Power Supplies 3. SDN-C Compact DIN Rail Series



Similar documents
Power Supplies 3. SDN-P DIN Rail Series

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

650W Single Output Power Supply

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Industrial Power Supplies

AC/DC Power Modules C B. TML Series, 20 & 40 Watt. Features. 20 Watt Models

O WA-120U series IP W Single Output Switching Power Supply. Features. Aplications

LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Redundancy Module QUINT-DIODE/40

Three-phase monitoring relay CM-PFE

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

TEP 200WIR Series, Watt

UMEC International Corporation

STRATO LED Drivers 70W, Single output

D1U54P-W HxxC Series 54mm 1U Front End AC-DC Power Supply Converter PRODUCT OVERVIEW FEATURES

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number:

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2

Thermistor motor protection

APD / Outputs 19" DC/DC Converter, 50 Watt

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

ST Series POWER SUPPLIES USER INSTRUCTIONS

EPL225 Series. 225 Watts. AC-DC Power Supplies. Models & Ratings. Summary

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CompactLogix Power Supplies Specifications

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Relés e Contatores de Estado Sólido SIRIUS

Digital input modules

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Your automation should be permanently supplied Our compact PROeco power supplies offer that as part of an economical concept Let s connect.

I STAR COMPUTER CO., LTD

NFF Series. CoolX600 NFF Series Cool. Patented Resonant Technology. NFF Series; No Fan Featured

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

HERZ-Thermal Actuators

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Silvertel. Ag Features. 2 Description. Power-over-Ethernet Plus Module. IEEE802.3at and IEEE802.3af compliant. Maximum 30W output power

Single Output Switching Power Supply

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

HFE1600 Series 1600W 1U Hot Swap Front End Power Supplies

38 Series - Relay interface modules A

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

Operating Manual UWAPS-TINY Series

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

3500/15 Power Supply Bently Nevada* Asset Condition Monitoring

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

NI NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

7 - Phaseo power supplies and transformers

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Series AMLDL-Z Up to 1000mA LED Driver

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

38 Series - Relay interface modules A

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Quick Connect. quick - simple - efficient.

Safety technique. Emergency stop module BO 5988 safemaster

Watts SHP Series

DMX-K-DRV. Integrated Step Motor Driver + (Basic Controller) Manual

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D E 0 VD00

Product Family of Capacitor Chargers PS-17XX for 1500J/Sec in the range 500Vac to 1,000Vac PS-22XX for 2200J/Sec in the range 500Vac to 1,000Vac

Datasheet. Arrant-Light Oy. 120W DR Series

MCR1900 Media Converter 19-Slot Chassis

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M Schaffhausen 1 / 10

MINI MCR-SL-R-UI(-SP)

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

RY2 miniature industrial relays

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

Panel Meters and Controllers Modular Panel Meter Type EDM 35

LOXONE 12 Channel Amplifier

is then retained absolutely without interruption.

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment

PHOENIX CONTACT Features

PHOENIX CONTACT - 01/2007

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

Contents. Document information

帝 聞 企 業 股 份 有 限 公 司 DEE VAN ENTERPRISE CO., LTD. SP DSL-20WA Revision: A Date: FOR AC-DC LED DRIVER MODEL NO.

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

E-STOP relays, safety gate monitors

Telephone- and leased line modem for industrial applications TD-36

MODEL PBA300F-3R3 PBA300F-5 PBA300F-7R5 PBA300F-12 PBA300F-15 PBA300F-24 PBA300F-36 PBA300F-48 MAX OUTPUT WATTAGE[W]

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Transcription:

