ALARM. Alarm Alarm description Reset AL: 002 Antifreeze lockout alar m



Similar documents
Thermo Top - Troubleshooting Tree

Oil and Coolant Circulating Heating System. Model - OCSM

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Failure code manual. content

SWIMMING POOL HEAT PUMP Owners Manual

Heat Pump Water Heater IOM Manual

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Technical Information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

SWIMMING POOL HEAT PUMP

ALL IN ONE. Heat Pump Water Heater

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

For installation guide see reverse of book

T6580 FAN COIL CONTROLLER

INSTALLATION MANUAL. Address card EKAC10B

SMM. Installation Operation Maintenance

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

ECOCIAT. Domestic hot water heat recovery unit

Application Engineering

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

DTC B1423/23 Pressure Sensor Circuit

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

USER S MANUAL HSC-24A

Operating Instructions Split System Air Conditioner

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

ELECTRIC CENTRAL HEATING FLOW BOILER

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

Use, installation and instruction manual

1 General information

14. Troubleshooting Guide

PORTABLE AIR CONDITIONER

Heat Pump. Quick Start Guide Models: 035, 055, 075, 090, 115, 110, 120, 121, 135, 155, 156, & 175

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Overheating limit control

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

Designed for multi-injector endurance testing, the

RAINCONTROL LCD Special

Technical service manual 2009

Condensing unit type EPSILON-ECHOS LE Technical information manual

HEAT PUMP PROGRAMMABLE THERMOSTAT

Luna 3 Comfort Troubleshooting Guide June 2008


, User s Manual

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

RVR Hybrid System Installer Instructions RVR Hybrid System Controller Installation Instructions

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

MP-4000 Alarm List (Software version or later)

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Evaluate, Clean, and Tune Guidance

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

COMMISSIONING OF HVAC SYSTEMS

RAPID WATER CHILLER RAPIDMAC 50. ISO 9001 Cert. N 0412/2 OUR SYSTEMS COMPLY WITH DIRECTIVES 73/23 EEC - 89/336 EEC INSTRUCTION MANUAL

SERVICE MANUAL REFRIGERATION

WHITE-RODGERS COMFORT-SET 90 SERIES

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HERZ-Thermal Actuators

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

Owner s Manual RBC-AMS41E. Remote controller with weekly timer. Owner s Manual

Integrated Metering Systems, Inc.

T-100-R Installation Guide

LOBOY 16 AIR CONDITIONERS

SWIMMING POOL HEAT PUMP (THP 55, THP 100, THP 120, THP 170) INSTALLATION AND USER GUIDE

CGC s Hybrid System Loop Control

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Using the Ducted Gas Central Heating Add-on Refrigerated Air Conditioning Ducted Evaporative Air Conditioning. with your.

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

C-Tech-10 Operation Manual

Installation and maintenance instructions. Danfoss Vent

Dealer Sales & Service Guide

Important Safeguards

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

ENERGY SMART TROUBLESHOOTING GUIDE TABLE OF CONTENTS:

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

Transcription:

