Distributing Power to Blade Servers



Similar documents
Increase the efficiency of power distribution in your high-density data center

How To Power A Bladecenter H Servers

Eaton epdu. Intelligent and flexible power distribution

Eaton epdu Data Center Product Catalog

Rack Power Distribution. Worldwide

Power Distribution Considerations for Data Center Racks

Rack Power Distribution

Build for today. Expand on demand.

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Rack Systems Solutions

Optimizing Power Distribution for High-Density Computing

Server Technology, Inc.

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

High-Efficiency AC Power Distribution for Data Centers

Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments

Emerson Network Power Rack PDU Systems

Data center solutions Medium & large enterprise, multi-tenant and hyperscale. Energize your data center, maximize the value of your investment

Wireless Networks and Power Quality

Power to the adaptable data center

Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity

ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

APC 3Phase Power Distribution

Three-Phase Electric Power Distribution for Computer Data Centers

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Intelligent Power Distribution in the Data Center

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation

The Different Types of AC Power Connectors in North America

QuickSpecs. HP 480/277 Volt Solutions. Overview

Cabinets 101: Configuring A Network Or Server Cabinet

QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA North America Version 5 August 22, 2008 Page 1

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Rack Power Distribution Unit For Critical IT Equipment

8 Intelligent PDUs. Intelligent Power Distribution Units for Data Centers

Spec Sheet. Cisco R42610 Rack CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, REV A.6 DECEMBER 9,

Application Briefs: Remote Office Environment

QuickSpecs. HP Modular Power Distribution Units (Zero-U/1U Modular PDUs) Overview

ED1259R5 Updated April 2011 For latest specs visit

Fundamentals of Power

Panduit Infrastructure Management Software for Data Centers and Enterprises

QuickSpecs. HP Managed Power Distribution Units (mapdu) Overview

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

Top 8. Considerations for Choosing the Right Rack Power Distribution Unit to Fit Your Needs

Power Commander Power Distribution Units from Wiremold/Legrand offer

The Vector Approach to Data Center Power Planning

Cisco Nexus 7000 Series Power Supply Modules

Power distribution in data centres

How To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit

Choosing Close-Coupled IT Cooling Solutions

PX100 MBP with Configurable Distribution

Data Center Trend: Distributed Power in the White Space

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

HP UPS R1500 Generation 3

Data Center Racks. Vantage S2. Enclosure System. Switch N to Eaton.

RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE

AC Power For Business-Critical Continuity. Liebert MPH. User Manual North American & European Applications

DCF Optimized Rack System Selection Guide

CTO Configuration Guide. Eaton Ferrups Ferrups 60Hz RM Series

Eaton epdu Product Catalog

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Qualitative Analysis of Power Distribution Configurations for Data Centers

Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers

InstaPATCH Cu Cabling Solutions for Data Centers

Power & Environmental Monitoring

Model Number Electrical Compatibility Module Connector Type. M LL-S22 60 cell PV module MC-4 Type 2 Locking

Power and Cooling for Ultra-High Density Racks and Blade Servers

415V DISTRIBUTION FOR GREEN DATA CENTERS

R5000 Uninterruptible Power System (UPS) Overview

R5000 Uninterruptible Power System (UPS) Overview

Smart-UPS 120 V. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS

Server Technology Inc.

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

Calculating power requirements for HP ProLiant rack-mounted systems

SUN BLADE 6000 CHASSIS

Rittal Liquid Cooling Series

Open Rack Hardware v1.0

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime

QuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview

Chassis, Power Supply, and Element Management

How To Fit A Dll 2420 And 4220 Rack Enclosure

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

SMARTPLAY7. Increase your Deal Size and Profitability with SmartPlays

HP ProLiant DL360 G4 and G4p Server High Density Deployment Solution White Paper

Remote Site Management Solutions

Transcription:

Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily produce dozens of power cords to manage and an appetite for 20 kw or more of reliable power. Traditional power strips are just not up to the task. Eaton offers a complete suite of enclosure-based power distribution units (epdu ) that streamline the power architecture and support rapidly escalating blade server power requirements. Eaton is unique in the industry for providing a tiered set of epdu product families along two dimensions tiered both in power capacity and in functionality. That means you can precisely match up the combination of features and power rating needed for each application. Which blade server epdu is right for your application? What deployment considerations apply? With the right epdu model and implementation strategy, you can satisfy present and future needs, optimally balance loads and enhance data center efficiency and uptime. Although the Eaton epdu family encompasses a host of models and options, selecting the right product and implementation scheme for any given application is a simple matter based on 10 key factors. 1. How many blade servers will be powered? Eaton offers models for applications of all sizes. A Mid-Range epdu (8.6-10 kw) supports two blade server chassis. A High-Range epdu (10-15 kw) supports up to three blade server chassis. An Ultra epdu (15 kw and up) supports up to four blade chassis. The following chart shows some sample configurations. Approximate number of blade servers that can be supported by various electrical configurations Configuration No. of servers Max Power Total Power Eaton epdu Height 30A/208V (threephase) 1 2* 2,878W / phase 8,636W PW309MOOU079 0U 60A/208V 2 3,200W / breaker 9,600W PW110MOOU087 PW110ME1U083 60A/208V (threephase) 3 2,878W / breaker 17,272W PW317ME2U092 2U 80A/208V (threephase) 4 3,200W / breaker 23,030W PW323MO0U095 0U Note that the figures above are approximate, based on typical servers that are not fully loaded. Your hardware supplier will be able to provide actual operating requirements for your specific blade servers. 0U 1U

Page 2 of 5 2. What type of input power plugs do your blade servers use? Most blade servers come with appliance plugs (IEC320-C20) or industrial plugs (such as L15-30P). The C20 appliance plug type is traditionally used for epdus with C19 outlets. The L15-30P plugs are used to plug directly into a UPS or independent outlet box. Some epdus offer L15-30R receptacles, but the options are limited and restricted to 19 horizontal rackmount power solutions. Deploying multiple L15-30P power cables to the rack can be much more costly than installing one larger amperage rated circuit. Eaton epdus are offered with a variety of power inputs and outputs to fit most power requirements. You can select from NEMA, IEC and hardwired inputs from 30A to 80A at 208V single- or three-phase. On the output side, you can select a mix of NEMA- and IEC-type output receptacles. 3. What other type of equipment must be served? In addition to blade servers, you may also need to accommodate other equipment that uses different receptacle types. The best solution, if possible, is to convert the other equipment to the IEC320-style connectors, rated at 208V. This approach will typically enable you to deploy more equipment in the rack, and power supplies are typically more efficient at the higher voltage level. Contact your hardware suppliers for IEC C13-to-C14 or C19-to-C20 optional cord sets. Most power supplies in today s IT equipment will auto-sense the input voltage and allow either 120V or 208V based on the cord set. 4. Does the equipment use single-phase or three-phase power? Most blade server power supplies are single-phase, except where an actual three-phase plug is being used, and then there may be the need for three-phase power. Larger storage array systems may also require three-phase power. There are advantages to either 30A/208V threephase or 60A/208V single-phase solutions. Three-phase. If you are powering legacy equipment that might require 120V power (such as routers, hubs and switches), consider the option of using 30A/208V three-phase power strips, as they are available with both 208V and 120V single-phase outputs. However, a shortcoming of this solution is that it requires three pole positions at the panelboard, so you will only be able to power 14 epdus from one 42-pole panelboard (42 poles / 3 pole breakers = 14 circuits). Single-phase. The 60A/208V single-phase power option only requires two pole positions at the panelboard, so you can feed 21 epdus from one 42-pole panelboard (42 poles / 2 pole breakers = 21 circuits). You can therefore serve more racks from the same panelboard. For higher power applications, you can also use 60A three-phase power distribution, but you must be aware of the limitations of the panelboard itself, as you could max out the panelboard with as few as four (4) circuits.

Page 3 of 5 5. Will you distribute power feeds for optimum redundancy and load balancing? Some blade servers permit the operator to adjust the performance of the primary between two and three internal power supplies. We recommend that the power be distributed across the maximum number of power supplies. Remember, the breakers for three-phase and singlephase, in-rack power units are divided into groups of three. A distributed power approach ensures the highest degree of load balancing at the enclosure level. 6. In what manner will you connect power sources to maximize availability? Blade servers have at least four input power cords. That means you have various options for how you plug server power cords into the epdu(s). For maximum availability, you should alternate not only the epdu sections you plug the primary power cords into, but alternate the epdus as well. The following is an effective example for load-balancing two blade servers with six power cords across two epdus. Server #1 Server #2 Plug # epdu #1 epdu #2 1 Outlet 1 - Section 1 2 Outlet 1 - Section 2 3 Outlet 1 - Section 3 4 Outlet 1 - Section 1 5 Outlet 1 - Section 2 6 Outlet 1 - Section 3 1 Outlet 2 - Section 1 2 Outlet 2 - Section 2 3 Outlet 2 - Section 3 4 Outlet 2 - Section 1 5 Outlet 2 - Section 2 6 Outlet 2 - Section 3 Note that this section refers to the output phases (AB, BC, CA) or sub-feed breakers. 7. Do you require onboard metering? It is critical that the epdu has an onboard ammeter to help prevent overload conditions, optimize power distribution, and, when applicable, to accurately bill internal customers for power usage. The ammeter also helps you set up a balanced equipment load in the enclosure. (Remember that inputs of large power devices are measured differently than the outputs. This is particularly important on three-phase power units where the outputs are single-phase.) While branch circuit monitoring may be used, it does not help in balancing loads on the output of the epdus. It is also impractical to walk back and forth between the panel board and the enclosure as you attempt to balance loads. Therefore, the power distribution unit you choose should monitor both inputs and outputs for three-phase units and all of the outputs for singlephase units.

