The New Brocade Data Center and Its Advantages

Size: px
Start display at page:

Download "The New Brocade Data Center and Its Advantages"

Transcription

1 WHITE PAPER DATA CENTER World-Class Data Center Realizes Goals of Investment Protection, Energy Efficiency, and Scalability In March of 2008, Brocade had a vision to build a worldclass campus, including a new data center to demonstrate the Brocade One concepts of unmatched simplicity, nonstop networking, investment protection, and optimized applications. In September of 2010, the vision was realized and we officially dedicated the new campus and data center.

2 The new Brocade campus in San Jose, California, was built to provide the business with flexibility needed to satisfy growth for our employees and for R&D and solution labs. Design principles of both the campus and the data centers were flexibility, scalability, energy efficiency, and sustainability. And the results were nothing short of extraordinary. Three buildings provide 562,000 square feet to house Brocade s 2,500 employees, labs, data center, café, fitness center, and so on. An overarching goal was thoughtful investment and that guided our decisions with regards to our employees, partners, customers, and vendors as well. Prior to the move, we had three data centers and R&D labs in five locations with a total of about 2000 racks. On the new campus, labs were consolidated in one building. The highly efficient electrical and mechanical design of Brocade data center and labs will save over 10 million Kilowatt-hours of energy consumption annually over the previous year. And over 4500 tons of carbon dioxide emissions annually will be offset over the previous year. This paper describes how we designed and built the data center and labs to achieve these spectacular results. 2

3 Introduction Looking back at the planning phase, a number of goals were mandated by the executive staff: Energy efficiency and sustainability Consolidation of footprint, while maximizing real estate investment Investment protection, that is, use as much of the existing equipment as possible Create a baseline for future growth and enhancements The following sections describe how we accomplished these goals followed by some best practices and lessons learned about planning and building or refreshing a corporate data center. Energy Efficiency and Sustainability Both industry best practices and innovative design played a part in delivering on the green promise in the new data center. Hot Aisle/Cold Aisle As is common in most organization, the IT equipment load is the number one consumer of electricity at a building level. One of the best ways to handle the heat generated by the many devices in the data center is by using a hot aisle/cold aisle equipment floor plan. Servers and network equipment are typically configured in standard 19 (wide) racks and rack enclosures, in turn, are arranged for accessibility for cabling and servicing. Increasingly, however, the floor plan for data center equipment distribution must also accommodate air flow for equipment cooling. This requires that individual units be mounted in a rack for consistent air flow direction (all exhaust to the rear or all exhaust to the front) and that the rows of racks be arranged to exhaust into a common space, called a hot aisle/cold aisle plan, as shown in Figure 1. COLD aisle Equipment row HOT aisle Figure 1. Hot aisle/cold aisle plan for consistent air flow. Equipment row Air flow COLD aisle Equipment row HOT aisle A hot aisle/cold aisle floor plan provides greater cooling efficiency by directing cold to hot air flow for each equipment row into a common aisle. Each cold aisle feeds cool air for two equipment rows while each hot aisle allows exhaust for two equipment rows, thus enabling maximum benefit for the hot/cold circulation infrastructure. Even greater efficiency is achieved by deploying equipment with variable-speed fans. Hot row containment provides a better working environment for IT personnel and temperatures are more comfortable. In Brocade data center and labs, we can control temperature to the level of a pod if we need to (two rows of equipment back to back make up a pod). The Solutions Center lab also uses both high end-doors and more economical curtain system heat containment methods. 3

