USC CFC Leak Repair and Recordkeeping Procedures

Size: px
Start display at page:

Download "USC CFC Leak Repair and Recordkeeping Procedures"

Transcription

1 USC CFC Leak Repair and Recordkeeping Procedures I. Introduction Chlorofluorocarbons (CFCs) released into the atmosphere can damage the ozone layer that protects the earth from the penetration of harmful ultraviolet radiation. Ultraviolet radiation can cause health and environmental concerns, including increased incidences of skin cancers, cataracts, and damage to crops and living organisms. This procedure will reduce the emissions of CFCs and HCFCs to the lowest achievable levels during the service, maintenance, and disposal of appliances at the University of South Carolina. This program is in compliance with the refrigerant recycling requirements of 40 CFR, Part 82, Subpart F, of the Clean Air Act, as amended in II. Definitions Comfort cooling appliance any air conditioning appliance used to provide cooling in order to control heat and/or humidity in facilities such as office buildings and computer rooms. Commercial refrigeration appliance Any refrigeration appliance used to store perishable goods in retail food, cold storage warehousing, or any other sector requiring cold storage. Cold storage includes refrigeration equipment used to house perishable goods or any manufactured product requiring refrigerated storage. Industrial refrigeration appliance Refrigeration equipment that may be complex or customized, that is used in a manufacturing process. Industrial process refrigeration appliances include equipment that is directly linked to a manufacturing process, such as manufacturing, power generation, ice manufacturing, etc. Initial verification leak test is a leak test that is conducted as soon as practicable after the repair is completed. An initial verification test requires the evacuation of the appliance, is conducted prior to the replacement of the full refrigerant charge, and before the appliance is returned to normal operating conditions. Follow-up verification leak test is a test that validates the effectiveness of repairs within 30 days of the appliance s return to normal operating conditions. Follow-up verification tests include, but are not limited to the following: use of soap bubbles, electronic or ultrasonic leak detectors, pressure or vacuum tests, fluorescent dye and black light, infrared or near-infrared tests, and handheld gas detection devices. Major Repair is a repair that involves the removal of the compressor, condenser, evaporator, or auxiliary heat exchanger coil. A major repair requires the removal or isolation of the refrigerant charge before work is started. Retrofit is the conversion of an appliance from a refrigerant to a substitute with a lower ozone-depleting potential. Leak rate is the rate at which an appliance is losing refrigerant, calculated at the time of refrigerant addition. Leak rate is expressed in terms of the percentage of the appliance s full charge since the last successful repair over a consecutive 12-month period: EHS-M-46 Page 1 Issued Date: 4/27/11

2 III. Basic CFC Requirements 1. Prohibition of Venting Since July 1, 1992, intentional venting of ozone-depleting substances into the atmosphere while maintaining, servicing, repairing, or disposing of air-conditioning or refrigeration appliances is prohibited. Small releases of refrigerant resulting from purging hoses or from connecting and disconnecting hoses are not considered as a violation of this rule. 2. Evacuation Requirements Technicians are required to evacuate or isolate refrigerant any time major repairs are to be done. Major repairs involve opening the equipment for maintenance, service, repair, or disposal. 3. Reclamation Requirement EPA has established that refrigerant recovered and/or recycled can be returned to the same system or other systems owned by the same owner without restrictions. 4. Refrigerant Recovery and Recycling Equipment Certification EPA has established a certification program for refrigerant recovery and recycling equipment. EPA requires that manufacturers or importers of refrigerant recovery and recycling equipment manufactured on or after November 15, 1993, have their equipment tested by an EPA-approved testing organization to ensure it meets requirements. EPA certified equipment will have a label stating that it meets EPA requirements. 5. Refrigerant Recovery Equipment Certification EPA regulations require facilities that service or dispose of refrigeration appliances certify that they have acquired recovery or recycling devices that meet EPA standards for these devices. To certify that you have acquired EPA certified equipment, each facility must submit EPA Form to their EPA Regional Office. Owners are not required to send in a new form each time they add recycling or recovery equipment. Each facility must keep a copy of this documentation for audit purposes. 6. Technician Certification EPA has established a technician certification programs for persons who perform maintenance, service, repair, or disposal that could be reasonably expected to release refrigerants into the atmosphere. The following 4 certifications have been developed: a. Type 1 for servicing small appliances, EHS-M-46 Page 2 Issued Date: 4/27/11

3 b. Type II for servicing or disposing of high or very high-pressure appliances, except small appliances and MVACs, c. Type III for servicing or disposing of low-pressure appliances, and d. Universal for servicing all types of appliances. Apprentices (person who is currently registered as an apprentice in service, maintenance, repair, or disposal of appliances with an Apprenticeship Council recognized by the Bureau of Apprenticeship and Training) are exempt from certification requirements provided they are closely and continually supervised by a certified technician. Certified technicians must keep a copy of their certificate at their place of business. 7. Refrigerant Sales Restrictions The sale of ozone-depleting refrigerant in any size container has been restricted to EPA certified technicians. 8. Appliance Self Disposal Requirements Refrigeration appliances that are dismantled on-site before disposal must have the refrigerant recovered in accordance with EPA requirements for servicing prior to disposal. When a technician has removed the refrigerant and is disposing of the appliance, the technician must provide a signed statement to the disposal company which includes the following: a. Name and address of person recovering refrigerant, b. Date the refrigerant was recovered, or c. Copy of contract stating the refrigerant will be removed prior to delivery. IV. USC Review and Documentation of Existing CFC Equipment 1. All areas, departments, and campuses must review their areas and develop: a. A list of all cooling units with more than 50 pounds of refrigerant charge with the following information: i. Description of appliance, ii. Location of appliance, iii. Type of refrigerant and number of pounds of charge, iv. Complete records of any required service information that you have not documented. b. The numbers of window cooling units for each building in your department/campus. (According to EPA, each window unit contains as much as 1.4 pounds of refrigerant.) c. The number of cooling units with 1.5 pounds to 50 pounds of refrigerant, when information is readily available. d. Send this information to the person responsible for maintaining your area, department, or campus CFC leak repair records. 2. Each department or campus will also send the following records to the person responsible for maintaining their CFC leak repair records: a. Type of refrigerant purchased, number of pounds purchased, and date obtained, EHS-M-46 Page 3 Issued Date: 4/27/11

