1. INSTALLATION 1.1 PANEL MOUNTING 1.2 CONNECTION AND WIRING 2. FRONT PANEL DESCRIPTION CONFIGURATION AND PARAMETERS SETTING...

Similar documents
Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016)

User Manual Auto Tuning PID Temperature Controller

+ A B V B NO NC V COM PV PV

SR1, SR3 Series Digital Controller Instruction Manual

HONEYWELL DC 1010 / / 1040 DIGITAL CONTROLLER PRODUCT MANUAL /02

Dyeing Programmer DP - 01

4-Channel Thermometer / Datalogger

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

Duct Humidity Transmitter

Operational Overview and Controls Guide

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

ACS-30-EU-EMDR-10-MOD

#1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(82-32) FAX:(82-32)

The E5CN provides communications or event input functionality when mounted with one of the following Option Boards.

Contents. Document information

*.ppt 11/2/ :48 PM 1

TC-9102 Series Surface Mount Temperature Controllers

TC 1818a. Operating Guide. Control Module SWM-015.5

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

DC1000 Series General Purpose UNIVERSAL DIGITAL CONTROLLERS

J TB/TW Temperature limiter, temperature monitor

INITIAL SETTING MANUAL

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Delta Temperature Controller User Manual

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta Gdańsk POLAND tel

PD 100A. Printing data system

User Manual for CH-PFC76810

Nokeval. User's Manual Models 301 / 302 / 305

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

DIGITRONIK Digital Indicating Controller SDC10. User s Manual

PCS0100en Persy Control Services B.V. Netherlands

Transmitter Interface Program

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

SYL-2342, SYL-2352 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 4.6 RTD R 4

User s Manual Before using the inverter, you need to read and save the safety instructions.

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

Single Channel Loop Detector

NC-12 Modbus Application

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

AUTODIALLER / QUICKDIALLER - SA132

User Manual. Humidity-Temperature Chart Recorder. Model RH520

Temperature & Humidity SMS Alert Controller

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

HERZ-Thermal Actuators

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

Operating Instructions. Single Loop Controller EC48 & EC96

ZC-24DO CANopen I/O Module: 24 Digital Outputs

Telefon (+45) Telefax (+45) Installation and operating manual

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

User's Guide. Integrating Sound Level Datalogger. Model Introduction

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Short information Parameters are programmed via front-side membrane keypad

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

AutoRanging Digital MultiMeter

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

INSTALLATION INSTRUCTIONS

PUSH BUTTON START INSTALLATION MANUAL

Fire Alarm Control Panel. Family. Operating Manual

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

Troubleshooting and Diagnostics

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Installation and User Guide

Automation System TROVIS 5100 Ventilation Controller TROVIS 5177

Technical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34)

Energy Management Power Analyzer Type WM14-96 Basic Version

IS3016A Passive Infrared Motion Sensor with Anti-Mask - Installation Instructions

IO-RM3 3-Stage Relay Module

Mobile Data Power Model: MDP-25

MP-4000 Alarm List (Software version or later)

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

FDC4100/7100/8100/9100 Auto-Tune Fuzzy / PID Process / Temperature Controller. User's Manual BTC-4100/7100/8100/9100 Process / Temperature Controller

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Quick Connect. quick - simple - efficient.

WD-AMX Water Detection Controllers

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

FAQ s on Siemens Magmeters

Multi-Range Programmable DC Power Supplies 9115 Series

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

DC Electronic Loads 8500 series

CPA PC-Programmable Current/Voltage and RTD/Thermocouple Limit Alarm Trips

Auto Dialer. Manual E-921APQ E-921GPQ

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Transcription:

