s 5 711 Web server For LPB/BSB plants OZS164... Remotely operate and monitor a LPB or BSB device Web browser operation via PC/laptop or Smartphone SMS operation via mobile phone (OZS164.23) 2 digital inputs for fault messages Send fault messages as email or SMS (OZS164.23) Connections: USB (commissioning), Ethernet (local/remote), GSM (OZS164.23) Software update CE1Q5711en 12.03.2010 Building Technologies
Use Buildings Owners/operators Single and multi-family homes Commercial and small industrial buildings Home owners Real estate agencies, real estate management companies. HVAC and electrical engineers Service organizations Heating system manufacturers (e.g. field tests) Functions Operation Web browser and SMS operation Attractive, clear web browser user interface Simultaneous support of multiple users Definable user profiles Faults / System report Fault sources Send faults and system reports to max 4 different email and SMS recipients Directly send SMS to mobile phone (OZS164.23 only) Each recipient has a "scheduler with calendar" to program three sending times per day and holidays/special days The web server is able to identify faults and failures of the bus device as well as own faults. Fault indication The web server indicates bus device and web server faults via LED lit for as long as the fault is present.. The LED is System messages Connection test The web server generates system reports and periodically sends the system operating state to different recipients. Messages are sent as per the set time (hh:mm), message cycle interval (1...255 days), and priority (urgent/non-urgent) to message recipients. When triggered via remote button, the web server sends a system report to all message recipients regardless of its own fault priority. Message history The message history includes the last 500 events on faults, fault messages, and system reports. The events are entered in the web server's circular message buffer. Message history data can be read via web browser. Time The web server has a system clock with adjustable daylight saving/standard time changeover. Clock time mode can be configured autonomous, or as either master or slave. Type summary Device Ethernet web server Ethernet web server and GSM Type (ASN) OZS164.13/101 OZS164.23/101 2 / 12
Ordering and delivery Please indicate the type (ASN) when ordering. Components: The web server is delivered in a cardboard box. The installation instructions G5711 are inserted in the package. The commissioning instructions C5711 (de / en) are available on the web server at http://<ip address>/doc/. Additional accessories: Power supply unit, Ethernet cable, USB cable, 2 cable ties. Equipment combinations LPB/BSB devices Notes An LPB or BSB device can be connected to the LPB/BSB interface of the central communications unit. The following devices with LPB or BSB connection are supported: Heating controllers RVA, RVS Boiler management units LMU Contact us for detailed compatibility list of LPB/BSB devices. SMS operation is not supported by all devices. Web browser PC/Laptop (1024 x 786) iphone (480 x 320) Internet Explorer V6.0 or higher Firefox V3.0 or higher Safari Number of browsers Any number of browsers can be used simultaneously. The max. data traffic on the line is divided up among the browsers. As a result, operation slows down depending on the number of simultaneous users. GSM (OZS164.23) SIM card GSM antenna Mobile phones allow for operation and monitoring via SMS. A standard SIM card can be used for the web server. A remote, suitable GSM band antenna with SMA plug (male) can be used in lieu of the delivered antenna, e.g. ANT-GXS6624 by Round Solutions. Product documentation Web server OZS164 Document type Installation instructions Commissioning instructions CE Declaration of conformity Document number G5711 C5711 T5711 3 / 12
Technical design Operation, monitoring, alarming Communication connections for local commissioning (USB), remote operation, remote monitoring and alarming via Ethernet or GSM (OZS164.23 only): Internet 5711Z01 Router heilibe droszdlockner mitte führe iblade un USB Ethernet * GSM * OZS164.. LPB/BSB Antenna and GSM network: OZS164.23 only Interfaces Cable/plug types USB Ethernet LPB/BSB Protocols Web operation Fault messages Digital inputs The web server has 3 interfaces for communication between web server and user: USB, Ethernet, GSM (OZS164.23 only). The LPB/BSB connection is used to connect the bus device. The USB interface directly connects the PC/laptop on site. The required USB cable type A / type Mini-B is delivered with the device. The router/network is connected to the Ethernet RJ45 plug. The Ethernet interface features Auto-MDI(X) for crossed and non-crossed Ethernet cables. A Ethernet cable category 5 is delivered. The bus device is connected to terminals DB/CL+ and MB/CL- designated "A " (see "Mechanical design"). Use HTTP (Port 80) via TCP / IP for web operation. A RNDIS driver on the PC is required for USB communication. The RNDIS driver is installed automatically when the PC is connected to the Internet. The driver is stored on the web server under http://<ip address>/drivers/. Fault messages via email use SMTP. Fault messages are sent as SMS via GSM (OZS164.23 only). The digital inputs D1, D2 help connect potential-free status contacts. They work as fault inputs. 4 / 12
