HyLife TM HVAC Line Corrosion testing. Precision Tubing Technology Centre, 2012
|
|
- Karen Claribel Daniels
- 8 years ago
- Views:
Transcription
1 Precision Tubing Technology Centre, 2012
2 Background: There is an increasing interest in the use of aluminium tubes for connecting lines for residential HVACR applications Connecting lines are often covered with a thermal insulating foam Extensive testing have been executed to investigate risk of corrosion underneath the foam and in the coupling/flare joint fitting area potentially caused by condensation on the tube, particularly in hot climates Test setup: Sample configuration: Flare joint with brass fitting, heat shrink sleeve on one side of the brass fitting, no protection on the other (Test 2) Line-set with insulating foam (Test 1) Tube material: Hylife TM HVAC Line alloy, 9,53 x 1 mm (*). Cu tube used as reference material *HyLife TM HVAC Line samples prepared for test are courtesy of Ebrille, Italy
3 Corrosion test conditions: Test 1: Accelerated salt spray corrosion test, ASTM B117* -> Line-set with thermal insulation Test 2: Accelerated salt spray corrosion test, ASTM G85-94-A3** -> Coupling area, flare joint with brass fitting * Deionised water solution with 5 wt% NaCl. ph neutral, Cabinet temperature: 35 C, Samples placed longitudinally in the chamber, Altubes with foam with defects and Cu-tubes with foam with defects introduced, Tap water at approx 10 C were running continuously through the tubes during testing, Test duration: 42 Days, continuous fog of the 5 wt% salt solution at a rate of 12 ml/hr, Samples taken out at selected intervals and characterised ** Synthetic sea water adjusted to ph by acetic acid, Cabinet temperature: 49 C, Two-hour cycling: 30 min spray followed by 90 min soak >98% RH, Tubes locked at each end, test duration 1000 hours
4 Artificial defect area in insulating foam Test 1: Line-set with thermal insulation Macro characterization after 42 days of exposure Slight corrosion formed underneath the edge of thermal insulation foam No salt ingress from the tube ends as they were covered with plastic fittings Salt ingress from the defect area and minor corrosion Metallographic examination (42 days) Minor pits up to max µm in the area without foam Similar setup with copper tube had max. 50 µm No corrosion under the foam Outside the thermal insulation 100 µm Under the thermal Insulation 100 µm
5 Test 2: Flare joint with brass fitting Macro characterisation, photos before and after testing Without heat-shrink sleeve (Not recommended) - Direct galvanic coupling between the brass nut and the Al tube thus rapid corrosion subsequent failure With heat-shrink sleeve (Recommended) - No significant corrosion taking place Metallographic examination (40 Days) Without heat-shrink sleeve (Not recommended) With sleeve - Significant corrosion Leakage in the aluminium just outside the brass fitting in the non insulated region With heat-shrink sleeve (Recommended) - No or very little corrosion in the insulated region 0 Days 40 Days No sleeve x With heat-shrink sleeve No sleeve
6 Conclusion Coupling area: No corrosion under a well applied heat-shrink sleeve Line area: No or very limited corrosion under the thermal insulation foam. Very limited corrosion in areas were the thermal insulation was missing Recommendation Coupling area: A properly applied heat-shrink sleeve must be covering the HyLife TM HVAC connecting line and onto the brass coupling. Line area: The Thermal insulation foam should cover the complete connecting line from coupling to coupling not exposing the tube to the environment
Multijacketed Tubing, Single-Jacketed Tubing, and Insulated Tubing
www.swagelok.com Multijacketed Tubing, Single-Jacketed Tubing, Insulated Tubing Features 1/4 to 6 to 12 tubing sizes available in 316/316L stainless steel copper Seamless welded tubing available in stainless