4 Variable Speed Fans Variable speed fans increase or decrease their spin rate in response to changes in equipment temperature. As shown in Figure 2, cold air flow into equipment racks with constant speed fans favors the hardware mounted in the lower equipment slots and thus nearer to the cold air feed. Equipment mounted in the upper slots is heated by their own power draw as well as the heat exhaust from the lower tiers. Use of variable speed fans in equipment racks enables each unit to selectively apply cooling as needed, with more even utilization of cooling throughout the equipment rack. Figure 2. Variable speed fans in equipment racks enable more efficient distribution of cooling. More even cooling Equipment at bottom is cooler Server rack with constant speed fans Server rack with variable speed fans Power Distribution Units High-voltage power is fed into the data center and labs to Power Distribution Units (PDUs), which physically sit inside these labs, minimizing the energy and line loss to the end-point. The PDUs have shadow metering capabilities to monitor and measure energy consumption with utility-grade precision. Green-labeled PDUs are backed up by UPS and emergency power, while red-labeled PDUs are backed up by emergency power only. Inside the data center, equipment is fed from both A and B power sources for redundancy, with A power having UPS and emergency generator backup. Figure 3. PDUs minimize energy and line loss to the end-point. In addition to known best practices in this area, Brocade worked with a trusted vendor to design and build a custom In-Row Cooling (IRC) system. To quote the vendor, This may well be the best system on the market today that s not on the market but will be. This IRC unit provides the ultimate solution in flexibility due to its unique custom design. It can fit into any rack space in the data center because of its similar physical footprint to the rack. Brocade s custom IRC is 80 percent more energy efficient than the conventional Clean Room Air Conditioning Unit (CRAC) and 70 percent more efficient than current alternative IRC units on the market. 4

5 The IRC unit provides added reliability by utilizing three high-efficiency fans directly driven by three EMC motors. The motors themselves are the most efficient on the market, consuming about 70 percent less energy than the nearest competitor. Each motor operates at 33 percent, and if a fan or motor fails the unit automatically ramps up the remaining fans to 66 Hz to provide the full cooling capacity of the unit. Automated Controls with Energy Monitoring Because vendor wattage and BTU specifications may assume maximum load conditions, using data sheet specifications or equipment label declarations does not provide an accurate basis for calculating equipment power draw or heat dissipation. An objective multi-point monitoring system for measuring heat throughout the data center is really the only means to observe and proactively respond to changes in the environment. A number of monitoring options are available today. For example, some vendors are incorporating temperature probes into their equipment design to provide continuous reporting of heat levels via management software. Some solutions provide rack-mountable systems that include both temperature and humidity probes and monitoring through a Web interface. In addition, new monitoring software products can render a three-dimensional view of temperature distribution across the entire data center, analogous to an infrared photo of a heat source. Although monitoring systems add cost to data center design, they are invaluable diagnostic tools for fine-tuning airflow and equipment placement to maximize cooling and keeping power and cooling costs to a minimum. An example of a three-dimensional view of temperature in the Brocade data center is shown in Figure 4. Starline Busway System It s interesting to note that Brocade was an early adopter of the Starline Busway System, an electrical power distribution system for mission-critical facilities. It is simple, versatile, fast and economical solution for supplying power to electrical loads and is unique because the busway can be tapped instantly at any location, without losing uptime giving you the ability to change or add to floor plans quickly and easily. Although the Starline Busway System has been on the market for a number of years, it s still winning awards, most recently the Tech 50 award from the 2009 Pittsburgh Technology Council in the Advanced Manufacturing category. Figure 4. A 6 Sigma application generates heat topologies at different heights from the floor. Cooling System The number two consumer of electricity at the building level are the chiller and then the pumps to circulate water for cooling to the HVAC units in the lab. Brocade selected the highest-efficiency chillers at partial loads and cooling towers with variable frequency drives. As a general rule, chillers never reach 100 percent load, the point at which their highefficiency features are triggered. However, the high-efficiency features of our chillers are triggered at partial loads below 50 percent load, which helps conserve energy at Day One loads Our chilled water system utilizes a water side heat exchanger, which is passive and has no electrical pumps and is capable of providing 2000 tons of free cooling without the use of a compressor. This water-side heat exchanger provides free cooling when the outside temperature permits. Despite what you may have heard, in Silicon Valley the sun doesn t shine all the time. 5

