? This depends entirely on the available flow, available head (fall) and the duration that the flow is available. Some farms struggle to maintain

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

Acoustics & Building Services An back to basics overview

Acoustics & Building Services An back to basics overview Acoustics & Building Services An back to basics overview Prepared for 20 th March 2012 ASK Consulting Engineers Since 1993, ASK Consulting Engineers has been providing clients from both the private and

More information

How To Reduce Noise From A Test Screen

How To Reduce Noise From A Test Screen Practical Approaches to Engineering Noise Controls Dave Yantek Mining Hearing Loss Prevention Workshop June 21-22, 22, 2005 Pittsburgh Research Laboratory Basics of sound Topics Measurement of sound Measurement

More information

ICQ Series - square centrifugal

ICQ Series - square centrifugal product ICQ Square Centrifugal (TEFC) dimensions mm 280-710 poles & duty 4-8 / up to 4,500 L/s application High performance centrifugal fans for medium to high pressure ducted systems. ICQ Series The ICQ

More information

An Installers Guide to

An Installers Guide to An Installers Guide to Installing an Air Conditioner? Noise from air conditioners can disturb neighbours. The noise can disrupt sleep, interfere with normal daily activities and can have significant impacts

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

Directorate for the Built Environment Building Standards Division

Directorate for the Built Environment Building Standards Division Directorate for the Built Environment Building Standards Division Energy Management Solutions Ltd Investigation of measures to improve the energy performance of a existing building: Retail JUNE 2009 Report

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages.

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages. Défumair XR smoke-extraction fan extraction casing for kitchen at F400-120 Personalisation : - Phonic insulation version by insulated double-skin panels through 25 mm glass wool, class M1. advantages Originally

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

squrboxbox heat recovery squrboxbox I technical information

squrboxbox heat recovery squrboxbox I technical information heatrecoveryrange heat recovery squrboxbox I technical information squrboxbox Low depth high performance Only 350mm deep & up to 430l/s, providing the most effective low depth solution. Quietest solution

More information

Energy to the Power of

Energy to the Power of Re n ewa b l es First Issue March 2009 Kingspan The Complete Solar Powered Cooling System Energy to the Power of Kingspan Renewables Ltd is a division of the Kingspan Group plc. The group has manufacturing

More information

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation

More information

Minimizing noise levels so future engineers can focus Classroom Acoustic Technical Reference Guide

Minimizing noise levels so future engineers can focus Classroom Acoustic Technical Reference Guide Minimizing noise levels so future engineers can focus Classroom Acoustic Technical Reference Guide ARE YOU GETTING THE RIGHT INFORMATION WHEN IT COMES TO CLASSROOM SOUND? There are many reasons why it

More information

Charlton Christian College, Fassifern Master Plan Acoustic Assessment for the Proposed Facilities Upgrade

Charlton Christian College, Fassifern Master Plan Acoustic Assessment for the Proposed Facilities Upgrade Master Plan Acoustic Assessment for the Proposed Facilities Upgrade Report No. 20C-12-0116-TRP-266092-3 2 nd April 2013 Acoustics Vibration Air Quality Mechanical & Structural Systems Fluid Mechanics Sustainability

More information

Manchester City Council List Item 10 Planning and Highways Committee 15 March 2012

Manchester City Council List Item 10 Planning and Highways Committee 15 March 2012 Application Number 097574/FO/2011/N1 Date of Appln 30th Jan 2012 Committee Date 15 th March 2012 Ward Cheetham Ward Proposal Location Applicant Agent Retrospective Application for the continued use of

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

How To Design A Gas Dryer

How To Design A Gas Dryer Non Domestic Laundry Gas Appliance Installation Code of Practice Introduction This code of practice has been produced with the assistance of all Companies within the OPL sector of SLEAT because of the

More information

Noise impact assessment of mass rapid transit systems in Delhi city

Noise impact assessment of mass rapid transit systems in Delhi city Indian Journal of Pure & Applied Physics Vol. 49, April 2011, pp. 257-262 impact assessment of mass rapid transit systems in Delhi city Naveen Garg a, Omkar Sharma a & S Maji b a Acoustics, Ultrasonic,

More information

NZDF Temporary Military Training Activities. Palmerston North City Council

NZDF Temporary Military Training Activities. Palmerston North City Council NZDF Temporary Military Training Activities for Palmerston North City Council File No. N1447TMT Version 22 nd June 2014 Nigel Lloyd Director of Acoustic Services E-mail: nigel@acousafe.co.nz 98 NZDF Temporary

More information

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:

PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power: PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV

More information

Building HVAC Load Profiling Using EnergyPlus

Building HVAC Load Profiling Using EnergyPlus Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: wang0807@e.ntu.edu.sg Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological

More information

How To Get A Passive House

How To Get A Passive House Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product

More information

Cool air quietly and efficiently. A guide to buying and operating an air conditioner

Cool air quietly and efficiently. A guide to buying and operating an air conditioner Cool air quietly and efficiently A guide to buying and operating an air conditioner Cool air quietly and efficiently Noise from air conditioners can be a serious issue between neighbours. If an air conditioner

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Weather/Sound Enclosure and Subbase Fuel Tank Package Applicable to the following: 40REOZJC 50/60REOZJD 80/100/150/200REOZJF 125/180REOZJG 230-275REOZJE 300REOZJ Enclosure

More information

White Rose Carbon Capture and Storage (CCS) Project Document Ref: 9.11 - Rev.1 PINS Ref: EN10048

White Rose Carbon Capture and Storage (CCS) Project Document Ref: 9.11 - Rev.1 PINS Ref: EN10048 White Rose Carbon Capture and Storage (CCS) Project Document Ref: 9.11 - Rev.1 PINS Ref: EN10048 The White Rose CCS (Generating Station) Order Land adjacent to and within the Drax Power Station, Drax,

More information

Noise in the Classroom

Noise in the Classroom ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed

More information

Planning Guidance for Food and Drink Establishments

Planning Guidance for Food and Drink Establishments Planning Guidance for Food and Drink Establishments ENVIRONMENT DIRECTORATE, CIVIC CENTRE, 44 YORK STREET, TWICKENHAM TW1 3BZ Planning Guidance for Food and Drink Establishments Introduction This guidance

More information

Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise

Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise Building Design for Advanced Technology Instruments Sensitive to Acoustic Noise Michael Gendreau Colin Gordon & Associates Presentation Outline! High technology research and manufacturing instruments respond

More information

ProRox Slabs (formerly known as RW slabs)

ProRox Slabs (formerly known as RW slabs) Slabs (formerly known as RW slabs) Versatile thermal acoustic insulation slabs ROCKWOOL's Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. They are

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Put us to the test. Construction testing and building investigations services from BRE. www.bre.co.uk

Put us to the test. Construction testing and building investigations services from BRE. www.bre.co.uk Put us to the test Construction testing and building investigations services from BRE www.bre.co.uk Backed by an extraordinary range of facilities BRE prides itself on being able to answer virtually any

More information

DATE: July 12, 2004 SUBJECT: Gaudet School Chiller Noise Survey Results

DATE: July 12, 2004 SUBJECT: Gaudet School Chiller Noise Survey Results 799 MIDDLESEX TNPK. BILLERICA MA 01821-3445 PHONE: 978-670-5339 FAX: 978-667-7047 E-mail: nonoise@ noise-control.com JOB MEMO TO: John McKenney COMPANY: McKenney Mechanical Contractors, Inc. FROM: Jesse

More information

Industrial Generator Set Accessories

Industrial Generator Set Accessories Industrial Generator Set Accessories Weather/Sound Enclosure and Subbase Packages Applicable to the following models: 600-1000REOZM Kohler enclosures protect stationary generator sets from the elements,

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

BEDELL CORPORATE TRUSTEES LIMITED AND ATRIUM TRUSTEES LIMITED AS JOINT TRUSTEES OF THE BURTON ROAD UNIT TRUST

BEDELL CORPORATE TRUSTEES LIMITED AND ATRIUM TRUSTEES LIMITED AS JOINT TRUSTEES OF THE BURTON ROAD UNIT TRUST Branston Depot, Burton on Trent BEDELL CORPORATE TRUSTEES LIMITED AND ATRIUM TRUSTEES LIMITED AS JOINT TRUSTEES OF THE BURTON ROAD UNIT TRUST Technical Report 13-IAC002 February 13 Innovate Acoustics is

More information

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump The basics... This guide can help you make an informed

More information

Technical Bulletin 005(A) Developed with Communities and Local Government

Technical Bulletin 005(A) Developed with Communities and Local Government Technical Bulletin 005(A) Developed with Communities and Local Government Title: Gas cookers in internal kitchens - Ventilation requirements as applied to England, Wales, the le of Man and Guernsey Date

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

NUAIRE VENTILATION SYSTEMS FLATMASTER AND FLATMASTER 2000 SYSTEMS

NUAIRE VENTILATION SYSTEMS FLATMASTER AND FLATMASTER 2000 SYSTEMS NuAire Ltd Western Industrial Estate Caerphilly Mid Glamorgan CF83 1NA Tel: 02920 858 200 Fax: 02920 858 300 e-mail: info@nuaire.co.uk website: www.nuaire.co.uk NUAIRE VENTILATION SYSTEMS APPROVAL INSPECTION

