Conventional Fire Alarm Systems

Size: px
Start display at page:

Download "Conventional Fire Alarm Systems"

Transcription

1 Conventional Fire Alarm Systems

2 Contents Introduction 3-7 Zeta UV/IR Optical Flame Detectors Premier SX Conventional Fire Alarm Panel 8 Premier Elite Conventional Fire Alarm Panel 9 Premier Conventional Repeater Panel 10 Zeta Conventional Manual Call Points 28 Zeta Conventional Weatherproof Call Point 29 Zeta Conventional Explosion Proof Manual Call Point 30 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel 11 Premier M Plus Repeater Panel 12 Premier 48 M Plus Zone Conventional Fire Alarm Panel 13 Premier 48 M Plus Repeater Panel 14 Premier MX Conventional Fire Alarm Panel 15 Fyreye Extra Conventional Optical Smoke Detector 16 Fyreye Extra Conventional Rate of Rise and Fixed Heat Detectors 17 Fyreye Extra Conventional Opto-Heat Detector 18 Fyreye Conventional Ultra-Violet Flame Detector 19 Fyreye Conventional Detector Bases 20 Zeta Remote LED Indicator 21 Miditone Conventional Electronic Sounder 31 Miditone Conventional Combined Electronic Sounder & Flasher 32 Securetone Conventional Electronic Sounder 33 Secure Light Xenon Flasher 34 Maxitone Conventional Sounder and Combined Sounder & Flasher 35 Zeta Conventional Fire Alarm Bells 36 Zeta Flame Proof Siren 37 Zeta Flame Proof Gong Bell 38 Zeta Magnetic Door Holders 39 Zeta Duct Unit 40 Premier Power Pack EN 54-4 Power Supply with LCD Screen 41 Batteries 42 Fyreye 50 & 100m Reflective Beam Smoke Detector Fyreye 50 & 100m Auto-aligning Beam Smoke Detector Systems 50 & 100m

3 Introduction Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded in 1985 and is a privately held UK manufacturer of Fire Alarm, Gas Detection and Emergency Systems. Our brand name is well known throughout the industry and is acclaimed in over forty countries worldwide. We are currently represented in the UK, Europe, Africa, the Middle East, Southern Asia & South America and this list continues to grow. Complete System Supplier To meet the requirements of our ever-changing market, we pride ourselves on being a complete system supplier. This means our customers can rely on us for their entire system requirements. One of the main advantages of using a complete system supplier, compared with a component supplier, is that system wide compatibility is assured and there is one point of contact. Marketing our products as systems has played a vital role in our worldwide success. The Future Our continued inward investment and constant endeavour to offer the very best products is recognised by our increased turnover and profit margin year-onyear. Our mission is to support our existing & future customers by providing them with the highest quality products, at the most competitive prices. Customer Support & Product Warranty We value our customers greatly and to ensure they have the best experience we have a dedicated support team who are able to assist with sales, technical or logistical queries. Research & Development As with all electronic equipment there is an ever present drive to manufacture products that are increasingly effective whilst becoming more cost sensitive. To meet this objective we spend a significant percentage of our profits on the continued development of products, whether it be introducing new items, or improving existing ones. We have a team of engineers & designers all of whom have vast industry knowledge & experience. As a manufacturer we always follow the market needs closely to evaluate how we should adapt our product range. This, combined with welcomed customer feedback, has proved to be a successful formula for meeting the current and future industry needs. Statement Of Quality Policy We maintain a Quality System, which conforms to BS EN ISO9001:2008. We are committed, where applicable, to manufacture in compliance with all appropriate legislation & regulatory requirements. Our products carry a full 24 month manufacturers guarantee from the date of purchase. Our network of authorised agents is fully trained on the use of our products and will provide a helpful & friendly service. 3

4 Introduction to Fire Alarm Systems Fire Detection & Alarm Systems BS5839 Fire alarm systems are used to detect a fire, and to signal a warning alarm to the appropriate source. In general, there are 3 types of system; 1. Manual Fire Alarm Systems which rely on manual call points to signal an alarm 2. Life Protection Fire Alarm Systems these are designed to protect the occupants of a building 3. Property Protection Fire Alarm Systems these are designed to protect buildings The warning may be simply ringing fire alarm sirens, however if a building is likely to be unoccupied, it may be more appropriate to signal to a monitoring station, or at least send a message to the building owner via telephone. Risk Assessment The Fire precautions (Workplace) Regulations require any business employing five or more persons to hold a written Fire Risk Assessment and Emergency Plan. This must be periodically reviewed. The local fire brigade can enforce compliance, and close any building that does not meet this act. In the event of a fire in a building without a written Fire Risk Assessment, those responsible may face fines and imprisonment, and/or private litigation. What the law requires you to do: Complete a fire risk assessment for your work place (considering all employees, the public, disabled people and people with special needs). Identify and record any significant findings or persons at risk. Provide and maintain fire precautions. Provide information, instruction and training. Nominate persons responsible to implement your emergency plan. Consult employees about the above nominations and your proposals to improve fire precautions. Inform other employees who may have work places in the building about any significant risks which may affect their safety and co-operate with them to reduce/control these risks. If you are not an employer, but control premises which contain more than one workplace, you are responsible for complying with fire regulations. You must establish a suitable means of contacting the emergency services. Your employees must co-operate to ensure the workplace is safe from fire and its effects. 4

5 System Zoning Information In order to aid identification of the source of a possible fire, the protected building should be divided into zones. When deciding on a suitable zoning scheme for a building, consideration should be given to the size, any existing fire routines, escape routes, zone accessibility, and structural fire compartmentation. The following guide lines should be observed: If the total floor area of the building is less than 300m 2 then the building needs only one zone, regardless of the number of storeys. Manual Call Points A Manual Call Point is a device which enables personnel to raise an alarm in the event of a fire incident by pressing a frangible element to activate the alarm system. Manual Call Points should be installed at a height of 1.2m above floor level at easily accessible, conspicuous positions, on exit routes, at the entry floor landings of staircases and at all exits to the open air. If the total floor area is greater than 300m 2 : The maximum area for a zone is 2000m 2 If a stairwell (or similar) extends beyond one floor it should be a separate zone. If a zone covers more than one fire compartment then the zone boundaries should follow the compartment boundaries. The search distance within the zone in order to ascertain the position of the fire should not exceed 60m. Remember that the use of Remote Indicator lamps may help to reduce the distance travelled. 1.2m - 1.4m Manual Call Points should be spaced so that one may always be found within a maximum distance of 45m apart or 25m for disabled person. 45m Max. or 25m Max. for disabled person 60m Max. If a building is divided between occupiers, zones must not be shared between them. 5

6 Detector Information Automatic Detectors When deciding on the type of detector to be used in any area it is important to remember that the detector has to discriminate between a genuine fire and the normal conditions existing therein. Smoke Detectors In open spaces under flat horizontal ceilings, every point should lie within 7.5m of a smoke detector. Heat Detectors General In open spaces under flat horizontal ceilings, every point should lie within 5.3m of a heat detector. 10.6m 7.5m 112m² (10.6m x 10.6m) 56.3m² (7.5m x 7.5m) Room boundary Room boundary 7.5m 5.3m 5.3m 3.8m Smoke detection should be generally avoided in the following areas to avoid unwanted alarms. They should be protected by means of other detectors such as heat detectors. Contamination in dusty areas may cause unwanted alarms and reduce the life of the detector. Damp or humid conditions such as showers, bathrooms and external areas should be avoided as the water vapour may cause unwanted alarms and reduce the life of the detector. Detectors should not be mounted where gases, vapours or fumes are present. Detectors should never be used at low temperature where ice or condensation can affect detector sensitivity. Kitchens, garages, welding shops and boiler houses should generally be avoided. Heat detectors are designed to either detect a rapid rise in temperature or to operate at a fixed temperature. Although they provide a slower response time than smoke detectors they do provide a method of protection for areas where smoke detectors cannot be used. Heat detectors should not be used for the protection of life or where extensive property loss may be expected. Rate of Rise Heat Detectors Rate of Rise heat detectors respond to both rapid increases of temperature and to fixed top temperature. Fixed Temperature Heat Detectors Fixed temperature heat detectors are available with different temperature settings, and are normally installed in kitchens, boiler rooms, etc. 6