SECTION I: USER I.6.8 LRM SIGNLS IMPORTNT! Malfunctions and alarms displayed b y the machine should NEVER b e ignored. The problem should b e checked and resolved as soon as po ssible. If the alarm re-occurs, call technical assistance. If the unit's electronic boar d detects any malfunctions, the L RM key will light up on the control panel and the alar m code in question will appear on the displ ay, with r eference to the following table. If the al arm is a type alarm, it will be automatically reset. If the alar m is a type M al arm, you will need to press the LRM key for 3 seconds to reset it. If the alarm is a type 3M alar m, it will be automaticall y reset 3 times and will then need to be manuall y reset.! LRM LRM Prg ON OFF No alarms detected MODE LRM! LRM Prg ON OFF L: 012 High pressure MODE larm larm description Reset L: 002 ntifreeze lockout alar m Indicates that probe ST2 has detected a lower temperatur e than the set antifreeze Set-point. M L: 005 Differential pressur e switch alarm Indicates that the differential pressure switch between the system i nput and output water has been activated. 3M L: 010 Low pressure alarm Indicates that the low pressur e switch has been acti vated. 3M L: 012 High pressure l arm Indicates that the high pressure switch has been acti vated. M L: 020 Fan thermal al arm Indicates that the ther mal protection i nside the fan's electric motor has been acti vated. M L: 021 larm pump 1 Indicates that following the L: 005 alarm the pump may be faulty. 3M L:022 larm pump 2 Indicates that following the L: 005 alarm the pump may be faulty. 3M L: 030 ST1 probe malfunction alar m (B1) Indicates that either the probe is faulty or has detached from connector B1. Check L:033 ST4 probe malfunction alar m (B4) Indicates that either the probe is faulty or has detached from connector B4. Check L:034 ST2 probe malfunction alar m (B5) Indicates that either the probe is faulty or has detached from connector B5. Check L:035 Faulty pr essure transducer alarm Indicates that either the pressur e transducer is faulty or has detached from connector B6. Check L: 037 ST8 probe malfunction alar m (B8) Indicates that either the probe is faulty or has detached from connector B8. Check L: 040 Maintenance pump 1 hours of the pump has exceeded the set val ue. The unit continues to oper ate as L: 041 Maintenance compressor 1 hours of the compressor has exceeded the set value. T he unit continues to operate as L: 042 Maintenance compressor 2 hours of the compressor has exceeded the set value. T he unit continues to operate as L:046 Maintenance pump 2 hours of the pump has exceeded the set val ue. The unit continues to oper ate as L: 055 Clock card al arm Indicates that the clock card ( accessor y) is faulty: cut off and resume the unit's power. If the al arm persists, contact an authorised ser vice centre and the clock card will be replaced. L: 056 Phase sequence al arm Indicates that the L1-L2-L3 phase sequence to the mains switch is incorrect. Cut the unit off, adj ust the sequence and resume power. M L: 057 Min/max voltage alarm L:060 High temperature al arm IN r ec/des Indicates that the recover y outlet water temperature has exceeded the safety threshold. 3M utomatic reset M Manual r eset 3M utomatic 3 times, then manual 50

SECTION II: INST LL TION ND MINTEN NCE II.8.1 CONFIGURTION Safet y component calibration settings Pressure switch Cut-in Reset high pressure 40.2 bar 28.1 bar - Manual low pressure 2 bar 3.3 bar utomatic water differential 80 mbar 105 mbar - utomatic Safety val ve 41.7 bar - DNGER! The safet y valve is calibrated to 41.7 bar. It could cut in if the calibration valve is reached during the refrigerant charging operations, cau sing a burst that could cau se scalding. Configuration parameters Standard setting Summer worki ng temper ature set poi nt 7 C Winter working temperature set poi nt (THEY) 45 C Wor king temperature differential 2 C ntifreeze temper ature set poi nt 1,5 C ntifreeze temper ature differential 2 C Water differenti al pressure switch time upon start-up 120" Water differential pressure switch exclusion time upon start-up 15" Circulation pump switch off time delay 15" Minimum time between two consecuti ve compressor start-ups 360" The units are tested in the factor y, where they are also calibrated and the default par ameter settings are put in. These guarantee that the appliances r un correctly in rated wor king conditions. The machi ne configuration is carried out in the factor y and should never be altered. II.8.2 IMPORTNT! If a unit is used for the production of chilled water, check the adjustment of the thermostatic valve. UNIT -UP ND UP FTER PROLONGED SHUTDOWN DNGER! lways use the switch to isolate the unit from the mains b efore carrying out an y mainten ance work, even if it is for inspection purposes only. Make sure that no one accidentally supplies po wer to the machine, lock the mains switch in the OFF position. Befor e starti ng the unit, perfor m the following checks: The el ectricity power suppl y must compl y with the specifications on the data plate and/or the wiring diagram and it must fall within the followi ng limits: Variation of the power suppl y frequency: ±2 Hz. variation of the power suppl y voltage: ±10% of the nominal voltage; imbal ance between the suppl y phases: <2%. the electrical power suppl y system must be able to suppl y adequate current and be suitabl y sized to handle the load; open the electric panel and make sure the terminals of the power suppl y and of the contactors are tight (they may have come loose during transport, which could lead to malfunctions); Electrical connections must be made in compliance with the l ocal installation standards i n force in the place where the unit is i nstalled, and with the i nstructions in the wiring diagram provided with the unit. 58