More informationAluminized Steel Type 1 STAINLESS 409 and 439
P R O D U C T D A T A B U L L E T I N Aluminized Steel Type 1 STAINLESS and Excellent Resistance to Pitting Corrosion from Road Salt Excellent Resistance to Muffler Condensate Corrosion Red Rust Protection
More informationSolar Hot Water Heaters
Solar Hot Water Heaters Three High Vacuum Water inlet Stainless Steel screw Gel seal and insulation Water outlet Dust proof seals Non Pressure Models Details ASWH-1b ( Color Painted 304 ) ASWH-1c ( stainless
More informationTest Report No. C829QPEN
Institut für Solartechnik Hochschule für Technik Rapperswil Oberseestrasse 10, CH 8640 Rapperswil Tel +41 55 222 48 21, Fax +41 55 222 48 44 www.solarenergy.ch Ordered by: Westech Components Wuxi Co.,
More informationVapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled
Vapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled Presented by Kelly Baker, Zerust Oil & Gas Efim Lyublinski, Monique Posner, Terry Natale, Yefim Vaks, Ronnie Singh
More informationOperators manual Basic water heater
Operators manual Basic water heater Isotemp Basic water heater has been designed and produced to ensure that your water heater will give long and trouble free operation for many years. It is important,
More informationCONTENTS. 1 cooling technology white paper
Using Surface Coatings to Extend LIfe and ImprovE Performance in industrial air conditioners CONTENTS 1. Introduction 2. Type of Corrosions 2.1 Galvanic Corrosion 2.2 General Corrosion 2.3 Formicary Corrosion
More informationIn recent years, formicary corrosion has wreaked havoc on. Micro-channel
As seen in the October issue of Micro-channel Evaporator-coil Technology An overview of all-aluminum micro-channel evaporator-coil technology, including technical differences HVAC professionals need to
More information1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None
1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements
More informationLITHIUM BATTERY CR123A SPECIFICATION
LITHIUM BATTERY CR123A SPECIFICATION Date: April 24, 2012 Approved by: Scotty Scott PANASONIC ENERGY CORPORATION OF AMERICA LITHIUM BATTERY DIVISION 1. Designation : CR123A 2. Nominal Voltage : 3 V 3.
More informationEngineering & Testing Services. Hydraulic Fitting Design and Hydro-Mechanical Testing
Engineering & Testing Services Hydraulic Fitting Design and Hydro-Mechanical Testing Aerofit, Inc. APT Laboratory 1425 South Acacia Avenue Fullerton, CA 92831 Main: 714-521-5060 Fax: 714-535-9862 Our Company
More informationVacuum Tube Solar Water heater Non-pressure. User manual
Vacuum Tube Solar Water heater Non-pressure User manual Please read this manual carefully before beginning installation Specification Tubes 12 --- 30 58X1800 Nominal volume tank capacity 100L --- 300L
More informationDesign qualification and type approval of PV modules
Design qualification and type approval of PV modules TÜV Immissionsschutz und Energiesysteme GmbH Test Centre for Energy technologies May 2003 Design qualification and type approval of PV-modules in accordance
More information2.1 The performance of bus air conditioning system is evaluated in the following operating conditions
1.0 Scope:- This test procedure is applicable for testing the Air Conditioning system performance at hot ambient and very hot ambient condition on intracity urban bus in a climatic hot chamber. This procedure
More informationENVIRONMENTAL TESTING
ENVIRONMENTAL TESTING Mobility Department Environmental Testing Foreword & Introduction Tests Heat - Cold - Climate Page 3 Thermal Shock Page 4 Low - High Pressure Page 4 Vibration Page 5 Mechanical Shock
More informationDefining Quality. Building Comfort. Heating and Cooling Coils
Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.
