Repeater Panel User Manual (TO BE RETAINED BY THE END USER)

Similar documents
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

Repeaters and Mimics Data Sheet

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU Rev 1

Product Data Sheet. User Manual. User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. Approved Document No. DFU Rev 1

AlarmSense 2-wire detection and alarm system. Product Guide

Gen4 Intruder Alarm Panels SIMPLY SECURE. For Residential & Small Commercial Applications

SECURIT 800L+ CONTROL PANEL

FIREDEX Conventional Fire Panels

VoCALL - CFVCM/CFVCWM & CFVCX8. Fire Telephone & Disabled Refuge Network System. User Manual & Log Book

ACTIVE 5 ENGINEERING MANUAL

Conventional Fire Detection and Extinguishant Control System Specification

IMPORTANT USER INFORMATION

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO B ISSUED AUG 2002 VERSION 1.18

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

CONTENTS 4. HOW TO UNSET THE PANEL...7

TS510 & TS500. Installation & User Guide. Compatible Equipment

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS EN Security Grade 2 Environmental Class 2

XR1. Intruder alarm system Operating Instructions. Unset system indications. Set System indication

SYSTEM 7000 IRIS+ USER MANUAL

VEGA Analogue Addressable Control Panels

astec Integrated Alarm System USER GUIDE

LCD5500Z / PKP-LCD v3.x Installation Instructions

Overview of Fire Alarm Systems and Maintenance

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

GST301. (Single Protection Zone) Operation Manual

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

WD-AMX Water Detection Controllers

D200+ Auto-Dialler Installation/Operators Manual

Analogue addressable devices

INSTALLATION MANUAL CONTENTS

Secure Keypads for access control

BS5839 Part 1:2002 Overview

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

Intruder alarm system Operating Instructions

FA701 Series. User s Guide. K6249-2V2 5/09 Rev. A

FIRE DETECTION AND ALARM SYSTEMS

SECURIT 800L+ CONTROL PANEL

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Installation guide H A. HSI hardwired system interface

Maintenance Manual PC6010. WARNING This manual contains information on limitations regarding product use and function

Users Guide to Keypad Functions

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

GSM Alarm System User Manual

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver

How To Set A Timer On A Gg System

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

HARDWIRED CONTROL PANELS

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

616, 626, 636 & 646 Keypads

Fire Alarm Systems Care and Maintenance

PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS

BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC

Fire Alarm Control Panel. Family. Operating Manual

conventional system operation

2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack

SNMP Web Management. User s Manual For SNMP Web Card/Box

Accenta/Optima. User Guide. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number: Honeywell Security

ICP-CP500. User's Guide ICP-CP500 Codepads

CAPTAIN 6. USER GUIDE System ver Zones Intruder Alarm System. PIMA Electronic Systems Ltd.

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Fire Detection Product Range

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

Drayton Digistat +2RF/+3RF

9452/9453 Installation and User Guide

TIG INVERTER INSTRUCTION MANUAL

INTELLIGENT CONTROL MODULE SA-2000-II HARDWARE MANUAL. Access Technologies International, Inc.

DESTINY 1/19/96 # A

OZW30. Central Unit SYNERGYR

Digiplex LCD Keypad DGP-641. User s Manual

Security System User Guide

Iso-Gard Series 6 Line Isolation Monitors

Reducing false alarms

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

ES-LCD User Control SD Card Location

TestManager Administration Guide

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

CB200W Water Leak Detection Panel Application Guide

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

10-Zone Spectra LED Keypads

PART 1 PRODUCT (GENERAL)...1.

