An innovative thermally activated light-weight steel deck system numerical investigations and practical tests



Similar documents
Floor systems - key elements for sustainable multi-storey buildings

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

HERZ-Thermal Actuators

Integrated Solar Radiant Systems

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

HDA

Module 3.7. Thermal bridging

- White Paper - Data Centre Cooling. Best Practice

Installation Instructions

TABLE OF CONTENT

Adaptive strategies for office spaces in the UK climate

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Thermal diffusivity and conductivity - an introduction to theory and practice

Optiffuser. High-performance, high bandwidth lightweight 1D diffuser.

COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -

BOFIRE A FEM-programm for non-linear analysis of structural members under fire conditions

Crawl space heat and moisture behaviour

Energy Efficient HVAC-system and Building Design

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark

Aluminium systems profile selection

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO

8 EXTRA LIGHT GRC SANDWICH ELEMENTS FOR ROOFING IN INDUSTRIAL BUILDINGS

Field test of a novel combined solar thermal and heat pump system with an ice store

LindabAtriumPlana. Heating and cooling panels. lindab atrium plana. lindab we simplify construction

Exemplary Retrofitting of an Old School in Stuttgart - EROS -

V K Raina. Reactor Group, BARC

Active noise control in practice: transformer station

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

First 14-storey wood building in the world at Bergen in Norway Premier bâtiment en bois à 14 niveaux au monde à Bergen en Norvège

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS

HVAC air curtains. Type InduAir

Drain Back systems Made in Germany

Thermal Performance of Steel Beam Junctions using Different Connection Methods

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

Federation of European Heating, Ventilation and Air-conditioning Associations

Art Basel Miami Beach Dec Booth Design Regulations

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

Composite Panel Firewall Systems

POROUS BURNER - A New Approach to Infrared

Optimising plate girder design

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

Influence of material data on injection moulding simulation Application examples Ass.Prof. Dr. Thomas Lucyshyn

Elegance SC. Solar Control

Test Report. Nr dated Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE Lammhult Sweden

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

KONRAD. Hybrid Fancoil Series

PROCESS TECHNOLOGY. for lightweight design in automotive industry. TRUMPF Laser- und Systemtechnik GmbH. Marc Kirchhoff Industry Management Automotive

How To Write An Analysis System For Bridge Test

Combi Unit Genius. The energy efficient Building Service Centre

SECTION MORTUARY REFRIGERATORS

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports.

Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation

Calibration of Dallas sensors

HFM Heat Flow Meter Thermal Conductivity Analyzer

Improving thermal insulation of concrete sandwich panel buildings

IEA SHC Task 47 Renovation of Non-Residential Buildings towards Sustainable Standards

Buildings Construction Procurement Strategy

FULL DC INVERTER SYSTEMS

COLUMN-FREE OFFICE SPACE RISES IN CHICAGO S LOOP

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

Kerkstoel Activ Floors for concrete core activation

OPERATION MANUAL INFRARED THERMOMETER

The simulation of machine tools can be divided into two stages. In the first stage the mechanical behavior of a machine tool is simulated with FEM

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

HANDOUT CLIMATIC WIND TUNNEL MAHLE BEHR GMBH & CO. KG STATUS: FEBRUARY 2014

PRODUCT AND ENGINEERING MANUAL

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Status quo of stress simulation for hot and warm work piece temperatures in forging

Simulation in design of high performance machine tools

Structural fire design Eurocode Timber structures

Comparative study for cables and busbars

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

جامعة البلقاء التطبيقية

Understanding Boiling Water Heat Transfer in Metallurgical Operations

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

heat treatment equipment & accessories

INTERNATIONAL HOCKEY FEDERATION PERFORMANCE REQUIREMENTS AND TEST PROCEDURES FOR HOCKEY BALLS. Published: April 1999

Thermo-Mechanical Coupled Simulation with LS-DYNA

Rate of Heating Analysis of Data Centers during Power Shutdown

HEAVY DUTY STORAGE GAS

Everline Module Application Note: Round LED Module Thermal Management

1 DESCRIPTION OF THE APPLIANCE

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

V RICONDITION C OOLING SOLUTIONS. Next Generation Cold Corridor. Takes modular thinking in energy-efficient data centre design to a new level

Air-water systems for efficient air conditioning

Self-piercing riveting

Learning Module 4 - Thermal Fluid Analysis Note: LM4 is still in progress. This version contains only 3 tutorials.

