StruxureWare Power Monitoring 7.0. Side By Side Upgrade Guide For Distributed Systems



Similar documents
StruxureWare Power Monitoring In-Place Upgrade Guide SQL Server Standard Edition Only

Administration guide. Host software WinCCU Installation. Complete gas volume and energy data management

StruxureWare Power Monitoring 7.0.1

ProSystem fx Document

SQL 2014 Configuration Guide

PowerLogic ION Enterprise 6.0

Moving the Web Security Log Database

Moving the TRITON Reporting Databases

InformationNOW Upgrading to Microsoft SQL Server 2008

Migrating MSDE to Microsoft SQL 2008 R2 Express

Install SQL Server 2014 Express Edition

QUANTIFY INSTALLATION GUIDE

UNICORN 6.4. Administration and Technical Manual

Using SQL Reporting Services with Amicus

Installation Instruction STATISTICA Enterprise Small Business

UNICORN 7.0. Administration and Technical Manual

E-Notebook SQL13.0 Desktop Migration and Upgrade Guide

Installing Autodesk Vault Server 2012 on Small Business Server 2008

STATISTICA VERSION 12 STATISTICA ENTERPRISE SMALL BUSINESS INSTALLATION INSTRUCTIONS

STATISTICA VERSION 9 STATISTICA ENTERPRISE INSTALLATION INSTRUCTIONS FOR USE WITH TERMINAL SERVER

SonicWALL CDP 5.0 Microsoft Exchange InfoStore Backup and Restore

ilaw Installation Procedure

Maintaining the Content Server

StruxureWare Power Monitoring 7.0.1

MIGRATING TO AVALANCHE 5.0 WITH MS SQL SERVER

Installing Windows Server Update Services (WSUS) on Windows Server 2012 R2 Essentials

Event Notification Module TM

NovaBACKUP xsp Version 15.0 Upgrade Guide

How To Upgrade Your Microsoft SQL Server for Accounting CS Version

STATISTICA VERSION 10 STATISTICA ENTERPRISE SERVER INSTALLATION INSTRUCTIONS

Abila MIP. Installation User's Guide

Migrating Mobile Security for Enterprise (TMMS) 8.0 to version 9.0

IMPORTANT: The person who installs and sets up the PCS Axis database on the central database server

Upgrade Guide BES12. Version 12.1

Portions of this product were created using LEADTOOLS LEAD Technologies, Inc. ALL RIGHTS RESERVED.

ACTi NVR Config Converter User s Manual. Version /06/07

Abila MIP. Installation Guide

Installing GFI MailArchiver

NETWRIX FILE SERVER CHANGE REPORTER

GUARD1 PLUS SE Administrator's Manual

StruxureWare Power Monitoring Expert 7.2

Juris Installation / Upgrade Guide

Crystal Reports Installation Guide

Set Up Setup with Microsoft Outlook 2007 using POP3

Metalogix SharePoint Backup. Advanced Installation Guide. Publication Date: August 24, 2015

Synchronizer Installation

Migrating Trend Micro Mobile Security for Enterprise (TMMS) 8.0 to TMMS 9.0

Installation Manual (MSI Version)

Richmond SupportDesk Web Reports Module For Richmond SupportDesk v6.72. User Guide

Upgrade Guide. CA Application Delivery Analysis 10.1

E-Notebook SQL 12.0 Desktop Database Migration and Upgrade Guide. E-Notebook SQL 12.0 Desktop Database Migration and Upgrade Guide

StruxureWare Power Monitoring Expert 7.2

StruxureWare Power Monitoring Expert Data Center Edition

Features - Microsoft Data Protection Manager

2014 Electrical Server Installation Guide

Team Foundation Server 2010, Visual Studio Ultimate 2010, Team Build 2010, & Lab Management Beta 2 Installation Guide

Migrating Trend Micro Mobile Security for Enterprise (TMMS) 8.0 to TMMS 9.0 Patch 1

