Special Requirements of IEEE C for Generator Circuit Breaker Applications

Similar documents
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

The standards mentioned in this document

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Contents. Description. Product Selection Guide

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Medium Voltage Switchgear

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Alternate Methods to Short Circuit Breaker Coordination

Best Practice Catalog Generator Switchgear

Power Quality Paper #3

Primary and Secondary Electrical Distribution Systems

Medium Voltage technical guide. Basics for MV cubicle design

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Cahier technique no. 193

Short Circuit Current Calculations

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Medium voltage circuit breaker

Arc Terminator Active Arc-Resistant Switchgear

SURGE PROTECTIVE DEVICES

The complete range of consumer switchboards and switchgear

Circulating Current Relay. Type IRXm

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

AMSC s Superconductor Cable Technologies for Electric Utilities

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Step Voltage Regulators

Secondary Unit Substations

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

F05D Meeting on Damped AC Voltage Testing

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Capacitor Bank Switching with Vacuum Circuit Breakers

UFES Active protection for switchgear

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

High-Voltage GIS yesterday - today - tomorrow

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Outdoor vacuum circuit-breakers and reclosers for medium voltage. Switching technology for distribution networks. Answers for energy.

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Transient Recovery Voltages (TRVs) for High-Voltage Circuit Breakers Part 2

The Intelligent AX1 Switchgear for Medium Voltage

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

ABB Fuses Competitive Advantages

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

DS 600. A contact free flux gate based current measurement sensor 600A rms

FIT TIER 2 Application

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

UCI274C - Technical Data Sheet

Unified requirements for systems with voltages above 1 kv up to 15 kv

UCI274H - Technical Data Sheet

Medium voltage indoor circuit breakers ANSI/IEC solutions

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Rack mounted telephone- and leased line modem for industrial applications

How To Choose A Transformer

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

PI734D - Technical Data Sheet

Introduction. Harmonics and IEEE 519 Page 1 of 19

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

PI734B - Technical Data Sheet

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Trip circuit supervision relay. Type RXTCS

38 Series - Relay interface modules A

PM734F - Technical Data Sheet Winding 28

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Engineering Series Ratings: Is It Practical?

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network.

3790 en / d. Alternators LSA Pole. Electrical and mechanical data

Electrical network protection. Protection guide. Guide

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

80 Series - Modular timers 16 A. Features

Insulation resistance

Power/Vac Product Family Application Guide

Electronic overload relay EF65, EF96 and EF146

RM4TG20 three-phase network control relay RM4-T - range V

Joslyn Clark Controls, Inc.

Verification of Short Circuit Test Results of Salient Poles Synchronous Generator

Fundamentals of Power

Transcription:

Special Requirements of IEEE C37.013 for Generator Circuit Breaker Applications November 20, 2009 Schutzvermerk / Copyright-Vermerk Siemens AG 2009

Generator Circuit Breaker Applications What is different about generator circuit breakers? Applicable standards Special considerations Vacuum versus SF6 technology Questions. Folie 2

Generator and Distribution Circuit Breakers Generator circuit breaker Distribution circuit breaker Folie 3

Circuit Breakers for Distribution Requirements Standards: IEEE C37.04 IEEE C37.09 IEEE C37.10 X/R ratio: Time constant of dc decay: Rating structure for HV circuit breakers Tests for HV circuit breakers Application guide for HV circuit breakers. 17 (60 Hz). 45 ms. TRV typical values (15 kv, class S1 cable): Peak voltage (uc) = 25.7 kv Time-to-peak (t3) = 66 µs RRRV 0.39 kv/µs. Duty cycle: Folie 4 O t CO t CO t = 0.3 s for reclosing / 15 s for non-reclosing t = 3 minutes.

Circuit Breakers for Generation Requirements Standards: IEEE C37.013 Generator circuit breaker. X/R ratio: Time constant of dc decay: 50 (60 Hz). 133 ms. TRV typical values (15 kv, 100 MVA machine): Peak voltage (E2) = 1.84 V = 1.84 x 15.0 = 27.6 kv Time-to-peak (T2) = 0.62 V = 0.62 x 15.0 = 9.3 µs RRRV 3.5 kv/µs. Duty cycle: CO 30 min CO. Folie 5

Notes on TRV Representation IEEEC37.04 for distribution circuit breakers expresses TRV in terms harmonized with IEC with peak voltage uc, and time-to-peak t3. IEEE C37.013 still uses old TRV expressions with peak voltage E2 and time-to-peak T2. Peak voltage is not changed, but t3 is approximately 0.88 x T2. The physics are not changed, just the representation. Folie 6

IEEE C37.04-1999 Scope IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers 1. Scope This standard establishes a symmetrical current rating structure and construction requirements for all indoor and outdoor types of ac high-voltage circuit breakers rated above 1000 V. It is only applicable to three-pole circuit breakers used in three-phase systems and single-pole circuit breakers used in single-phase systems. This standard does not cover circuit breakers used at frequencies other than 50 Hz or 60 Hz, or generator circuit breakers that are covered in IEEE Standard C37.013-1997. Folie 7

IEEE C37.013-1997 Scope IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis 1. Scope This standard applies to all ac high-voltage generator circuit breakers rated on a symmetrical current basis that are installed between the generator and the transformer terminals... Note: Since no other national or international standard on generator circuit breakers exists, this standard is used worldwide. Folie 8

IEEE C37.013 the International Standard for Generator Circuit Breakers IEEE C37.013 Revision PAR (Project) PAR approved by IEEE-SA Standards Board, March, 2009 Joint development with IEC SC 17A (HV Switchgear and Controlgear) IEEE WG chair is convenor (WG chair) of IEC working group. IEC has no standard for a generator circuit breaker. The IEEE and IEC intent has been that IEEE C37.013 would be the global standard. IEC SC 17A WG 52 WG scope: Joint IEC/IEEE revision of IEEE C37.013: IEEE Standard for AC High- Voltage Generator Circuit Breakers Rated on a Symmetrical Current Basis Folie 9