More informationRAUFOSS EXPLOSIVE COMPRESSION FITTINGS
INSTRUCTION MANUAL FOR RAUFOSS EXPLOSIVE COMPRESSION FITTINGS Box 7 2831 Raufoss Norway Tlf.: +47 61 15 17 87 Fax: +47 61 15 25 56 25 January 2013, rev 2 Available on www.vpmetall.no Page 1 CONTENTS GENERAL
More informationDispelling the Myths of Heat Transfer Fluids. Kevin Connor The Dow Chemical Company
Dispelling the Myths of Heat Transfer Fluids Kevin Connor The Dow Chemical Company Heat Transfer Chill Water Loop Secondary Coolant (Heat Transfer Fluid) Primary Refrigerant Expansion Device Air Handler
More informationMold Preventing I nterior System
interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal
More informationDIAMOND Retractable Rodding Robot Model SPRAYROD-R
2004-12-21 2 1 (23) DIAMOND Retractable Rodding Robot Model SPRAYROD-R 2004-12-21 2 2 (23) Table of contents 1 TECHNICAL DESCRIPTION...4 1.1 MAIN DETAILS...5 1.2 COMPONENTS DESCRIPTION...5 1.2.1 Pneumatic
More informationFire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
More informationQuartz Glass. Tubes and Rods
Quartz Glass Tubes and Rods PH 300, GE 214, QI PN GVB Solutions in Glass Schlackstrasse 3 52080 Aachen Germany +49-241/9108588 +49-241/9108589 E- info@g-v-b.de www.g-v-b.de Table of contents General Information
More informationIndoor Coil Corrosion Industry Research Report
Indoor Coil Corrosion Industry Research Report Identifying Common Sources Introduction Fin Pack Leaks Formicary Corrosion Indoor coil corrosion failures are an issue in the HVAC industry today. Although
More informationCenturion. Scientific Limited Making Science Look Good. Quality Profile
Centurion Scientific Limited Making Science Look Good Quality Profile Within the following pages, we show what makes up the quality of our centrifuges and why we are so successful. Not only do we use the
More informationDesign qualification and type approval of PV modules acc. to IEC 61215:2005 / IEC 61646:2008
Design qualification and type approval of PV modules acc. to IEC 61215:2005 / IEC 61646:2008 TÜV Rheinland Immissionsschutz und Energiesysteme GmbH Renewable Energies 2009-01-22 January 2009 Design qualification
More informationRE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
More informationproduces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
More informationENVIRONMENTAL TESTING SERVICES. Product and component performance verification
ENVIRONMENTAL TESTING SERVICES Product and component performance verification environmental testing State-of-the-art technology and increased demands for product and component reliability have intensified
More informationVacuum. How It Relates to Refrigeration And Air Conditioning Service
Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationBest Practice in Boiler Water Treatment
Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler
More informationCatalog May 2015. Cable Accessories < 1 kv
Catalog May 2015 Cable Accessories < 1 kv Table of content Cable Accessories 1 Cable Accessories 1 kv Product range 2 Universal cleats 3 List of content 4 Notes 5 We reserve the right to make technical
More information(Issued 1 Dec. 1965) CRD-C 45-65 METHOD OF TEST FOR THERMAL CONDUCTIVITY OF LIGHTWEIGHT INSULATING CONCRETE 1
CRD-C 45-65 METHOD OF TEST FOR THERMAL CONDUCTIVITY OF LIGHTWEIGHT INSULATING CONCRETE 1 Scope 1. This method of test covers a procedure for measuring the thermal conductivity of lightweight concrete of
More informationEvidence of Performance. Class 2. Class 5A. Class C4 / B4. Test Report No. 15-003655-PR01. ift Rosenheim 16.12.2015
Evidence of Performance Test Report No. 15-003655-PR01 (PB-A01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions (W x H) Special features Alüminyum San. Tic.
More informationCAUSTIC SOLUTION REPLACEMENT (Mud Safe CR) STABILITY TESTING
CAUSTIC SOLUTION REPLACEMENT (Mud Safe CR) STABILITY TESTING Cormetrics Job #: 13-207 Prepared for: Heartland Energy Group Ltd. Date: March 20, 2013 Revision 2 Lab: Bay 4 2280 39 th Avenue NE, Calgary,
More informationAccelerated Aging and Life Time Prediction for Solar Concentrators
Chart 1 Accelerated Aging and Life Time Prediction for Solar Concentrators CSP Today 2015, Sevilla J. Wette, F. Sutter (DLR) A. Fernandez (CIEMAT) Chart 2 Contents Motivation/Solar mirrors Outdoor testing
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationWIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS
CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables
More informationitaltec PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines
PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines On customer request it is possible to supply: Benches for PCB Oven for PCB Chemicals
More informationUltra Coolant. The Best Performance. The Best Cost. The Best Coolant.