Power Supplies 3 SDN-C Compact DIN Rail Series The SDN-C DIN rail power supplies are the next generation of the popular SDN series. These models combine high efficiency and compact size with new visual diagnostic LEDs to offer the most performance available from SolaHD. Essential industrial features such as Sag Immunity, Power Factor Correction, and universal voltage input have been retained in this series. Wide temperature operating range and parallel operation capability make the new SDN-C units suitable to a variety of industrial applications. Applications Industrial Machine Control and Process Control Conveying Equipment Material Handling Vending Machines Packaging Equipment and Amusement Park Equipment Semiconductor Fabrication Equipment DeviceNet TM UL E61379 508 Listed E137632 UL 60950 E137632 IND. CONT. EQ. E234790 CUL/CSA-C22.2 E61379 No. 234-M90 EMC and Low Volt. Directive UL Recognized Component, ITE, E137632 60950 - UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition E137632 CUL/CSA-C22.2 No. 234-M90 - Low Voltage Directive EMC and Low - IEC/EN60950-1, Volt. 2nd Edition Directive Sag Immunity: SEMI F47 RoHS Compliant Features Compact packaging to save space on the DIN rail Visual diagnostic LEDs for input and output status at a glance High MTBF means high reliability and long life Higher efficiency saves energy and lowers amount of heat generated in panel PowerBoost TM overload capability to start high inrush loads Accepts Universal voltage 85-264 Vac, 50/60 Hz input Active Power Factor Correction Patented DIN rail mounting clip User Adjustable output voltage accessible via front face Parallel capability standard Large, rugged, accessible screw terminals Industrial grade design - -25 o C to 60 o C operation without derating Fully tested and burned-in at factory Highly efficient switching technology Five year limited warranty Certifications and Compliances * All Models Listed, Ind. Control Equipment, E61379 UL 508 Listed - UL 508, CSA C22.2 No. 107.1 IND. CONT. EQ. E61379 * Refer to user manual for installation requirements when used in hazardous locations. Models SDN 20-24-100C, SDN 20-24-480CC, SDN 40-24-480C UL Recognized Component, Haz. Loc., UL 60950 E234790 E137632 CUL/CSA-C22.2 No. 234-M90 - ISA 12.12.01, CSA C22.2 No. 213 - Class I, Division 2, Groups A, B, C, D Models SDN 5-24-100C, SDN 10-24-100C, SDN 40-24-100C, SDN 5-24-480C, SDN 10-24-480C UL Recognized Component, Haz. Loc., UL 60950 E234790 E137632 CUL/CSA-C22.2 No. 234-M90 - UL 60079-15/CSA E60079-15 - Class I, Zone 2, AEx nc IIC, Ex nc IIC ATEX Directive - EN60079-0, EN60079-15 - II 3 G, Ex nc IIC Gc Related Products SDN-P series SDP TM series SCP series SDU UPS Accessories Chassis Mount Bracket (SDN-PMBRK2) Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com. 117

3 The SolaHD Difference Power Supplies Rugged metal housing Multiple output connections for ease of wiring multiple devices Visual diagnostic LEDs show input and output status (see table below) Large, IP20-rated, screw terminals for #10 AWG/6 mm 2, for quick, easy installation DC OK Relay Single or parallel use selectable by user Adjustable output voltage Clearly labeled front panel No internal fan, no extra cooling required in any power level Multiple certifications for versatility in applications Automatically adjusts for global Input voltages. No manual intervention required. Narrow width saves panel space LED Light Status Conditions Normal AC Power Loss AC Input Low No DC High Load Overload Hot Too Hot Input Green - Yellow Green Green Green Green Green Output Green - Green - Yellow Yellow Green - Alarm - - - Red Yellow Red Yellow Yellow 118 Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com.