7 Detection In Apex Roofs If the ceiling is pitched or sloping, smoke will tend to rise towards the highest point (apex) of the roof, therefore detection should be placed in the apex. As the slope tends to reduce the delay before smoke or heat reaches the detectors, it is permissible to use a greater spacing between the detectors mounted there. Fire Alarm Sounders Fire Alarm Sounders should be installed throughout the building with an even distribution, to generally provide a minimum sound level of 65dB(A) or 5dB(A) above any background noise which is likely to persist for more than 30 seconds. Limits of Ceiling Height 500Hz Hz 500Hz Hz Heat Detector Smoke Detector Heat Detector Smoke Detector Background noise Apex <150mm Apex <600mm Apex >150mm Apex >600mm Small Apex = Standard Spacing Large Apex = Extended Spacing Cabling The operation of a Fire Alarm and Detection System depends on the cabling and connections between the components. It is essential that connection between Manual Call Points and Detectors function correctly when they are operated. Cables within the system are required to function correctly for significant periods after being attacked by fire. These include the power supply cables to the control panel, the detection circuits and the fire alarm sounder circuits. Thus the cables chosen must be correctly rated to withstand these conditions. Where the alarm may have to arouse sleeping persons e.g. Hotel bedrooms, nursing homes, etc, a minimum sound level of 75dB(A) is required, at the bed head with all the doors shut. 75dB(A) All fire alarm sounders in a building should produce the same sound, distinct from any other audible warning devices in the building. Where fire alarm sounders are required in extremely noisy areas e.g. Machine shops, it may be necessary to install additional Visual Indication Beacons. 7

8 Premier SX Conventional Fire Alarm Panel (NPSX1, NPSX2, NPSX4, NPSX6, NPSX8) The Premier SX control panel range is available in 1, 2, 4, 6 and 8 zones, housed in a light grey flame retardant ULV0 enclosure, designed to meet modern architectural surroundings, with a removable hinged door. The Premier SX has been designed with ease of installation in mind, in addition to the robust electronic design expected from Zeta Alarm Systems. 73mm 100mm LPCB Approved to EN54 parts 2 & 4 One man test facility Disablement facility for zones & sounders Space for up to 7Ahr batteries Sounder delay option (0 9 min) Panel can be flush mounted Flush Mount Wall Mount Model NPSX1 NPSX2 NPSX4 NPSX6 NPSX8 Part No Mains Voltage 230V AC +10% / 50/60Hz System Voltage 24V DC (nominal) Zone Voltage 21V DC (nominal) Sounder Alarm Output 2 x 24V DC (nominal) Fault Relay Output 1 x relay 1A maximum Fire Relay Output 1 x relay 1A maximum Zone Capacity 32 devices per zone Remote Sounder Activation Via N/O contact (class change) Sounder Activation Delay 0-9 minutes in 1 minute increments Zone End Of Line IN4002 Diode (cathode stripe to +) Sounder End Of Line 10K resistor Charger Voltage 20 C (with battery disconnected) Zone Short Circuit Protection 100mA Charger Short Circuit Protection Battery voltage less than 20V Enclosure Size 355 (l) x 275 (h) x 100 (d) mm Weight 3.25kg (excluding batteries) 8

9 Premier Elite Conventional Fire Alarm Panel (PE1, PE2, PE4, PE6, PE8) The Premier Elite 1-8 zone fire alarm panels are ideal for small to medium sized installations. They meet all the requirements of EN54 parts 2 & 4, and come in an attractively styled enclosure. The zonal output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel. 73mm Flush Mount 100mm Wall Mount Fault relay (4, 6 & 8 zone only) Alarm relay Current limited charger to prevent flat batteries drawing too much current (4, 6 & 8 zone only) Built in diode base compatibility (4, 6 & 8 zone only) Sounder delay facility (4, 6 & 8 zone only) Connection to optional add on zonal output card (4, 6 & 8 zone only) Zone disablement facility (4, 6 & 8 zone only) One man test facility (4, 6 & 8 zone only) Model PE1 PE2 PE4 PE6 PE8 Part No Detection Zones Mains Voltage 230V AC 50/60Hz System Voltage 24V DC (nominal) 29V DC (nominal) Zone Voltage 22V DC (nominal) Sounder Alarm Output 2 x 24V DC (nominal) Fault Relay Output N/A 1 x relay 1A maximum Fire Relay Output 1 x relay 1A maximum Zone Capacity 20 Devices 32 Devices Remote Sounder Activation N/A Via N/O Contacts Sounder Activation Delay N/A 0-9 minutes in 1 minute increments Zone End Of Line 10K resistor IN4002 Diode (cathode stripe to +) Sounder End Of Line 10K resistor 10K resistor Charger Voltage 27.6V DC (No Batt Connected) 25 C (No Battery Connected) Zone Short Circuit Protection N/A 100mA Charger Short Circuit Protection N/A Batteries less than 21V Operating Temperature 0 C to 50 C Enclosure Size 355 x 275 x 100mm Weight 2.5kg (excluding batteries) 3.25kg (excluding batteries) 9

10 Premier Conventional Repeater Panel (PRE-REP) The Premier Repeater panel is a hard-wired repeater panel for use with the Premier SX (all sizes), and the Premier Elite (4-8 zone) panels. It is display only (no controls) and indicates power, general fault, general fire & the zone in alarm. It also has an internal buzzer to indicate that it requires attention. It comes supplied with an interface card to connect to the Premier SX and Premier Elite (4-8 zone) panels. 73mm 100mm Zonal indication for fire Common fault indication Surface or semi flush fixing Flush Mount Wall Mount Model PRE-REP Part No Supply Voltage 20 35V DC Supply Voltage 29V DC (nominal) A+ 0V Supply +VE Supply VE Connections GA CF- TN- General Alarm Common Fault Tone (Buzzer Active) Z1- to Z8- Operating Temperature -0 C to 50 C Enclosure Size 355 x 275 x 100mm Weight 1kg Zonal Alarm 10

11 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel (PMP8, PMP16, PMP24) The Premier M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate and maintain. Being of modular construction, the basic M Plus panel has 8 zone capacity, expandable to 16, 20 and 24 zones. The Premier M Plus is suitable for surface mounting or semi-flush fitting (with just the door protruding). 4 Common sounder circuits (150mA each) Optional add-on zonal sounder circuits (50mA Max.) Serial repeater output Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility Zonal to common timer (when fitted with zonal sounder boards) One man test mode Model PMP8 PMP16 PMP24 Part No Detection Zones Mains Voltage 230V AC +10% / 50/60 Hz System Voltage 24V DC (nominal) Zone Voltage 21V DC Sounder Alarm Output 4 x 24V DC Fault Relay Output 1 x relay 1A maximum Fire Relay Output 1 x relay 1A maximum Zone Capacity 32 Devices Remote Sounder Activation N/A Sounder Activation Delay 0 9 minutes in 1 minute increments Zone End Of Line IN4002 Diode Sounder End Of Line 10KΩ Resistor Charger Voltage 28.4V DC (batteries disconnected) Zone Short Circuit Protection 100mA Charger Short Circuit Protection Batteries less than 20V Charger Size 3.0 Amp Operating Temperature 0 C - 50 C Enclosure Size 485 x x 125mm 11