II.8.3 -UP PROCEDURE IMPORTNT! The unit must be started up for the first time b y skilled technicians only, qualified to work on conditioning and refrig erant units. SECTION I: USER Once the unit installation and connecti on operations have been completed, it can be started up for the first time. For a correct first start-up of the unit carefully follow the diagrams provided in the following paragraphs. II.8.3.1 General unit conditions Have the technical clearance distances indicated in the manual been respected? YES NO Restore the indicated technical spaces. re the finned coils fr ee fr om obstructions? NO Clean the finned coils. YES re the fan grilles free from obstructions? NO Remove the obstr uctions. YES Is the unit damaged due to transport/installation? YES NO The general conditions of the unit are compliant! Danger! D o not start the unit! Restore the unit! II.8.3.2 Checking the compressor oil level Is the oil level sufficient? NO Top up as necessary YES Was pre-heating activated at least 24 hours before start-up? YES The compressor is read y for startup! NO ctivate pre-heati ng and wait 24 hours. II.8.3.3 Checking the water connections Have the water connections been made to a professional standard? NO Bring the connections up to standard. YES Is the water input/output direction correct? NO Correct the input/output directi on. YES re the circuits full of water and have the pipes been bled of any air residue? NO Fill the circuits and/or bleed the air. YES Does the water flow conform to what is stated in the user manual? NO Correct the water flow. YES Do the pumps turn in the right direction? NO Correct the rotation direction. YES re the flow meters (if installed) acti ve and correctl y connected? NO Repair or replace the component. YES re the water filters placed upstream from the heat exchanger and recover y unit in good worki ng order and correctl y installed? YES The water connections are compliant! NO Repair or replace the component. 59

SECTION I: USER II.8.3.4 Checking the electrical connections Does the unit power suppl y match the values indicated on the plaque? YES NO Restore the correct power supply. Is the phase sequence correct? NO Restore the correct phase sequence. YES Does the earth confor m with current r egulations? NO Danger! R estore the earth connection! YES re the power circuit electric conductors of the size indicated in the manual? YES Is the circuit breaker positioned upstream from the unit of the right size? YES The electric connection is compliant! NO NO Danger! R eplace the wires immediatel y! Danger! R eplace the component immediatel y! II.8.3.5 First start-up (Standard Unit) sk all unauthorised personnel to leave the area. De-activate the magnetother mal switches on the compressor power suppl y. Simul ate an empty start i n order to ensure that the power contactors have been inserted correctl y. re the power contactors inserted correctl y? NO YES Disconnect the power from the auxiliary supply again. De-activate the magnetother mal switches on the compressor power suppl y. Power the auxiliar y circuit. Start up the machine usi ng the control panel (ON/OFF key). Choose the oper ating modes (MODE key). Check the correct rotation of the pumps and fans, the flows and the operation of the heat exchangers sensors. NO Start-up procedure completed! Check and r eplace the component if necessary. ll ON/OFF operations must be carried out EXCLUSIVEL Y using the ON/OFF key on the control panel. Check and r eplace the component if necessary. 60

SECTION II: INST LL TION ND MINTEN NCE II.8.3.6 First start-up (Unit with recovery) sk all unauthorised personnel to leave the area. De-activate the magnetother mal switches on the compressor power suppl y. Simul ate an empty start i n order to ensure that the power contactors have been inserted correctl y. re the power contactors inserted correctl y? NO Check and r eplace the component if necessar y. YES Disconnect the power from the auxiliary supply again. De-activate the magnetother mal switches on the compressor power suppl y. Power the auxiliar y circuit. Start up the machine usi ng the control panel (ON/OFF key), also starting up the recover y circuit pumps and disabling the heat recover y units through the control panel or excluding the heat recover y differential pr essure switch consent. Check that the pumps rotate correctl y, check the flows and the operation of the heat recovery sensors. Put the unit in the right mode (summer or wi nter), then activate the recover y unit consent. Start-up procedure completed! ll ON/OFF operations must be carried out EXCLUSIVEL Y using the ON/OFF key on the control panel. NO Check and r eplace the component if necessar y. II.8.3.7 Checks to be made while the machine is running sk all unauthorised personnel to leave the area. YES Cut-in test: use the water intercept valves to reduce the flow to the evaporator. Is the water differenti al pressure switch acti vated correctly? YES Is the wor king pressure reading correct? NO Check and/or repl ace the component. NO YES If you take the pressur e on the high pressure side to approx. 8 bar, ar e there gas l eaks of > 3 grams/year? YES NO Does the unit display feature any alarms? YES NO Start-up procedure completed! Stop the unit and check the cause of this anomal y. Stop the unit and check the cause of the l eak (EN 378-2). Check the cause of the alarm. See table of al arms. 61