Power Supplies 3 SDN-C Specifications (Single Phase) Nominal Voltage -AC Range -DC Range 1 -Frequency Description SDN 5-24-100C Input Catalog Number 115-230 Vac 85-264 Vac 90-375 Vdc 43-67 Hz SDN 10-24-100C Nominal Current 2 1.65-0.55 A 3.2-1.0 A -Inrush current max. Typ. < 15 A Typ.< 30 A Efficiency (Losses 3 ) > 88% typ. (14 W) > 90% typ. (24 W) Power Factor Correction Active power factor correction to better than 0.92 Output Nominal Voltage 4 24 V (23.5~28.5 Vdc Adj.) -Tolerance < ±2 % overall (combination Line, load, time and temperature related changes) Initial Voltage Setting 24.5 V ± 1% -Ripple 5 PARD Overvoltage Protection Power Back Immunity < 50 mvpp PARD (Periodic and Random Deviation) = 100 mv peak-peak max > 30.5 but < 33 Vdc, auto recovery Nominal Current 5 A (120 W) 10 A (240 W) -Peak Current 6 -Short Circuit Current -Current Limit Parallel Operation Holdup Time Voltage Fall Time < 35 V 1.5 Nominal Current for 4 seconds minimum while holding voltage > 20 Vdc 1.5 x Nominal Current at near zero volts at short circuit condition PowerBoost Switch selectable single unit or parallel unit operation. Units will not be damaged by parallel operation (regardless of switch position setting). >20 ms (Full load, 100 Vac Input @ T amb =+25 C) to 95% output voltage <150 ms from 95% to 10% rated voltage @ full load (T amb =+25 C) Line and Load Regulation < 0.5% EMC: -Emissions -Immunity Temperature 7 MTBF 8 Warranty General Protection/ Safety Status Indicators Fusing -Input Mounting -Output Connections Case -Free Space H x W x D inches in (mm) General EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2 EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, IEC 61000-4-34 voltage dip immunity standard Storage: -40 o C to + 85 o C, Operation -25 o C to +60 o C full power, with linear derating to half power from 60 to 70 o C (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. > 550,000 hrs 5 Year Limited Warranty Protected against continuous short -circuit, continuous overload, continuous open circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1) Visual: 3 status LEDs (Input, Output, Alarm) Relay: N.O. contact rated 200ma/50 Vdc Installation Internally fused Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm 2 ) for solid conductors. Screw torque: 4.4 lb-inch (~ 50 N-cm). Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6 mm 2 ) for solid conductors. Screw torque: 7 lb-inch (~ 80 N-cm). Fully enclosed metal housing with fine ventilation grid to keep out small parts. 25 mm above and below, 10 mm left and right, 15 mm in front 4.85 1.97 4.36 (123.0 50.0 110.0) 4.85 2.36 4.36 (123.0 60.0 110.0) Weight lbs (kg) 1.1 (0.50) 1.7 (0.80) 1. Not UL listed for DC input. 2. Input current ratings are conservatively specified with low input, worst case efficiency and power factor. 3. Losses are heat dissipation in watts at full load, nominal input line. 4. 24-28 Vdc adjustable guaranteed at full load. 5. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor. 6. Peak current is calculated at 24 Volt levels. 7. Contact tech support for operation at -25 o C. 8. Demonstrated through extended life test. Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com. 119