More information

Access onto roof from Center Block

Access onto roof from Center Block 2 2 Tap 4 Tank 3 3 4 5 5 6 4 1 Services PV panels Forth floor structure (later additions) Rooflights Access / Walkways Access onto roof from Center Block muf architecture/art LLP 4.3 Roof alterations and

More information

Fixed Vertical Access Ladders

Fixed Vertical Access Ladders Fixed Vertical Access Ladders Index 1. Fixed Vertical Access Ladders 2. Aluminium Fixed Vertical Access Ladders: Standard Specification 3. Aluminium Fixed Vertical Access Ladders: Technical Drawing 4.

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Combi Unit Genius. The energy efficient Building Service Centre

Combi Unit Genius. The energy efficient Building Service Centre Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Combi Unit Genius The energy efficient Building Service Centre systemair Central Building Services

More information

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23 COMMERCIAL REPORT / STOCK CONDITION SURVEY For Sydenham Hill Estate Sydenham Hill London SE 23 Submission Prepared by Gas Advisory Services Limited Date: 4 th June 2013 Gas Advisory Services Limited Phoenix

More information

How To Ensure Safety At A Swimming Pool Or Spa

How To Ensure Safety At A Swimming Pool Or Spa Index Purpose... 2 Application... 2 Referral Agency... 2 Associated Requirements... 2 Referenced standards... 2 Definitions... 2 Disinfection System... 4 Filtration equipment... 4 Small child safety...

More information

White Bay Berth 4 Bulk Liquids Handling. Doris Ruby. Ship Noise Monitoring Report. Report Number 10-4309-R58. 1 August 2014

White Bay Berth 4 Bulk Liquids Handling. Doris Ruby. Ship Noise Monitoring Report. Report Number 10-4309-R58. 1 August 2014 Sydney Ports Corporation Level 4, 20 Windmill Street Walsh Bay NSW 2000 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW 1595 Australia)

More information

Acoustic Terms, Definitions and General Information

Acoustic Terms, Definitions and General Information Acoustic Terms, Definitions and General Information Authored by: Daniel Ziobroski Acoustic Engineer Environmental and Acoustic Engineering GE Energy Charles Powers Program Manager Environmental and Acoustic

More information

COOKING THE ROOF CFD BEYOND THE WHITE SPACE

COOKING THE ROOF CFD BEYOND THE WHITE SPACE COOKING THE ROOF CFD BEYOND THE WHITE SPACE Alex Nock 20 November 2013 CONTENTS 1. Introduction» Introduction to RED» Modeling in Data Centres 1. What is CFD» How it works» CFD in Data Centres 3. Cooking

More information

Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists

Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals

More information

Topvex SX/C, Topvex TX/C. Air Handling Unit

Topvex SX/C, Topvex TX/C. Air Handling Unit Air Handling Unit Document in original language 131677-EN_GB 23-12-2015 A001 Contents 1 Declaration of Conformity... 1 2 Warnings... 2 3 Product information... 2 3.1 General... 2 3.2 Technical data...

More information

Web: Blake Lapthorn Solicitors. www.rbkc.gov.uk/planning New Kings Court Tollgate Date: 02/08/2012 Chandler's Ford, Tollgate Eastleigh, Hants

Web: Blake Lapthorn Solicitors. www.rbkc.gov.uk/planning New Kings Court Tollgate Date: 02/08/2012 Chandler's Ford, Tollgate Eastleigh, Hants Planning and Borough Development Kensington Town Hall, Hornton Street, LONDON, W8 7NX Executive Director Planning and Borough Development Jonathan Bore Mr. S. Drake Web: Blake Lapthorn Solicitors www.rbkc.gov.uk/planning

More information

Kings Lynn B SoS Decision Letter. The Proposed Palm Paper CCGT 3 Order. Proposed Combined Cycle Gas Turbine by Palm Paper Ltd

Kings Lynn B SoS Decision Letter. The Proposed Palm Paper CCGT 3 Order. Proposed Combined Cycle Gas Turbine by Palm Paper Ltd Proposed Combined Cycle Gas Turbine by Palm Paper Ltd The Proposed Palm Paper CCGT 3 Order Palm Paper Mill, Saddlebow Industrial Estate, King s Lynn PINS Ref: EN010039 Document Ref: 12.11 Kings Lynn B