6 Finally, we have a primary system only and no secondary pumping system. Before the 1980s, primary-only systems were the norm. With the growth of high-tech labs and critical labs, a primary/secondary system has been typically prevalent until very recently. Organizations were reluctant to do away with primary/secondary systems, because they felt that it made them vulnerable in the event of a fluctuation differential pressure that might exist in a primary only system. But in Brocade s case where through the design and selection of the correct equipment, automation and controls, and its constant load, there is no concern or need to utilize a primary/secondary system to regulate pressure in load. We simply don t need it and have avoided initial capital investment cost and inefficiencies. Figure 5. Main cooling system substations. Consolidation Through the consolidation of three data centers into one we were able to consolidate our space requirements by decreasing the physical footprint by 30 percent and decreasing data center energy consumption by 37 percent. Racks One of the decisions that we made was to use taller racks 8 tall instead of 6 with standard 19 width. We were able to consolidate 2011 racks to the 1860 rack capacity in for all labs. In 2011, it is projected that we will be occupying 1587 of these racks, with 300 targeted for growth. With these taller racks and greater rack count, a question that comes to mind is how to fit them into the data center and labs. We used a flat floor design, which allows for more vertical rack space, rather than a raised floor, which requires ramps and stairs for access. A flat floor design was selected because it allowed 10 percent more rack counts in comparison to conventional raised floor systems which require ramps and stairs. Cabling One of the most critical areas for consolidation is in fact the proliferation of cables in highdensity racks, with high-port-count devices. In both the data center and other labs, two separate conveyance systems were deployed: structured and horizontal cabling systems (Systimax) and ad hoc cabling in the data center (Systimax, Tyco) and ad hoc cabling in the solutions and proof-of-concept labs (Corning, Splice, Tyco, and Systimax). This lab also features a flexible two-tier cable conveyance design that provides both a structured cable tray conveyance system for the backbone network and a high capacity open cable conveyance system for ad-hoc cabling. In the Proof-of-Concept (PoC) lab, Brocade products are physically connected to an optical switching matrix that lets us rapidly build out and store network topologies for each customer. This allows us to share equipment and minimize set up time. 6

7 Investment Protection The new data center is initially a Tier 1 (no N+1 power or cooling), but the infrastructure is in place for a Tier 2 infrastructure (generator pads, UPS, additional chillers) on which N+1 systems can be placed when the business requirement exist The data center has installed the latest in fire suppression technology. This includes a double-action, pre-action dry pipe system that prevents water leaks and false alarms from interrupting business-critical applications. Fire and smoke detection is monitored by very early smoke detection, which senses the smallest amount of combustion or smoke particles and activates a dry green agent fire suppression system that stops and prevents fire from spreading by removing the oxygen in the space. Campus Sustainability To summarize, by meeting sustainability challenges head on: This campus uses 40 percent less water than a standard office or campus building. This is achieved by the collection of rain and run-off water recycled, filtered, and reused for irrigation. The selection of sustainable trees and landscaping features, and the selection of no-water and low-flow water fixtures throughout the campus help us accomplish this. The campus utilizes a 550 KW photovoltaic (PV) system attached to our garage structure that harnesses the suns energy to offset power consumption and the carbon footprint. The power from the PV system is fed into Building 2. This system is capable of offsetting the total amount of power consumed by our data center. By strategically implementing the best practices at a building and lab level one of the lowest calculated Power Utilization Factors in Data Center design of 1.3 has been achieved. The design has also allowed us to exceed California energy code requirements by 16%. Due to the selection of a sustainable site, water efficiency, energy efficiency, selection and reuse of renewable materials, indoor air quality achievements, and innovation of design, the campus is scheduled to receive accreditation from the U.S. Green Building Council for Leadership and Energy and Environmental Design (LEED) certification of silver for core and shell and gold for corporate Interiors. Figure 6. Power Usage Effectiveness (PUE): a measure of data center energy efficiency calculated by dividing the total data center energy consumption by the energy consumption of the IT computing equipment. About Brocade Founded in 1995, Brocade is an industry leader in providing reliable, high-performance network solutions that help the world s leading organizations transition smoothly to a virtualized world where applications and information reside anywhere. Today, Brocade is extending its proven data center expertise across the entire network with future-proofed solutions built for consolidation, network convergence, virtualization, and cloud computing. Headquartered in San Jose, California, the company has approximately 4000 employees worldwide and serves a wide range of industries and customers in more than 160 countries. With a complete family of Ethernet, storage, and converged networking solutions, Brocade helps organizations achieve their most critical business objectives through: Unmatched simplicity to overcome today s complexity Non-stop networking to maximize business uptime Optimized applications to increase business agility and gain a competitive advantage Investment protection to provide a smooth transition to new technologies while leveraging existing infrastructure Brocade combines a proven track record of expertise, innovation, and new technology development with open standards leadership and strategic partnerships with the world s leading IT companies. This extensive partner ecosystem enables truly best-in-class business solutions. To find out more about Brocade, visit 7