3 SDN-C Specifications (Single Phase) Description Nominal Voltage -AC Range -DC Range 1 -Frequency Power Supplies SDN 20-24-100C Input Catalog Number 115-230 Vac 85-264 Vac 90-375 Vdc 43-67 Hz SDN 40-24-100C Nominal Current 2 6-3 A 12-4 A -Inrush current max. < 40 A Typ. <60 A Efficiency (Losses 3 ) > 92% (38 W) > 93 % (67 W) Power Factor Correction Active power factor correction to better than 0.92 Output Nominal Voltage 4 24 V (23.5~28.5 Vdc Adj.) -Tolerance < ±2 % overall (combination Line, load, time and temperature related changes) Initial Voltage Setting 24.5 V ± 1% 5 -Ripple <100 mvpp < 100 mvpp PARD PARD (Periodic and Random Deviation) = 100 mv peak-peak max Overvoltage Protection > 30.5 but < 33 Vdc, auto recovery Power Back Immunity < 35 V Nominal Current 20 A (480 W) 40 A (960 W) -Peak Current 6 1.5 Nominal Current for 4 seconds minimum while holding voltage > 20 Vdc -Short Circuit Current 1.5 x Nominal Current at near zero volts at short circuit condition 1.8 x Nominal Current at or near zero volts at short circuit condition -Current Limit PowerBoost Parallel Operation 7 Switch selectable single unit or parallel unit operation. Units will not be damaged by parallel operation (regardless of switch position setting). Active Paralleling Holdup Time >20 ms (Full load, 100 Vac Input @ T amb =+25 C) to 95% output voltage Voltage Fall Time <150 ms from 95% to 10% rated voltage @ full load (T amb =+25 C) Line and Load Regulation < 0.5% General EMC: -Emissions -Immunity Temperature 8 EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2 EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4- 11, IEC 61000-4-34 voltage dip immunity standard EN61000-6-3, EN61000-6-4, Class B EN55011, EN55022 Radiated and Conducted including Annex A, EN61000-3-2, EN61000-3-3 EN61000-6-1, EN61000-6-2, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-4 Level 4 input and Level 3 output, EN61000-4-5 Installation Class 4, EN61000-4-6 Level 3, EN61000-4-8, EN61000-4-11, SEMI F47 Sag Immunity, Transient protection according to VDE 0160/W2 over entire load range. Storage: -40 o C to + 85 o C, Operation -25 o C to +60 o C full power, with linear derating to half power from 60 to 70 o C (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. MTBF 9 > 450,000 hrs > 500,000 hours demonstrated Warranty General Protection/Safety Status Indicators Fusing -Input Mounting -Output Connections 10 Case -Free Space 5 Year Limited Warranty Protected against continuous short -circuit, continuous overload, continuous open circuit. Protection Class 1 (IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1) Visual: 3 status LEDs (Input, Output, Alarm) Relay: N.O. contact rated 200ma/50 Vdc Installation Internally fused Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm 2 ) Input: Screw terminals, connector size range: 16-10 AWG for solid conductors. Screw Torque: 4.4 lb-in (~ 50 N-cm). (1.5-6 mm 2 ) for solid conductors. Screw Torque: 4.4 lb-inch (~ 50 N-cm). Output: Two terminals per output, connector size range: 16-10 AWG Output: Two terminals per output, connector size range: 10-6 AWG (1.5-6 mm 2 ) for solid conductors. Screw Torque: 7 lb-inch (~ 80 N-cm) (6-14 mm 2 ) for solid conductors. Screw Torque: 15.6 lb-inch (~ 176 N-cm) Fully enclosed metal housing with fine ventilation grid to keep out small parts. 25-40 mm above and below, 10 mm left and right, 15 mm in front H x W x D inches in (mm) 4.85 x 3.42 x 4.98 (123.0 x 87.0 x 127.0) 4.85 x 7.09 x 4.81 (123.0 x 180.0 x 122.0) Weight lbs (kg) 2.6 (1.20) 6.0 (2.75) 1. Not UL listed for DC input. 2. Input current ratings are conservatively specified with low input, worst case efficiency and power factor. 3. Losses are heat dissipation in watts at full load, nominal input line. 4. 24-28 Vdc adjustable guaranteed at full load. 5. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor. 6. Peak current is calculated at 24 Volt levels. 7. All models except the 40amp unit are capable of parallel operation by use of a jumper pin, accessible by the end user. 40 amp unit will have active current sharing signal. 8. Contact tech support for operation at -25 o C. 9. Demonstrated through extended life test. 10. SDN 40-24-100C only = Output signaling terminal block features (Shut down, Power Good, Current Monitor, Current Balance, signal GND). 120 Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com.

