VLT Series 600 Watt True Sine Wave Inverter

Similar documents
VLT Series 300 Watt True Sine Wave Inverter

User s Manual Before using the inverter, you need to read and save the safety instructions.

Battery Power Inverters

3000W Power Inverter

E Manual N Phoenix

OWNER'S MANUAL. Model CUL AC Power Inverter/Charger System OM/A96283 REV. A

HI400. Owner s Guide

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

CHARGING SYSTEMS INTERNATIONAL

Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

OWNER S MANUAL. Model AE150/AE300/AE AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT

70-Series CAN Power Management System

POWER TO GET THE JOB DONE

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

XC120 XC180. Owner's Guide Conforms to / Conforme à UL std. 458, Toll Free

Installation and Operating Instructions (for chargers shown below)

XPower Inverter Installation Guide. This guide for use by qualified installers only.

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

IQ SERIES. Industrial Quasi Sine Wave AC Power Inverter. Models IQ IQ IQC IQC IQC

Installation and Operating Instructions (for chargers shown below)

ST Series POWER SUPPLIES USER INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

BATTERY CHARGER OWNER S MANUAL

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

How To Use A Power Supply Unit (Upu)

Installation and Operation Guide for PD4000 Series Power Control Center

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Manual for Fire Suppression & Methane Detection System

Freedom SW Sine Wave Inverter/Chargers

Advantium 2 Plus Alarm

User s Manual AURORA 1.2K/2.2K

Mobile Data Power Model: MDP-25

MODEL 2202IQ (1991-MSRP $549.00)

Xantrex PRO Inverter XM 1000 and XM 1800

XPower Inverter Owner s Guide

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Online UPS. PowerWalker VFI 1000R/1U

victron energy USER MANUAL GEBRUIKSAANWIJZING MODE D'EMPLOI BEDIENUNGSANLEITUNG Phoenix 12/220 Phoenix 24/220 Phoenix 48/220

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

MCR1900 Media Converter 19-Slot Chassis

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

400 Amp Rechargeable Jump Start System RAC-HP082

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

1500 WATT POWER INVERTER

BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

RAY-MAX Integrated Solar Power Strip

Q1-750 Q Q Q Q2-200 Q4-90 Q4-120 HIGH PERFORMANCE AMPLIFIER

LOXONE 12 Channel Amplifier

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

ACTIVE.

TIG INVERTER INSTRUCTION MANUAL

USER MANUAL GEBRUIKSAANWIJZING MODE D'EMPLOI BEDIENUNGSANLEITUNG

G670 Intermittent Pilot Ignition Controls

Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters

XPower 1000 Inverter. Owner s Guide

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

Installation and Operation Guide for PD4100 Series Power Control Centers

HM-W536 Install Guide

USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions

12V Battery Charger & Engine Starter

INSTALLATION & SERVICE MANUAL. Display Panel

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Freedom Owner's Manual. Xantrex Freedom 458 Series Inverter/Charger

6 & 12 Volt Battery and Systems Tester with 100 Amp Load

StorTrends 3400 Hardware Guide for Onsite Support

REDI-LINE ELECTRIC GENERATORS USER'S GUIDE. Rugged, Reliable, DC to AC Power Conversion

aseries A13B Mini Bullet Camera User Manual

XPower 1500 Portable Household Power

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

HP UPS R1500 Generation 3

Dehumidifier Users manual. For Models: DH45S DH65S

Home Solar Kit Owner s Manual. Model: HS

Oil and Coolant Circulating Heating System. Model - OCSM

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Battery Management Innovation DIAGNOSTIC CONDUCTANCE CHARGER. For testing and charging 12-volt automotive batteries INSTRUCTION MANUAL

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

USER S MANUAL HSC-24A

V94 BULK TAPE DEGAUSSER

BATTERY CHARGER OPERATOR'S MANUAL

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

Installation Instructions for Alarm Module Kit A043F059

FOR THE FOLLOWING MODELS: EE-8075W EE-8075O EE-8075R EE-8075BK

12-Volt 10-Amp Regulated Power Supply

Electric Fryers Instruction Manual Models: 8047D, 8048D, 8049D, 8050D, 8051D 8066, 8068, 8068FL, 8073, 8073BF and 8075

Portable Air Conditioner

Owner s Manual. ULTRA-POWER II ACCU-POWER & ACCU-POWER ONBOARD Solid State Fully Automatic Chargers. Manual Number Edition Code 0493B0101A

User Manual 1K/2K/3K Online UPS

SWIMMING POOL HEAT PUMP

OWNER S MANUAL FOR MINN KOTA ONBOARD BATTERY CHARGERS Models: MK110D,MK210D, MK220D, MK315D, MK330D

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

Single Phase Soft Starter

120Volt 60-70A ARC WELDER Rev

750 WATT Power Inverter

Transcription:

VLT Series 600 Watt True Sine Wave Inverter Pure Sine Wave Inverter I 0 ON OFF INPUT LEVEL LOAD LEVEL FAULT AC OUTPUT FREQ. 50Hz 60Hz Models VLT12-600 VLT24-600 600 Watt VLT Series Inverter - 1 -

TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IMPORTANT SAFETY INSTRUCTIONS... 3 2.1.1 General Safety Precautions... 3 2.1.2 Precautions When Working With Batteries... 4 3 SPECIFICATIONS AND FEATURES... 5 3.1.1 Specifications... 5 3.1.2 Front Panel... 6 3.1.3 ON / OFF Control Switch... 6 3.1.4 Remote Control Terminal... 6 3.1.5 DC Input Level LED... 6 3.1.6 AC Load Level LED... 7 3.1.7 AC Output GFCI Duplex Receptacle... 7 3.1.8 Rear Panel... 8 3.1.9 Single Wire Remote Control... 8 3.1.10 DC Input Terminals... 9 3.1.11 Chassis Ground Bonding Lug... 9 3.1.12 Fan... 9 3.1.13 Measurements... 9 4 INSTALLATION... 10 4.1.1 DC Wiring Considerations...10 4.1.2 DC Cable and Fuse Sizing Chart...11 4.1.3 DC Wiring Installation Procedure...11 5 TROUBLESHOOTING... 12 6 MAINTENANCE... 12-2 - 600 Watt VLT Series Inverter