8 WHITE PAPER Corporate Headquarters San Jose, CA USA T: European Headquarters Geneva, Switzerland T: Asia Pacific Headquarters Singapore T: Brocade Communications Systems, Inc. All Rights Reserved. 10/10 GA-WP Brocade, the B-wing symbol, BigIron, DCFM, DCX, Fabric OS, FastIron, IronView, NetIron, SAN Health, ServerIron, TurboIron, and Wingspan are registered trademarks, and Brocade Assurance, Brocade NET Health, Brocade One, Extraordinary Networks, MyBrocade, and VCS are trademarks of Brocade Communications Systems, Inc., in the United States and/or in other countries. Other brands, products, or service names mentioned are or may be trademarks or service marks of their respective owners. Notice: This document is for informational purposes only and does not set forth any warranty, expressed or implied, concerning any equipment, equipment feature, or service offered or to be offered by Brocade. Brocade reserves the right to make changes to this document at any time, without notice, and assumes no responsibility for its use. This informational document describes features that may not be currently available. Contact a Brocade sales office for information on feature and product availability. Export of technical data contained in this document may require an export license from the United States government.

Brocade and McAfee Change the Secure Networking Landscape with High Performance at Lowest TCO

Brocade and McAfee Change the Secure Networking Landscape with High Performance at Lowest TCO WHITE PAPER www.brocade.com IP NETWORK SECURITY Brocade and McAfee Change the Secure Networking Landscape with High Performance at Lowest TCO The Non-Stop Secure Network, a Brocade and McAfee joint solution,

More information

Multi-Chassis Trunking for Resilient and High-Performance Network Architectures

Multi-Chassis Trunking for Resilient and High-Performance Network Architectures WHITE PAPER www.brocade.com IP Network Multi-Chassis Trunking for Resilient and High-Performance Network Architectures Multi-Chassis Trunking is a key Brocade technology in the Brocade One architecture

More information

Data Center Evolution without Revolution

Data Center Evolution without Revolution WHITE PAPER www.brocade.com DATA CENTER Data Center Evolution without Revolution Brocade networking solutions help organizations transition smoothly to a world where information and applications can reside

More information

Ethernet Fabrics: An Architecture for Cloud Networking

Ethernet Fabrics: An Architecture for Cloud Networking WHITE PAPER www.brocade.com Data Center Ethernet Fabrics: An Architecture for Cloud Networking As data centers evolve to a world where information and applications can move anywhere in the cloud, classic

More information

Building Tomorrow s Data Center Network Today

Building Tomorrow s Data Center Network Today WHITE PAPER www.brocade.com IP Network Building Tomorrow s Data Center Network Today offers data center network solutions that provide open choice and high efficiency at a low total cost of ownership,

More information

THE PATH TO A GREEN DATA CENTER. Hitachi Data Systems and Brocade. Joint Solution Brief

THE PATH TO A GREEN DATA CENTER. Hitachi Data Systems and Brocade. Joint Solution Brief THE PATH TO A GREEN DATA CENTER Hitachi Data Systems and Brocade Joint Solution Brief Hitachi Data Systems The Growing Need for Green Data Center Solutions 50 percent of data centers worldwide will have

More information

Facilitating a Holistic Virtualization Solution for the Data Center

Facilitating a Holistic Virtualization Solution for the Data Center WHITE PAPER DATA CENTER Facilitating a Holistic Virtualization Solution for the Data Center Brocade solutions provide a scalable, reliable, and highperformance foundation that enables IT organizations