Mechanical design Design The web server consists of the housing lower section with printed circuit boards and interfaces as well as connection terminals. The upper housing section contains the printed circuit boards. The upper housing section contains the LED displays and one operating button. The LEDs and operating button are labeled. A removable cover provides access to the terminal area. This area contains the connection terminals, one additional button, one LED, one double DIP switch, and a SIM card slot (OZS164.23 only). 11 12 13 14* 2 1 6 8 9 10 A A 1 D1 2 M C 3 D2 4 M B B 3 4 7 5 15* Pos. Name Element 1 On-LED LED (green / red) 2 LPB/BSB LED A LED (green) 3 (LED) B LED (no function) 4 Fault LED LED (red) 5 (LED) LED (no function) 6 Remote button Button 7 Service button Button 8 DIP switch message suppression Switch 9 (Switch) Switch (no function) 10 Terminals Connection terminals LPB/BSB (left) A Terminals Connection terminals digital inputs (center) C Terminals (Connection terminals) (right) B Terminals (no function) 11 External voltage plug DC connection 12 USB plug USB connection Mini-B 13 Ethernet plug RJ45 network connection 14* GSM antenna Rod antenna 15* SIM card slot Card slot * OZS164.23 only 5 / 12
Notes Mounting You can mount the web server in a panel, a distribution box, or on flat wall. Plan sufficient space around the unit for easy wiring. Make sure service can easily access the unit and the unit is ventilated properly. Vertical mounting (circulation via vent holes) is required at ambient temperatures greater than 35 C. Standard mounting On standard rail TH 35-7.5 Wall mounting Screwed to wall Mounting position Horizontal or vertical Mounting and dimensions See "Dimensions" Installation Important Operating voltage Wiring Connection terminals Commissioning Connections Router IP address Observe the following when installing: Run fuses, switches and wiring as per local regulations for electrical installations. We do not recommend plant monitoring via USB interface in environments with strong electromagnetic interference (e.g. in industrial environments with electrical welding equipment). See "Technical data" for electromagnetic compatibility. The delivered power supply unit supplies the required 24 VDC operating voltage for the web server. The terminals for the LPB/BSB bus as well as the digital inputs are located at the bottom of the device. The operating voltage plug 24 VDC as well as the plugs for USB, Ethernet, and GSM (OZS164.23 only) interfaces are located on top of the device. The terminals are designed for 0.25...1.5 mm 2 solid wire cross-sections, or 0.25...1.0 mm 2 stranded wire cross-sections. Commission the web server locally via USB interface using the PC or laptop. The PC/laptop must contain a suitable web browser (see "Equipment combinations"). You need a USB cable type A / type Mini-B to locally connect the USB interface of the web server to the PC laptop. See the installation instructions G5711 (attached) or commissioning instructions C5711 (saved on web server at http://<ip address>/doc/ ) for more information. You need a suitable router for remote operation via Internet. The router must support NAT/PAT as well as DynDNS for dynamic IP addressing. The IP address via USB is canned: 192.168.250.1. Default setting for IP address via Ethernet: 192.168.251.1. Users must manually set the IP address as per their home network. 6 / 12
User groups User accounts are created and assigned to specific user groups for customized user operation. End user Service Administrator Works with end user data, fault overview, and manages own user account. Works with data at Service and End user levels, fault overview, message history, logos, documents, system definitions, and manages own user account. Works with data at Service and End user levels, fault overview, message history, logs, documents, system definitions, creates device web pages, and manages all user accounts. Maintenance The OZW164 web server is maintenance free (no battery changes, no fuses). Clean the housing only with a dry towel. Repair The OZS164 cannot be repaired on site. If faulty, return to the Repair Center of the relevant Regional Company. Disposal Dispose of the device as electronic waste in compliance with European directive 2002/96/EEC (WEEE) and not as municipal waste. Observe all relevant national regulations and dispose of the unit correctly. Observe all local and applicable laws. 7 / 12