Power Supplies 3 SDN-C Specifications (Three Phase) Description Catalog Number SDN 5-24-480C SDN 10-24-480C SDN 20-24-480CC SDN 40-24-480C Input Nominal Voltage 380-480 Vac Two - phase input Yes 1 -AC Range 2 320-540 Vac -DC Range 450-760 Vdc 450-760 Vdc 450-760 Vdc 10 N/A -Frequency 50/60 Hz Nominal Current 3 3 x 0.5 or 2 x 0.7 A 3 x 0.8 or 2 x 1.2 A 3 x 0.9 or 2 x 1.3 A 3 x 1.6 A -Inrush current max. Typ. <25 A Negligible Negligible Efficiency (Losses 4 ) > 85% (18 W) 91.2% (23.6 W) 93% (42 W) 94% (78 W) Power Factor Correction Power factor correction to meet EN61000-3-2 Class A Active Power Factor Correction Output Turn on time Typ. 1s Voltage Rise Time ca. 5-20 ms <100 ms full resistive load (T amb =+25 C ) Power Back Immunity <35 V Overvoltage Protection >30.5 but <33 Vdc auto recovery Nominal Voltage 5 24 V (23.5~28.5 Vdc Adj.) Voltage Regulation < ±2 % overall Initial Voltage Setting 24.5 V ± 1% -Ripple 6 <100 mvpp PARD PARD = 100 mv peak-peak max PARD = 200 mv peak-peak max Nominal Current 5 A (120 W) 10 A (240 W) 20 A (480 W) (constant power, not constant current) 40 A (960 W) -Peak Current 7 6A, 2 Nominal Current <2sec 12A, 2 Nominal Current <2sec 1.5 Nominal Current for 4 sec minimum while holding voltage > 20Vdc -Current Limit PowerBoost Derating typ. 6 W/ o C typ. 12 W/ o C typ. 24 W/ o C typ. 48 W/ o C Holdup Time >20 ms >15 ms Voltage Fall Time <150 ms from 95% to 10% rated voltage @ full load (T amb =+25 C) <50 ms from 95% to 10% rated voltage @ full load (T amb =+25 C) Parallel Operation 8 Single or Parallel operation selectable via front switch. For redundant operation, use of external diode module is preferred Active Paralleling General Case Fully enclosed metal housing with fine ventilation grid to keep out small parts. Min. Required 25mm above and below or 25mm above and below or 70mm above and below or 70mm above and below, 15mm in Free Space 15mm in front 10mm in front 25mm in front and 25mm left & right front, 25mm left & right H W D inches (mm) 4.85 1.97 4.36 4.85 2.36 4.36 4.85 x 3.35 x 4.68 4.85 x 7.09 x 4.66 (123.0 50.0 111.0) (123.0 60.0 111.0) (123.0 x 85.0 x 119.0) (123.0 x 180.0 x 119.0) Weight lbs (kg) 1.2 (.52) 1.5 (0.70) 2.9 (1.30) 5.3 (2.40) EMC: -Emissions EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2 -Immunity EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11 Temperature Storage : -40 to + 85 o C, Operation -25 to +60 o C full power, with linear derating to half power from 60 to 70 o C (Convection cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation. Humidity < 90% RH, noncondensing; IEC 60068-2-2, 68-2-3 Altitude 0 to 3000 meters (0 to 10,000 feet) Vibration 2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6 Shock 3(g) peak, three axes, 11mseconds for each axis - IEC 60068-2-27 Warranty 5 Year Limited Warranty MTBF >500,000 hrs MTBF (Nominal voltage, full load, T amb = 25 o C) General Protection/Safety Protected against short -circuit, overload, open circuit. Protection class 1 (IEC536), degree of protection IP20 (IEC 529) Safe low voltage: SELV (acc. EN60950) Over-temperature protection LED Alarm, Output shutdown with automatic restart Status Indicators Visual: 3 status LEDs (Input, Output, Alarm) Relay: SSR or dry relay contact, signal active when V out = 18.5 Vdc = +/-5% Installation Fusing: -Input Externally fused -Output Not fused. Output is capable of providing high currents (PowerBoost) for motor load startup. Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system. Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail. 1. SDN 20 will operate at 75% load; SDN 40 will operate at 50% load under loss of 1 phase; SDN 5 and SDN 10 will operate with single phase input power at 100% of load. Unit will shut down if thermal threshold is exceeded under this condition. 2. Unit passed input voltage overstress test at 600 Vac without failure. 3. Input current ratings are specified with low input, line conditions, worst case efficiency values and power factor spikes. Input current at nominal input settings will typically be half these values. 4. Losses are heat dissipation in watts at full load, nominal line. 5. 24-28 Vdc adjustable guaranteed at full load. 6. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com. scope and 50 Ohm resistor. 7. SDN 20 and 40 unit will go to HICCUP mode. SDN 5 and 10 will maintain min 4 secs to deliver 150% load then drops to almost zero V out. The output voltage will immediately drop to almost zero when load rises above 150%. 8. All models except the 40amp unit are capable of parallel operation by use of a jumper pin, accessible by the end user. 40 amp unit will have active current sharing signal. 9. SDN 40-24-100C only = Output signaling terminal block features (Shut down, Power Good, Current Monitor, Current Balance, signal GND). 10. 70% maximum rated load. 121