Installing GFI MailArchiver

Instructions for update installation of ElsaWin 5.00

4cast Client Specification and Installation

WhatsUp Gold v16.2 Database Migration and Management Guide

RFID Tracking System Installation

Microsoft Corporation. Project Server 2010 Installation Guide

SQL Server 2008 R2 Express Edition Installation Guide

StruxureWare Power Monitoring Expert - Data Center Edition

Snow Inventory. Installing and Evaluating

Secret Server Installation Windows 8 / 8.1 and Windows Server 2012 / R2

WhatsUp Gold v16.1 Database Migration and Management Guide Learn how to migrate a WhatsUp Gold database from Microsoft SQL Server 2008 R2 Express

1. Overview... 2 Documentation... 2 Licensing... 2 Operating system considerations... 2

iw Document Manager Cabinet Converter User s Guide

How do I EVOLVE to Best Practice Software?

KEYWORDS InteractX, database, SQL Server, SQL Server Express, backup, maintenance.

To install Multifront you need to have familiarity with Internet Information Services (IIS), Microsoft.NET Framework and SQL Server 2008.

Exchange Mailbox Protection

Table of Contents. CHAPTER 1 About This Guide CHAPTER 2 Introduction CHAPTER 3 Database Backup and Restoration... 15

Sophos Disk Encryption License migration guide. Product version: 5.61 Document date: June 2012

WhatsUp Gold v16.1 Installation and Configuration Guide

Installation Instruction STATISTICA Enterprise Server

System Protection for Hyper-V Whitepaper

Team Foundation Server 2012 Installation Guide

Installing Exchange and Extending the Active Directory Schema for Cisco Unity 8.x

NETWRIX WINDOWS SERVER CHANGE REPORTER

DigitalPersona Pro Server for Active Directory v4.x Quick Start Installation Guide

SAS 9.3 Foundation for Microsoft Windows

BackupAssist v6 quickstart guide

WhatsUp Gold v16.0 Database Migration and Management Guide Learn how to migrate a WhatsUp Gold database from Microsoft SQL Server 2005 Express

Power Monitoring Expert 7.2

Snapshot Reports for 800xA User Guide

STATISTICA VERSION 11 CONCURRENT NETWORK LICENSE WITH BORROWING INSTALLATION INSTRUCTIONS

StruxureWare Power Monitoring Expert 7.2

Portions of this product were created using LEADTOOLS LEAD Technologies, Inc. ALL RIGHTS RESERVED.

How to protect, restore and recover SQL 2005 and SQL 2008 Databases

SQL Server Protection

SonicWALL CDP Local Archiving

Reference and Troubleshooting: FTP, IIS, and Firewall Information

Fairfield University Using Xythos for File Sharing

VERITAS Backup Exec 9.1 for Windows Servers Quick Installation Guide

Snow Active Directory Discovery

System Protection for Hyper-V User Guide

SharePoint Server for Business Intelligence

Transcription:

StruxureWare Power Monitoring 7.0 Side By Side Upgrade Guide For Distributed Systems

Document Overview Author Power Software, Schneider Electric Last Revised 21 st March 2013 Document Purpose Provides guidance for performing a side by side upgrade from ION- Enterprise 6.0 SP1 to StruxureWare Power Monitoring 7.0.1 in a distributed system (Database Server + Application Server) Note(s) None Recommendations * * * Ensure you have enough hard drive space available on your database server Plan an ION-Enterprise system downtime window Consider archiving data (with Trim) to reduce system downtime Overview An in-place upgrade is not available where the combination of operating system and SQL Server Edition is not compatible with StruxureWare Power Monitoring 7.0.1. A Side By Side Upgrade performs a backup of the old system's data and restores it on an operating system hosting StruxureWare Power Monitoring 7.0.1 with a supported combination of Windows operating system and SQL Server edition. To ensure you require the Side By Side upgrade process, consult the upgrade flow chart in StruxureWare Power Monitoring 7.0.1: Determine Your Upgrade Type (RESL#207578). Side by Side Upgrade for a Distributed System A Distributed System consists of a database server and an application server. The Application Server hosts the StruxureWare Power Monitoring configuration files and the services that are required for the system to function. The Database Server hosts Microsoft Reporting Services, and the SQL Server instance used for the StruxureWare Power Monitoring databases. Note that it is possible to install Microsoft Reporting Services on the Application Server, but if this is done, an additional SQL Server license must be purchased. This document assumes that Reporting Services is installed on the Database Server.