VT20 SERIES FUZZY ENHANCED PID CONTROLLERS INSTRUCTION MANUAL (VERSION 3.0) 1. INSTALLATION...1 1.1 PANEL MOUNTING... 1 1.2 CONNECTION AND WIRING... 1 2. FRONT PANEL DESCRIPTION...2 2.1 DISPLAY AND INDICATOR... 2 2.2 KEY FUNCTION... 3 3. CONFIGURATION AND PARAMETERS SETTING...3 3.1 USER LEVEL... 3 3.2 PID LEVEL... 3 3.3 OPTION LEVEL... 4 4. OPERATION...5 4.1 AUTO TUNE... 5 4.2 TUNING THE CONTROLLER MANUALLY... 5 4.3 MANUAL CONTROL... 5 5. ALARM...6 5.1 ALARM FUNCTION... 6 1. INSTALLATION 1.1 PANEL MOUNTING a. Prepare a panel cutout. The cutout required is as show in table 1-1. Table 1-1 Panel Cutout Model High Width VT4820 45mm+0.5 45mm+0.5 VT4920 45mm+0.5 92mm+0.5 VT7220 68mm+0.5 68mm+0.5 VT9620 92mm+0.5 92mm+0.5 b. For VT4820, remove plastic panel clamp from controller. Slide the controller into the cutout. Replace panel clamp and press it firmly against the panel. Gently tighten the screws in the clamp till the controller front panel is fitted snugly in the cutout. c. For other models, slide the controller into the cutout. Install the mounting clamp back. Gently tighten the screws in the clamp still the controller front panel is fitted snugly in the cutout. 1.2 CONNECTION AND WIRING BEFORE WIRING, VERIFY THE LABLE FOR CORRECT MODEL AND OPTIONS. 5.2 ALARM MODE... 6 6. ERROR MESSAGE AND TROUBLESHOOTING...7 7. SPECIFICATION...8 FHD177V3-VT20 Series Installation Manual 1

4 ~ 20 ma. Maximum load 600 ohms 1 ~ 50mV, 1 ~ 5V, 0 ~ 10V..( Resistive 600 ohms Min) 0 / 24 VDC pulsed voltage to drive SSR.. Relay contact. 10A/240VAC. 2. FRONT PANEL DESCRIPTION 2.1 DISPLAY AND INDICATOR PV (Process Value) Display Displays the actual measurement of the input sensor. Displays the parameter index code. Displays the error message. SV (Set Value) Display Displays the set value. Displays the parameter data. Displays the output percentage value. Status indicators a. Power input The controller is supplied to operate on 90 ~ 264 VAC 50/60 Hz. power should be connected via a fuse with rate not exceeding 2 Amps. b. Sensor input Do not run sensor cable adjacent to power carrying conductors. The correct type of thermocouple extension lead wire or compensating cable must be used. Ensuring the polarity of thermocouple/linear input is correct. c. Control output Different output module might be installed in the controller. Be sure that correct output device is select to meet your application. Available output modules are: a. A1 status LED indicator (Alarm 1 relay status LED) This LED is lit in red when the alarm 1 relay is active. b. A2 status LED indicator (Alarm 2 relay status LED) This LED is lit in red when the alarm 2 relay is active c. C1 status LED indicator (Control output 1 status LED) Illuminates in green when the control output 1 is active. d. C2 status LED indicator (Control output 2 status LED) Illuminates in green when the control output 2 is active. e. AT status indicator When the controller is auto tuning. The rightmost decimal on the PV display will blink. When the tuning process is FHD177V3-VT20 Series Installation Manual 2