SECURITY SYSTEM MANUAL

SECTION DETECTION AND ALARM

JUNIOR V3. Fire Alarm Control Panel INSTALLATION & COMMISSIONING MANUAL GLOBAL REVISION 2.3 FIRE EQUIPMENT QUEUE REVIEW STATUS ZONES

Surveyor Excel-K. Fire Alarm Control Equipment. Installation, Commissioning and Operating Manual

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

INSTALLATION MANUAL XM3 Reader

Premier M Plus & Infinity 8

TMS TANK MANAGEMENT SYSTEM

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

LCD and 16-Zone LED Keypads. User s Manual

Transcription:

Fire Detection & Alarm System Repeater Panel (Suitable for TWINFLEX pro control panels from V2.00) Repeater Panel User Manual (TO BE RETAINED BY THE END USER) 26-1194 Issue 1

Fike s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of such contents. Due to the complexity and inherent importance of a life risk type system, training on this equipment is essential and commissioning should only be carried out by competent persons. Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation. E&OE. TWINFLEX, Mulitpoint, Fike and Fike Corporation are registered trademarks of Fike Corporation and its subsidiaries. All other trademarks, trade names or company names referenced herein are the property of their respective owners. Fike equipment is protected by one or more of the following patent numbers: GB2426367, GB2370670, EP1158472, PT1035528T, GB2346758, EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690 2009 Fike Safety Technology Ltd. All rights reserved. Document revised July 2013. 2

Contents Introduction... 4 System Design... 4 Equipment Guarantee... 4 Anti-Static Handling Guidelines... 4 Warning... 4 EMC... 5 The TWINFLEX pro System... 5 Repeater Panel, Remote Display Unit (RDU)... 5 General Operation of Repeater Panel... 6 Control Panel Front... 6 LED Indication... 6 Fire Alarm Controls... 7 System Controls... 7 Access Levels... 7 Access Level 1 (Normal): Controls Enabled LED off... 8 Access Level 2 (user): Controls Enabled LED on... 8 End User Training... 9 Maintenance... 9 Technical Data... 10 Repeater Panel Specification... 10 Fire Alarm System Notice... 11 To Enable the Control Panel Keys... 11 To Manually Operate the Fire Alarm Sounders... 11 Following a Fire Alarm Operation... 11 Following a Fault Condition... 11 Important Notes... 12 Fire Alarm User Notice... 13 Engineers Notes... 14 Technical Support... 15 3

Introduction This Manual is intended as a guide to the engineering and commissioning principles of the TWINFLEX pro Repeater Panel and covers the system hardware information only. Due to the complexity and inherent importance of a system covering a Life Protection Risk, training on this equipment is essential and commissioning should only be carried out by competent and approved persons. For further details of the availability of commissioning services, please contact your supplier. System Design! This document does not cover Fire Alarm system design and a basic understanding is assumed. A knowledge of BS5839: Pt 1: 2002: Fire Detection and Alarm Systems for Buildings is essential. It is strongly recommended that a suitably qualified and competent person is consulted in connection with the Fire Alarm System design and that the entire system is commissioned in accordance with the current national standards and specifications. Equipment Guarantee! The equipment carries no warranty unless the system is installed, commissioned and serviced in accordance with this manual and the relevant standards by a suitably qualified and competent person or organisation Anti-Static Handling Guidelines! Immediately prior to handling any PCBs or other static sensitive devices, it is essential to ensure that a personal connection to earth is made with an anti-static wrist-strap or similar apparatus. Always handle PCBs by their sides and avoid touching any components. PCBs should also be stored in a clean dry place, which is free from vibration, dust and excessive heat and is protected from mechanical damage. Warning! Do not attempt to install this equipment until you have fully read and understood this manual. Failure to do so may result in damage to the equipment and could invalidate the warranty. For technical support please contact your distributor. Do not call the Fike Safety Technology support department unless your distributor has first given their advice and attempted to rectify the issue. 4

