Data Sheet SS/_5 Boundless motorized valve controller no need for slidewire feedback; improves reliability Two sealed 5A control relays suitable for direct connection to the valve, reducing installation costs Universal process input with integral 2-wire transmitter power supply direct connection for any process signal Retransmission of process variable analog output for recorder or datalogger IP66/NEMA4X front face ideal for use in the harshest environments Quick code, front face or P configuration easy operation and commissioning using our Windows -based software RS485/Modbus serial communication SADA, PL or open system integration dedicated /4 DIN controller for motorized valves
SS/_5 The Valve Position controller is a dedicated, single loop controller designed for direct control of motorized valves. Universal input and integral transmitter power supply ensure that the has the capabilities to measure a wide range of process signals such as temperature, pressure, flow and level. Two 5A relays are fitted as standard for either direct control of the positioner or via intermediate relays plus retransmission of the process variable for connection to a recorder or datalogger. Further I/O capabilities can be added, such as an alarm relay, remote set point and digital input, to suit the application. The configuration of the is achieved by moving the security switch and entering a simple code from the front panel keys or via our P configuration package. No passwords, no input links, no complications. With IP66/NEMA4X front panel protection and superior RF immunity as standard the has been designed to control reliably in the harshest of today s industrial environments. Process onnections Universal Process Input Thermocouple RTD 4 to 2mA Volts, millivolts Boundless ontrol Output 2 x Relays (5A) Valve Open Valve lose Transmitter Power Supply Auxiliary Outputs x Analog Process Variable Retransmission Auxiliary Inputs Digital Remote Set Point Additional Alarm Outputs x Relay Alarm Annunciator KEY: Standard Option Serial ommunications RS485 Modbus RTU SADA systems (on P) 2
SS/_5 Applications 5. lose Open PID ontrol Boundless control of an electrically-positioned valve with a travel time between and 5s using in-built 5A relays. The gives pulsed outputs to the valve which are based on the difference in Process Variable and Set Point. The signals the direction and time of travel to the valve. The controller does not require information on the absolute regulator position but uses the PV inputs as its feedback. The deadband setting prevents the valve from hunting. OMMANDER PR25 A 324. Boiler Temperature 5. Retransmission As standard the has a 4 to 2mA retransmission output of the process variable for connection to a chart recorder, datalogger or PL. P onfiguration To make configuration of the quicker and simpler, a Windows-based configuration software package is available. The is supplied with an in-built P configurator port as standard. onfigurations can be saved and downloaded to other instruments and a printout generated. 5. Alarm Type Alarm 2 Type Alarm Hysteresis Set Point Type SP E F G H 3 2 4 Quick ode Setting A simple 4-digit code enables all standard parameters to be set from the front face. Ramp/Soak Set Point Profiles The ramp/soak facility available on every provides for a single program, four-segment profile. This facility also includes guaranteed ramp/soak, repeat program, skip and reset features. t RS485/Modbus Fitted with an optional RS485 serial communication board, the can communicate with PLs and SADA systems using the Modbus protocol. 5. 5. 5. 3
SS/_5 Specification Summary PI, PID single loop, valve position controller Fully user configurable NEMA4X/IP66 P configuration Operation Display High-intensity 7-segment, 2 x 4-digit LED display Display range 999 to 9999 Display resolution digit Display height 4mm (.56 in.) onfiguration User-defined via front panel or via P configurator ontrol Functions ontrol types PI or PID Boundless Valve travel time to 5s Adjustable deadband (engineering units) 999 to 9999 ontrol terms P=. to 999.9% I = to 72s D=. to 999.9s Set points strategies Local Remote 4 selectable, fixed value Ramping Set Point Profile controller Number 4 Ramp/Soak segments Features Guaranteed Ramp/Soak, Self-seeking Set point, Program Repeat ontrols Run, Hold and Stop from Front Panel Switches Run/Hold or Run/Stop from digital input Alarms Number Two user-defined Type High/Low process High/Low deviation Standard Build Relay output Two relays with arc suppression components included as standard (SPDT) 5A @ 5/23V A, 5A @ 24V D Logic output 8V D at 2mA Min. load 4 PV retransmission Analog, configurable