12 Premier M Plus Repeater Panel (PMP-REP, PMP-REP/M) The Premier M Plus repeater is available in 2 versions standard & multiple. The standard repeater offers display & control functions, however it is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system). A single repeater can be powered from the panels auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required. Model PMP-REP PMP-REP/M Part No Functions Display & control Control only Supply Voltage 20-30V DC Max. Quantity Per System 1 5 Serial Repeater A Connections Serial Repeater B +24V DC 0V Operating Temperature 0 C to 50 C Enclosure Size 375 x 335 x 125mm Weight TBC 12

13 Premier 48 M Plus Zone Conventional Fire Alarm Panel (PMP48/24, PMP48/32, PMP48/40, PMP48/48) The Premier 48 M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate & maintain. Being of modular design, the basic panel has 24 zones built in and it can be expanded to 32, 40 & 48 zones. The construction of the panel is epoxy painted steel enclosure, with top & rear cable entries. 4 common sounder circuits (400mA each) Optional add-on zonal sounder circuits (50mA Max) Serial repeater output Auxiliary supply (29 Volts, 250mA) Zone & sounder disablement facility Sounder delay facility Zonal to common timer (when fitted with zonal sounder boards) One man test mode Model PMP48/24 PMP48/32 PMP48/40 PMP48/48 Part No Detection Zones Supply Voltage 230V AC 50/60 Hz System Voltage 29V DC (nominal) Zone Voltage 21V DC Sounder Alarm Output 4 X 24V DC Fault Relay Output 1 relay 1A (normally energised) Fire Relay Output 1 relay 1A maximum Other Connections Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire) Zone Capacity Up to 32 devices Remote Sounder Activation N/A Sounder Activation Delay 0 to 9 minutes Zone End Of Line 100μF capacitor Sounder End Of Line 10K resistor Charger Voltage 28.4V DC (Batteries disconnected) Zone Short Circuit Protection 100mA Charger Short Circuit Protection Batteries less than 20V Charger Size 3 Amp IP Rating IP43 Operating Temperature 0 C to 50 C Enclosure Size 675 x 480 x 135mm Weight 13kg 13

14 Premier 48 M Plus Repeater Panel (PMP48-REP, PMP48-REP/M) The Premier 48 M Plus repeater is available in 2 versions standard & multiple. The standard repeater offers display & control functions, however is limited to one per system. The second version allows multiple repeaters on the same system however they do not have any control functions (i.e. they cannot be used to silence or reset the system). A single repeater can be powered from the panels auxiliary 24V supply. If more than one repeater is to be used, a separate 24V is required. Model PMP48-REP PMP48-REP/M Part No Functions Display & control Control only Supply Voltage 20 30V DC Maximum Quantity Per System 1 5 Serial Repeater A Connections Serial Repeater A +24V DC 0V Operating Temperature 0 C to 50 C Enclosure Size 480 x 330 x 60mm Weight 4.8kg 14

15 Premier MX Conventional Fire Alarm Panel (MX-16 & MX-32) The Premier MX ranges of panels are available in either 16 or 32 zone versions and have been approved by LPCB to EN54 parts 2 & 4. The panels offer an extensive range of configuration options whilst remaining easy to install and configure. Model MX-16 MX-32 Part No Detection Zones Supply Voltage 230V AC +/- 10% System Voltage 24V DC (Nominal) Zone Voltage 24V DC (Nominal) Relay, 1A Zone End of Line 22uF, 35V Axial Capacitor Sounder Output 4 X 24V DC Sounder EOL 3K9 Resistor Aux DC Output 24V DC (Nominal) 1A Repeater option Yes Panel Inputs Remote Evacuation Remote Silence Alarms Remote Reset Class Change Panel Outputs Fault Routing Relay, 1A Fire Routing Relay, 1A Fire Protection Relay, 1A Disablement Active (Open Collector Output) Evacuation Active (Open Collector Output) Buzzer Active (Open Collector Output) RS 485 Repeater Connection Operating Temperature -5 C to 40 C Size 325 x 370 x 126mm 400 x 441 x 131mm Weight 7.05kg 9.35kg LPCB Approved to EN54 parts 2 & 4 Zonal one-man test facility Latching or non-latching zones Delayed or non delayed zone operation Standard or intrinsically safe zone mode Short circuit to fire mode for compatibility with old detectors Zonal or common alarm operation (requires output expansion PCBs) Latching or non-latching fault modes Fault routing, fire routing & fire protection relays can be programmed as 24V output (monitored) or volt free Fault routing, fire routing & fire protection relays can have delayed operation in any configuration The panel is available as flush mount on request Repeater panel option (up to 5 maximum per panel) 15

16 Fyreye Extra Conventional Optical Smoke Detector (FEOE2000) The Fyreye Extra optical smoke detector uses a pulsing IR LED & photodiode to detect IR scatter caused by smoke entering the chamber. The detector is particularly suitable for detecting optically dense smoke, involving materials such as soft furnishings, PVC, plastic, foam and all similar materials which produce small visible particles (0.5 to 10μm). The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal. The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition. 100mm 37mm Designed to meet EN54 requirements Attractive design Dual LEDs for 360 visibility Lockable base to stop unauthorised removal Compatible with all Fyreye bases Model FEOE2000 Part No Detector Class Optical Smoke Design Standard EN54 part 7 Approval DIFT Operating Voltage 9-33V DC Quiescent Current 65μA Alarm 24V DC 53mA MAX Operating Temperature -10 C to +50 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH non-condensing Alarm Condition 2.4% obscuration per metre Coverage 100m 2 IP Rating IP43 Start-up Time 10 Seconds Size (with Base) 100 x 37mm (101 x 53mm) Weight (with Base) 95g (153g) 16

17 Fyreye Extra Conventional Rate of Rise and Fixed Heat Detectors (FEHE2000 & FEFHE2000) The Fyreye Rate of Rise heat detector (FEHE2000) uses a thermistor arrangement to sense a quick rise in temperature and also a final threshold temperature of 57 C. The Fyreye fixed heat detector (FEFHE2000) has a single thermistor arrangement that gives an alarm at a temperature of 90 C. The detectors will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal. The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition. 100mm 48mm Designed to meet EN54 requirement Lockable to base to stop unauthorised removal Remote LED output Dual LEDs for 360 visibility Compatible with all Fyreye bases Model FEHE2000 FEFHE2000 Part No Detector Class Rate of Rise & Fixed Heat Detector Fixed Heat Only Design Standard EN54 part 5 Approval DIFT Operating Voltage 9-33V DC Quiescent Current 40μA Alarm 24V DC 34mA Operating Temperature -10 C to +50 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH non-condensing Alarm Condition Rate of rise or fixed heat 57 C Fixed heat C Coverage 50m² IP Rating IP43 Start-up Time 10 Seconds Size (with Base) 100 x 48 mm (101 x 64 mm) Weight (with Base) 75g (133g) 17