finished or stopped, the decimal will cease blinking and disappear. Auto tuning may take from several minutes to several hours depending upon the process in question. f. MA status indicator When the manual control mode is selected. The rightmost decimal on SV display will blink. 2.2 KEY FUNCTION SET key Press once to access the next programmable parameter. SHIFT key Shift digits to be adjusted by up/down key. DOWN key Press to decrease the set point or parameter value. UP key Press to increase the set point or parameter value. removed and the display sequence is configurable to simplify the operation. : Set point value of control. : Alarm 1 set point value. : Alarm 2 set point value. : Auto tune. Used to set Pb,ti,td parameters value automatically by auto tuning. : Auto tuning is disable. : Standard type auto tuning. PV is compared with SV during auto tuning. : Low PV type auto tuning. PV is compared with SV-10%FS during auto tuning. : Hand (manual) control. Used to enable or disable the manual mode. : Disable the manual mode : Enable the manual mode. : Output percentage. Adjustable when Hand is set to YES. 3.2 PID LEVEL Press the SET and UP keys once to return the normal operation. LEVEL key Press the SET and SHIFT keys simultaneously for 5 seconds to select programming level, then press SET key to enter the level. 3. CONFIGURATION AND PARAMETERS SETTING All programmable parameters are user friendly and clearly structured as three levels. To change level from one to the others, please press keys for at least 5 seconds to access level selection. Use UP/DOWN key to select programming level. 1. Pid level. ( ) 2. Option level. ( ) 3.1 USER LEVEL : Proportional band value. Setting range from 0.0 to 300.0 % of controller s Span. set to 0.0 for on/off control action. This value is automatically calculated by activating the auto tune. If desired, the user can later adjust the value to better suit the application. : Integral (reset) time. This value is automatically calculated by activating the Auto tune function. If desired, the user can later adjust this parameter to better suit the application. When PB=0.0, this parameter will be not available. When set to zero, Pb & td 0 for PD control. : Derivative (rate) time. This value is automatically calculated by activating the Auto tune function. If desired, the user can later adjust this parameter to better suit the application. When PB=0.0, this parameter will be not available. When set to zero, Pb & td 0 for PI control. : Cycle time of control output 1. Setting range is from 0 to 100 seconds. Set to 1 for pulsed voltage output, set to 0 for 4 ~ 20 ma analog The following parameters are listed in a default output and set to 15 or longer possible to help sequence. However any unused parameter can be FHD177V3-VT20 Series Installation Manual 3

prolong the life of relay. The longer the time set. The less responsive the controller will be to process changes. : Proportional band value for secondary control output (cooling). Set 0.0 for ON/OFF. : Integral time for secondary control output. When PB=0.0, this parameter will be not available. When set to zero, Pb & td 0 for PD control. : Derivative time for secondary control output. When Pb=0.0, this parameter will be not available. When set to zero, Pb & ti 0 for PI control. : Cycle time of secondary control output. / : Hysteresis for on/off control on output 1and output 2. Users can create a dead band region from 0.0 to 200.0. / : Hysteresis for alarm 1 and alarm 2.the setting range is 0.0 to 200.0. : Dead band value. Setting range is from -100.0 to 100.0. This defines the area in which output 1 and output 2 are both active (negative value) or the area in which output 1 and output 2 are both inactive (positive value). : Set point offset. Setting range is from -100.0 to 100.0 or 1000 to 1000. This value will be added to SV to perform control. It mainly used to eliminate offset error during P control.set point offset. : Process value offset. Setting range form -100.0 to 200.0 or 1000 to 2000 permits the user to offset the PV indication from the actual PV. : Parameter lock. This security feature locks out selected levels or single parameters prohibiting tampering and inadvertent programming changes. Table 3-1 Parameter lock selection Setting Description 0000 All parameters are locked out. 0001 Only SP is adjustable. 0010 Only USER level is adjustable 0011 USER and PID level are adjustable. 0100 USER, PID, OPT1 levels are adjustable. 0101 ~ All parameters in all levels are opened. 0111 1000=0000, 1001=0001, 1010=0010, 1000 ~ 1011=0011, 1100=0100 but Output2 1111 is opened. 3.3 OPTION LEVEL : Sensor input selection. Table 3-2 Input and range TYPE DISPLAY RANGE J -50 ~1000-58 ~ 1832 K -50 ~1370-58 ~2498 T -270 ~400-454 ~752 E -50 ~1000-58 ~1832 B 0 ~1800 32 ~3272 R -50 ~1750-58 ~3182 S -50 ~1750-58 ~3182 N -50 ~1300-58 ~2372 C -50 ~1800-58 ~3272 DPT -200 ~850-328 ~1652 JPT -200 ~600-328 ~1112 LINEAR -1999~9999 : Unit of measure selection. : Degrees C. : Degrees F. : Engineering unit. Only for linear input. : Decimal point selection. : No decimal point. : 0.1 resolution. : 0.01 resolution. Only for linear input. : 0.001 resolution. Only for linear input. After change decimal point, please reconfirm the parameter. : Output 1 control action. : Reverse action. Used for heating control. : Direct action. Used for cooling control. : Low limit of span or range. Set the low limit lower than the lowest expected SV and PV display. : High limit of span or range. Set the high limit higher than highest expected SV and PV display. FHD177V3-VT20 Series Installation Manual 4