Technical support will not be available if the instruction manual has not been read and understood. Please have this instruction manual available whenever you call for technical support. EMC! This equipment when installed is subject to the EMC directive 2004/108/EC. It is also subject to UK Statutory Instrument 2006 No. 3418. To maintain EMC compliance, this system must be installed as defined within this manual. Any deviation from this renders the installer liable for any EMC problems that may occur either to the equipment or to any other equipment affected by the installation. The TWINFLEX pro System The TWINFLEX pro system is an intelligent 2-wire system utilising a conventional type cabling format. The system is classed as Analogue non-addressable due to the architecture used within the design. All field devices including sounders can be connected to the zone via a common 2-core screened cable. The devices communicate with the control panel using the TWINFLEX data protocol. Repeater Panel, Remote Display Unit (RDU) The TWINFLEX pro repeater panel is smaller than the TWINFLEX pro control panel. It does not itself connect to or control detection devices. Instead, it connects to a control panel and reports events which occur on the control panel. It can also perform system controls over the network (i.e. Silence Alarms, Reset, Sound Alarms & Silence Buzzer). A maximum of 8 repeater panels can be connected to a single control panel. 5

General Operation of Repeater Panel Control Panel Front General Indication LEDs Repeater Information Screen Fire Alarm Controls / Controls Enabled Keyswitch System Controls LED Indication The operation of the LED indication on the front of the repeater panel is described below. The LED indication on the repeater panel can also be confirmed by checking the message displayed in the repeater information screen or by accessing the relevant event log from the repeater menu. Description Colour State Reason FIRE Red Continuous The control panel is in the fire state. Display will show the zone of origin. FAULT Yellow Continuous The control panel is in the fault state. Display will show the origin. DISABLED Yellow Continuous This indicates that a disablement action is in place. TEST Yellow Continuous This indicates that a test routine is in place. POWER Green Continuous This indicates that power is being supplied to the panel. 6

Fire Alarm Controls The main Fire Alarm Controls may be enabled by turning the key switch to the controls enabled position to go from access level 1 to access level 2. System Controls The menus may be navigated to by using the UP / DOWN keys to move the required selection to the top and pressing ENTER to select the chosen one. In the example below pressing enter will select current faults. Current Events 2. Current Faults 3. Current Disables Select / /Enter / ESC Press the ESC key to exit to the previous menu. Access Levels The menu system is divided into two access levels in order to restrict access to those who require it. For simple indication, the status of the Controls Enabled light will show the level selected as follows; Access Level Description Controls Enabled LED Key Operation 1 NORM Normal OFF N/A 2 USER User ON YES Access to the Controls requires the operation of the enable controls key, Access Level 2 (User) in order to protect against unauthorised access to the system. 7

Access Level 1 (Normal): Controls Enabled LED off Note: When in the normal mode, the quiescent screen will automatically change to display any fires or faults on the system. Pressing the enter button when in level 1 will show the Current Events Menus and may be scrolled through by pressing the UP and DOWN keys. Press the ESC key to exit the menu. Option 1. Current Fires Option 2. Current Faults Option 3. Current Disables Option 4. Current warnings Events are displayed in text format and may be scrolled through by pressing the UP and DOWN keys. Press the ESC key to exit the menu. Access Level 2 (user): Controls Enabled LED on Pressing the enter button when in level 2 will show the Main Menu and may be scrolled through by pressing the UP and DOWN keys. Press the ESC key to exit the menu. Option 1. Current Events 1. Current Fires 2. Current Faults 3. Current Disables 4. Current warnings Option 2. Test Repeater 1. Test LEDs 2. Test Keypad 3. Test Buzzer 4. Test LCD 5. Test Backlight Option 3. Repeater Details 1. Buzzer 2. Software Version 3. Repeater Panel # 4. Display Baudrate 8

End User Training A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in the building do not know how to operate and respond to the system. It is therefore essential that commissioning includes training for the users of the system and responsible persons. User instructions and a Zone Chart should be left adjacent to the control panel. As access to the system must be controlled by responsible persons, it would be unusual to display the access codes on this notice. These codes must however be available for the responsible persons, so ensure that they know and record them in a secure place. The TWINFLEX pro User Guide should be explained and left with the responsible person on site, for storage in an accessible and known location, in order that the responsible person and the service engineer may keep information records up to date. A single page user instruction sheet is included at the end of this manual. A copy of this should be mounted adjacent to the control panel. Maintenance The repeater panel does not require user maintenance, however periodic functional checks should be carried out by an engineer or responsible persons. 9