18 Fyreye Extra Conventional Opto-Heat Detector (FEOH2000) The Fyreye Extra opto-heat detector incorporates both an optical chamber and heat sensing element with advanced detection technology & discrimination algorithms. This multisensor is the perfect replacement for ionisation detectors. The detector will work with most modern fire alarm control panels and comes supplied with a locking grub screw to prevent unauthorised head removal. The Fyreye Extra range of detectors has an extra LED to improve detector identification in an alarm condition. 100mm 50mm Advanced electronic technology used to minimise false alarms Designed to meet EN54 requirement Built-in 10 seconds alarm verification Lockable to base to stop unauthorised removal Remote LED output Dual LEDs for 360 visibility Compatible with all Fyreye bases Model FEOH2000 Part No Detector Class Optical / Heat Design Standard EN54 Approval DIFT Operating Voltage 17-20V DC Quiescent Current 100μA Alarm 24V DC 70mA MAX Operating Temperature -20 C to +60 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH non-condensing Alarm Condition 3% obscuration per metre Coverage 100m² IP Rating IP43 Start-up Time 10 Seconds Size (with Base) 100 x 50mm (100 x 66mm) Weight (with Base) 95g (153g) 18

19 Fyreye Conventional Ultra-Violet Flame Detector (FEUV2000) The Fyreye ultra-violet flam detector is particularly suited to applications where flames can be expected to develop initially rather than smoke. This is typically due to the nature of the materials being protected for instance camera film, computer, audio & video tapes or disks. The detector is for indoor use only and should not be exposed to spurious sources of UV, such as sparks, uncovered halogen lights, lightening, etc. as these may trigger a false alarm. Due to the operational nature of flame detectors it is generally recommended to fit just one detector per zone ANODE CATHODE UV EMISSION POINT VERTICAL VIEWING (top fig.) HORIZONTAL VIEWING (bottom fig.) Low profile shape The detector is solar blind and incorporates an electronic filter to eliminate unwanted alarms from naturally occurring phenomena Fast response time High immunity to electrical noise & RF interference ANODE CATHODE Horizontal & Vertical Detector Field Of View Model FEUV2000 Part No Detector Class Ultra Violet Flame Detector Operating Voltage 12-28V DC Quiescent Current 320μA Alarm 24V DC 45-50mA Operating Temperature 0 C to 45 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH non-condensing Alarm Condition 10 seconds for 30mm 4 metres Detection Angle 120 UV Sensitivity nm Size (with Base) 98 x 36mm (98 x 52mm) Weight (with Base) 85g (143g) 19

20 Fyreye Conventional Detector Bases (FE-CB, FE-DB, FE-RB) FE-CB FE-CB/S FE-CB/D FE-RB FE-DB There are 3 types of base available for the Fyreye conventional range of detectors namely common base, diode base and relay base. The Fyreye common base and diode base are available in standard, shallow or deep versions. The common base is used on systems that do not need to keep line integrity on head removal and also on addressable systems. The diode base is used on systems that do need line integrity on head removal. This would include all conventional systems that mix detectors & call points on the same line (please note that the Premier M Plus panels will need an active end of line to work with diode bases). The relay base is mainly used on 12V security systems to signal detector operation to the panel. They can also be used on 24V fire systems where the activation of a particular detector requires a signal to nearby equipment (for instance door holders). Please note that a remote led indicator cannot be used with a relay base as the detector cannot sink enough current to operate both. Model FE-CB FE-CB/S FE-CB/D FE-DB FE-DB/S FE-DB/D FE-RB Part No S D S D Type Common base Diode base Relay base Supply Voltage 9-33V DC 24V DC Quiescent 24V 0μA Alarm 24V 0mA 15mA Relay Max Switching Power N/A 30W, 50VA Relay Max Switching Power N/A 30W, 50VA Relay Max Switching Current N/A 1A resistive Relay Max Switching Voltage N/A 50V AC Relay Minimum Capability N/A 10μA, 10mV Relay Dropout Voltage N/A <6V Operating Temperature -20 C to 90 C (non-condensing or icing) Max. Wind Speed Not affected Connections L1in, L1out, L2, -R & Earth Size 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm 100 x 8mm 100 x 25mm 100 x 15mm Weight 48g 42g 61g 48.2g 42.2g 61.2g 171.4g 20

21 Zeta Remote LED Indicator (ZT-RL) Remote LEDs indicators are used in installations where a detector going to alarm is likely to occur out of sight (for instance behind a locked door or in a ceiling void). In these instances the indicator will then show the location of the alarm. Twin LED s Surface or flush mounting Model ZT-RL Part No Input Voltage 5 30vdc Quiescent Current 0mA Alarm Current 12mA Operating Temperature 0 C - 50 C Max Humidity 95% Relative Humidity Non-condensing IP Rating IP41 Size 85 x 85 x 70mm Weight 113g 21

22 Fyreye 50 & 100m Reflective Beam Smoke Detector (ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV) The Fyreye reflective beam detectors comprise of a single unit incorporating an infrared transmitter & receiver. The signal is reflected by a prism and analysed for smoke presence. Should a predetermined level be reached then the detector will signal an alarm. The system is designed to be mounted so that the beam will project between 0.3 and 0.6 metres below the ceiling and parallel to it. Lateral detection may be up to 7.5 metres either side of the beam. 126mm 120mm 70mm 50 or 100 metre reflective beam smoke detector VdS approved Complies fully to; 140mm 210mm 100mm 100mm BS 5839 part 5 EN54 part 12 Single compact housing Horizontal or vertical mounting 9.5mm 12-24V DC operation Low current consumption Latching or non latching alarm Reflector targeting mode to ease set-up Microprocessor controlled Automatic contamination compensation Selectable sensitivity Robust construction 22

23 The Fyreye beam detectors are available with ranges of up to 50 or 100 metres and either 2 or 4 wire connections. The 2 wire models (ZT-50RZ & ZT-100RZ) are zone powered (please note these will only work on Premier SX & M Plus panels). The 4 wire models (ZT-50RV & ZT-100RV) require an external 24V power supply and have a fire & fault relay output for wide compatibility. Typical Applications Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where several regular smoke detectors would be aesthetically unacceptable. Such places include; Shopping centres Heritage sites Churches or mosques Museums Leisure centres Open Plan offices Warehouses Factories Power stations and more Model ZT-50RZ ZT-100RZ ZT-50RV ZT-100RV Part No A A Range 5-50m m 5-50m m Number of Wires 2 4 Supply Voltage Quiescent Current 10.2V to 30V DC <4mA Operating Temperature -30 C to 55 C Max Humidity Max Wind Speed 95% RH non-condensing Not affected Alarm Current 35mA (typical) <15mA Fire Output 470 OHM resistor placed across zone internally Fault Output Schottky diode introduced between VE in & -VE out Power Down Reset <2 seconds >5 seconds Beam Misalignment Tolerance at 35% Detector ± 0.8 Prism ± 5.0 Alarm Thresholds 2.50dB (25%), 3.74dB (35%), 6.02dB (50%) Optical Wavelength 880nm Construction Flame Retardant ABS (Grey /Black) IP Rating IP50 Size 130 x 210 x 120mm Weight 0.75kg 0.7kg Fire relay closing (relay contact is normally open) Fault relay opening (relay contact is normally closed) 23

