BRE Global Test Report



Similar documents
BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Eco-Sol Ltd. Document Reference:

BS 476: Part 7: Method For Classification Of The Surface Spread Of Flame Of Products. A Report To: Gurit (UK) Ltd. Document Reference:

Safety Data Sheet according to (EG)1907/2006

Test Report: ICL/H11/979. BS 7837: 1996 Flammability performance for textiles used in the construction of marquees and similar textile structures.

18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS

Fire safety in buildings and implementation of European fire test standards

Test report No

Light-Weight Panels. High quality panels.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Put us to the test. Construction testing and building investigations services from BRE.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Loss Prevention Standard

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN :2007

PRODUCT SHEET 1 MIDLAND LEAD MANUFACTURERS LTD S CAST LEAD SHEET

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN : 2007

furnishings flammability characteristics

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Fire safety in timber buildings

A Guide to the European Standard for Safety Storage Cabinets (BS EN )

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007

Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

How To Test For Premer Retardant

CHAMELEON THERMOCHROMIC UV FLEXO INK

Technical Specification Fire Blanket Firemaster Fire Protection-Cables Tray Fire Protection Department

Want to exceed customer expectations and stand out from the crowd? Third party approval of management systems from BRE Global.

A pro s guide to photo prints on Alu-dibond

Loss Prevention Standard

fr fire retardant MARMOLEUM

Report Number BTC 17755F

IMO Resolution A.754(18) Fire Resistance Tests Fire Safety Onboard Ships BY

CONE CALORIMETER A TOOL FOR MEASURING HEAT RELEASE RATE

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire testing for BCA compliance

Annex of the certificate (Page 1/6) Accreditation Scope

European technical approval

Risk Management Guidelines

Watermist fire suppression systems for commercial low hazard occupancies

Code of Practice for fire resisting metal doorsets

Safety Storage Cabinets

European Technical Approval ETA 13/0526

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

Risk Management Guidelines

UNLIMITED VARIETY OF CREATIVE SHEET MATERIAL.

>active antimicrobial wall cladding for hygienic environments

Temperature C Cure time to reach hours LSS > 1MPa minutes

WHITE PAPER Fire & safety performance standards

Fire-Rated Glass and Glazing START

Specifications, Product Testing and Terminology

Ageing effect and long term performance of cement bonded particleboard. Prepared for: Viroc Portugal Indústrias de Madeira e Cimento S.A.

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

WATERPROOFING FOR CONCRETE STRUCTURES

MAIB SAFETY BULLETIN 1/2006. Fire on board the Bermuda registered cruise ship. Star Princess

Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles. Prepared for: Ben Hales

FATRA ROOF COVERING SYSTEMS FATRAFOL FF807 AND FATRAFOL FF807/V ROOF COVERING SYSTEMS

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Approved. Property Test/Standard Description. gloss (70-85) Flash point ISO 3679 Method 1 30 C calculated VOC-US/Hong Kong. US EPA method 24 (tested)

SIKA TANKING MEMBRANES SIKAPROOF A MEMBRANES

EUROPEAN STANDARDS PERSONAL PROTECTIVE CLOTHING FOR FLAME RESISTANT. Alexander Gstettner, Lenzing AG Austria

A new approach to the Danish guidelines for fire protection of combustible insulation

Cold trichloroethylene degreasing Film Thickness 70± 10 µm 10 minutes at 170 C (PZ 770 alone) 5 minutes 30 sec. at 220 C (maximum curing conditions)

SPREFIX SPRAY INSULATION _ in the marine market.

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Course of Construction Questionnaire

P.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk The Netherlands

CERTIFICATE OF APPROVAL No ME 5078

Use of Decision Support Tools for Bushfire Risk Management in NSW

SILASTIC 9161 RTV Silicone Elastomer

Technical Data SeaQueen

RHEPANOL RHEPANOL FK ROOF COVERING SYSTEM

ALUMASC ROOF WATERPROOFING MEMBRANES EUROROOF MASTERGOLD ROOF WATERPROOFING MEMBRANE

Approval Standard for Plastic Suspended Ceiling Panels

Tremco Fire Protection Systems Group Technical Bulletin

CHESTERFLEX ROOF WATERPROOFING MEMBRANES

Low VOC Performance Protection Systems

For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems

Likely performance of Breezway aluminium framed glass window assembly incorporating alternative steel mesh screens

Classification of reaction to fire of glass products Recommendation from Glass for Europe

Terms and Definitions In Canada

PYROSWISS VETROFLAM CONTRAFLAM

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports.