Ultra Coolant The Best Performance. The Best Cost. The Best Coolant. Ultra Coolant is not an oil. Ultra Coolant is an engineered synthetic coolant specifically designed to help rotary screw compressors
More informationEVERGREEN (C.P.) USA INC. TEL: (650) 952-8091 FAX: (650) 952-3629 E-MAIL: sales@evergreencpusa.com. SPECIFICATIONS Lithium Battery CR123A- 1700mAh
Voltage (V) Voltage (V) Voltage (V) EVERGREEN (C.P.) USA INC. SPECIFICATIONS Lithium Battery CR123A- 1700mAh Temperature characteristics(20ma) (mah) Pulse discharge characteristics Model CR123A Nominal
More informationSTAR PIPE Polska S.A ul. Gdyńska 51 62-004 Czerwonak tel. +48 61 667 41 20 fax +48 61 667 41 38
THE ALARM SYSTEM The base of the system consists of two non-insulated copper alarm wires with section equal to 1.5 mm2, located inside polyurethane foam parallel to the conduit pipe, offset in relation
More informationOperating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
More informationEvaluating Protective Coatings for Ballast Tanks
Evaluating Protective s for Ballast Tanks The lifetime of vessels, such as tankers and bulk carriers, is determined to a large extent by the condition of their ballast tanks. In recent years, serious accidents
More informationCompany and Product Presentation
Company and Product Presentation Company Presentation NBG Systems & FCT are private companies owned by NBG Holding Both are Austrian companies, operating under the highest European Union requirements &
More informationGENERAL PROPERTIES //////////////////////////////////////////////////////
ALLOY 625 DATA SHEET //// Alloy 625 (UNS designation N06625) is a nickel-chromium-molybdenum alloy possessing excellent resistance to oxidation and corrosion over a broad range of corrosive conditions,
More informationResidential/Commercial Gas Condensing High Efficiency Tankless Water Heaters
Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger
More informationOASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
More informationAutomotive Application Questionnaire for Electronic Control Units and Sensors. Electronic Components and Systems
Automotive Application Questionnaire for Electronic Control Units and Sensors Electronic Components and Systems Automotive Application Questionnaire for Electronic Control Units and Sensors Published by:
More informationCLAMPS CONNECTORS & EQUIPOTENTIAL RING
CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata
More informationNickel Free Room Temperature Seal: an innovative and ecological process
Nickel Free Room Temperature Seal: an innovative and ecological process 2015 ANODIZING CONFERENCE San Diego, California Prepared by: Marcello Rossi Italtecno Srl Italy NICKEL FREE ROOM TEMPERATURE SEAL:
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationCable ladder installation at S.C.M. Chemicals Limited s titanium dioxide Plant in Western Australia
Exel Composites Cable Support Systems offer engineers a structural product for solving many design and plant engineering problems, enabling long term reliable support of expensive and often critical cables.
More informationSafety Safety glasses or goggles must be worn in the laboratory at all times.
APPLE BROWNING: A STUDY OF OXIDATION OF FOODS 2005, 1997 by David A. Katz. All rights reserved. Reproduction permitted for education use provided original copyright is included. You are preparing for a
More informationSOURIAU s discrete wire sealing
SOURIAU s discrete wire sealing Description Using proven grommet technology from SOURIAU s extensive knowledge of harsh environments, the UTO & UTS connectors with grommet garantie a discrete wire sealing
More informationFREQUENTLY ASKED QUESTIONS (SOLAR WATER HEATER)
FREQUENTLY ASKED QUESTIONS (SOLAR WATER HEATER) Q.No.1 What is Solar Water Heater? A Solar Water Heater is a device which provides hot water for bathing, washing, cleaning, etc. using solar energy. It
More informationZINCROLYTE VS DUPLEX 700
TEST REPORT Date: 03-05-2012 Reference: Duroc NV Corrosion Protection Moerelei 149 2610 Antwerp Belgium Written by: Ing. Martijn Wirken - mw@duroc.be ZINCROLYTE VS DUPLEX 700 This document is not legally
More informationWHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
More informationTechnical Data May, 2015
3 Scotch-Weld TM s DP460 NS Technical Data May, 2015 Product Description s and are high performance, two-part epoxy adhesives offering outstanding shear and peel adhesion, and very high levels of durability.
More informationX15TN TM. A high hardness, corrosion and fatigue resistance martensitic grade CONTINUOUS INNOVATION RESEARCH SERVICE.