24 Fyreye 50 & 100m Auto-aligning Beam Smoke Detector Systems 50 & 100m (ZT-5000R & ZT-5000R/100) Based on the proven technology of the standard Fyreye reflective beam detectors, the Fyreye auto-aligning beam detector has been designed to help improve ease of installation. The system is ideally suited for the protection of large areas where the use of traditional detection technologies would prove to be too difficult and/or costly to install. The system combines an infrared transmitter and receiver in the same discrete unit and operates by projecting a well-defined beam to a reflective prism, which returns the beam to the receiver for analysis. Smoke in the beam path causes a drop in power, which, if below a pre-determined level, results in an alarm signal. The system consists of 2 parts; the beam detector itself and a low level control unit. The system can be fully customised, according to local conditions and installation guidelines; alarm thresholds (sensitivity) and time to alarm/fault can be set from the low level system controller. Each detector head is independently configurable from 8m through to 100m and has its own individual fire threshold. The system controller retains one set of fire and fault relays that is common to all detectors that are installed. The system is supplied as either a 50 or 100 metre version with a single detector head. Additional heads and a long range kit (additional prisms to allow the detector head to reach 100m) are available separately. Additional System Components ZT-5000R/DH Fyreye Auto-aligning Single Beam Detector Head 50m ZT-5000R/100/DH Fyreye Auto-aligning Single Beam Detector Head 100m ZT-5000R/LRK Fyreye Auto-aligning Beam Detector Long Range Kit Worldwide approvals including EN54:12 and UL268 Up to 4 detectors per system controller Each detector configurable from 8m to 100m Integral LASER Auto-align fast automatic beam alignment Auto-optimise building movement and contamination compensation Low level system controller 20mm cable gland knockouts on system controller 2-wire interface from system controller to detector 24

25 202mm 81mm 135mm 135mm 230mm 135mm Model ZT-5000R ZT-5000R/100 Part No Range 50m 100m Number of Wires 4 Supply Voltage Operating Current 14-28V DC Operating Temperature -20 C to 55 C Storage Temperature -40 C to 85 C Max Humidity Max Wind Speed Alarm Current Fire Output Fault Output 8-12mA (low current mode with 1 detector) 48-52mA (high current mode with 1-4 detectors) 85% RH non-condensing Not affected 35mA (typical) Volt free relay contact Volt free relay contact Beam Misalignment 35% Detector ± 0.8, Prism ± 5.0 Alarm Thresholds 2.50dB (25%), 3.74dB (35%) & 6.02dB (50%) Optical Wavelengths Construction IP Rating Detector Size Detector Weight Controller Size Controller Weight 850nm Flame Retardant ABS (Grey / Black) IP x 135 x 135mm 0.5kg 202 x 230 x 81mm 0.9kg 25

26 Zeta UV/IR Optical Flame Detectors (VS-200P & VS-200EX) VS-200P VS-200EX The VS-200P & VS-200EX UV/IR flame detectors detect fuel & gas fires at long distances with the highest immunity to false alarms. The detectors can detect a 0.1m² gasoline pan fire at 30m in less than 5 seconds. Typical Applications Non-hazardous (VS-200P) Parking buildings Warehouse Waste disposal facilities Culture centres Hazardous (VS-200EX) Offshore oil & gas installations Onshore oil & gas installations and pipelines Petrochemical plants Chemical plants Shipbuilding facility Automotive industry Storage tank farms Power generation facility Petrochemical plants Painting industry Warehouse Waste disposal facility Explosive & munitions UV/IR spectrum for medium distance detection and high false alarm immunity Compact & lighter design User selectable sensitivity & functions Multiple output options (relays for alarm & fault, 0-20mA (stepped) and RS-485/RS-232 spectrum monitoring) ATEX approved by DNV for explosion-proof (VS- 200EX UV/IR only) CE certified 26

27 Model VS-200P VS-200EX Part No Spectrum Response Spectrum Response (at highest sensitivity setting for 0.1m² pan fire) UV /IR (Dual Bands) Fuel n-heptane Gasoline Diesel LPG* Distance 30m 30m 20m 20m Fuel Ethanol IPA Methanol Distance 20m 25m 20m *0.5m high / 0.2m width plume fire Response Time Typically 5 seconds Adjustable Time Delay Up to 20 seconds Sensitivity Range 4 sensitivity ranges for 0.1m² n-heptane pan fire from 15m to 65m Field of View Horizontal 90, Vertical 90 Built-in-Test Manual (optionally Automatic) Temperature Range Operating/Storage: -40 C to 75 C Humidity Up to 95% non-condensing Operating Voltage 24VDC norminal (17-31VDC) Power Consumption Standby: max. 35mA, Alarm: max. 75mA Cable Entry 1 x M20 (ISO) Wiring AWG (Str 1.5mm² to 0.13mm²) Electromagnetic Compatibility EMI/RFI protected to EN61000 series Electrical Interface The detector includes twelve(12) terminals with four(4) wiring options Relays Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC Non-isolated Source configuration 0-20mA (stepped) Materials Mounting (Tilt Mount) Dimensions Weight Fault: Normal: Alarm: 0 +1mA 4mA±10% 20mA±10% Polycarbonate Enclosure Stainless Steel Detector: 80 x 82 X 86 mm Detector : 0.3kg (1.0kg with cable gland / 1m-length cable / Tilt Mount) Bit Fault: Warning: Resistance Loop: 2mA±10% 16mA±10% Max. 800Ω Heavy duty copper free aluminium (less than 1%) with bright grey anodizing finish Enclosure options - Stainless Steel 316L with electro polish finish Heavy duty copper free aluminium (less than 1%) with grey epoxy enamel finish Options - Stainless Steel 316L with electro polish finish Detector: 83(d) x 126(l) mm Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland / 1m-length Detector (St. SUS316L): 2.0 kg Tilt mount (aluminium/ St.): 0.3kg / 0.7kg Water and Dust IP66 per EN60529 IP66 and IP67 per EN60529 EMI/RFI Performance CE Marking EN54-10 (designed to meet) ATEX Ex II 2 G Exd IIC T6, -40 C to +75 C (DNV 09 ATEX 0000) KFI (Korea) EN54-10 (designed to meet) 27

28 Zeta Conventional Manual Call Points (ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W) The Zeta conventional manual call point has a modern design and has been approved by BSI to EN54 part 11. It is a resettable call point that signals an alarm with a yellow flag entering the window area and a red alarm LED. There are two versions available; the ZT-CP2 call points comes complete with a protective Perspex cover as well as a snaplatch catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point). Alternatively the ZT-CP1 is supplied without the Perspex cover & snaplatch and is single action or Type A call point. The recommended colour for these call points is red however white is also available to meet architectural requirements. BSI approved to EN54 part 11 Attractive design Model ZT-CP2 ZT-CP2/W ZT-CP1 ZT-CP1/W Part No Type Type B Type A Element Type Resettable Alarm Activation Break snaplatch, lift Perspex cover, press element Press element Colour Red White Red White Input Voltage 9-33V DC Quiescent Current 0mA Alarm Current Typical 35mA (maximum 51mA) Alarm Load 470 Ω resistor Operating Temperature -20 C to 50 C Max Humidity 95% RH non-condensing IP Rating IP43 Size 111 x 100 x 67mm 105 x 100 x 58mm Weight 198g 175g 28