C US LISTED 3 Power Supplies SDN-C Series Dimensions W D Catalog Number Dimensions - inches (mm) H W D H + + 24 VDC /2.5 A OK 24-28 V Single Parallel - - OK NEC Class 2 Power Supply S O L A Power Supply SDN5-24-100C 2.5-24-100P SDN 5-24-100C 4.85 (123.0) 1.97 (50.0) 4.36 (111.0) SDN 10-24-100C 4.85 (123.0) 2.36 (60.0) 4.36 (111.0) SDN 20-24-100C 4.85 (123.0) 3.42 (87.0) 4.98 (127.0) SDN 5-24-480C 4.85 (123.0) 1.97 (50.0) 4.36 (111.0) SDN 10-24-480C 4.85 (123.0) 2.36 (60.0) 4.36 (111.0) U L SDN 20-24-480CC 4.85 (123.0) 3.35 (85.0) 4.68 (119.0) 115/230 VAC 1.3-0.7 A 50/60 HZ N L SDN 40-24-100C and SDN 40-24-480C Dimensions W D 5.51 in. (139.96 mm) H Power Supply Signal Connector 1 D + 0.54 in (13.80 mm) Catalog Number Dimensions - inches (mm) H W D SDN 40-24-100C 4.85 (123.0) 7.09 (180.0) 4.66 (118.0) SDN 40-24-480C 4.85 (123.0) 7.09 (180.0) 4.81 (122.0) 1. SDN 40-24-100C and SDN 40-24-480C output signaling terminal block features: Shut Down, Power Good, Current Monitor, Current Balance, GND, and active current sharing through I_SHARE connectors (See Signals Manual for connection information). 122 Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com.

Power Supplies 3 SDN-C Series Mounting Chassis Mounting Instead of snapping a SolaHD SDN unit on the DIN Rail, you can also attach it using the screw mounting set SDN-PMBRK2. Dimensional Diagram - in (mm) This set consists of two metal brackets, which replace the existing two aluminum profiles..70 (17.8).43 (10.9) 1.59 (40.4).60 (15.2).23 (5.8).51 (13.0).18.86 (4.6) (21.8).60 (15.2) 1.30 (33.0) 1.80 (45.7) 2.16 (54.9).35 (8.9).08 (2.0).23 (5.8).40 (10.2).25 (6.4).26 (6.6).52 (13.2).52 (13.2) Detachment from DIN Rail: DIN Rail Mounting Snap on the DIN Rail: 1. Tilt unit slightly backwards 2. Put it onto the DIN Rail 3. Push downwards until stopped 4. Push at the lower front edge to lock 5. Shake the unit slightly to ensure that the retainer has locked Alternative Panel Mount: Using the optional SDN-PMBRK2 accessory, the unit can be screw mounted to a panel. Contact Technical Services at (800) 377-4384 with any questions. Visit our website at www.solahd.com. 123