4 b. Information on any refrigerants reclaimed and disposed through recycling vendors, including type of refrigerant, number of pounds, vendor, and date disposed. c. Updated list of EPA certified recovery and recycle equipment maintained by each department. d. Information on new refrigeration systems as they are installed/replaced in buildings. 3. The individual responsible for maintaining your CFC leak repair records will: a. Record and maintain this information into their CFC program. Develop the following lists: i. Active appliance list of all units with more than 50 pounds of refrigerant charge, ii. Departmental buildings with the number of AC window units in each building, iii. Known cooling units containing 1.5 pounds to 50 pounds of refrigerant. b. Maintain copies of technician certification cards for each technician, c. Maintain list of refrigerant types and quantities purchased, d. Maintain list of refrigerants reclaimed and vendors who reclaimed them. e. Maintain list of refrigerant recovery and recycle equipment by department. V. USC Procedure for CFC Employee Repairs in Facility-Serviced Departments for Appliances With Greater Than 50 Pounds Refrigerant 1. When a supervisor receives a work order from FAMIS (or other appropriate work order system), the supervisor will assign the work to a certified technician. (See the flow chart attached as Appendix C.) 2. The technician identifies the unit to be serviced, evaluates the unit s operational status, and checks the refrigerant level. The technician will use the USC Refrigerant Activity Report to record all work done on a refrigeration appliance. (A copy of the USC Refrigerant Activity Report is attached as Appendix A.) a. If there is a leak and this is a major repair, the technician will recover or isolate the refrigerant before the repair is begun. Once a leak is determined, the units with more than 50 pounds of refrigerant must be repaired within 30 days, if possible. b. After the repair, the technician will complete an initial verification leak test before replacing the refrigerant charge. c. When the leak repair is confirmed, the technician will recharge the refrigerant and add any additional amount of refrigerant to fully charge the appliance. d. Within 30 days, the technician will complete a follow-up verification leak test while the appliance is operating at normal operating conditions. e. The technician will then fully complete the USC Refrigerant Activity Report and give a copy to his/her supervisor. f. The supervisor will: i. Complete his review of the Refrigerant Activity Report to ensure it is completely filled out, ii. Verify refrigerant type and account for quantity used by the technician, iii. Sign the form, and forward the Refrigerant Activity Report to the person responsible for maintaining the area, department, or campus CFC leak repair records. g. If the supervisor requires management decisions for work completion, he/she will follow up with the manager, superintendent, or Director responsible for maintaining the equipment. h. When decisions have been finalized, the supervisor will send the completed Refrigeration Activity Report to the person responsible for maintaining CFC leak repair records. The person responsible for CFC leak repair records will: EHS-M-46 Page 4 Issued Date: 4/27/11

5 i. Post the information into their management software or program, and ii. Calculate a leak rate for all appliances with greater than 50 pounds of refrigerant. iii. Maintain all records required by EPA. 3. If either the initial verification leak test or the follow-up verification leak test is not successful, the technician will determine the problem and report the findings to his/her supervisor. 4. The technician s supervisor, along with the owner manager or superintendent will determine whether the leaking appliance is repairable or if it should be retired or retrofitted with a lower ozone-depleting refrigerant. a. If it is determined that the appliance can t be repaired within 30 days and the appliance contains more than 50 pounds of refrigerant, the owner supervisor/manager must develop a written and dated retrofit or retirement plan. b. A copy of the written and dated retirement or retrofit plan must be kept at the location of the appliance. c. Having the retirement and retrofit plan provides up to 6 months, and possibly up to 1 year (depending on documented circumstances) to complete the project. VI. USC Procedure for CFC Employee Repair in Non-Facility Serviced Departments and Senior/Regional campuses For Appliances With Greater Than 50 Pounds Refrigerant 1. When a technician works on an appliance, the technician will: a. Identify the unit to be serviced, evaluate the unit s operational status, and check the refrigerant level. The technician will document all work performed on cooling appliances using the USC Refrigerant Activity Report (See Attachment A). b. If there is a leak and this is a major repair, the technician will recover or isolate the refrigerant before the repair is begun. Once a leak is determined, the units with more than 50 pounds of refrigerant must be repaired within 30 days, if possible. c. After the repair, the technician will complete an initial verification test before replacing the refrigerant charge. d. When the leak repair is confirmed, the technician will recharge the refrigerant and add any additional amount of refrigerant to fully charge the appliance. e. Within 30 days, the technician will complete a follow-up verification leak test while the appliance is operating at normal operating conditions. f. The technician will then fully complete the USC Refrigerant Activity Report and send a copy of the form to his/her supervisor. g. The supervisor will i. Complete his/her review of the Refrigerant Activity Report to ensure it is completely filled out, ii. Verify refrigerant type and account for the quantity used by the technician, iii. Sign the form, and iv. Forward the Refrigerant Activity Report to the person responsible for maintenance of CFC leak repair records. h. If the supervisor requires management decisions for work completion, he/she will follow up with the manager, superintendent, or director responsible for maintaining the equipment. i. When decisions have been finalized, the supervisor will send the completed Refrigeration Activity Report to the person responsible for maintaining CFC leak repair records. The person responsible for CFC leak repair records will: EHS-M-46 Page 5 Issued Date: 4/27/11