29 Zeta Conventional Weatherproof Call Point (ZT-CP2/WP) The Zeta conventional weatherproof manual call point is an IP65 rated call point which complies with EN54 part 11. It is resettable and signals an alarm with a yellow flag entering the window area and a red alarm LED. The call point comes complete with a protective Perspex cover as well as a snaplatch catch that needs to be broken off before the call point cover can be lifted (this acts as a deterrent to malicious activations and forms a Type B call point). Complies with EN54 part 11 Attractive design Resettable element Protective cover Model ZT-CP2/WP Part No Type Type B Element Type Resettable Alarm Activation Break snaplatch, lift Perspex cover, press element Colour Red Input Voltage 9-33V DC Quiescent Current 0mA Alarm Current Typical 35mA (maximum 51mA) Alarm Load 470 Ω resistor Operating Temperature -20 C to 50 C Max Humidity 95% RH non-condensing IP Rating IP65 Size 87 x 87 x 70mm Weight 198g 29

30 Zeta Conventional Explosion Proof Manual Call Point (ZT-BGU/WP/R & ZT-BGU/WP) The Zeta conventional explosion proof manual call point is manufactured from aluminium with a built-in push button activator. The call point is finished with red anti-corrosive epoxy powder coating with 2 x 20mm cable entries. This unit is equipped with a stainless steel hammer and chain. Two models are available; the ZT-BGU/WP/R with 470Ω built-in resistor for connection to a standard fire alarm system or the ZTBGU/WP for mains connection. Model ZT-BGU/WP/R ZT-BGU/WP Part No /WP /WP 4 Holes - ø7 Contact Rating Voltage Rating 10 Amp 500V AV Build-in Resistor 470Ω N/A IP Rating IP65 IN CASE OF Earthling 2No M6 eternal & 1No M5 internal 185mm B R E A K F I R E G L A S S Hammer Chain Size Weight TBC 1.5kg 105mm 2 Nos.0.75 ET 30

31 Miditone Conventional Electronic Sounder (ZMDD/8R & ZMDD/8W) The Miditone sounder is a small, high output conventional sounder which designed to meet the requirements of EN54 part 3 and is CE marked. The sounder is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 1m with volume control. It is available in red or white to meet architectural requirements. Complies to EN54 part 3 1m sound output 8 Tone patterns Flush or surface fixing Model ZMDD/8R ZMDD/8W Part No A Sound Output See current consumption table Colour Red White Operating Voltage 9-30V DC Quiescent Current 0mA Alarm 24V See current consumption table Operating Temperature -10 C to 50 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH Non Condensing IP Rating IP43 Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm) Weight (with Back Box) 100g (150g) DIL Switch Settings (SW4 N/A) Tone Description db Level Current (ma) Off Off Off Sweep Negative Hz In 1 Second 97 (+/- 2dB) 21 On Off Off Alternating 554 and 440Hz 0.5s Each 95 (+/- 2dB) 17 Off On Off Continuous 660Hz 96 (+/- 2dB) 22 On On Off Alternating 0.4s 94 (+/- 2dB) 17 Off Off On Intermittent 0.5s On/Off 93 (+/- 2dB) 8-24 On Off On Continuous 970Hz 95 (+/- 2dB) 25.5 Off On On Sweep Positive Hz 99 (+/- 2dB) 25 On On On Alternating 800 and 0.25s Each 100 (+/- 2dB) 25 31

32 Miditone Conventional Combined Electronic Sounder & Flasher (ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G) The Miditone combined sounder & flasher is a small, high output conventional sounder & flasher which is designed to meet the requirements of EN54 part 3 and is CE marked. The device is a compact unit that fits a standard European back box and can be either surface or flush mounted. It has a choice of 8 tone patterns, selectable by an internal dip switch and a sound output of 1m with volume control. This is an ideal solution to upgrade an existing sounder to a combined sounder & flasher. It is available with either a red, amber, blue, clear or green lens to meet architectural requirements. Complies to EN54 part 3 1m sound output 8 tone patterns Flush or surface fixing Model ZMDF/8R ZMDF/8A ZMDF/8B ZMDF/8C ZMDF/8G Part No A B 42-02C G Sound Output See current consumption table Lens Colour Red Amber Blue Clear Green Operating Voltage 17-30V DC Quiescent Current 0mA Alarm 24V See current consumption table Operating Temperature -10 C to 50 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH non condensing IP Rating IP43 Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm) Weight (with Back Box) 112g (162g) DIL Switch Settings (SW4 N/A) Tone Description db LEVEL CURRENT (ma) Off Off Off Sweep Negative Hz In 1 Second 102 (+/- 2dB) 35 On Off Off Alternating 554 and 440Hz 0.5s Each 100 (+/- 2dB) 27 Off On Off Continuous 660Hz 100 (+/- 2dB) 33 On On Off Alternating 0.4s 98 (+/- 2dB) 26 Off Off On Intermittent 0.5s On/Off 93 (+/- 2dB) On Off On Continuous 970Hz 103 (+/- 2dB) 37 Off On On Sweep Positive Hz 103 (+/- 2dB) 45 On On On Alternating 800 and 0.25s Each 103 (+/- 2dB) 42 32

33 Securetone Conventional Electronic Sounder (ZST/8R & ZST/8W) The Securetone sounder is designed to be aesthetically pleasing and unobtrusive. It has an elegant round design and fits to its supplied mounting plate with a bayonet action to avoid unsightly screws. It has 8 selectable tones with a volume adjust screw to set the required sound level. This product is designed to meet the requirements of EN54 part 3 and is CE marked. 85mm 8 selectable tones Volume control 100mm Model ZST/8R ZST/8W Part No A Sound Output 1 metre Colour Red White Operating Voltage 10-30V DC Quiescent Current 0mA Alarm 24V 35mA MAX Operating Temperature -0 C to 50 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH Non Condensing IP Rating IP43 Size (including Plate) 100 x 100 x 75mm (100 x 100 x 85mm) Weight (including Plate) 230g (260g) 33

34 Secure Light Xenon Flasher (ZTSL6/R & ZTSL6/A) The Secure Light Xenon Flasher range is designed to provide a visual warning at alarm condition. Both red and amber versions are available with the lenses constructed of high-impact and heat resistant ACRYREX. The case is made of high-impact resistant ABS plastic. 97mm Available in Red & Amber Fits onto a standard outlet box 100mm Model ZST/8R ZST/8W Part No Colour Red Amber Flash Energy 3 Watt Flash Frequency 60 times per minute Operating Voltage 20-30V DC Quiescent Current 0mA Alarm 24V 100mA MAX Operating Temperature -30 C to 60 C Minimum Continuous Temperature 0 C Maximum Humidity 95% RH Non Condensing IP Rating IP54 Size 97 x 100mm Weight (including Plate) 231g 34

35 Maxitone Conventional Sounder and Combined Sounder & Flasher (ZMT/8R, ZMT/8W & ZMTF/8R) The Maxitone sounder is an ideal alternative to fire bells and for external use. It is housed in an attractive horn comprises of flame retardant ABS. Eight selectable tones and volume control are featured to meet most requirements. The Maxitone is also available with transparent polycarbonate front which will provide both visual and audible alarm. 120mm High output 8 selectable tones Volume control 126mm 107mm Model ZMT/8R ZMT/8W ZMTF/8R Part No A Sound Output See current consumption table Colour Red White Red Operating Voltage 17-30V DC Quiescent Current 0mA Alarm 24V See current consumption table Operating Temperature -20 C to 60 C Minimum Continuous 0 C Temperature Maximum Humidity 95% RH non condensing IP Rating IP65 Size 124 x 130 x 100mm Weight 357g DIL SWITCH SETTINGS (SW4 N/A) Tone Description db Level Off Off Off On Off Off Sweep Negative Hz In 1 Second Alternating 554 and 440Hz 0.5s Each Off On Off Continuous 660Hz On On Off Off Off On Alternating 0.4s Intermittent 0.5s On/Off On Off On Continuous 970Hz Off On On On On On Sweep Positive Hz Alternating 800 and 0.25s Each 101 (+/- 2dB) 98 (+/- 2dB) 101 (+/- 2dB) 98 (+/- 2dB) 98 (+/- 2dB) 103 (+/- 2dB) 103 (+/- 2dB) 102 (+/- 2dB) Current (ma)