More information

Duplexvent DV72 EC So light, so slim it fits inside a 600mm cupboard

Duplexvent DV72 EC So light, so slim it fits inside a 600mm cupboard Duplexvent DV72 EC So light, so slim it fits inside a 600mm cupboard Duplexvent DV72 EC MVHR is designed to provide constant volume ventilation levels to exceed the latest Building Regulations 2010. The

More information

PROPOSED RESIDENTIAL DEVELOPMENT LAND OFF MACCLESFIELD OLD ROAD, BUXTON. Construction Management Plan

PROPOSED RESIDENTIAL DEVELOPMENT LAND OFF MACCLESFIELD OLD ROAD, BUXTON. Construction Management Plan PROPOSED RESIDENTIAL DEVELOPMENT LAND OFF MACCLESFIELD OLD ROAD, BUXTON Construction Management Plan May 2013 CONTENTS Page No: 1.0 INTRODUCTION 1 2.0 PROJECT ORGANISATION AND RESPONSIBILITIES 2 2.1 Client

More information

Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP

Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP ABB The Preferred Partner Egypt Cement Corporation, a major cement manufacturer, has chosen ABB wound rotor motors for all key applications

More information

CFD Beyond the Whitespace. Datacentres Central & Eastern Europe

CFD Beyond the Whitespace. Datacentres Central & Eastern Europe CFD Beyond the Whitespace Datacentres Central & Eastern Europe September 2013 CONTENTS 1.0 Introduction 2.0 What is CFD? How it Works CFD in Data Centres 3.0 CFD Outside the White Space Case Study 4.0

More information

Document No Amendment No Approved By Approval Date Review Date NS200 MAJOR SUBSTATIONS VENTILATION DESIGN STANDARD

Document No Amendment No Approved By Approval Date Review Date NS200 MAJOR SUBSTATIONS VENTILATION DESIGN STANDARD Network Standard NETWORK Document No Amendment No Approved By Approval Date Review Date : : : : : NW000-S0059 1 Chief Engineer 19/01/2016 01/12/2018 NW000-S0059 NS200 MAJOR SUBSTATIONS VENTILATION DESIGN

More information

How To Make Your House Breathe

How To Make Your House Breathe RENEWABLES VENTILATION UNITS Nothing lost plenty of healthy fresh air gained Innovative ventilation units that offer healthy indoor air and significantly lower energy bills 04 2015 STIEBEL ELTRON is full

More information

Technical Solution Sheet 7.08 7: Mechanical Services (Including duct heating)

Technical Solution Sheet 7.08 7: Mechanical Services (Including duct heating) 7: Mechanical Services (Including duct heating) Split System Air Conditioning AIM The aim of this technical solution is to inform practitioners on the requirements for the safe discharge of condensate

More information

KRUGER ENERGY CHATHAM WIND PROJECT ENVIRONMENTAL SCREENING REPORT / ENVIRONMENTAL IMPACT STATEMENT. Appendix E. Environmental Noise Impact Assessment

KRUGER ENERGY CHATHAM WIND PROJECT ENVIRONMENTAL SCREENING REPORT / ENVIRONMENTAL IMPACT STATEMENT. Appendix E. Environmental Noise Impact Assessment KRUGER ENERGY CHATHAM WIND PROJECT ENVIRONMENTAL SCREENING REPORT / ENVIRONMENTAL IMPACT STATEMENT Appendix E Environmental Noise Impact Assessment Executive Summary The purpose of this environmental

More information

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe

More information

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Baltimore, Maryland NOISE-CON 2010 2010 April 19-21 Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Scott Harvey

More information

Capital Projects, NHS C/o Steve Boxall Royal United Hospital Combe Park Bath BA1 3NG. Dear Sir. Town and Country Planning Act 1990

Capital Projects, NHS C/o Steve Boxall Royal United Hospital Combe Park Bath BA1 3NG. Dear Sir. Town and Country Planning Act 1990 Planning Services PO Box 5006, Bath, BA1 1JG Fax: (01225) 394199 Telephone: (01225) 394041 DX: 8047 (Bath) Development_control@bathnes.gov.uk Date: 19th June 2012 www.bathnes.gov.uk Our Ref: 12/01384/FUL

More information

Australian/New Zealand Standard

Australian/New Zealand Standard Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

An update on acoustics designs for HVAC (Engineering)

An update on acoustics designs for HVAC (Engineering) An update on acoustics designs for HVAC (Engineering) Ken MARRIOTT To cite this version: Ken MARRIOTT. An update on acoustics designs for HVAC (Engineering). Société Française d Acoustique. Acoustics 2012,

More information