6 i. Post the information into their management software or program ii. Calculate a leak rate for all appliances with greater than 50 pounds of refrigerant. iii. Maintain all required records and data required by EPA. 2. If either the initial verification test or the follow-up verification test is not successful, the technician will determine the problem and report the findings to his/her supervisor. 3. The supervisor, along with the owner manager or superintendent will determine whether the leaking appliance is repairable, or if it should be retired or retrofitted with a lower ozone-depleting refrigerant. a. If it is determined that the appliance can t be repaired within 30 days and the appliance contains more than 50 pounds of refrigerant, the supervisor/manager must develop a written and dated retrofit or retirement plan. b. A copy of the written and dated retirement or retrofit plan will be kept at the location of the appliance. c. Having the retrofit and retirement plan provides up to 6 months, and possibly up to 1 year (depending on documented circumstances) to complete the project. VII. USC Procedure for Contractor CFC Leak Repairs For Appliances With Greater Than 50 Pounds Refrigerant 1. The Columbia Energy Department will use the following process to manage their CFC work. (See the flow chart in Appendix D for contractor repairs.) a. A licensed contractor will be called to service chillers and other equipment. In these areas, the supervisor or shift manager will contact a contracting HVAC company for repair. b. When the repair has been completed, the supervisor or shift manager will ensure that the contractor completely fills out the USC Refrigerant Activity Report (See Appendix A), including the initial leak-repair verification and the follow-up leak test verification sections. The supervisor or shift manager will sign the report and give it to the assistant superintendent of Energy. c. The assistant superintendent will review and sign the Refrigerant Activity Report and forward it to the person responsible for maintaining CFC leak repair information. d. If the assistant superintendent requires management decisions for work completion, he will follow up with the superintendent or director responsible for maintaining the equipment. e. When decisions have been finalized, the assistant superintendent will send the completed Refrigeration Activity Report to the person responsible for maintaining CFC leak repair records. The person responsible for CFC leak repair records will: i. Post the information into their management software or program ii. Calculate a leak rate for all appliances with greater than 50 pounds of refrigerant. III. Maintain all required records and data required by EPA. EHS-M-46 Page 6 Issued Date: 4/27/11

7 2. Other departments and campuses which use contractors to service cooling appliances will use the following process: a. A supervisor or shift manager will contact a contracting HVAC company for repair. b. When the repair has been completed, the supervisor or shift manager will ensure that the contractor completely fills out the USC Refrigerant Activity Report (See attachment A), including the initial leak-repair verification, the follow-up leak test verification sections, and technician signature. The supervisor or shift manager will sign the report. c. If the department or campus contracts with the USC Columbia Facility department, the department will send the Refrigerant Activity Report to the Columbia Facilities person designated to keep CFC leak repair records. d. If the department or campus is not serviced by the USC Columbia Facility department, the department or campus will be responsible for keeping all required CFC leak repair records. (See Appendix B: Reporting and Recordkeeping Requirements for Appliances with Greater than 50 Pound Charge.) VIII. Refrigerant Reclaim Operations 1. Columbia facility refrigerant reclaim operations will be supervised or completed by the Columbia lead HVAC technician. The lead HVAC technician will oversee the following operations for refrigerant which requires cleaning or recovery: a. Equipment is properly evacuated of refrigerant, b. Refrigerant that requires cleaning is sent to a certified refrigerant reclaimer, and c. Records of reclaimed refrigerant (pounds, type of refrigerant, date reclaimed, and vendor information) are sent to the person responsible for maintaining CFC leak repair information. 2. Other departments and senior and regional campus groups will have an HVAC technician who performs these functions for their department or campus. 3. Technicians opening appliances, except for small appliances and MVACs, must evacuate the unit to the following levels (in inches of mercury vacuum relative to standard atmospheric pressure of 29.9 inches of Hg): Type of Appliance Recovery/Recycling Equipment Manufactured Before 11/15/93 1 (Inches of Hg) HCFC-22, containing less than pounds HCFC-22, containing 200 pounds or 4 10 more Very high pressure equipment 0 0 Other high pressure equipment, 4 10 containing less than 200 pounds Other high pressure equipment, 4 15 containing more than 200 pounds Low pressure equipment Except for small appliances, MVACs, and MVAC-like appliances Recovery/Recycling Equipment Manufactured After 11/15/93 1 (Inches of Hg) EHS-M-46 Page 7 Issued Date: 4/27/11

8 Attachment A: USC REFRIGERANT ACTIVITY REPORT Unit Serviced Department Building Date Location Work order No. Manufacturer Model No. Serial No. Serial No. Duty Type Comfort Cooling Industrial/Commercial Other (Explain Below) Duty Type, if other: Refrigerant Type Charge <50 Lbs. >50 Lbs. Service Performed Minor Maintenance Major Maintenance Confirm Charge Refrigerant Conversion Unit Disposal Other (explain below) Service Description: Refrigerant Activity Recovery Unit: Vacuum (inches) Recover From Appliance Cylinder Name Lbs. Oz. Condition Reused Reclaim Total Lbs. Total Oz. Refrigerant Added to Appliance Added to Appliance Leak Repairs Cylinder Name Lbs. Oz. New Recovered Total Lbs. Total Oz. Location(s) Leak Found? Yes No Date Any Additional Information: Leak Repaired? Yes No Date If no, was owner notified? Yes No Customers Initials: Initial Leak test? Yes No Date Method: Pressurizing Electronic Deep Vacuum Soap Bubble Follow Up LeakTest? Yes No (> 50 Pounds Refrigerant) Accidental Release? Yes No Approx. Amt. Comments for Future Services Other: Date Method: Electronic Soap Bubble Other: Explain situation Signatures Technician s Signature (Required) Date Owner: Supervisor/Manager (Required) Date Owner: Superintendent (only if decisions required) Date When fully completed, send one copy to technician s supervisor. After review and any required follow-up, the supervisor will send a copy to person who maintains CFC Leak Repair information. EHS-M-46 Page 8 Issued Date: 4/27/11