The Side by Side upgrade case assumes that the existing ION Enterprise 6.0 SP1 system will not be directly upgraded on the existing server, but rather the configuration of the existing system will be backed up and packaged using the SBS Upgrade Utility tool, found on the StruxureWare Power Monitoring 7.0.1 (SPM701) DVD, and then restored, using this same tool, into a newly installed SPM7 system on a new server. In the distributed case, the SBS tool will need to be run both on the database server and the application server. Side By Side Standalone upgrade considerations Read StruxureWare Power Monitoring 7.0.1: Database Upgrade FAQ (RESL#206536) for more information on how much additional hard disk space is required and expected system downtime due to the software upgrade. After the ION Enterprise 6.0 SP1 files (including the databases) have been backed up, and then restored into the new SPM701 system, the database will be upgraded. The upgrade of the ION_Data database can be a lengthy process, making the new SPM701 system unusable until the database upgrade has completed. Some Side By Side Tool Considerations Be sure to use the most recent version of this tool. There are some known issues: Required drive space calculation will be wrong if the database is not on same drive as the installed files You can backup to a network drive or external device, but you will have to copy the backup files locally to do the Restore. Custom hierarchies created in ION E 6.0 SP1 will not be propagated to SPM7.0.1 Customer-specific settings such as running the Default Website on a port other than 80, using SSL will not be propagated. You will have to manually edit the CFG_ItemValue table in ION_Network. The details are discussed later in this document. Preparing your SPM 7.0.1 Server Install SQL Server 2008 R2 on your SPM 7.0.1 Database Server. Be sure to include Reporting Services as per the SPM 7.0.1 Installation Guide, but do not let the SQL Server installer do the Reporting Services configuration. The SPM701 installer will do this for you.

The Installation Guide is located on the SPM 7.0.1 DVD in the documentation folder. Then Install SPM 7.0.1 on the new Application server, choosing the SQL Server instance on the database server installed in the previous step. You will have to manually type in the Report Server instance during the installation process. Once the SPM 7.0.1 system has been set up be sure to verify the following to be sure the install was successful, particularly Reporting Services and Web Reporter: Log in to Web Applications Go to the Reports tab and run a System Configuration Report Backing up ION Enterprise 6.0 SP1 files from the existing system. IMPORTANT: Be sure to use the version of the Side By Side Utility that is on the most recent version of the SPM 7.0.1 DVD. This tool will need to be run on both the database server and the application server. On the database server: Open the SPM 7.0.1 DVD in an Explorer window and find setup.exe inside the SBS Upgrade Utility folder:

Double-click on MainSetup to launch the SBS Upgrade Utility. Proceed though the screens until you come to the Setup Type screen and choose Backup Database Server from the drop down list. The utility will do a number of checks to ensure that a valid backup package can be created. When you get to the Ready to Configure screen, click on the Backup button to proceed. This will create a package the will include the databases..

If you have any Report Subscriptions configured in your ION Enterprise 6.0.1 system, when the Backup Database Server process finishes, restart the SBS tool and this time choose Export Subscriptions from the dropdown list. An xml file called IONSubscriptionData will be created. This file can be put in the ION_Backups folder along with the database When you are finished, the set of files inside the ION_Backups directory should look like this: Copy the ION_Backups directory and its files onto the SPM 7.0.1 database server. On the Application Server: Once again, launch the SBS tool on the Application Server from the SPM 7.0.1 DVD, this time choosing Backup Primary Server :

This will create a package the will include all user-created files and saved reports. The set of files inside the ION_Backups directory should something like this: Copy the ION_Backups directory and its files to your SPM 7.0.1 Application Server. Importing the ION Enterprise 6.0 SP1 files into your SPM7 system Before proceeding, shut down all ION and =S= services on the Application server in preparation for importing the IONE 6.0.1 files On the Database Server: Take note of the location of the ION_Backups directory that was copied to some location local to your SPM 7.0.1 database server. It is assumed that SPM 7.0.1 is installed and functional.