Page 4 of 5 All but the most basic Eaton epdus have onboard metering at the outlet, branch circuit and epdu levels, with time-stamped activity logging. Eaton offers the only epdus on the market that support outlet-level monitoring. Other enclosure-based epdus only show aggregated current at the branch circuit or epdu level. 8. Will blade servers be clustered or distributed in the data center? Depending on the total number of blade servers being deployed, you need to evaluate whether these units should be isolated in their own location in the data center. After all, these highdensity systems create unique powering and cooling concerns. Grouping blade servers together offers some benefits from an electrical architecture perspective, and can offer advantages in developing a modified cooling strategy as well. 9. Where do you want to mount the epdu? As epdus have become more powerful and sophisticated, they have grown larger as well, to accommodate UL489 branch circuit breakers and internal wiring. Mounting large epdus can be problematic in 24 wide enclosures. Some of these epdus can extend 3.5 to 4 from their mating surface and, if not mounted correctly, can block rear rackmount rails and cabling and inhibit airflow for cooling. Some customers elect to use deeper enclosures (44 to 48 ), but Eaton recommends 30 deep enclosures for better thermal management and ease of access. Eaton offers epdu models that mount horizontally in minimal rack space (1U or 2U), or vertically in rack side pockets or rear channels. Our high-density Ultra epdus can be hardwired directly to the panelboard. 10. What will your data center look like in 12 to 18 months? What expansion plans are on the horizon? With the rate of change in most IT environments, it is not uncommon for the load profile of a datacenter to change even before the day equipment is commissioned. Plan ahead for this inescapable reality. You don t want to find yourself redesigning the power distribution system for your enclosures or a portion of the data center. Eaton recommends that you factor in at least 20 to 30 percent headroom over today s requirements for future expansion. Closing thoughts Eaton is unique in providing a full complement of epdus that combine the functionality you need with the power range you need. Eaton epdus offer features and options to match your unique requirements, from various mounting options to remote monitoring to individual control of load segments. epdus are just one element of Eaton s unified family of data center solutions, which also includes power protection, backup power, power monitoring, enclosures, services and more. For example, the Eaton BladeUPS power system, designed for high-density blade server environments, delivers 12 kw of protected power in a 6U module, up to 60 kw with redundancy in a single rack. Eaton s Rack Power Module (RPM) distributes up to 36 kw of power in an organized manner to loads of various voltages, power cords and layouts. Eaton s software and connectivity options enable administrators to monitor power conditions from anywhere.

Page 5 of 5 The unified power architecture has fewer cables to manage, fewer distribution points to monitor and greater flexibility for IT personnel to make changes without an electrician. With integrated, compatible elements, you create a power infrastructure that is as resilient, flexible and adaptable as the data center needs to be. About the author Kevin Macomber is a business development manager for power quality solutions at Eaton Electrical. He holds a BS in business economics and started his career as an electrician in the U.S. Navy. Kevin has more than 10 years of experience in data center electrical architectures and has been instrumental in the design and development of dozens of market-leading power distribution products. About Eaton Eaton is a global leader in power quality and management solutions named by Frost & Sullivan as Power Quality Company of the Year for three years in a row (October 2006). Eaton s rugged epdus reflect more than 40 years of expertise in industrial-strength power quality solutions. In fact, Eaton has been manufacturing epdus for several other major brands for years. For more information - www.powerware.com - 1-800-356-5794. Eaton, Powerware, and BladeUPS are trade names, trademarks, and/or service marks of Eaton Corporation and its subsidiaries or affiliates.