More information

Choosing the Best Open Standards Network Strategy

Choosing the Best Open Standards Network Strategy WHITE PAPER IP network Choosing the Best Open Standards Network Strategy In order to truly align the enterprise infrastructure strategy with business requirements, organizations must be free to choose

More information

The Road to SDN: Software-Based Networking and Security from Brocade

The Road to SDN: Software-Based Networking and Security from Brocade WHITE PAPER www.brocade.com SOFTWARE NETWORKING The Road to SDN: Software-Based Networking and Security from Brocade Software-Defined Networking (SDN) presents a new approach to rapidly introducing network

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Brocade One Data Center Cloud-Optimized Networks

Brocade One Data Center Cloud-Optimized Networks POSITION PAPER Brocade One Data Center Cloud-Optimized Networks Brocade s vision, captured in the Brocade One strategy, is a smooth transition to a world where information and applications reside anywhere

More information

The Business Case for Software-Defined Networking

The Business Case for Software-Defined Networking WHITE PAPER The Business Case for Software-Defined Networking Brocade enables customers a means of reducing costs of service delivery through Software-Defined Networking (SDN) technologies. In addition,

More information

Scalable Approaches for Multitenant Cloud Data Centers

Scalable Approaches for Multitenant Cloud Data Centers WHITE PAPER www.brocade.com DATA CENTER Scalable Approaches for Multitenant Cloud Data Centers Brocade VCS Fabric technology is the ideal Ethernet infrastructure for cloud computing. It is manageable,

More information

NETWORK FUNCTIONS VIRTUALIZATION. The Top Five Virtualization Mistakes

NETWORK FUNCTIONS VIRTUALIZATION. The Top Five Virtualization Mistakes WHITE PAPER www.brocade.com NETWORK FUNCTIONS VIRTUALIZATION The Top Five Virtualization Mistakes Virtualization is taking the IT world by storm. After years of IT build-out, virtualization suddenly fixes

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

BROCADE OPTICS FAMILY

BROCADE OPTICS FAMILY DATA SHEET www.brocade.com BROCADE OPTICS FAMILY ENTERPRISE LAN SWITCHING Highly Reliable, Brocade- Qualified Optics HIGHLIGHTS Rigorously tested for performance and reliability by Brocade Hot-swappable

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

BROCADE PERFORMANCE MANAGEMENT SOLUTIONS

BROCADE PERFORMANCE MANAGEMENT SOLUTIONS Data Sheet BROCADE PERFORMANCE MANAGEMENT SOLUTIONS SOLUTIONS Managing and Optimizing the Performance of Mainframe Storage Environments HIGHLIGHTs Manage and optimize mainframe storage performance, while

More information

Ensuring a Smooth Transition to Internet Protocol Version 6 (IPv6)

Ensuring a Smooth Transition to Internet Protocol Version 6 (IPv6) WHITE PAPER www.brocade.com APPLICATION DELIVERY Ensuring a Smooth Transition to Internet Protocol Version 6 (IPv6) As IPv4 addresses dwindle, companies face the reality of a dual-protocol world The transition

More information

Brief Summary on IBM System Z196

Brief Summary on IBM System Z196 WHITE PAPER www.brocade.com DATA CENTER Deploying Strategic Data Center Solutions for IBM zenterprise System z Environments The Brocade DCX Backbone provides industry-leading performance, scalability,

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

WHITE PAPER. Cloud Networking: Scaling Data Centers and Connecting Users

WHITE PAPER. Cloud Networking: Scaling Data Centers and Connecting Users WHITE PAPER Cloud Networking: Scaling Data Centers and Connecting Users While the business promise of cloud computing is broad, there are a few basic enabling themes underlying an effective cloud design:

More information

Designing the Data Center. Gail M. Roper CIO City of Raleigh, North Carolina

Designing the Data Center. Gail M. Roper CIO City of Raleigh, North Carolina Designing the Data Center Gail M. Roper CIO City of Raleigh, North Carolina Why Build for Raleigh Extend the life of an existing data center infrastructure. Rationalize the data center infrastructure across