SDN 40-24-100C Competitive Comparison SolaHD Phoenix Siemens PULS Allen Bradley Part Number SDN 40-24-100C QUINT-PS/ 1AC/24DC/40 6EP1 337-3BA00 QS40.241 1606-XLS960EE # of Conditions 8 4 3 3 2 Diagnostics Normal, AC Power Loss, AC Input Law, No DC, High Load, Overload, Hot, Too Hot IOUT < IN, IOUT > IN, VOUT < 0.9x VN, VOUT >0.9x VN Normal, Yellow LED, for Overload, RED LED for latching shutdown Normal, Overload, No DC output DC ON, DC OFF Nominal Input Voltage 100-240Vac 100-240Vac set by jumpers 85-132V/ 176-264V 100-240Vac 200-240Vac AC Input Range 85-264Vac 85-264Vac 90-264Vac 90-264Vac 90-264Vac Output Voltage 24 Vdc 24 Vdc 24 Vdc 24Vdc 24Vdc Ouptut Current @ 40amps @ 40amps @ 40amps @ 40Amps @ 40Amps Output Voltage Adjustment Range 23.5-28.5 Vdc adjustable 18-29.5 Vdc (> 24V constant capacity) 24-28.8 Vdc adjustable 24-28 Vdc adjustable 24-28 Vdc Efficiency > 93% (67 W) >92 % (for 230Vac and nominal values) approx 88% (131 W) > 93.2% Typ. 94.6% Mains Frequency 50 60 Hz 45 65 Hz 47 63 Hz 50 60 Hz +/-6% 50 60 Hz +/-6% Reliability (MTBF) > 500,000 hrs > 500 000 h in acc. with IEC 61709 (SN 29500) Not published > 274,000 hr acc. to SN 29500, IEC 61709 at full load current and 40 C > 274,000 hr acc. to SN 29500, IEC 61709 at full load current and 40 C Size (cm3 ) 2712.1 5050.8 3750.3 1968.5 1968.5 Width along the DIN rail inch (mm) 7.09in (180mm) 7.09 in (180mm) 9.45 in (240mm) 4.92 in (125mm) 4.92 in (125mm) Installation Clearance Required 25 mm above and below, 25 mm left and right, 15 mm in front. Do not obstruct air flow 50 mm verticaly to ensure sufficient convection; 15 mm laterally required when installed next to other active compoents. 50 mm above and below 40mm on top, 20mm on the bottom, 15 mm left and right, Do not obstruct air flow 40mm on top, 20mm on the bottom, 15 mm left and right, Do not obstruct air flow Full Power Ambient -25 C to +60 C -25 C to + 60 C 0 C to + 70 C -25 C to + 70 C -25 C to + 70 C Hazardous Location Rating Class I, Division 2 Class I, Zone 2 No rating No rating Class 1, Div 2 Pending Class I, Division 2 ATEX Rating Yes No rating Yes Pending No rating Weight lb/kg 6.0lb (2.75kg) 7.2lb (3.3kg) 6.33lb (2.9kg) 4.2lb (1.9kg) 4.2lb (1.9kg) Warranty 5 years 5 years Not published 3 years 1 year www.solahd.com solahd.technicalservices@emerson.com 1-800-377-4384

SolaHD SDN-C Series DIN Rail Power Supplies Reliable delivery of power in a compact footprint for single- or three-phase input

SDN-C SERIES: SINGLE- AND THREE-PHASE POWER SUPPLIES Maximize uptime and lower energy costs. The SolaHD SDN-C Series delivers: Higher efficiency. Improved visual diagnostics. Greater reliability. Compact size. Meet all your bulk power supply needs with a complete product line: 24 Vdc, DIN rail-mounted power supplies. Single- and three-phase models. New 40 Amp single-phase model. 2

HIGHER EFFICIENCY Advanced SolaHD technology eliminates the need for an input inductor and provides more efficient AC/DC conversion. Lower energy consumption. A more efficient design helps reduce energy costs. Lower cooling costs. With no input inductor, less energy is wasted in the form of dissipated heat with no need for additional cooling fans in the panel. Longer life. Less heat inside the panel enclosure means SDN-C power supplies and other components perform longer and more reliably. 3