9 Appendix B: Required Practices and Recordkeeping for Appliances With Greater Than 50 Pounds of Refrigerant Charge 1. Required Practices For Appliances With Greater Than 50 Pounds of Refrigerant The EPA has revised the trigger level for repairing leaks in cooling appliances having greater than 50 pounds of refrigerant for: Comfort cooling appliances 10% of full charge (instead of previous 15%) Commercial refrigeration and industrial process refrigeration 20% of full charge (instead of previous 35%) 1. For comfort cooling appliances, commercial refrigeration, and industrial process refrigeration with a full charge greater than 50 pounds of refrigerant, all leaks (at EPA trigger level) must be repaired within 30 days. 2. Owners may have more than 30 days to repair a leak (at EPA trigger level) if equipment is: a. Located in an area subject to radiological contamination; b. Necessary parts are unavailable and statement from component manufacturer is maintained; c. Other regulations make a repair impossible where such records are maintained. 3. The leak rate must be calculated immediately upon each addition of refrigerant after repair, unless the addition is due to seasonal variance where records justify the addition. 4. An initial verification test must be conducted immediately upon completion of repairs. Methods and results must be maintained. 5. A follow-up verification test must be conducted within 30 days of completion, but no sooner than 24 hours after repair and recharge of the appliance. The follow-up verification test must be conducted at normal operating characteristics and conditions. Methods and results of all follow-up tests must be maintained. 6. If the initial or follow-up verification test is NOT successful and leaks remain, an additional repair attempt must be made within 30 days of the failed verification; and additional initial and follow-up verification tests must be completed as described. 7. Comfort cooling appliances, commercial refrigeration, and industrial process refrigeration systems which have experienced 3 failed verifications tests within a 6-month period must be retired or retrofitted with a lower ozone-depleting potential coolant. 8. Owners are not required to repair equipment within 30 days if they develop a written and dated retrofit or retirement plan. Retrofit or retirement plan must include: a. Six month schedule to permanently retire or retrofit equipment for use with lower ozonedepleting potential coolant. b. Plan must be maintained at physical location of equipment. c. More than 6 months may be available if a supplier quotes a time of more than 12 weeks delivery and the written statement is maintained. EHS-M-46 Page 9 Issued Date: 4/27/11

10 Appendix B: (Continued) 2. Reporting and Recordkeeping Requirements for Appliances With Greater Than 50 Pounds Charge 1. Persons servicing appliances with a full charge greater than 50 pounds of refrigerant must provide owner with documentation which includes: a. Quantity and type of refrigerant added, b. Identity and location of the appliance, c. Date and service performed, d. Physical location of any leaks, e. Amount and type of any refrigerant recovered, f. Date, method, and results of initial verification and follow-up verification tests. 2. Owners of appliances with a full charge greater than 50 pounds of refrigerant must keep records for a period of 3 years which document: a. Quantity and type refrigerant added, b. Full charge of equipment, c. Calculated leak rate, d. Identity and location of equipment, e. Date and type of service, f. Physical location of any leaks, g. Types and quantities of refrigerant recovered from appliances, address of facility accepting used refrigerant, and date refrigerant was transferred, h. Date, method, and results of initial verification and follow-up verification tests, and i. Written and dated retrofit or retirement plan that establishes 6-month schedule to retrofit or retire leaking appliance. This must include: i. Identification and location of equipment; ii. Type and full charge of refrigerant used by leaking appliance; iii. Location of all leaks and efforts taken to address leaks; iv. Type and full charge of substitute to which appliance will be converted; v. If retrofitted, is there an itemized procedure for retrofit, including procedure for flushing old refrigerant and lubricant, changes in lubricants, filters, gaskets, o-rings or valves; vi. Plan for disposition of recovered refrigerant; vii. Plan for disposition of appliance, if retired; and viii. Six-month schedule for complete retrofit or retirement of appliance. 3. Owners of appliances who are unable to complete repairs in 30 days due to radiological conditions, unavailability of components, or government regulations must maintain following records: a. Written statement describing radiological conditions or government regulations that prevent repair; b. Written statement from manufacturer or distributor estimating date of delivery for required parts; EHS-M-46 Page 10 Issued Date: 4/27/11

11 c. Documenting date of delivery of required component. 4. Certified technicians must keep a record of certificate on-site, at place of business. EHS-M-46 Page 11 Issued Date: 4/27/11

NYU Safety Policy Manual

NYU Safety Policy Manual NYU Safety Policy Manual Page 1 of 9 APPLICATION All New York University academic, commercial and residential facilities. PURPOSE New York University has established a policy to comply with the regulations

More information

Refrigerant Compliance Policy

Refrigerant Compliance Policy Refrigerant Compliance Policy Updated: July 12, 2012 TABLE OF CONTENTS I. SCOPE... 1 A. Relevant Subparts of 40 CFR Part 82... 1 B. Technician Training and Certification... 1 C. Recycling and Recovery

More information

It s Your Choice Retrofitting Your Car s A/C System 1EPA. 2 Printed on paper that contains at least 20 percent postconsumer fiber.

It s Your Choice Retrofitting Your Car s A/C System 1EPA. 2 Printed on paper that contains at least 20 percent postconsumer fiber. United States EPA430-F-97-052 Environmental Protection June 1997 Agency 1EPA Air and Radiation (6205J) It s Your Choice Retrofitting Your Car s A/C System 2 Printed on paper that contains at least 20 percent

More information

Refrigerant Management Program

Refrigerant Management Program Refrigerant Management Program Revised: February 2009 2009. University of New Hampshire Office of Environmental Health and Safety. All Rights Reserved. The most current version of this document can be

More information

Compliance Guidance For Industrial Process Refrigeration Leak Repair Regulations Under Section 608 Of The Clean Air Act

Compliance Guidance For Industrial Process Refrigeration Leak Repair Regulations Under Section 608 Of The Clean Air Act Compliance Guidance For Industrial Process Refrigeration Leak Repair Regulations Under Section 608 Of The Clean Air Act Prepared by: The Chemical Manufacturers Association and The Environmental Protection

More information

APPENDIX X INTRODUCTION. Purpose

APPENDIX X INTRODUCTION. Purpose APPENDIX X CLEAN AIR ACT CIVIL PENALTY POLICY FOR VIOLATIONS OF 40 C.F.R. PART 82, SUBPART F: MAINTENANCE, SERVICE, REPAIR, AND DISPOSAL OF APPLIANCES CONTAINING REFRIGERANT June 1, 1994 INTRODUCTION Purpose

More information

JFK High School, Environmental Science, Mr. Kent Name : Period: Date: 3. Why is ozone important to us and other organisms?