36 Zeta Conventional Fire Alarm Bells (ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP) ZTB6B ZTB8B 152mm 152mm 55mm The Zeta motorised fire alarm bells combine styling and functional efficiency. They incorporate a low power rotary centrifugal mechanism, which gives a high sound output with low current consumption at 24V dc. The bells are available in 2 sizes; 6 (152mm) and 8 (203mm). These sizes suit a wide variety of installations. 203mm 55mm There is a 230V ac version of the 6 bell, and a 24V dc Weatherproof version of the 8 bell. 203mm Low current Universally accepted fire evacuation signal Model ZTB6B ZTB8B/230 ZTB8B ZTB8B/WP Part No Supply Voltage 18-30V dc V AC 18-30V dc Diameter 6 (152mm) 8 (203mm) Quiescent Current 25mA 28mA Nominal 1M 95dB(A) 97dB(A) Dimensions 152 x 152 x 55mm 203 x 203 x 55mm Weight 860g 960g 1700g 1800g 36

37 Zeta Flame Proof Siren (ZTSR/EXD24 & ZTSR/EXD230) The Zeta flame proof siren is an explosion proof siren available in either 24V or 230V versions. An intrinsically safe circuit is housed in the main chamber and it is duly wired up to terminal chamber through sealed bushes. The horn unit is placed on the main chamber cover and the output signals are taken through sealed coils. Neoprene 0 rings are provided for the weather proof protection. 170mm 240mm 390mm Model ZTSR/EXD24 ZTSR EXD230 Part No / /230 Type Of Protection Flame proof Exd T6 IP 65 Area Classification Zone 1 & 2 Gas Groups Group I, II A, II B, II C Apparatus Standard IS CMRI Certificate CMRI / TC / S / H388 Approvals CCE, DGFAS Materials Cast Aluminium LM 6 Weight 5 Kg (approx.) Size 170 (w) x 390 (h) x 240 (d) mm IP Protection IP 65 to IS / 93 Finish Anti corrosive Epoxy Powder Coated Cable Entry 2 x ¾ ET Gasket Neoprene Hardware Stainless Steel Terminals 4 x 2.5 sq. mm (standard) 6 x 2.5 sq. mm (for looping) Voltage 24 V DC 230 V AC 50 Hz Output Current 600mA Peak. Galvanically Isolated Power Rating 18 Watts Sound Output 106 db 900 Hz On & Off alternatively at 1C/s Earthing External: 2 Nos. - M6 Internal: 1 No. - M5 37

Premier M Plus & Infinity 8

Premier M Plus & Infinity 8 25 Years of Manufacturing Excellence Premier M Plus & Infinity 8 Conventional Fire Alarm Systems 007 Assessed to ISO 9001: 2008 Certificate number 330 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel

More information

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently

(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently (68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

Addressable Fire Alarm Systems

Addressable Fire Alarm Systems Addressable Fire Alarm Systems Contents Introduction 3-7 Premier AL -4 Loop Analogue Addressable Fire Alarm Panel 8-9 Premier AL 5-8 Loop Analogue Addressable Fire Alarm Panel 0 Premier AL: Addressable

More information

Triple Waveband Infra-Red Flame Detection

Triple Waveband Infra-Red Flame Detection Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source

More information

CB200W Water Leak Detection Panel Application Guide

CB200W Water Leak Detection Panel Application Guide Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

AlarmSense 2-wire detection and alarm system. Product Guide

AlarmSense 2-wire detection and alarm system. Product Guide AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

CB200 1 8 Zone Conventional Control Panel

CB200 1 8 Zone Conventional Control Panel CB200 1 8 Zone Conventional Control Panel > features Built-in detector removal indication facility From 1 to 8 zones 4 Alarm circuits on 4-8 zone panels Conforms to the requirements of EN54-2 User-friendly

More information

Analogue addressable devices

Analogue addressable devices Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

FIRERAY 2000 Installation Guide

FIRERAY 2000 Installation Guide FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description

More information

MINERVA MX MX Virtual Multi-Sensor Detectors

MINERVA MX MX Virtual Multi-Sensor Detectors DATASHEET MINERVA MX MX Virtual Multi-Sensor Detectors Over 20 fire detection modes Tyco MX FASTLOGIC Expert algorithms MX HPO detection Algorithms Up to 250 detectors per loop Optional bi-directional

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

How To Use A Ds340 (Dsp)

How To Use A Ds340 (Dsp) Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk

welcome to our world fire alarm systems - series 600 www.staticsystems.co.uk Static Systems Group PLC Heath Mill Road, Wombourne Staffordshire WV5 8AN. United Kingdom. Tel: +44 (0) 1902 895551 Fax: +44 (0) 1902 324969 www.staticsystems.co.uk welcome to our world In line with our

More information

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 2.1 GENERAL...2 2.1.1 Scope 2 2.1.2 References 2 2.1.3 Contractor s Responsibility 2 2.1.4 System Description

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

HART HSSD High Sensitivity Smoke Detection

HART HSSD High Sensitivity Smoke Detection HART HSSD High Sensitivity Smoke Detection The HART High Sensitivity Smoke Detection system (HSSD) is an Aspirating Smoke Detection system (ASD) designed to give very early indication of an incipient

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

3. MOUNTING THE FIRE ALARM PANEL... 7 3.1 PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

3. MOUNTING THE FIRE ALARM PANEL... 7 3.1 PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL INSTALLATION MANUAL CONTENTS 1. INTRODUCTION. 3 1.1 HANDLING THE PCBS 1.2 USING THIS MANUAL 1.3 ABOUT THE PREMIER SX FACP & INTEGRAL PSE 1.4 DESIGNING THE SYSTEM 1.5 EQUIPMENT GUARANTEE 2. FIRST FIX GUIDELINES.

More information

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex

More information

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

Emergency Voice Communication Systems EVCS Network 8 Data Sheet Emergency Voice Communication Systems EVCS Network 8 Data Sheet The Emergency Voice Communications System (EVCS) Network 8 is for use as a Fire Telephone system, Disabled Refuge Call system or as a combined

More information

Repeaters and Mimics Data Sheet

Repeaters and Mimics Data Sheet Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Flame detection across the spectrum. Range Brochure

Flame detection across the spectrum. Range Brochure talentum Flame detection across the spectrum Range Brochure Talentum - Why use our Flame Detectors... Talentum Flame Detectors are ideal for applications where fast acting and accurate detection of fire

More information

Fire Detection Systems

Fire Detection Systems Fire Detection Systems contents conventional fire alarm systems 4 intelligent fire alarm systems 9 detector application guide 15 conventional fire alarm systems principle of operation A conventional fire

More information

ALARMLINE ANALOGUE Linear Heat Detection System

ALARMLINE ANALOGUE Linear Heat Detection System ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces

More information

VEGA Analogue Addressable Control Panels

VEGA Analogue Addressable Control Panels Analogue Addressable Control Panels Representing the future of fire alarm control technology, Vega's modular concept enables the tailoring of system design for the smallest to the largest system. Designed