Open the SBS Upgrade Utility folder on the DVD and double-click on MainSetup to launch the Utility. Advance through the screens and in the Setup Type screen choose Restore Database Server You will need to browse to the location where the 6.0.1 backup files were copied. At this point the utility will look for installed SQL Server instances. Choose the one that is hosting SPM and click Next:

There will be a system verification check Check disk space could there be a problem if ION_Backups and the dbs are on different drives? To import your 6.0.1 files, click on the Restore button:

If the ION_Data database is large, the Restore System portion could take a significant amount of time since the database will need to be upgraded. When the process is finished, click the Close button. This completes the database restore portion To import your saved report subscriptions into your now SPM7 system, restart the SBS tool by doubleclicking on MainSetup and this time choose Import Report Subscriptions. Once again, you will be prompted to browse the location of your ION_Backups directory, and then to choose a SQL Server instance. A system check will be performed. Then click on the Import button. When the subscriptions have been imported, you will see this dialog:

If you have subscriptions configured to save to a file share, you will likely have to adjust the fileshare path once the Restore has been done on the Primary server. See the Manual Steps section at the end of this document for instructions on how to do this. On the Application Server: Open the SBS Upgrade Utility folder on the SPM 7.0.1 DVD and double-click on MainSetup to start the tool. Choose Restore Primary Server from the dropdown list.

You will be asked to browse to the location of your ION_Backups folder, and then asked to select a SQL Server instance. Choose the one from your database server. A system check will be performed. Once it is complete, click on the Next button to advance to the next screen, and then click on the Restore button.

Once the Primary server restore has finished, exit the tool by clicking on the Close button. Once this is done, there are still a few manual steps required to complete the side by side upgrade process. Manual Steps: 1. Use SQL Server Management Studio on the database server to check the settings in the CFG_ItemValue in ION_Network. Verify that the ReportServer instance name is correct. The SBS tool may not append the instance name to ReportServer. Assuming ION instance, it needs to be ReportServer_ION, rather than ReportServer in three places, as in the screen capture below:

2. Start the three Schneider Electric services on the Application Server (the SBS tool will have started the ION services) 3. If you have Report Subscriptions that have been configured to save to a file share, you will likely have to modify the file share path due to the server migration. To do this a. Log in to Web Applications b. Choose the Reports tab c. Click on the Manage icon on the right hand side of the screen d. When the dialog appears, choose Subscribe, select the report for which you need to change the file share path and click on Modify

e. Make the required changes and save 4. It will be necessary to change the old server name with new server name in any custom Vista diagrams where the server name is referenced. This will affect diagrams with Data Log Viewers, and also any diagrams referencing VIPs. Post-installation tasks Perform the following procedures once the upgrade is complete and your system is functioning correctly StruxureWare Power Monitoring. Check ION Enterprise Services Open the Windows Services dialog and ensure that all of the necessary ION Enterprise services are started. The services run under the Local System account, by default. You can change the Log On As attribute of a service by specifying the account and password. Use the Log On tab on the service properties dialog to do this. The Log On As account must have read/write permissions in the StruxureWare Power Monitoring network. See the ION Enterprise Services topic in the online StruxureWare Power Monitoring Help for more information. Create local user groups Create the following Microsoft Windows local user groups on the StruxureWare Power Monitoring primary server and grant access as follows: Group Name Access to..\ion Enterprise\system 1 Access to..\ion Enterprise\Config 1