JFK High School, Environmental Science, Mr. Kent Name : Period: Date: 3. Why is ozone important to us and other organisms? JFK High School, Environmental Science, Mr. Kent Name : Period: Date: AIM: How have people been destroying the ozone layer? HW: 39e 1. What chemical is ozone? 2. How does ozone form in the atmosphere?

More information

CHILLER EMISSIONS PROGRAM Region 8 Sustainability & Environmental Management System

CHILLER EMISSIONS PROGRAM Region 8 Sustainability & Environmental Management System 1.0 Purpose & Scope The GSA Chiller Emissions Program is designed to help ensure chillers are not leaking refrigerant; therefore reducing air pollution. The program will ensure compliance with Federal,

More information

Certification Training Manual

Certification Training Manual Revised 12/2008 Certification Training Manual Including: Refrigerant Recycling and Service Procedures for Mobile Air Conditioning Technicians Best Service Practices Approved by the U.S. EPA for technician

More information

RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE

RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE (Adopted January 6, 1978)(Amended August 3, 1979)(Amended July 11, 1980) (Amended August 3, 1990)(Amended December 7, 1990) (Amended November 17, 2000) RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN

More information

Federal Clean Air Act Section 609 Training Manual & Exam

Federal Clean Air Act Section 609 Training Manual & Exam Federal Clean Air Act Section 609 Training Manual & Exam Table of Contents INTRODUCTION... Who Must Be Certified... Training and Certification... Test Format... Test Administration and Grading... i STRATOSPERIC

More information

Information on New Refrigerant (R-1234yf) for A/C Service

Information on New Refrigerant (R-1234yf) for A/C Service Information on New Refrigerant (R-1234yf) for A/C Service 2013 Cadillac ATS, XTS This bulletin is being revised to include procurement and labeling information for recovery cylinders to be used with GE-50957-Contaminated

More information

Guidance for Stationary Refrigeration & Air- Conditioning

Guidance for Stationary Refrigeration & Air- Conditioning Department for Environment, Food and Rural Affairs Guidance for Stationary Refrigeration & Air- Conditioning The EU Ozone Regulation: Legislative update and strategies for HCFC Phase-out Information Sheet

More information

The EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out

The EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out Information Sheet RAC 8 R22 Phase-out The EC Ozone Regulation Legislative Update and Strategies for HCFC Phase-out 1. Background to HCFC Phase Out The EC Ozone Regulation (EC/2037/2000) provides the legislative

More information

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate

More information

SEE INSTRUCTIONS FOR TAKING TEST AND OTHER INFORMATION ON INSIDE FRONT COVER

SEE INSTRUCTIONS FOR TAKING TEST AND OTHER INFORMATION ON INSIDE FRONT COVER This technician certification program is not intended to test the technical skills of technicians regarding the diagnosis and repair of motor vehicle air conditioners. The basic goal of the technician

More information

Flushing and Cleaning the A/C System

Flushing and Cleaning the A/C System Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING

More information

Subject: 2005 Air Conditioning Service Guidelines

Subject: 2005 Air Conditioning Service Guidelines Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning

More information

EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps

EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps Information Sheet 5: Stationary Air-conditioning and Heat Pumps Target audience for this Information Sheet This Information Sheet is aimed at organisations that are operators (usually the owner) of stationary

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

COMPLIANCE MONITORING STRATEGY FOR TITLE VI SECTION 609 SERVICING OF MOTOR VEHICLE AIR CONDITIONERS

COMPLIANCE MONITORING STRATEGY FOR TITLE VI SECTION 609 SERVICING OF MOTOR VEHICLE AIR CONDITIONERS COMPLIANCE MONITORING STRATEGY FOR TITLE VI SECTION 609 SERVICING OF MOTOR VEHICLE AIR CONDITIONERS INTRODUCTION Section 609 of the Clean Air Act, as amended deals with the servicing of motor vehicle air

More information

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and

More information

EPA 608 Certification. Study Guide. 1 P a g e

EPA 608 Certification. Study Guide. 1 P a g e EPA 608 Certification Study Guide 1 P a g e Foreword All HVACR technicians must become certified for the equipment they work on, under the Environmental Protection Agency s (EPA), refrigerant recovery

More information

Elements Elements describe the essential outcomes.

Elements Elements describe the essential outcomes. AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes

More information

Facilities & Services UNIVERSITY OF ILLINOIS AT URBANA-CHAMPAIGN

Facilities & Services UNIVERSITY OF ILLINOIS AT URBANA-CHAMPAIGN Facilities & Services UNIVERSITY OF ILLINOIS AT URBANA-CHAMPAIGN Compliance Suite Overview Last Updated: 11/18/2010-1 - Change log Date Changes Author 11/17/2010 Initial Draft T Reid - 2 - Table of Contents

More information

SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT.

SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT. SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING Effective From :- UNDER DEVELOPMENT Prepared by: Curriculum development cell Institute of Research Development

More information

Guidance for Stationary Refrigeration & Air-Conditioning

Guidance for Stationary Refrigeration & Air-Conditioning Information Sheet RAC 3 Key Obligations Guidance for Stationary Refrigeration & Air-Conditioning This Information Sheet provides a description of the key obligations under the EC F gas and Ozone Regulations

More information

The phase out of R22. Phase out of HCFCs

The phase out of R22. Phase out of HCFCs The phase out of R22 The Montreal Protocol on Substances that Deplete the Ozone Layer is widely regarded as the world s most successful environment protection agreement. It is the only treaty with universal

More information

Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives

Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives 1 Introduction 1.1 Background 1.2 Guideline Purpose 1.3 Definitions 2 Roles and Responsibilities 2.1 Department

More information

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 REFRIGERANT 410A Information compiled by Frank Prah, CMS INTRODUCTION Recently a new refrigerant, R-410A, has been formulated