IMPROVED VISUAL DIAGNOSTICS Multicolored LEDs show the status of input power, output power and alarm conditions at a glance. Normal AC Power Loss AC Input Loss NO DC High Load Overload Hot* Too Hot* Input Green ----- Yellow Green Green Green Green Green Output Green ----- Green ----- Yellow Yellow Green ----- Alarm ----- ----- ----- Red Yellow Red Yellow Yellow * Hot and Too Hot indicate the unit is about to shut down due to high temperature or has shut down. Not intended to be used as a thermostat or to monitor temperature. Reduce downtime. Troubleshoot power supply problems quickly and confidently. Diagonstic key. Affix the included sticker to the power supply or panel door to provide a handy diagnostic reference. 4

GREATER RELIABILITY Count on an improved design and SolaHD manufacturing quality for dependable performance. Reduced parts count. Fewer components provide lower failure rates compared to more complex power supplies. Less heat. With no input inductor, the SDN-C Series is less prone to heat buildup that can damage components. Smarter component layout. Heat-sensitive components are placed near cool air intakes and away from heat-producing components. 5

COMPACT SIZE SDN-C Series power supplies are smaller and more compact, so they are easier to work with and let you do more in the available space. More room to work. SDN-C power supplies save space on the DIN rail and in the electrical enclosure, so it s easier to terminate wires and configure components. Better heat dissipation. With more space around individual components, air circulates more freely. Increased enclosure capacity. Add more components to increase the capacity and efficiency of your operations, while avoiding the need to add a new enclosure. 6

NEW: 40 AMP POWER SUPPLY WITH SINGLE-PHASE INPUT For industries located in buildings with single-phase power, there is no need to let power supply capacity limit what you can do. Our newest single-phase SDN-C model delivers the same 40 Amp capacity as our largest three-phase model. The power you need today. Run large industrial loads such as sorting, conveying and packaging equipment, using the single-phase power available in any commercial building. The power you need tomorrow. Add new equipment to your operation and get the power you need within your existing power structure with little or no retrofitting required. 7

NEW: 40 AMP POWER SUPPLY WITH SINGLE-PHASE INPUT Single-phase power is by far the most commonly available. Even when industries require three-phase service to run large industrial motors, many branch circuits are likely to be on a single phase. Our new 40 Amp, single-phase SDN-C transformer is a perfect fit for powering large DC loads on a standard, single-phase AC circuit. 8

SPECIFICATIONS/CERTIFICATIONS Listed, Industrial Control Equipment, E61379 UL508, CSA C22.2 No. 107.1 UL Recognized Component, ITE, E137632 UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition UL Recognized Component, Haz. Loc., E234790 UL 60079-15/CSA E60079-15 Class I, Zone 2, AEx nc IIC, Ex nc IIC Low Voltage Directive IEC/ EN60950-1, 2nd Edition Directive EN60079-0, EN60079-15 II 3 G, Ex nc IIC Gc Sag Immunity: SEMI F47 9

CATALOG INFORMATION Product offering Single-Phase Catalog Number Watts Amps SDN 5-24-100C 120 5 SDN 10-24-100C 240 10 SDN 20-24-100C 480 20 SDN 40-24-100C 960 40 Three-Phase Catalog Number Watts Amps SDN 5-24-480C 120 5 SDN 10-24-480C 240 10 SDN 20-24-480CC 480 20 SDN 40-24-480C 960 40 For more information and to order your SDN-C power supply, contact your SolaHD representative. 10

WHY SOLAHD? Since 1915 in the most demanding environments, SolaHD has supplied total power-quality solutions to keep production lines moving and people, equipment and information safe. Turn to SolaHD for industrial-grade power conversion and power quality products to ensure reliable operation across your entire production environment. 11