Technical data Power supply unit for web server OZS164 Operating voltage Rated voltage Frequency Power consumption OZS164 (incl. power supply unit) Protection class Output voltage Supply line fusing AC 100-240 V 10 % AC 100-240 V 50 / 60 Hz 3 VA typical II SELV 24 VDC Max. 16 A Cable length (distance 230 VAC plug to web server) Max. 1.6 m. Web server OZS164 Operating voltage SELV 24 VDC 5 %, 625 ma max. Power consumption 2 W typical Functional data Clock reserve Min. 72 h Device list 1 Bus device Connection terminals PC interface LPB/BSB bus Ethernet Digital inputs Screw terminals for 1 solid wire per terminal 1 stranded wire per terminal. Interface Standard Device class Baud rate Connection cable for operator station Cable length Cable type for connection to PC/laptop Cable type for connection to OZS164 Interface type 2-wire bus Bus load Permissible line length and cable types Interface type Bit rate Protocol Identification Connection Cable type Cable length Interface type Voltage at open contact Current at closed contact 0.25...1.5 mm 2 0.25...1.0 mm 2 USB V2.0 RNDIS Max. 12 Mbps (full speed) Max. 3 m USB type A USB type Mini-B 2-wire connection DB/CL+, MB/CL (non-exchangeable) E 0.6 See: - Albatros2 System manual P2359 - Local Process Bus System engineering basic documentation P2370 100BaseTX, IEEE 802.3 compatible 100 Mbps TCP / IP Auto MDI-X RJ45 plug (screened) Standard Cat-5, UTP or STP Max. 100 m Protective low voltage for potential-free low voltage-capable contacts DC (16 19) V DC (4...6) ma Industry standards Product safety Information technology equipment - Safety EN 60950-1 Electromagnetic compatibility Immunity (Industrial sector) Emissions (Residential, commercial and industrial sectors as well as small business) Radio communications (OZS164.23) -Conformity EMC directive Low voltage directive Ecodesign directive (power supply unit) R&TTE (Radio & Telecom. Equipment) (OZS164.23) EN 61000-6-2 EN 61000-6-3 EN 301 489-1, EN 301 489-7 EN 301 511 2004/108/EC 2006/95/EC 2005/32/EC 1999/5/EC 8 / 12
-Conformity (OZS164.13) Australian Radio Communication Act EN 61000-6-3 -Conformity (OZS164.23) Australian Radio- and Telecommunication Act EN 61000-6-3 EN 301 489-1, EN 301 489-7 EN 301 511 Environmental compatibility The product environmental declaration E5711en contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) ISO 14001 (environment) ISO 9001 (quality) SN 36350 (environmentally compatible products) 2002/95/EC (RoHS) Degree of protection Degree of protection of housing OZS164 IP 30 as per EN 60529 Safety class OZS164 III as per EN 60950-1 Ambient conditions Materials and colors Dimensions Weight Operation Climatic conditions Temperature (housing and electronics) Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Upper housing section Lower housing section OZS164.13 (without antenna): Length x width x height (max. dimensions) OZS164.23 (with antenna): Length x width x height (max. dimensions) OZS164.13 Full unit Complete device (basic unit with packaging, installation instructions, power supply unit, USB and Ethernet cable, cable ties) OZS164.23 Full unit Complete device (basic unit with packaging, installation instructions, power supply unit, USB and Ethernet cable, cable ties) Packaging IEC 60721-3-3 Class 3K5 0...50 C 5...95 % r. h. (non-condensing) Class 3M2. IEC 60721-3-2 Class 2K3 25... 70 C < 95 % r. h. Class 2M2 PC + ASA, RAL 7035 (light-gray) PC + ASA, RAL 5014 (dove blue) 87.5 mm x 90 mm x 40 mm 87.5 mm x 134.5 mm x 40 mm 0.136 kg 0.589 kg 0.143 kg 0.601 kg Cardboard box Terms, abbreviations Auto Medium Dependent Interface - Crossed Auto MDI-X Dynamic Domain Name System DynDNS Hyper Text Transfer Protocol HTTP Internet Protocol IP Konnex KNX Network Address Translation NAT Port and Address Translation PAT Remote Network Driver Interface Specification RNDIS Shielded Twisted Pair STP Simple Mail Transfer Protocol SMTP Transmission Control Protocol TCP Universal Serial Bus USB Unshielded Twisted Pair UTP 9 / 12
Connection diagrams Connection terminals A DB/CL+ DB/CL+ DB/CL- DB/CL- D1 M C D2 M * GSM: OZS164.23 only Power supply unit Type Euro plug per EN 50075 and VDE 0620-1. For 230 VAC External voltage plug 24 VDC plug 1 24 VDC (+) 2 GND ( ) Pin assignments USB plug Type Mini-B 1 VCC 4 ID 2 D 5 GND 3 D + Ethernet plug RJ45 (standard assignment) 1 Tx + 5 Unassigned 2 Tx 6 Rx 3 Rx + 7 Unassigned 4 Unassigned 8 Unassigned LPB/BSB connections Terminal assignment A 1 DB/CL+ 2 DB/CL+ 3 MB/CL- 4 MB/CL- Digital inputs Terminal assignment C 1 D1 2 M 3 D2 4 M 10 / 12
Connection diagram P1 P2 N2 5711A02 DC 24 V LPB/BSB D1 M D2 M DB/CL+ MB/CL- N1 N1 Web server N2 LPB/BSB device P1, P2 Devices with potential-free contact output for fault indication Dimensions 39.2 134.5 87.5 6 11 / 12
12 / 12 2010 Siemens Switzerland Ltd Subject to change