Building Energy Systems. - HVAC: Heating, Distribution -

Half the cost Half the carbon

Transcription:

An innovative thermally activated light-weight steel deck system numerical investigations and practical tests Dipl.-Ing. Bernd Döring, Prof. Dr.-Ing. Markus Feldmann, Dipl.-Ing. Markus Kuhnhenne RWTH Aachen University, Lehrstuhl für Stahlbau und Leichtmetallbau, Germany Corresponding email: bdo@stb.rwth-aachen.de SUMMARY A prefabricated deck system made of laser-welded steel sandwich panels (LSP), up to now only used for decks in shipbuilding, shall be improved for the use in buildings. Beneath other items like fire safety, acoustics and vibrations here the thermal performance is of particular interest. Due to the very low weight the thermal inertia is very low. For compensation of this property this deck element was designed with an integrated piping system for simulating the thermal behaviour of a heavy construction, furthermore the characteristic of a heating and cooling ceiling could be reached, depending on the supply temperature. Prototypes of these new deck panels were produced and implemented into the research building of the Institute of Steel and Light-weight Constructions, RWTH in Aachen. A detailed scientific programme was performed to work out the thermal capabilities of these elements using a detailed monitoring system, heat meters and infrared surveys. In parallel numerical investigations were made (FEM-calculations and TRNSYS-simulations) to compare the results and to show further steps for improvements. The investigations show interesting results: The manufacturing must be properly performed to get sufficient thermal contact from pipes to the ceiling, the response time is low due to the low mass, and the benefit for the indoor climate of light-weight constructions is high with acceptable additional costs. INTRODUCTION The deck element in the scope of this investigation is a laser-welded steel sandwich panel (LSP) with vertical webs in a Vierendeel system. Figure 1 shows this element, which is originally used for decks in shipbuilding, and gives the range of dimensions, in which this panel is available, the maximum span amounts 10 m. The column indicated with RWTH shows the dimensions of the elements used for testing in the RWTH Modular Research Building (see below). The very low depth could only achieved by penetrating the laser-weld beam from the outside. These deck elements have a high stiffness at a very low mass. These properties make the panels interesting for highly prefabricated construction systems.

from [mm] to [mm] RWTH [mm] tb Width 500 3000 1800 ts hs Length 1000 10000 t 2 10 5400 3 p t p 120 120 hs 40 100 120 80 ts 3 4 4 Figure 1: Laser welded steel sandwich panel with upper deck plate, vertical webs and lower deck plate (left), dimensions of laser-welded panels (right) One problem of having this very low mass is the missing thermal inertia, therefore a solution to compensate this disadvantage was developed and tested. A steel pipe meander was integrated in the panel to create a heating / cooling ceiling resp. a thermally activated building component (Figure 2). The denomination is not clear-cut, on one hand, the hydronic system is integrated in a structural component similar to a concrete core cooling, on the other hand it behaves like a cooling ceiling Steel sheets Steel pipe Webs Sound insulation Floor plate Figure 2: Integration of steel pipes in the steel deck system (left: steel pipes in the module before welding the upper steel sheet, right: principle of the completed deck system) IMPLEMENTATION AND TESTING OF THE DECK SYSTEM IN A RESEARCH BUILDING In 2005 the Institute of steel and light-weight construction, RWTH Aachen University, in collaboration with the german association IFBS (Industrieverband für Bausysteme im Metallleichtbau, Düsseldorf), erected a research building using light weight, prefabricated components made of steel. Drawings of the building are given in figure 3, figure 4 shows the erection and figure 5 the completed building. One objective of this research building is the measurement of the thermally activated LSP. The test room in the center of the ground floor is equipped with these elements.

Figure 3: Ground plan of modular research building (left: ground floor, right: upper floor) Figure 4: Erection of Modular Research Building

Figure 5: Modular Research Building, elevation North-West (left), South-East (right) TESTING EQUIPMENT FOR DECK SYSTEM The two active deck elements are feeded by a refrigerated circulator, providing pre-heated or pre-cooled water. Various valves are integrated in the circuit to allow different running modes (only one panel active or both in parallel or serial connection). Each panel has a heat meter for measuring volume flow and the consumption of heat resp. coolth (figure 6). Additionally heat flux plates and an infrared camera were used to get more reliable data by using different measurements at once. Thermo-Electron Umwälz-Heiz-/Kühlgerät WM1/WM2: Heat-/Volumeflowmeter T1/T2: Temperature probes Valves Panel 2 Panel 1 T2 WM2 T1 WM1 Figure 6: Sketch of testing set-up Measurements were made for heating and cooling, due to the lack of space only the cooling results are presented (further results: see [4]). Figure 7 shows the specific cooling power depending on the mean temperature difference water room. In the diagramm results taken from the heat meters and by heat flux meters in combination with infrared surveys are shown. Results between ca. 30 and more than 45 W/m² were measured at temperature differences between 6 and 8 K (room mean water temperature).

50 spec. power and mean water temperature difference spec. power [W/m²] 40 30 20 10 Heat meter Heat flux plates / IR camera 0 0 1 2 3 4 5 6 7 8 mean water temperatur difference [K] Figure 7: Measured cooling power of active deck element, cooling mode An infrared survey from the ceiling were taken to get detailed information about the temperature distribution (figure 8). The view on the lower side of the panels shows some remarkable aspects: The steel pipes are sticked-welded to the lower deck plate of the section every 100 cm, these positions can be identified as cold spots, here is a good thermal contact guaranteed. In between the contact is more or less random in some parts there is good contact also between the welded points, but in the majority part the temperature is higher the thermal contact is not sufficient. Figure 8: Infrared survey of active deck element, cooling mode (view underneath the steel slab) FEM-CALCULATIONS The tested deck element was also numerically investigated. A representative sectional model was used for a FEM-study. Two different cases were considered: The pure LSP with the pipe