More information

Recharge Procedure for Telemark TVP-2000 and TVP-3500

Recharge Procedure for Telemark TVP-2000 and TVP-3500 Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure

More information

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4 Course Description: Text, References and Supplies: Course Goals/Objectives: Theory of automotive air conditioning and heating systems. Emphasis on the basic refrigeration cycle and diagnosis and repair

More information

EU F-Gas Regulation Guidance Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors

EU F-Gas Regulation Guidance Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors Information Sheet 14: Refrigeration, Air-Conditioning and Heat Pump Contractors Target audience for this Information Sheet This Information Sheet is aimed at contractors that carry out installation, maintenance

More information

CLIMATE CHANGE POLICY FRAMEWORK FOR REFRIGERATION AND AIR CONDITIONING SECTOR

CLIMATE CHANGE POLICY FRAMEWORK FOR REFRIGERATION AND AIR CONDITIONING SECTOR European Partnership CLIMATE CHANGE POLICY FRAMEWORK FOR REFRIGERATION AND AIR CONDITIONING SECTOR A proposal by the European Partnership (EPEE) for action in the European Union I. INTRODUCTION Set out

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Facilities Maintenance Standards rev 9-1-2015

Facilities Maintenance Standards rev 9-1-2015 Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will

More information

Certification Training Manual

Certification Training Manual Keep this book! You may need it for your retest. Revised 01/2015 Certification Training Manual Approved by the U.S. EPA for technician training requirements under Section 609 of the Clean Air Act. Including:

More information

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE. ACHP 104 Refrigeration & Air Conditioning Service II

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE. ACHP 104 Refrigeration & Air Conditioning Service II STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE ACHP 104 Refrigeration & Air Conditioning Service II Prepared By: Stan Skowronek CANINO SCHOOL OF ENGINEERING TECHNOLOGY

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants

More information

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE Faculty are required to have the outline submitted to the Academic Affairs Office. The course outline is the form used for approval of new courses

More information

MEM18084A Commission and decommission split air conditioning systems

MEM18084A Commission and decommission split air conditioning systems MEM18084A Commission and decommission split air conditioning systems Release: 1 MEM18084A Commission and decommission split air conditioning systems Modification History Not Applicable Unit Descriptor

More information

2009 ASE Refrigerant Recovery and Recycling Training Booklet

2009 ASE Refrigerant Recovery and Recycling Training Booklet 2009 ASE Refrigerant Recovery and Recycling Training Booklet This online version of the booklet contains the same content as the 2009 printed version, with the exception of the quiz. You may take the quiz

More information

Protection of Stratospheric Ozone: Update to the Refrigerant Management Requirements

Protection of Stratospheric Ozone: Update to the Refrigerant Management Requirements This document is scheduled to be published in the Federal Register on 11/09/2015 and available online at http://federalregister.gov/a/2015-26946, and on FDsys.gov 6560-50-P ENVIRONMENTAL PROTECTION AGENCY

More information

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. Dry Cleaner Compliance Calendar 2012

NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM. Dry Cleaner Compliance Calendar 2012 NEW JERSEY SMALL BUSINESS ENVIRONMENTAL ASSISTANCE PROGRAM Dry Cleaner Compliance Calendar 2012 Welcome The New Jersey Small Business Environmental Assistance Program developed this guidance document to

More information

HCFC phase-out has started.

HCFC phase-out has started. HCFC phase-out has started. 02 HCFC phase-out has started. HCFC phase-out has started. Are you prepared? Global phase-out of HCFCs is already underway. This will impact the availability and pricing of

More information

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List

More information

RS-24 (R426A): Q & A

RS-24 (R426A): Q & A RS-24 (R426A): Q & A 1 Q: What is RS-24? A: RS-24 is a non ozone depleting Drop-in replacement for R12 in all applications including mobile air conditioning. 2 Q: Yes, but what does RS-24 contain? A: RS-24

More information

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale

More information

Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals

Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals HVAC PROGRAMS The school s Heating, Ventilation, and Air Conditioning Programs provide training for entry level employment

More information

Refrigeration, Air-conditioning and Heat Pump Sector. The Environmental Protection Agency

Refrigeration, Air-conditioning and Heat Pump Sector. The Environmental Protection Agency The COMPLYING WITH REGULATIONS CONTROLLING FLUORINATED GREENHOUSE GASES AND OZONE DEPLETING SUBSTANCES A GUIDANCE NOTE FOR CONTRACTORS IN THE Refrigeration, Air-conditioning and Heat Pump Sector The (EPA)

More information

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History

Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History providing insights for today s hvac system designer Engineers Newsletter volume 40 2 HVAC Refrigerants: A Balanced Approach One of the constant themes throughout the history of the HVAC industry is the

More information

BOMA BESt Assessment Overview

BOMA BESt Assessment Overview BOMA BESt Assessment Overview BOMA Building Environmental Standards OFFICE Module August 2013 The Voice of the Commercial Real Estate Industry in Canada The Building Owners and Managers Association of

More information

Heating and Air Conditioning

Heating and Air Conditioning Heating and Air Conditioning S Y L L A B U S Your Course Learning Plan UAWLETC EK 4-13-06 A. General Course Information Course description: The Heating and Air Conditioning students of UAW-LETC will successfully

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 1 Page 1 of 6 I. PURPOSE This procedure establishes the process to conduct asbestos work as it applies to Operation and Maintenance activities, including emergencies. II. PERSONNEL AFFECTED

More information

Table of Contents. First Aid for Refrigerant Exposure 35. First Aid for Skin Exposure / First Aid for Eye. Chapter 3:

Table of Contents. First Aid for Refrigerant Exposure 35. First Aid for Skin Exposure / First Aid for Eye. Chapter 3: Table of Contents Chapter 1: Introduction to Automotive Heating, Air Conditioning, and Ventilation 11 Heating, Ventilating, and Air Conditioning (HVAC) Systems 12 Why Is It Called HVAC? Major Heating,

More information

Freon Removal. There are three basic options for getting Freon removed from appliances/equipment in your community:

Freon Removal. There are three basic options for getting Freon removed from appliances/equipment in your community: Freon Removal What kinds of appliances/equipment contain Freon? Several different types of refrigeration equipment contain Freon such as refrigerators, air conditioners, dehumidifiers, freezers, and water

More information

Background. Page 1. Table 1. Environmental impacts of MVAC refrigerants. Global warming potential

Background. Page 1. Table 1. Environmental impacts of MVAC refrigerants. Global warming potential Background To prevent refrigerant emissions during the servicing of motor vehicle air conditioning (MVAC) systems, the U.S. Environmental Protection Agency (EPA), under Section 609 of the Clean Air Act,

More information

7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES... 7-1 7.1 INTRODUCTION...