TM A high hardness, corrosion and fatigue resistance martensitic grade CONTINUOUS METALLURGICAL SPECIAL STEELS INNOVATION RESEARCH SERVICE DEVELOPMENT Enhancing your performance THE INDUSTRIAL ENVIRONMENT
More informationAccumulators and Receivers
aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Accumulators and Receivers Catalog C-1, October 2007 Page 2 / Catalog
More informationPIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant
More informationSFxxx-S PID Test Report (Potential Induced Degradation) TUV Rheinland Japan. ARC Product Management 2015.07 Ver. 1
SFxxx-S PID Test Report (Potential Induced Degradation) TUV Rheinland Japan ARC Product Management 2015.07 Ver. 1 Outline SLIDE 1 2 Outline What is PID? TOPICS 3 4 5 6 7 8 Principle of PID & resistance
More informationRobot Welding Torch System
T e C H N O L O G y f O R T H e W e L d e R s W O R L d. Robot Welding Torch System W W Robot welding torch system... The universal MIG/MAG-torch system for robot welding: A new interface and cable assembly
More informationSICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A
s SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A Introduction The technical and descriptive information on the function, construction and selection of the new types of 3SE3 limit switches is
More informationTEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
More information60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING
60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed
More informationFolding Bath Screen Instruction Manual
Folding Bath Screen Instruction Manual Consumer Guarantee - Please make sure the purchaser/end user completes and returns the Guarantee card which is enclosed with this product. Failure to validate the
More informationTHE WHOLE WORLD OF GAS SAFETY ENGINEERING. MINISPRAYJET Flame spraying gun
MINISPRAYJET MINISPRAYJET Flame spraying gun MINISPRAYJET A compact and light weight flame spraying gun Flame spraying gun thermal spraying with powder using oxy-fuel gas flame. Function and safety are
More informationDraft Specification PEX tubing. Section 23 83 16. Radiant-Heating Hydronic Piping. (Roth Radiant Heating Systems)
This draft specification is for hydronic radiant heating systems using PEX tubing in slab, floor, wall and ceiling applications, and as distribution piping. Roth Industries supplies these systems under
More informationData Sheet VITOSOL 100. Flat collectors for the utilisation of solar energy. Vitosol 100. Part nos. and prices: see price list
VITOSOL 100 Flat collectors for the utilisation of solar energy Data Sheet Part nos. and prices: see price list File in: Vitotec 1 Manual, Index 16 Vitosol 100 Type s 1.7 Vitosol 100 Type s 2.5 Vitosol
More informationFan Dia. Motor Amps Connections Approx. 115 V 10 O TD 15 O TD H W D CFM (Quantity) 115 V 230 V Inlet Suction Drain Ship. Wt. Lbs.
COMPACT UNIT FOR CEILING OR WALL MOUNT Fan Dia. Motor Amps Connections Approx. 115 V 10 O TD 15 O TD H W D CFM (Quantity) 115 V 230 V Inlet Suction Drain. MJ-40 400 600 7 13 5/8 8 125 5 1/4" 0.65 0.35
More informationCERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
More informationRS Stock No. 724-4207 Instruction Manual RS-1340 Hot Wire Anemometer
RS Stock No. 724-4207 Instruction Manual RS-1340 Hot Wire Anemometer EN FR IT DE ES CONTENTS / EN Title CONTENTS Page 1. SAFETY INFORMATION...1 2. INTRODUCTION...2 3. SPECIFICATIONS...3 4. PARTS & CONTROLS...4
More informationMaxCell Technical Manual Design Parameters
MaxCell Technical Manual Design Parameters Breaking Strength by Product Style, lbs Product Style Standard MaxCell Fire Resistant MaxCell Test Method 4 Cell 2,750 2,200 ASTM D 5 Bellcore 5 5.. Cell 2,50
More informationAdBlue. Technical Leaflet
Technical Leaflet M 6221 e November 2006 Page 1 of 6 = Registered trademark of Verband der Automobilindustrie AdBlue Very pure NO x -reduction agent for Diesel engines equipped with SCR catalysts. AdBlue
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationADDENDUM TO 2011 TAN SHEETS. Tempers For Aluminum And Aluminum Alloy Products Metric July 16, 2013. New and Revised Registrations
s For Aluminum And Aluminum s Metric July 1, 201 By Date Over Thru Basis 1 Ult. Yield 0 mm 201T11 Sumitomo 0/01/2012 Drawn Tube D or. A.00.00 2 1 20 * Tentative 201T11 Sumitomo 12/1/2011 Drawn Tube 22T1
More informationGENERAL RUBBER LINING PRINCIPLES