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

500r+ Installation and User Guide

500r+ Installation and User Guide 500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

now faster and boasting many new useful features this is by far the best beam on the market

now faster and boasting many new useful features this is by far the best beam on the market now faster and boasting many new useful features this is by far the best beam on the market Motorised reflective optical beam smoke detector Developed to overcome the problems of old outdated technology

More information

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access CSP Combined Series Telephone Door Entry with Proximity Keyfob Access PD-094 Issue 3 General Description The CSP series systems are combined Door Entry Telephone and Proximity Access Systems. The entrance

More information

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Guide to Fire Alarm Systems

Guide to Fire Alarm Systems Guide to Fire Alarm Systems Guide to Fire Alarm Systems INDEX Introduction Page 2 When is a Fire Alarm System Required Page 2 The Fire Precautions Act 1971 & Fire Precautions (Workplace) Regulations 1997Page

More information

Page 162. Page 154. Page 158 Page 146. Page 157. Page 152. Page 160. Page 149. Page 159. Page 156. Page 150

Page 162. Page 154. Page 158 Page 146. Page 157. Page 152. Page 160. Page 149. Page 159. Page 156. Page 150 Page 162 NEW Page 154 Page 158 Page 146 Page 157 Page 152 Page 160 Page 159 Page 149 Page 156 Page 150 Summary Audible Signal Devices Page 151 Page 163 Page 148 installation version Free-standing Electronic

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

Fire Detection Product Range

Fire Detection Product Range Fire Detection Product Range World Leading Fire Detection Products from the NITTAN group Issue 1.0 Business Overview The Nittan Group has been at the forefront of the fire protection industry since 1954

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

720r Addendum: Siting the 720r

720r Addendum: Siting the 720r 720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited

More information

Section D..General Auto Electrical Corporation

Section D..General Auto Electrical Corporation 43 Section D..General Auto Electrical Corporation 1. LED Based Signal unit GAEC manufacture LED based signaling system for use in electrified and non electrified sections of Indian railways. The exceptional

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 4 1.2.3

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Emergency voice communications Product Name

Emergency voice communications Product Name Product Name 76 EATON FIRE AND VOICE ALARM SYSTEMS CFCC2556 January 2015 Contents Contents Emergency voice communications Panels Network exchange units 78 Non network exchange units 80 Devices Outstations

More information

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

FAAST. Fire Alarm Aspiration Sensing Technology

FAAST. Fire Alarm Aspiration Sensing Technology FAAST Fire Alarm Aspiration Sensing Technology The world s finest manufacturing facility System Sensor s European products are researched, designed and manufactured at our 10,000m2 state-ofthe-art facility

More information

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

Consultant s Guide for Fire Detection & Alarm Systems for Buildings

Consultant s Guide for Fire Detection & Alarm Systems for Buildings section one specification for a digital addressable fire system Consultant s Guide for Fire Detection & Alarm Systems for Buildings section one specification for a digital addressable fire system section

More information

C E R T I F I C AT I O N LPCB B O A R D P R E V E N T L O S S. Cooper Fire Systems

C E R T I F I C AT I O N LPCB B O A R D P R E V E N T L O S S. Cooper Fire Systems P R E V E N T L O S S I O N C E R T I F I C AT LPCB B O A R D I O N Cooper Fire Systems ONE COOPER Every day, thousands of people all over the world use products made by Cooper Industries. As a premier

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

Floodlight Range Installation Guide

Floodlight Range Installation Guide SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected

More information

QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 1 Part 01: General

QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 1 Part 01: General QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 1 Part 01: General 1 GENERAL... 2 1.1 INTRODUCTION... 2 1.1.1 Scope 2 1.1.2 General 2 1.2 REGULATIONS... 2 1.2.1 Electrical Installations

More information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate 1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration

More information

TS510 & TS500. Installation & User Guide. Compatible Equipment

TS510 & TS500. Installation & User Guide. Compatible Equipment Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.

More information

TX GSM SMS Auto-dial Alarm System. Installation and User Manual

TX GSM SMS Auto-dial Alarm System. Installation and User Manual TX GSM SMS Auto-dial Alarm System Installation and User Manual Product Features: 1. 16 wireless zones, 3 wired zones alarm system, suitable for small to medium size offices and homes. 2. The system uses

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE User manual v1.5 Compatible with: ESIM264 v7.09.02 and up. ESIM364 all versions. Main features: Hardwired zone expansion adding 16 additional zones per

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

Communication A BRITISH MANUFACTURER. Features:

Communication A BRITISH MANUFACTURER. Features: care2 Radial Wired Emergency Voice Communication Manufacturing EVC systems since 2001 CARE2 is a radial wired emergency voice communication system built to the high standard you expect from Baldwin Boxall.

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE

More information

Product Specification instalert Rapid Messenger Variable Message Sign

Product Specification instalert Rapid Messenger Variable Message Sign instalert 2 units to cover any application instalert 18 (ia18): 18 x 28 full matrix instalert 24: (ia24): 24 x 60 full matrix Size, Weight without battery ia18: 30 x 20 x 2.74, 29 lbs ia24: Folds to fits

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

Laserlyte-Flex Alignment System

Laserlyte-Flex Alignment System Laserlyte-Flex Alignment System LaserLyte-Flex The LaserLyte-Flex Alignment System is a unique, interchangeable, low cost plug and play laser system. Designed specifically for aligning and positioning

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

ICP-CP500. User's Guide ICP-CP500 Codepads

ICP-CP500. User's Guide ICP-CP500 Codepads ICP-CP500 EN User's Guide ICP-CP500 Codepads ICP-CP500 User's Guide 1.0 ICP-CP500 Series Codepads Overview EN 2 1.0 ICP-CP500 Series Codepads Overview The codepad is the communications interface between

More information

INSTALLER INSTRUCTIONS

INSTALLER INSTRUCTIONS 230V~ SMOKE & HEAT ALARMS ALKALINE BATTERY BACK-UP Ei141RC - Ionisation Ei144RC - Heat Ei146RC - Optical RECHARGEABLE LITHIUM CELL BACK-UP Ei161RC - Ionisation Ei164RC - Heat Ei166RC - Optical INSTALLER

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide

Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide Discovery 1-4 Loop Analogue Addressable Control Panel Application Guide Contents Page 1.0 Introduction and Typical System Illustration 2 2.0 Cabinet Specifications 4 3.0 Hardware Specifications 7 4.0 Software

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Application Guide HMOs

Application Guide HMOs Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application

More information

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI)

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI) FLARE MONITORS Infrared Sensors for Monitoring Smokeless Flares, Pilots, and Flame Intensity FMDS2014 FLARE MONITOR (FM) Monitor smokeless flare combustion efficiency to maximize destruction of hazardous

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

Overview of Fire Alarm Systems and Maintenance

Overview of Fire Alarm Systems and Maintenance Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety

More information

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals INFINITY The Intelligent 2 Wire Fire Detection System for Professionals Infinity ID 2 The intelligent 2 wire fire detection system for professionals In a nutshell Zeta Alarm Systems is proud to introduce

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle

More information

DOMESTIC SMOKE ALARMS

DOMESTIC SMOKE ALARMS SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE

More information

Tubular Analog model resolution: 0,5 mm (SLOW mode), 1 mm (FAST mode) Right angle Repeatibility: 0,7 mm Vdc

Tubular Analog model resolution: 0,5 mm (SLOW mode), 1 mm (FAST mode) Right angle Repeatibility: 0,7 mm Vdc Ultrasonic sensors for high precision detection of clear and transparent objects Clear object detection, inspection on transparent or highly reflective film and liquid level measurement Standard M18 tubular

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information