ION Enterprise_Administrators Full Control Full Control ION Enterprise_Users Read Change 1 This is the path under Program Files\Schneider Electric (assuming default installation path) Note: the LocalSystem account must belong to the ION Enterprise Administrators group; the LocalSystem account requires read/write access to the system and config directories in order to run the ION Enterprise services. Review Database Manager Database Manager has preconfigured schedules for performing archives (disabled by default), backups, and trims on your ION Enterprise databases. Review these schedules and make any modifications that you require. You can also configure alarming to notify you when you are reaching your database or hard disk space limits. Refer to the Database Manager section in the online StruxureWare Power Monitoring Help for more information. Security Considerations This section outlines specific security considerations after the StruxureWare Power Monitoring installation. Default passwords for SQL Server The default user identification and password for some of the database accounts need to be preserved for the proper operation of ION Enterprise. Contact Technical Support for details before you attempt to modify user IDs and passwords. NTFS and Share permissions on the ION Enterprise directory All share permissions are automatically set to Read permissions for the Everyone group; this includes the StruxureWare Power Monitoring share (ION-Ent). Change the ION-Ent share permission to Read/Write for users of Engineering Clients computers who need to modify files, such as Vista diagrams. StruxureWare Power Monitoring software security A user account with an access level of Supervisor is created by default when StruxureWare Power Monitoring is first installed. The account name is supervisor and the default password is 0 (zero). This account has the highest level with unrestricted access. The administrator for the StruxureWare Power Monitoring system can use User Manager to change the password for the supervisor account before deploying the StruxureWare Power Monitoring system to users. Refer to the User Manager section under Management Console Tools in StruxureWare Power Monitoring Help for more information. Run the ION Power Quality Aggregation Service In order to generate Power Quality reports in the Reports application on power quality data collected prior to the upgrade, you need to manually run the ION Power Quality Aggregation Service on the pre-

existing data. For instructions on running this service manually, see Running the ION Power Quality Aggregation Service Manually topic in the Reports section of the Web Applications online help. Appendix A: Upgrading a Standalone ION Enterprise 6.0.1 System using SQL Server Express to a Distributed SPM 7.0.1 System Introduction This upgrade scenario is very similar to the one described in detail above, so this appendix will focus on the differences, without going into detail on each step in the process. You will need to have SPM7.0.1 installed and operational on your two new servers the database server and the application server. On the Standalone ION Enterprise 6.0.1 system: 1. Start by launching the SBS Upgrade utility on the Standalone ION E 6.0.1 system 2. Choose Backup Standalone Server from the dropdown list. 3. Copy the ION_Backups folder created by the SBS utility to both Application and Database server. Restoring your ION Enterprise 6.0.1 files into your new SPM 7.0.1 system: In preparation for the restore, shut down all ION and Schneider Electric services on the Application server. On Database Server: 1. Launch the SBS Upgrade utility. 2. Choose Restore Database Server, advance through the screens and click on the Restore button. This will restore and upgrade the databases. If ION_Data is large, the upgrade could take a long time. On the Application Server: 1. Launch the SBS Upgrade utility 2. Choose Restore Primary Server 3. Choose the correct SQL Server instance 4. Click Restore Manual Steps: 5. Use SQL Server Management Studio on the database server to check the settings in the CFG_ItemValue in ION_Network. Verify that the ReportServer instance name is correct. The SBS tool may not append the instance name to ReportServer. Assuming ION instance, it needs to be ReportServer_ION, rather than ReportServer in three places, as in the screen capture below:

6. Start the three Schneider Electric services on the Application Server (the SBS tool will have started the ION services) 7. If you have Report Subscriptions that have been configured to save to a file share, you will likely have to modify the file share path due to the server migration. To do this a. Log in to Web Applications b. Choose the Reports tab c. Click on the Manage icon on the right hand side of the screen f. When the dialog appears, choose Subscribe, select the report for which you need to change the file share path and click on Modify

g. Make the required changes and save 8. It will be necessary to change the old server name with new server name in any custom Vista diagrams where the server name is referenced. This will affect diagrams with Data Log Viewers, and also any diagrams referencing VIPs. See the section above on Post-Installation Checks to complete the migration process.