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

The Brocade SDN Controller in Modern Service Provider Networks

The Brocade SDN Controller in Modern Service Provider Networks WHITE PAPER The Controller in Modern Service Provider Networks The OpenDaylight-based Controller combines innovations with modular software engineering and model-driven network management for a cost-effective,

More information

Brocade Premier and Premier-Plus Support

Brocade Premier and Premier-Plus Support DATA SHEET Brocade Premier and Premier-Plus Support HIGHLIGHTS Streamlines communication and accelerates problem resolution with a single point of contact into Brocade Technical Support Provides priority

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Introducing Brocade VCS Technology

Introducing Brocade VCS Technology WHITE PAPER www.brocade.com Data Center Introducing Brocade VCS Technology Brocade VCS technology is designed to revolutionize the way data center networks are architected and how they function. Not that

More information

IMPLEMENTING VIRTUALIZED AND CLOUD INFRASTRUCTURES NOT AS EASY AS IT SHOULD BE

IMPLEMENTING VIRTUALIZED AND CLOUD INFRASTRUCTURES NOT AS EASY AS IT SHOULD BE EMC AND BROCADE - PROVEN, HIGH PERFORMANCE SOLUTIONS FOR YOUR BUSINESS TO ACCELERATE YOUR JOURNEY TO THE CLOUD Understand How EMC VSPEX with Brocade Can Help You Transform IT IMPLEMENTING VIRTUALIZED AND

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units

Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units By Suresh Soundararaj & David Admirand, PE Experts for Your Always Available Data

More information

Fibre Channel over Ethernet: Enabling Server I/O Consolidation

Fibre Channel over Ethernet: Enabling Server I/O Consolidation WHITE PAPER Fibre Channel over Ethernet: Enabling Server I/O Consolidation Brocade is delivering industry-leading oe solutions for the data center with CNAs, top-of-rack switches, and end-of-row oe blades

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning

More information

Brocade Network Monitoring Service (NMS) Helps Maximize Network Uptime and Efficiency

Brocade Network Monitoring Service (NMS) Helps Maximize Network Uptime and Efficiency WHITE PAPER SERVICES Brocade Network Monitoring Service (NMS) Helps Maximize Network Uptime and Efficiency Brocade monitoring service delivers business intelligence to help IT organizations meet SLAs,

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Ten Ways to Optimize Your Microsoft Hyper-V Environment with Brocade

Ten Ways to Optimize Your Microsoft Hyper-V Environment with Brocade WHITE PAPER Server Connectivity Ten Ways to Optimize Your Microsoft Hyper-V Environment with Brocade To maximize the benefits of network connectivity in a virtualized server environment, Brocade works

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

How To Connect Your School To A Wireless Network

How To Connect Your School To A Wireless Network WHITE PAPER campus networks Enabling the Wireless School The growing demand for Wireless LAN access in K 12 schools. Many K 12 schools are seeking new technological solutions that help optimize learning

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Solution Guide: Brocade Server Application Optimization for a Scalable Oracle Environment

Solution Guide: Brocade Server Application Optimization for a Scalable Oracle Environment Solution Guide: Brocade Server lication Optimization for a Scalable Oracle Environment Optimize the performance and scalability of Oracle applications and databases running Oracle Enterprise Linux (OEL)

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

DATA CENTERS BEST IN CLASS

DATA CENTERS BEST IN CLASS Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Get the Most Out of Data Center Consolidation

Get the Most Out of Data Center Consolidation WHITE PAPER www.brocade.com DATA CENTER Get the Most Out of Data Center Consolidation Brocade networking solutions help ensure that organizations benefit from decreased costs and increased business agility

More information

Deploying Brocade VDX 6720 Data Center Switches with Brocade VCS in Enterprise Data Centers

Deploying Brocade VDX 6720 Data Center Switches with Brocade VCS in Enterprise Data Centers WHITE PAPER www.brocade.com Data Center Deploying Brocade VDX 6720 Data Center Switches with Brocade VCS in Enterprise Data Centers At the heart of Brocade VDX 6720 switches is Brocade Virtual Cluster