and a complete deck system including insulation and floor plate (figure 9). These two variations were tested in the research building, too. Ausschnitt für 2D-FEM-Simulation θ i α oben hs t ts θ F,m α F α unten θ i p t Figure 9: FEM-model of thermally activated LSP (left: sketch with boundary conditions, mid: FEM-model without flooring, right, FEM-model with insulation an floor plate) The following boundary conditions were taken into account [2],[3]: Mean water temperature θ F,m : 18 C Room temperature θ i : 26 C Heat transfer coefficient α top : 6.7 W/m²K Heat transfer coefficient α unten : 8.92 (θ i θ F,m ) 0.1 W/m²K Heat transfer coefficient water/pipe α F : 200 W/m²K Figure 10 shows the results of the FEM-calculations. Without insulation a part of the coolth reaches the floor, the ceiling temperature is about 20 C, the floor approx. 22 C. If the insulation and floor plate is added, nearly all coolth is transferred by the ceiling (temperature 19 20 C), the floor temperature is close to the room temperature. 18 19 20 21 22 23 24 C 26 18 19 20 21 22 23 24 C 26 Figure 10: Results FEM-calculation (left: without flooring, right: with insulation and floor plate)

Based on these results the cooling power for various temperature differences was calculated (Figure 11); the diagram shows additionally curves for existing cooling ceilings, furthermore the measured results as shown in Figure 7 are marked. The FEM-results show a high performance of the thermally activated LSP, on the other hand, the measured results are significantly lower. This difference was studied in detail by an analysis of the IR-survey and a variation of the FEM-calculations (Figure 12). 160 spec. power [W/m²] 140 120 100 80 60 40 Form A Form B Form C Form D Active steel panel, FEM-result Active steel panel, measured FEM-Result Measured results 20 4 5 6 7 8 9 10 11 12 13 14 mean water temperatur difference [K] Figure 11: FEM-result (thermally activated LSP with insulation and floor plate), in comparison with conventional existing cooling ceilings (Form A to D, [1]) and the measured results The comparison of Figure 12 shows, that very small air gaps between the pipe and the sheet lead to a significant loose of performance. The measured section L3 is close to the calculated result for a 1 mm air gap, on the other hand the measured cold spots (see L02) reach the temperature 24 23 22 L03 IR-Bild, L01 21 IR-Bild, L02 Temp [ C] 20 19 L01 L02 IR-Bild, L03 FEM, guter Kontakt log. Wassertemp. FEM, 1 mm Luftspalt 18 log. Wassertemp. 17 16 0 240 480 720 960 1200 1440 x [mm] Figure 12: Comparison of FEM-results (good contact and 1 mm air gap) and sections of the IR-survey (as marked in Figure 8)

RESULTS The thermal activation of a laser-welded steel sandwich panel is possible. The thermal performance was tested by measurements and in parallel investigated with numerical calculations. The theoretical performance is very good, a specific cooling power of 70 W/m² by a mean temperature difference water room of 8 K was calculated, which is in the top range of existing cooling ceilings. The measured results are lower, a value of ca. 48 W/m² at the same temperature difference can be extrapolated from the measurements. The main reason for this deviations was identified: The steel pipes have good contact to the lower steel sheet only at the fixing points, in between frequently an air gap exist, whereas small gaps (1 mm) lead to a significant loss of power DISCUSSION Generally the deck system LSP presented in this paper has the potential for a high cooling performance, as the FE-calculations show. To reach this value in practice, the contact between pipe and sheet has to be worked out carefully. The punctual stitched welds lead to unwanted decrease of the cooling power. A continuous welding or other techniques (glue, thermal paste, e.g.) to improve the thermal contact will bring the practical results closer the calculated values. ACKNOWLEDGEMENT The investigations has been carried out with a financial grant of the Research Programme of the Research Fund for Coal and Steel within the project EEBIS - Energy Efficient Buildings through Innovative Systems in steel (RFS - CR 03017). The Modular research building was supported by IFBS (Düsseldorf, D), the laser-welded steel sandwich panels by Meyer Werft (Papenburg, D). These funds are greatly acknowledged. REFERENCES 1. Recknagel, H., Sprenger, E., Schramek, E., Taschenbuch für Heizung und Klimatechnik, 72. Auflage, Oldenbourg Industrieverlag, München, 2005 2. Gütegemeinschaft Flächenheizungen und Flächenkühlungen e.v.: Allgemeine Güte- und Prüfbestimmungen für die Systeme der Thermischen Bauteilaktivierung (Betonkernaktivierung) RAL GZ 964 3. Glück, Bernd RAL Gütesicherung für Systeme der thermischen Bauteilaktivierung; HLH Heizung Lüftung Haustechnik 2004, Heft 5 4. Research Programme of the Research Fund for Coal and Steel, Project EEBIS - Energy Efficient Buildings through Innovative Systems in steel (RFS - CR 03017), final report (in preparation), 2007