: Software filter. / : Alarm function selection. See section 5.1 for detail. / : Alarm mode selection. See section 5.2 for detail. : Address of the controller when communicate with a master device. This parameter provides an identity code for the RS485 communication interface. Communication baud rate. 2.4k=2400 bps, 4.8k=4800 bps, 9.6k=9600 bps, 19.2k=19200 bps 4. OPERATION 4.1 AUTO TUNE The auto tune is mainly to teach the controller the main characteristics of the process. It learns by cycling the output on and off. The results are measure and used to calculate optimum Pb, ti, td values, which are automatically entered into nonvolatile memory. The auto tune program is applied during Initial set-up The set point is changed substantially from previous auto tune. The control result is unsatisfactory. The auto tune procedure: In order to automatically set the PID parameters; first adjust the controller s set point (SV) to a value, which closely approximates your application. Make sure that the value of Pb is not zero (zero initialize on/off control). Set the parameter to for standard type auto tune or for low PV type auto tune. The rightmost decimal (AT) on the PV display will blink during tuning process. After two oscillatory cycle of on/off control action. The controller performs PID control with the learned PID value to verify the results. Finally the PID values will be entered into the memory and then start the fuzzy enhanced PID control. To abort an auto tune process. Simply set the parameter to. 4.2 TUNING THE CONTROLLER MANUALLY To ensure that all parameters correctly. are configured Set to zero. Set to smallest. Set the controller s set point (SV) to a value, which closely approximates your application. The controller will perform the on/off control action. So the process value will oscillate about the set point. The following parameters should be noted: a. The peak-to-peak variation (P) in / (i.e. the difference between the highest value of the overshoot and the lowest value of the undershoot). b. The cycle time of the oscillation in seconds. The control setting should be then calculated as follows: Pb= (P 100) Span ( %) ti = T td = T/4 Note: The span is the difference between the high limit value and low limit value. The PID parameters determined by the above procedures are just rough values. If the control results are unsatisfactory. The following rules may be used to further adjust the PID parameters. Adjustment sequence Symptom Solution Slow response. Decrease PB. 1. Proportional Band High overshoot Increase PB. or Oscillations Slow response Decrease ti. 2. Integral Time Instability or Increase ti. 3. Derivative Time Oscillations Slow or Oscillations response Decrease td. High overshoot 4.3 MANUAL CONTROL Increase td. Manual control allows the user to manually drive the output percentage from 0.0 through 100.0% (usually used for testing purposes). To access the manual control mode, set the parameter to yes, the rightmost decimal (MA) on SV display will flash. Then FHD177V3-VT20 Series Installation Manual 5