Technical Data Repeater Panel Specification Dimensions (mm) 250 x 140 x 85 Weight Construction Cable Entry Cable type Operating voltage Operating current Quiescent @ 24V DC Operating current Max @ 24V DC Communications Total peripheral bus length 650 grams UL94-V0 rated ABS 6 x 20mm knockouts, 4 x double 20mm knockouts 2 core 1.5mm 2 screened fire rated cable Nominal 24V DC (Range 21-32V DC) 16 ma (back light off) 50 ma (controls enabled, back light on) Multi-drop RS-485 500m (max) IP rating 20 Maximum number of repeaters per control panel Operating temperature 8 5 O C to 50 O C 10

Fire Alarm System Notice To Enable the Control Panel Keys You may gain access to the fire alarm controls by inserting the key turning ¼ turn. The Controls Enabled LED should then be illuminated. To disable the control panel keys, turn the key switch off. When disabled, the Controls Enabled LED should then be extinguished. To prevent unauthorised operation, the controls should be kept disabled and the key kept secure under the control of the responsible person. To Manually Operate the Fire Alarm Sounders Enable the controls and then press SOUND ALARMS. To silence the alarm sounders press SILENCE ALARMS. Following a Fire Alarm Operation The red FIRE LED will illuminate. The fire alarms and the internal buzzer will operate as programmed. Take appropriate action as defined by the emergency plan for the premises. To silence the alarm press SILENCE ALARMS, then establish the cause of the alarm and enter the details in the log book. Reset any Manual Call Points which may have been operated, or if a detector has been operated be sure that the cause of the alarm has been removed, before resetting the system by pressing RESET SYSTEM. Following a Fault Condition The fault LED will illuminate. The internal buzzer will sound. To mute the internal buzzer press SILENCE BUZZER. Investigate and rectify the appropriate fault (competent persons). Once the fault has been rectified the fault indication will clear automatically. 11

Important Notes FIRE ALARM COMPANY: ADDRESS: FOR SERVICE CALL: (Working hours) (Call Out) FIRE ALARM COMPANY: ADDRESS: For Service Phone: (During Working Hours) (Out of Working Hours) 12

Fire Alarm User Notice Note The Fire alarm system installed in this building has Alarm Confirmation technology to help eliminate false alarms. Please read and understand the following information in order to make the most use of the system. Operation When the detector within your area activates it will initially only operate the sounders within your own area for a predetermined Confirmation time. At the end of the Confirmation time the system will check the detector again to see if the activation has cleared. If so, the sounders will silence and no further action need be taken. If, however, the detector is still activated, the entire system will go into alarm, operating all the sounders on the system. Action Required If you think that you may have accidentally set off the fire alarms, then check the following: If the fire alarm within your area only is sounding, then check your own area for the cause of the alarm. If this proves to be a false alarm due to dust, cooking fumes, steam, cigarette smoke, etc, then clear the smoke from the area in order to allow the system to reset itself after a few minutes. If this happens then no further action is required. If the fire alarms in the communal areas are also sounding, then follow the building s fire procedures for evacuation. If you discover a genuine fire, then follow the building s fire procedures for evacuation, activating the nearest Fire Alarm manual call point on the way out if the alarms are not already sounding. Do not attempt to put out the fire unless it is safe to do so. Further Information Further information will be located adjacent to the Main Fire Alarm Control Panel, or may be obtained from either the person responsible for building maintenance or from the Fire Alarm Company responsible for maintaining the Fire Alarm System. 13

Engineers Notes 14

Technical Support Contact your distributor for technical support on this product. Do not call the Fike Safety Technology technical support department unless your distributor has first given their advice and attempted to rectify the issue. Technical support will not be available if the instruction manual has not been read and understood. Please have this instruction manual available whenever you call for technical support. Fike Safety Technology Ltd, 31 Springvale Ind Est, Cwmbran, UK. NP44 5BD 13 DoP-505-0010 15