in the range of 4 to 2mA Max. load 5V (75 at 2mA) Accuracy.25% of span Analog Inputs Number One standard process variable One optional remote set point input Input sampling rate 25ms per channel Type Universally configurable hannel Thermocouple (TH) Resistance Thermometer (RTD) Millivolt urrent D voltage hannel 2 4 to 2mA Input impedance ma mv, V >M Linearizer functions Programmable for standard inputs:, TH types B, E, J, K, N, R, S, T or Pt Broken sensor protection Upscale drive on TH and RTD Downscale drive on milliamps and voltage old junction compensation Automatic J incorporated as standard Stability <.5 / change in ambient temperature Input protection ommon mode isolation >2dB at 5/6Hz with 3 imbalance Series mode rejection >6dB 5/6Hz Transmitter power supply 24V, 3mA max. powers one 2-wire transmitter Optional I/O specification Relay output SPDT 5A @ 5/23V A Digital input Type Volt-free Minimum pulse 25ms Modbus serial communications onnections RS422/485, 2- or 4-wire Speed 2.4k or 9.6k baud rate Protocol Modbus RTU slave Remote Set Point Input 4 to 2 ma D, nominal input impedance Preset to process variable engineering units 4
SS/_5 Physical Size 96 wide x 96 high x 22.5mm deep (3.78 in. wide x 3.78 in. high x 4.82 in. deep) Weight 52g (. lb) approx. Electrical Voltage 85 to 265V A (5/6Hz) 24V D Power consumption <6VA Power interruption protection <6ms/<3 cycles, no effect >6ms/>3 cycles, instrument returns to operation after a controlled reset Environmental Operating limits to 55 (32 to 3 F) 5 to 95% RH non-condensing Temperature stability <.2% of reading or 2 V/ ( V/ F) Front face IP66 (NEMA4X), case rear IP2 EM Emissions and Immunity Meets requirements of IE 6326 for an Industrial Environment Design and manufacturing standards Designed to meet SA requirements E Mark Electrical safety EN6 Standard Analog Input Ranges Thermocouple Maximum Range Maximum Range F Accuracy (% of reading) B 8 to 8 to 327 2 (3. 6 F) [above 2 (392 F )] * E to 9 4 to 65 J to 9 4 to 65 K to 3 4 to 235 N 2 to 3 325 to 235 R 8 to 7 to 3. (. 8 F) [above 3 (572 F )] * S 8 to 7 to 3 5 (. 9 F) [above 2 (392 F )] * T 25 to 3 4 to 55 * For B, R and S thermocouples, performance accuracy is not guaranteed below value stated M in. span below zero Type T 7º (26ºF) Type N 5º (89ºF) TH standards DIN 437 IE 584 RTD Maximum Range Maximum Range F Accuracy (% of reading)* * Pt 2 to 6 325 to ** RTD, 3-wire platinum, per DIN 4376 standard (IE 75), with range of to 4 Linear Inputs Milliamps Milliamps Volts Volts Millivolts R ange Accuracy (% of reading) to 2mA 2 A 4 to 2mA 2 A to 5V 2 V to 5V 2 V to 5mV 2 V Square Root Input Milliamps R ange Accuracy (% of reading)** * 4 to 2mA 2 A *** Below input of 4.64mA (2% flow) the input is linear 5
SS/_5 Overall Dimensions Dimensions in mm (in.) 7.5 (.69) 22.5 (4.82) 92.8. (3.622.3. ) 96 (3.78) 9.8 (3.6) 92.8..3 (3.622 ). Panel ut-out 96 (3.78) 5. (.2) 4 (.55) 3 (.8) Electrical onnections 25 26 27 28 29 3 3 32 33 34 35 36 2 3 4 5 6 7 8 9 2 Terminal Details Auxiliary Input (Remote set point) Digital Input Relay Output 2 25 26 2 27 3 N/O N/ 28 29 3 3 4 5 6 7 RTD Analog Input (see below) Transmitter PSU Analog Output RS485 TX RS485 RX RS485 32 33 34 35 36 Analog O/P 2 Relay O/P 3 N/O N/ Analog O/P 2 32 33 34 35 36 8 9 2 N/O N/ N L Relay Output *** 85 to 265V A Mains Supply or _ 24V D 2 3 4 TH millivolts and volts 3-lead RTD 3 rd lead RTD RTD 2-lead RTD and resistance RTD RTD RTD Milliamps ** * Milliamps ** * Using internal transmitter power supply ** Use shunt resistor provided with the instrument *** Fit the arc suppression component supplied with the instrument 2-wire Tx transmitter 6
SS/_5 Ordering Information V 25 / X X X X / X X X X Options Standard * additional alarm relay digital input remote set point 4 to 2mA digital input remote set point RS485/Modbus Power Supply 85V to 265V A 24V D Build ABB Standard Programming/Special Features onfigured to factory standard onfigured to customer requirements Special features *As standard the is fitted with 2 relays (open/close), 4 to 2mA retransmission, universal input and transmitter power supply. Accessories P onfiguration Kit (part no. /7) 2 3 S S T U P D S X X Licensing, Trademarks and opyrights Modbus is a trademark of Modicon, Inc. Windows is a trademark of the Microsoft orp. 7
SS/_5 ABB has Sales & ustomer Support expertise in over countries worldwide www.abb.com The ompany s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in UK (8.7) ABB 27 SS/ Issue 5 ABB Limited Howard Road, St Neots ambridgeshire PE9 8EU UK Tel: 44 ()48 47532 Fax: 44 ()48 27948 ABB Inc. 25 E. ounty Line Road Warminster PA 8974 USA Tel: 25 674 6 Fax: 25 674 783