GENERAL RUBBER LINING PRINCIPLES I. METAL PREREQUISITES Metal to be lined should meet the requirements as stated in section 8 Metal Fabrication and section 12 Blasting and Cementing Procedures. The surface
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationUsing Portable Spot Air Conditioners in Industrial Applications
Using Portable Spot Air Conditioners in Industrial Applications Cooling People, Processes and Equipment In today s highly competitive manufacturing sector, companies are constantly looking for new ways
More informationDISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT. Jim Riley, Texas A&M University February 10, 2015
DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT Jim Riley, Texas A&M University February 10, 2015 Piping at Texas A&M 2 History of Distribution Piping at Texas A&M Concrete reinforced
More informationSMA Connectors. RF Coax Connectors. Product Facts
SMA Connectors Product Facts Performance to 12.4 GHz and beyond Available in various base metal options, including stainless steel, brass and zinc diecast Uses industry standard crimp tools and processes
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationSALT SPRAY AND IMMERSION CORROSION TESTING OF PM STAINLESS STEEL MATERIALS. W. Brian James Hoeganaes Corporation. Cinnaminson, NJ 08077
SALT SPRAY AND IMMERSION CORROSION TESTING OF PM STAINLESS STEEL MATERIALS W. Brian James Hoeganaes Corporation Cinnaminson, NJ 08077 Leander F. Pease III Powder-Tech Associates Inc. Andover, MA 01845
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationPeltier Application Note
Peltier Application Note Early 19th century scientists, Thomas Seebeck and Jean Peltier, first discovered the phenomena that are the basis for today s thermoelectric industry. Seebeck found that if you
More informationEXPERIMENT #9 CORROSION OF METALS
EXPERIMENT #9 CORROSION OF METALS Objective The objective of this experiment is to measure the corrosion rate of two different metals and to show the effectiveness of the use of inhibitors to protect metals
More informationLG Floor Standing Type Air Conditioner INSTALLATION MANUAL
website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG Floor Standing Type Air Conditioner INSTALLATION MANUAL LG IMPORTANT Please read this installation manual completely before
More informationbuilding applications copper - redefined
building applications copper - redefined copper - redefined The task The development of an innovative tube for the future: economical, environmentally friendly, ecological, completely safe and easy to
More informationPerformance Testing of HVOF Coatings and Comparison with Hard Chrome Plate (HCP)
Performance Testing of HVOF Coatings and Comparison with Hard Chrome Plate (HCP) HCAT/CHCAT Meeting December 14, 2000 by David Lee Deloro Stellite Co. Inc. - Stellite Coatings Div. Program Participants
More informationAdvanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler
Advanced Heating & Hot Water Systems A Trailblazing Energy Star Listed Boiler that Installs like a Mid-Efficiency Boiler with the Performance of a High-Efficiency Product Ultra High Efficiency Energy Star
More informationTHE CAPABILITIES OF ZINC DIE CASTING
THE CAPABILITIES OF ZINC DIE CASTING Presented by: Ryan Winter (Manager Customer Engineering Services) Eastern Alloys, Inc. Eastern Alloys, Inc. Introduction to ZINC Introduction to Zinc Zinc is the 4th
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationIndoor Coil Corrosion
Indoor Coil Corrosion Industry Research Report Identifying Common Sources Introduction Fin Pack Leaks Formicary Corrosion Indoor coil corrosion leading to coil failure is an issue that affects coils manufactured
More informationConstruction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
More informationHELLA MEANS QUALITY EXCELLENCE SINCE 1899
HELLA MEANS QUALITY EXCELLENCE SINCE 1899 QUALITY CRITERIA 03 HELLA MEANS QUALITY HELLA has set itself the ambitious aim of guaranteeing a consistently high level of product quality in every respect.
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationHexavalent Chrome Removal in Aircraft Painting Schemes
Technical Workshop C3P & NASA 2007 Escola Superior de Tecnologia do Mar Peniche, Portugal Hexavalent Chrome Removal in Aircraft Painting Schemes Joana Vide Pereira - C3P November 9, 2007 Scope Aeronautical
More informationSECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
More information