7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES... 7-1 7.1 INTRODUCTION... 7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES... 7-1 7.1 INTRODUCTION... 7-1 7.2 HISTORICAL AND BASELINE HFC EMISSION ESTIMATES...

More information

Michigan Dry Cleaning Environmental Compliance Workbook

Michigan Dry Cleaning Environmental Compliance Workbook Michigan Dry Cleaning Environmental Compliance Workbook Michigan Department of Environmental Quality Environmental Science and Services Division Clean Air Assistance Program Jennifer M. Granholm, Governor

More information

HVAC MAINTENANCE SUPERVISOR (Range 121)

HVAC MAINTENANCE SUPERVISOR (Range 121) (Range 121) DEFINITION Supervises, plans, coordinates and performs a variety of fundamental and skilled work in the building and mechanical trades to ensure the overall physical integrity of District Locations.

More information

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs

More information

REFRIGERANT REFERENCE GUIDE

REFRIGERANT REFERENCE GUIDE REFRIGERANT REFERENCE GUIDE WORLWIDE REFRIGERANT SUPPLIER 2004 FOURTH EDITION 2004 DISCLAIMER This publication is designed to provide accurate and authoritative information. It is not to be construed as

More information

http://www.bls.gov/oco/ocos192.htm

http://www.bls.gov/oco/ocos192.htm Skip Navigation Links Latest Numbers http://www.bls.gov/oco/ocos192.htm Heating, Air-Conditioning, and Refrigeration Mechanics and Installers Nature of the Work Training, Other Qualifications, and Advancement

More information

REQUIREMENTS FOR CERTIFICATION SCHEME FOR SERVICING QUALITY FOR CHILLERS AIR-CONDITIONING INSTALLATIONS GOVERNMENT BUILDINGS

REQUIREMENTS FOR CERTIFICATION SCHEME FOR SERVICING QUALITY FOR CHILLERS AIR-CONDITIONING INSTALLATIONS GOVERNMENT BUILDINGS REQUIREMENTS FOR CERTIFICATION SCHEME FOR SERVICING QUALITY FOR CHILLERS IN AIR-CONDITIONING INSTALLATIONS IN GOVERNMENT BUILDINGS OF THE HONG KONG SPECIAL ADMINISTRATIVE REGION BUILDING SERVICES BRANCH

More information

AUTOMOTIVE AIR CONDITIONING

AUTOMOTIVE AIR CONDITIONING 3rd Edition 3rd Edition Resources available For the instructor Register online at: www.cengagebrain.com for the study tools that come with your textbook! Companion website: includes weblinks and downloadable

More information

Precision for Professionals: Air Conditioner Service with Bosch ACS 751, 651 and 551

Precision for Professionals: Air Conditioner Service with Bosch ACS 751, 651 and 551 Precision for Professionals: Air Conditioner Service with Bosch ACS 751, 651 and 551 ACS 751, 651 and 551 A/C service unit from Bosch for R134a u ACS 751 fully automatic: Air-conditioning system service

More information

Refrigeration and Air Conditioning Mechanic On-the-Job Training Guide

Refrigeration and Air Conditioning Mechanic On-the-Job Training Guide Refrigeration and Air Conditioning Mechanic On-the-Job Training Guide Refrigeration and Air Conditioning Mechanics install, maintain and repair primary and secondary refrigeration and cooling systems,

More information

ASE 133 AUTO HVAC SYSTEMS

ASE 133 AUTO HVAC SYSTEMS ASE 133 AUTO HVAC SYSTEMS PRESENTED AND APPROVED: DECEMBER 7, 2012 EFFECTIVE: FALL 2013-14 Prefix & Number ASE 133 Course : Auto HVAC Systems Purpose of this submission: New Change/Updated Retire If this

More information

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you

More information

RS-44 (R424A) : Q & A

RS-44 (R424A) : Q & A RS-44 (R424A) : Q & A 1 Q: What is RS-44? A: RS-44 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-44 contain? A: RS-44 is a blend of HFC134a, HFC125,

More information

Plan Number. 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020. www.charlottemechanical.com. Simplified Service Plan. Air Conditioning.

Plan Number. 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020. www.charlottemechanical.com. Simplified Service Plan. Air Conditioning. Plan Number 1624- A Cross Beam Dr. Charlotte, NC 28217 704.771.1020 www.charlottemechanical.com Simplified Service Plan Air Conditioning And Heating System PARTS, LABOR, & EMERGENCY REPAIR Effective Date:

More information

Automobile Air Conditioning Primer

Automobile Air Conditioning Primer Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the

More information

Elements Elements describe the essential outcomes.

Elements Elements describe the essential outcomes. Application Competency Field Unit Sector Elements Elements describe the essential outcomes. This unit describes the performance outcomes required to service air conditioning systems, including heating,

More information

Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop

Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop Fully automatic air conditioning service! Bosch ACS 600, 601 and 650 for the workshop ACS 600, 601, 650: Air conditioning service units from Bosch u ACS 600 even the entry model is fully automatic u ACS

More information

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9 SUPER SEAL PROFESSIONAL FORMULA Training Manual a. b. c. d. e. f. g. h. i. j. k. l. m. Inside Your Guide Frequently Asked Questions... How does Super Seal work?... Can you use Super Seal on 410a systems

More information

Staff shall ensure that airflow is not obstructed by the blocking of ventilators with posters, furniture, books, or other obstacles.