Site and Storage Conditions for Class 3.1 Flammable Liquids

How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System

EN Export Manager Pulastic Sports Surfaces The Netherlands

Safe Operating Procedure

Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems

means the period during which the Contractor is engaged by the Employment Business to render services to the Client.

How To Comply With The Loss Prevention Certification Board

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

INSTRUCTIONS FOR COORDINATION SECTION SOLID SURFACE FABRICATIONS

720r Addendum: Siting the 720r

SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES

FIRE BEHAVIOR CERTIFICATION OF THERMAL INSULATION MATERIALS

Transcription:

BRE Global Test Report IMO 2010 FTP Code Part 5 - Test For Surface Flammability MSC.307(88) on PVC film ORAJET 3951-010, printed with solvent based inks in colour Orange. Laminated with ORAGUARD 290 and applied on aluminium Prepared for: ORAFOL Europe GmbH Date: 04 December 2014 Report Number: 299377 BRE Global Ltd Watford, Herts WD25 9XX Customer Services 0333 321 8811 Prepared for: ORAFOL Europe GmbH Orafolstraβe 2 D16515 Oranienburg Germany From outside the UK: T + 44 (0) 1923 664000 F + 44 (0) 1923 664010 E enquiries@bre.co.uk www.bre.co.uk

Prepared by Name S M Warbus Position Senior Consultant Signature Authorised by Name S J Howard Position Principal Consultant Date 04/12/14 Signature This report is made on behalf of BRE Global and may only be distributed in its entirety, without amendment, and with attribution to BRE Global Ltd to the extent permitted by the terms and conditions of the contract. Test results relate only to the specimens tested. BRE Global has no responsibility for the design, materials, workmanship or performance of the product or specimens tested. This report does not constitute an approval, certification or endorsement of the product tested and no such claims should be made on websites, marketing materials, etc. Any reference to the results contained in this report should be accompanied by a copy of the full report, or a link to a copy of the full report. BRE Global s liability in respect of this report and reliance thereupon shall be as per the terms and conditions of contract with the client and BRE Global shall have no liability to third parties to the extent permitted in law. Opinions and interpretations expressed herein are outside the scope of UKAS Accreditation. Commercial in Confidence BRE Global Ltd 2014 Page 1 of 8

Table of Contents 1 Objective 3 2 Sample 3 2.1 Traceability 3 2.2 Description of sample and test format. 3 3 Conditioning 4 4 Results 4 4.1 Flame spread data 4 4.2 Observations. 4 4.3 Heat release curves 4 4.4 Derived fire characteristics 6 5 Criteria 7 6 Conclusion 7 7 Validity 7 8 Reference 8 Commercial in Confidence BRE Global Ltd 2014 Page 2 of 8

1 Objective To determine the flame spread characteristics of the sample described in Section 2 in accordance with the test method and criteria for bulkhead wall and ceiling linings, floor coverings, and primary deck coverings, specified in the IMO 2010 FTP Code Part 5 - Test For Surface Flammability (Test For Surface Materials And Primary Deck Coverings). MSC.307(88) 1. 2 Sample 2.1 Traceability The test samples were supplied by the test sponsor. BRE Global were not involved in the sample selection process and therefore cannot comment upon the relationship between samples supplied for test and the product supplied to market. 2.2 Description of sample and test format. Unless otherwise stated all measurements are nominal. Test Sponsor Manufacturer of sample Sample name/reference Sample description (as provided by test sponsor/manufacturer) Description of sample (as received) Mean sample weight per unit area (kg/m 2 ) Sample thickness (mm) ORAFOL Europe GmbH Orafolstraβe 2 D16515 Oranienburg Germany As above PVC film ORAJET 3951-010, printed with solvent based inks in colour Orange. Laminated with ORAGUARD 290 and applied on aluminium As above ORAGUARD 290 Cast PVC film, 50µm thick with solvent polyacrylate permanent adhesive ORAJET 3951-010 - Cast PVC film with gloss surface, 55µm thick with solvent polyacrylate repositionable permanent adhesive On aluminium Metal sheet with orange film on one face 8.31 3.2 (inc. aluminium substrate) Sample receipt date 06 November 2014 Test face Film face Commercial in Confidence BRE Global Ltd 2014 Page 3 of 8