X/R Ratio Determines %dc Component X/R = 17, τ = 45 ms X/R = 50, τ = 133 ms %dc vs Contact Part for X/R = 17 and X/R = 50 120.0 100.0 %dc Component 80.0 60.0 40.0 20.0 0.0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Folie 10 Contact Part time (ms) X/R = 17 X/R = 50

X/R Ratio Effect on Asymmetrical Interrupting Current (Isc = 1.00) 3.00 2.50 2.00 1.50 1.00 0.50 0.00-0.50-1.00 Instantaneous (total) current dc component S-factor (C37.04-1979) dc component (in decimal form) (multiply by 100 for %dc component) (C37.04-1999) Folie 11-1.50-2.00 Symmetrical current (ac component) 0 180 360 540 720 900 1080 1260 1440 1620 1800 1980 2160 2340 2520 2700 2880 3060 3240 3420 3600 Time (in degrees)

X/R Ratio Effect on Asymmetrical Interrupting S = I I total symmetrical = 1+ 2(% dc /100) S factor (from IEEE C37.04-1979) Ratio of rms asymmetrical current to rms symmetrical current Assume contact part time of 55 ms, and 50 ka symmetrical current X/R = 17 %dc = 29.5 S = 1.084 I = 54.2 ka X/R = 50 %dc = 66.1 S = 1.369 I = 68.5 ka over 26% higher Folie 12

Short-Circuit Currents Consider system shown: Transformer 1,000 A full load (self-cooled) impedance = 10% Generator 1,000 A full load Xd (subtransient reactance) = 20% For fault at F2, circuit breaker sees transformer fault current, roughly 1,000 A / 0.10 = 10 ka For fault at F1, circuit breaker sees generator fault current, roughly 1,000 A / 0.20 = 5 ka G F1 F2 Note: Fault current for generator source fault is only about 50% of fault current for system (transformer) source fault Folie 13

Generator Circuit Breaker Ratings Characteristic Maximum voltage Dielectric 60 Hz / BIL Short-circuit current Transformer source Generator source %dc component Delayed current zero* TRV parameters Peak voltage (1.84 V) RRRV transformer source RRRV generator source * Higher values may be available Folie 14 Unit kv kv/kv ka ka % ms kv kv/µs kv/µs Drawout (Metal-Clad) 15.0 38 / 95 40 / 63 20 / 31.5 73 / 61 40 / 30 27.6 3.5 / 4.5 1.6 / 1.8 Fixed- Mounted 17.5 50 / 110 50 / 63 / 72 25 / 31.5 / 36 75 / 65 / 65 30 / 30 / 30 32.2 4.5 / 4.5 / 4.5 1.4 / 1.8 / 1.8

Generator Circuit Breakers Folie 15

Generator Circuit Breakers Folie 16

Out-of-Phase Switching Circuit Breakers for Standard Applications: IEEE C37.04 (clause 5.12): Out-of-phase switching is optional, not required for general purpose circuit breakers If a rating is assigned, the preferred rating is 25% of the rated symmetrical interrupting rating, with recovery voltage of (250% rated voltage / 1.732). Therefore, out-of-phase ratings are not typically assigned to general purpose circuit breakers rated per IEEE C37.04 and tested to IEEE C37.09. Folie 17

Out-of-Phase Switching Circuit Breakers for Generator Switching Applications: IEEE C37.013 (clause 6.2.9): Out-of-phase switching is optional, not required for generator circuit breakers If a rating is assigned, the assigned rating is shall be 50% of the rated symmetrical interrupting rating (transformer or system source). Out-of-phase switching recovery voltage values are based on a maximum out-of-phase condition of 90 degrees between generator and system. This is reasonable as more extreme angles would result in damage to the machine. The likelihood of out-of-phase switching is influenced by generator inertia, i.e., low-inertia machines are more likely to be subject to out-of-phase switching conditions. Generator circuit breakers should have an assigned out-of-phase switching rating. Folie 18

Other Differences Reclosing: Reclosing duty not required for generator circuit breakers. Short-time current duration: Normal circuit breakers 3 seconds (metal-clad switchgear = 2 seconds) Generator circuit breakers 1.0 second (typically test to 3 seconds). Closing & latching rating: Normal circuit breakers Peak current 260% of symmetrical short-circuit (60 Hz) With X/R = 17, real peak is 259.3% Generator circuit breakers Peak current 274% of symmetrical short-circuit (60 Hz) With X/R = 50, real peak is 274.2%. Folie 19

Delayed Current Zero Example C37.013 0.500 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 0.000-0.500-1.000 Current (unitized) -1.500-2.000-2.500-3.000-3.500-4.000 Time (ms) Folie 20

Delayed Zero Test Example 20.6 ms 30.0 ms 40.1 ms 57.7 ms Folie 21

Generator Circuit Breaker Technologies Vacuum Well-suited to smaller units (up to 6,000 A or so) Most economic for small units Derived from proven distribution unit operators and interrupters High experience-base Very low arc voltage (20-50 V) Little affect on X/R ratio Lower arc voltage = less arc energy = lower contact erosion SF 6 Only option for very large units VERY expensive Unlike distribution products Lower experience-base SF 6 low arc voltage (several 100 V) Somewhat higher impact on X/R ratio Higher arc voltage = higher arc energy = greater contact erosion Extremely rapid recovery of dielectric strength between contacts after interruption good for extreme TRV levels Less able to cope with high TRV levels Folie 22