SECTION II: INST LL TION ND MINTEN NCE II.8.4 TBLE OF LRMS The display on the control panel displ ays the alarms, with reference to the following table. larms are r eset by pressing the LRM key on the control panel once the cause has been identified and eliminated. Typ e of alarm Possible cause Cut-in L:002 ntifreeze alarm L:005 larm for water differential pressure switch on condenser/evaporator Set-point set too l ow Insufficient water fl ow Insufficient water fl ow Presence of air in the water system Intercept val ves closed The circulati ng pump (if present) does not run Check set-point and reset Check and adj ust if necessar y Restore the correct water flow Bleed Open val ves See Troubl eshooting section Water circuit filter obstructed Check and cl ean if necessar y Indicates that the low pressur e switch has been activated: the alar m is reset manually from the keyboard. Note: the alar m will be automatically reset 3 ti mes L:010 Lo w pressure alarm in the region of an hour and will then need to be reset manuall y. When this alarm is triggered the L:021 and L:022 signals are acti vated simultaneousl y. If the alarm persists refer to Troubleshooting section. Indicates that the high pressure switch has been activated: r eset the pressure switch manuall y by L:012 High pressure switch alarm firmly pressing the button on the pressure switch itself. Then reset the alar m manuall y fr om the keyboard. If the alarm persists refer to Troubleshooting section. L:020 Fan thermal protection activation alarm Short-circuited fan Check and r eplace the fan if necessary L:21 larm pump 1 Indicates that following the L: 005 alarm the pump may be faulty. T he alarm is r eset manuall y from the keyboard. L:22 larm pump 2 Note: the alar m will be automatically reset 3 ti mes in the region of an hour and will then need to be reset manuall y. L:030 Inlet water temperature sensor Sensor faulty alarm (ST1) Sensor detached from connector B1 Insert terminal into connector B1 L:034 Temp erature sen sor alarm: Sensor faulty evaporator outlet water (ST2) Sensor detached from connector B5 Insert terminal into connector B5 L:033 Temp erature sen sor alarm: buffer Faulty sensor tank outlet water (ST4) Sensor detached from connector B4 Insert terminal into connector B4 L:035 Pressure transducer alarm Transducer faulty Replace the transducer Transducer detached from connector B6 Insert tr ansducer into connector B6 L:037 Inlet water recovery temp erature Sensor faulty sensor alarm (ST8) Sensor detached from connector B8 Insert terminal into connector B8 L:041 Compressor 1 maintenan ce signal L:042 Compressor 2 maintenan ce signal This alarm does not i ndicate a malfunction but onl y signals that the number of wor king hours of the compressor has exceeded the set value. T he unit continues to operate as nor mal. Contact an authorised ser vice centre for maintenance inter vention. Press the LRM key to deacti vate the signal. L:055 Clock card alarm Indicates that the clock card ( accessor y) is faulty: cut off and resume the unit's power. If the alar m persists, contact an authorised ser vice centr e and the cl ock card will be replaced. T he alarms are reset automaticall y. Indicates that L1-L2-L3 phase sequence L:056 Ph ase sequence alarm all interruttore gener ale is incorrect. Cut the unit off, adj ust the sequence and resume power. T he alarms are reset automaticall y. Indicates that the general power suppl y voltage L:057 Min/max voltage alarm (in volt) is outside the set range. Check power line. The al arms are reset automaticall y. L:060 Inlet water high temperature alarm rec/d es Indicates that the recover y inl et water temperature has exceeded the safety threshold. 62