Test format The sample was tested with a calcium silicate backing board Date of test 10 November 2014 3 Conditioning The specimens were conditioned as required by the standard. 4 Results 4.1 Flame spread data Observed ignition time, extinction time, duration of test, final spread of flame for each specimen and time to reach each reference point. Flame spread times: Run 1 e7533-2 Run 2 e7533-1 Run 3 e7533-4 Flame spread distance (mm) minutes seconds minutes seconds minutes seconds 50 1 26 1 34 1 24 100 1 26 1 34 1 24 150 1 32 1 41 1 24 200 1 36 1 52 1 34 250 2 14 2 09 1 57 300 2 41 2 39 2 27 350 400 450 500 550 600 650 700 750 Maximum flame spread (mm) 330 340 340 Time to ignition (minutes : seconds) 01 24 01 29 01 20 Flaming ceased (min:sec) 03 36 03 21 03 17 Test stopped 10 00 10 00 10 00 4.2 Observations. On each of the specimens blistering occurred approximately 2 seconds before ignition 4.3 Heat release curves Heat release curves for each specimen are given below Commercial in Confidence BRE Global Ltd 2014 Page 4 of 8

Commercial in Confidence BRE Global Ltd 2014 Page 5 of 8

4.4 Derived fire characteristics Derived fire characteristics for each specimen as defined in the objective. Criteria Specimen 1 2 3 Average Heat for Ignition (MJ/m 2 ) 4.10 4.50 3.75 4.12 Critical Flux at Extinguishment ((kw/m 2 ) Average Heat for sustained burning (MJ/m 2 ) CFE 27.28 26.01 26.01 26.43 Qsb 4.49 4.69 4.11 4.43 Total Heat release (MJ) Qt 0.03 0.02 0.06 0.04 Peak Heat release (kw) Qp 0.50 0.38 0.81 0.56 Commercial in Confidence BRE Global Ltd 2014 Page 6 of 8

5 Criteria Samples giving average values for all the surface flammability criteria not exceeding those listed below, are considered to meet the requirements for low flame spread. Bulkhead, wall and ceiling linings Floor coverings Primary deck coverings CFE (kw/m 2 ) 20.0 7.0 7.0 Qsb (MJ/m 2 ) 1.5 0.25 0.25 Qt (MJ) 0.7 2.0 2.0 Qp (kw) 4.0 10.0 10.0 Burning droplets Not produced No more than 10 burning drops Not produced Where CFE = Critical flux at extinguishment Qsb = Average heat for sustained burning Qt = Total heat release Qp = Peak heat release rate 6 Conclusion The results of this test show that the sample as described in this report, when tested and classified in accordance with IMO 2010 FTP Code. Part 5 - Test For Surface Flammability (Test For Surface Materials And Primary Deck Coverings). MSC.307(88)1 satisfied the requirements for low flame spread for use as: Bulkhead, wall and ceiling linings Floor coverings Primary deck coverings 7 Validity The test results relate only to behaviour of the test specimens of the product under the particular conditions of test, they are not intended to be the sole criteria for assessing the potential fire hazard of the product in use. Commercial in Confidence BRE Global Ltd 2014 Page 7 of 8

The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over 5 years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. 8 Reference 1 Resolution MSC.307(88) Adoption of the International Code for application of fire test procedures 2010, Annex 1, Part 5 Test for surface flammability. Test for surface materials and primary deck coverings. International Maritime Organisation: London 2010. Commercial in Confidence BRE Global Ltd 2014 Report Ends Page 8 of 8