Staff shall ensure that airflow is not obstructed by the blocking of ventilators with posters, furniture, books, or other obstacles. 1 Environmental Safety AR 3514 The Superintendent may designate and train one or more employees to oversee and coordinate the district's environmental safety program(s). The responsibilities of the coordinator(s)

More information

Environmental Management Systems in Hotels. 15 Steps to the Successful Implementation of an Environmental Management System in a Hotel

Environmental Management Systems in Hotels. 15 Steps to the Successful Implementation of an Environmental Management System in a Hotel Environmental Management Systems in Hotels 15 Steps to the Successful Implementation of an Environmental Management System in a Hotel 2 15 STEPS 1. Assemble the team 2. Initial Review 3. Environmental

More information

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm) RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE

More information

HVAC Claims: Repair vs. Replacement

HVAC Claims: Repair vs. Replacement HVAC Claims: Repair vs. Replacement Curtis M. VanNess Field Operations Manager Outline Brief history of HVAC How do HVAC systems work? Types of systems and equipment Causes of failure Repair vs. Replace

More information

Tools & Equipment Robinair

Tools & Equipment Robinair Tools & Accessories 2 Robinair Product overview AC RAnge Robinair is VDA and TüV approved and carries SAE-J approval. Robinair is approved by the following OEM s: 3 Robinair Moving from R134a to R1234yf

More information

Guidance for Mobile Air Conditioning (MAC) Sectors. Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations

Guidance for Mobile Air Conditioning (MAC) Sectors. Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations Department for Environment, Food and Rural Affairs Guidance for Mobile Air Conditioning (MAC) Sectors Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations April 2012 Contents

More information

ENVIRONMENTAL HEALTH AND SAFETY HAZARDOUS MATERIALS MANAGEMENT PLAN

ENVIRONMENTAL HEALTH AND SAFETY HAZARDOUS MATERIALS MANAGEMENT PLAN ENVIRONMENTAL HEALTH AND SAFETY HAZARDOUS MATERIALS MANAGEMENT PLAN November 2011 University of Northern Colorado Hazardous Materials Management Plan I. General II. III. IV. Responsibilities Definition

More information

COMPRESSOR REPLACEMENT PROCEDURE

COMPRESSOR REPLACEMENT PROCEDURE COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright

More information

EU F-Gas Regulation Guidance Information Sheet 15: Fire Protection System Contractors

EU F-Gas Regulation Guidance Information Sheet 15: Fire Protection System Contractors Information Sheet 15: Fire Protection System Contractors Target audience for this Information Sheet This Information Sheet is aimed at contractors that carry out installation, maintenance and decommissioning

More information

WASTE MANAGEMENT PLAN CERTIFICATION AND COMPLIANCE FORM (GSFA Residential Energy Retrofit Program)

WASTE MANAGEMENT PLAN CERTIFICATION AND COMPLIANCE FORM (GSFA Residential Energy Retrofit Program) Golden State Finance Authority (GSFA) 1215 K Street, Suite 1650 Sacramento, California 95814 Phone: (855) 740-8422 Fax: (916) 444-3219 www.gsfahome.org WASTE MANAGEMENT PLAN CERTIFICATION AND COMPLIANCE

More information

BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS

BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS BOSTON COLLEGE ENVIRONMENTAL HEALTH AND SAFETY LABORATORY GUIDE FOR RENOVATIONS, REMODELS, MOVES AND TERMINATIONS I. Policy for Termination of Laboratory Use of Hazardous Materials The Principal Investigator

More information

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

Utah WAP Cooling Equipment Policy

Utah WAP Cooling Equipment Policy Utah WAP Cooling Equipment Policy A. General 1. There are 4 instances where an Agency may consider new installation, replacement, or repair of cooling equipment: a. Crisis A target HEAT qualified client:

More information

Car and commercial cial air conditioning service solutions

Car and commercial cial air conditioning service solutions Car and commercial cial air conditioning service solutions THE STANDARD IN INFORMATION AND DIAGNOSTICS SYSTEMS INTRODUCTION For the KoolKare range of vehicle air conditioning service equipment we went

More information

Planned, Limited Notice and Emergency Outage Guidelines

Planned, Limited Notice and Emergency Outage Guidelines Applies to: All Facilities Management Employees GUIDELINES: Issued: April 22, 2014 Revised: February 24, 2015 Author: Communications Coordinator PURPOSE: The purpose of these guidelines is to define roles

More information

http://www.cityofsacramento.org/personnel INVITES APPLICATIONS FOR THE POSITION OF: HVAC Systems Mechanic An Equal Opportunity Employer

http://www.cityofsacramento.org/personnel INVITES APPLICATIONS FOR THE POSITION OF: HVAC Systems Mechanic An Equal Opportunity Employer CITY OF SACRAMENTO Department of Human Resources 915 I Street, Historic City Hall Sacramento, CA 95814-2604 http://www.cityofsacramento.org/personnel INVITES APPLICATIONS FOR THE POSITION OF: HVAC Systems

More information

HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY

HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY The impact of refrigeration

More information

THE REPLACEMENT OF R-22

THE REPLACEMENT OF R-22 ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department

More information

Chris Clement 701 Bayou Lane Thibodaux, LA 70301 985.446.7320

Chris Clement 701 Bayou Lane Thibodaux, LA 70301 985.446.7320 Chris Clement 701 Bayou Lane Thibodaux, LA 70301 985.446.7320 Position: Facility Assistant Maintenance Manager B Date: May 17, 2010 - present 70% OF TIME- is spent on following duties. Assist the Facility

More information

Maintenance for Energy Efficiency

Maintenance for Energy Efficiency Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark

More information

http://www.smartpdfcreator.com

http://www.smartpdfcreator.com Technical Service Bulletin Transaction No.: 2018162/2 87 Cleaning of the air conditioning refrigerant circuit Release date: Dec 5, 2008 Condition REVISION HISTORY Revision Date Purpose 2 - Revised Title

More information