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

Zen Internet Case Study

Zen Internet Case Study Zen Internet Case Study About Zen Internet Zen Internet is an independent Internet Service Provider (ISP) that offers a full range of data, voice, and hosting services to businesses and residential users

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

CENIC 2009 Conference

CENIC 2009 Conference Green Datacenter Initiatives at UCSD CENIC 2009 Conference Dallas Thornton SDSC Division Director, Cyberinfrastructure Services dallas@sdsc.edu Campus Quick Facts With a daily population of over 45,000,

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

BASCS in a Nutshell Study Guide for Exam 160-020 Brocade University Revision 03-2012

BASCS in a Nutshell Study Guide for Exam 160-020 Brocade University Revision 03-2012 BASCS in a Nutshell Study Guide for Exam 160-020 Brocade University Revision 03-2012 2013 Brocade Communications Corporate Headquarters - San Jose, CA USA T: (408) 333-8000 info@brocade.com European Headquarters

More information

Brocade Fabric Vision Technology Frequently Asked Questions

Brocade Fabric Vision Technology Frequently Asked Questions Brocade Fabric Vision Technology Frequently Asked Questions Introduction This document answers frequently asked questions about Brocade Fabric Vision technology. For more information about Fabric Vision

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Data Center Solutions - The Containerized Evolution

Data Center Solutions - The Containerized Evolution Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center WHITE PAPER: Energy Efficiency Go Green: Energy Efficiency for the IT Organization Table of Contents 2 Why IT Organizations Everywhere Need to go Green 3 Greening the Data Center 5 Savvis Commitment to

More information

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Cloud-Optimized Performance: Enhancing Desktop Virtualization Performance with Brocade 16 Gbps

Cloud-Optimized Performance: Enhancing Desktop Virtualization Performance with Brocade 16 Gbps Cloud-Optimized Performance: Enhancing Desktop Virtualization Performance with Brocade 16 Gbps Discussing the enhancement of Desktop Virtualization using 16 Gbps Fibre Channel and how it improves throughput

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

How To Test A Theory Of Power Supply

How To Test A Theory Of Power Supply A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2016

European Code of Conduct for Data Centre. Presentation of the Awards 2016 European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational

More information

Top 5 Trends in Data Center Energy Efficiency

Top 5 Trends in Data Center Energy Efficiency Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,

More information

Data Centers That Deliver Better Results. Bring Your Building Together

Data Centers That Deliver Better Results. Bring Your Building Together Data Centers That Deliver Better Results Bring Your Building Together 1 Meeting the high demands of your data center Meeting the increasing heat loads associated with growing computational needs requires

More information

Cloud Optimized Performance: I/O-Intensive Workloads Using Flash-Based Storage

Cloud Optimized Performance: I/O-Intensive Workloads Using Flash-Based Storage WHITE PAPER Cloud Optimized Performance: I/O-Intensive Workloads Using Flash-Based Storage Brocade continues to innovate by delivering the industry s first 16 Gbps switches for low latency and high transaction

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

How Microsoft Designs its Cloud-Scale Servers

How Microsoft Designs its Cloud-Scale Servers How Microsoft Designs its Cloud-Scale Servers How Microsoft Designs its Cloud-Scale Servers Page 1 How Microsoft Designs its Cloud-Scale Servers How is cloud infrastructure server hardware design different

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

Brocade Campus LAN Switches: Redefining the Economics of

Brocade Campus LAN Switches: Redefining the Economics of WHITE PAPER www.brocade.com Enterprise Campus Networks Campus LAN Switches: Redefining the Economics of Campus Networks Efficient switching technology and flexible acquisition models help enterprises reduce

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

EMC DURHAM CLOUD DATA CENTER

EMC DURHAM CLOUD DATA CENTER EMC DURHAM CLOUD DATA CENTER Energy efficient design and construction EMC IT was hard at work reducing operational costs, increasing IT agility, and preparing for a dynamic future in the cloud when it

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Microsoft Technology Center: Philadelphia

Microsoft Technology Center: Philadelphia A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information