the parameter will display alternately and process value. The output percentage then can be adjusted by using up or down key. To abort the manual control just simply set the to. 5. ALARM 5.1 ALARM FUNCTION There are two independent alarm outputs available in VT20 series controllers. Each alarm can be set to be one of six alarm function (process high, process low, deviation high, deviation low, band high and band low) from or. When the alarm output is not used, set to to prevent alarm action. A special alarm mode can be set from and. : No special mode : Standby mode When selected, in any alarm function, prevents an alarm on power on. The alarm is enabled only when the process value reaches set point. Also known as Startup inhibit and is useful for avoiding alarm trips during startup. : Latch mode When selected, the alarm output and indicator latch as the alarm occurs. The alarm output and indicator will be energized even if the alarm condition has been cleared unless the power is shut off. : Standby and Latch mode ACTION ACTION DIAGRAM No alarm action Process high alarm Process low alarm Deviation high alarm Deviation low alarm Band high alarm Band low alarm 5.2 ALARM MODE FHD177V3-VT20 Series Installation Manual 6

6. ERROR MESSAGE AND TROUBLESHOOTING Symptom Probable Solution -Input signal below the low limit -Set a higher value to high limit. -Incorrect input sensor selection -Check connect input sensor selection. -Input signal below the low limit -Incorrect input sensor selection -Set al lower value to low limit. -Check correct input sensor selection -Sensor break error -Sensor not connected -Replace sensor -Check the sensor is connected correctly -Unit must be repaired or replaced. -A/D converter damage -Check for outside source of damage such as transient voltage spikes. -Keypads are locked -Set to a proper value Keypad no function -Keypads defective -Replace keypads Process value -Improper setting of Pb, Ti, Td -Start AT process to set Pb, Ti, Td automatically( Refer to 4.1) unstable and CT -Set Pb, Ti, Td manually( Refer to 4.2) No heat or output -No heater power or fuse open -Check output wiring and fuse -Output device defective or -Replace output device incorrect output used All LED s and display -No power to controller -Check power lines connection not light -SMPS failure -Replace SMPS -Electromagnetic Interference -Suppress arcing contacts in system to eliminate high voltage Process Value (EMI) or Radio Frequency spike sources. Separate sensor and controller wiring from dirty changed abnormally Interference (RFI) power lines. Ground heaters Entered data lost -Fail to enter data to EEPROM -Replace EEPROM

7. SPECIFICATION INPUT Thermocouple J, K, T, E, B, R, S, N, C TYPE RTD DIN PT-100; JIS PT-100 Linear 4~20mA; 0~50mV; 1~5V; 0~10V.. Range User configurable Accuracy ±1 C for thermocouple, ±0.2 C for RTD, ±3mA for Linear Cold Junction Compensation 0.1 C/ C ambient Sampling Time 0.5 sec. Normal Mode Rejection 60 db Common Mode Rejection CONTROL FUNCTION 120 db Proportional Band 0.0 ~ 300.0 % Integral Time 0 ~ 3600 sec. Derivative Time 0 ~ 900 sec. Hysteresis 0.0 ~ 200.0/ 0 ~ 2000 Cycle Time 0 ~ 100 sec. Control Action OUTPUT Relay Contact Output Pulsed Voltage Output Current Output Continuous Voltage Output GENERAL Rated Voltage Consumption Memory Backup Direct (for cooling) or Reverse (for heating) 10A/240 VAC (Resistive Load) 0 or 24 VDC (Resistive 250 ohms Min.) 4 ~ 20mA (Resistive 600 ohms Max.) 0 ~ 50mA, 1 ~ 5V, 0 ~ 10V (Resistive 600 ohms Min.) 90 ~ 264 VAC 50/60 Hz Less than 5 VA EEPROM and non-volatile memory (Approx. 10 years) Ambient Temperature 0 ~ 50 C Ambient Humidity 0 ~ 90% RH (Non-condensing) Fast Heat UK Ltd Unit 7, Alder Close Eastbourne East Sussex BN23 6QF TEL: 01323 647375 FAX: 01323 410355 EMAIL: sales@fastheatuk.com or tech-support@fastheatuk.com WEB: www.fastheatuk.com FHD0177-10-1105