1 INTRODUCTION Thank you for purchasing a Vanner 600 Watt VLT SERIES Inverter. We are confident that you will be satisfied with the inverter s performance and its many features. With proper installation and care, you can look forward to years of service from this high performance product. This document will describe the operation, technical specifications and installation procedures. 2 IMPORTANT SAFETY INSTRUCTIONS Electrocution hazard exists Fire hazard exists A potentially dangerous condition Explosive hazard exists Corrosive hazard exists To get the most out of the power inverter, it must be installed and used properly. Please read the instructions in this manual before installation. Keep this manual for future reference. 2.1.1 General Safety Precautions Do not expose the inverter to rain, snow, spray, or dust. To reduce risk of hazard, do not obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may result. To avoid a risk of fire and electric shock, make sure the wiring is in good electrical condition and is proper gauge. Do not operate the inverter with damaged or substandard wiring. This equipment contains components that can produce arc or sparks. To prevent fire or explosion, do not install in compartments containing batteries or flammable materials or in locations which require ignition protected equipment This includes any space containing gasoline-powered machinery, fuel tanks, or joints, fittings, or other connection between components of the fuel system 600 Watt VLT Series Inverter - 3 -

2.1.2 Precautions When Working With Batteries If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 20 minutes and get medical attention immediately. Never smoke or allow a spark or flame in vicinity of battery or Engine. Do not drop a metal tool onto the battery. The resulting spark or short-circuit on the battery or other electrical part may cause an explosion. Remove personal metal items such as rings, necklaces, and watches when working with a leadacid battery. A lead-acid battery can produces a short-circuit current high enough to weld a ring or the like to metal, causing severe burns. - 4-600 Watt VLT Series Inverter

3 SPECIFICATIONS AND FEATURES 3.1.1 Specifications Model Number SPECIFICATIONS VLT12-600 VLT24-600 AC Power Output Rated Continuous Output Surge Rating (3S) Output Waveform Total Harmonic Distortion 600 Watts 800 Watts True Sine Wave < 3% THD Output Voltage 120 VAC +/- 3% Output Frequency 60 Hz AC Output Wiring Method GFCI Duplex Receptacle Maximum, Efficiency % 88 90 DC Input Voltage 12V Nominal 24V Nominal DC Input Voltage Range 11.5 to 16.0 23.0 to 32.0 Low DC voltage Shutdown / Restart 11.3 / 13.5 22.5 / 26.5 High DC voltage Shutdown / Restart 16.3 / 15.8 32.6 / 31.5 DC Input Current Inverter ON with no AC load < 1A System Protection Safety Remote Control Ambient Operating Temperature Storage Temperature Fan Cooling Enclosure Dimensions (L x W x H) Weight Overload, Short Circuit, Reverse Polarity (internal fuses), Over/Under Input Voltage, Over Temperature UL458 ON/OFF Control by customer supplied external switch -25 +50ºC (-13 to +122ºF) -30 to +70ºC (-22 to 158ºF) Thermostatically controlled cooling fan Painted aluminum 11.0 L x 7.25 W x 3.0 H 6.6 pounds 600 Watt VLT Series Inverter - 5 -

3.1.2 Front Panel Pure Sine Wave Inverter I 0 ON OFF INPUT LEVEL LOAD LEVEL FAULT AC OUTPUT FREQ. 50Hz 60Hz 3.1.3 ON / OFF Control Switch The ON/OFF Switch must be in the ON position when using Remote Control. 3.1.4 Remote Control Terminal A green two-terminal connector located on the rear panel allows remote ON/OFF control of the inverter by a customer-supplied ON/OFF switch. The connector can be removed from the inverter by pulling the connector outward. The two upward facing screws are used to tighten the compression terminals for attachment of the signal wire(s). Torque to 4 lb-in max. Standard Operation (no remote control) The inverter is shipped with a jumper connecting terminals Vout and Vin. With the jumper in place (remote control not being used) the inverter is fully functional using the ON/OFF control switch located on the front of the inverter. 3.1.5 DC Input Level LED VLT12-600 and VLT24-600 DC Input Voltage Status Indication Inverter shut down due to low voltage Normal Operating Range Inverter shut down due to high voltage Voltage Input Level Status LED Red Slow Blinking with Fault LED Red Slow Blinking Red Solid Orange Solid Green Solid Orange Fast Blinking RED Fast Blinking Red Fast Blinking with Fault LED VLT12V-600 VLT24V-600 11.3V 11.7V 12.0V 13.1V 15.2V 16.0V 22.5V 23.2V 24.0V 26.2V 30.5V 32.0V 16.3V 32.5V After low voltage shutdown, inverter will automatically restart when voltage rises above 13.5V / 27.0V or can be manually reset/restarted after voltage rises above 11.5V / 23.0V After high voltage shutdown, inverter will automatically restart when voltage falls below 15.5V / 31.0V - 6-600 Watt VLT Series Inverter

3.1.6 AC Load Level LED LED Display and Color Dark Green Orange Red Red Blink Approximate Load Condition 0 ~ 30W 30W ~ 200W 200W ~ 450W 450W ~ 580W Over 580W Red Fault Led Solid when unit has shut down for over load. 3.1.7 AC Output GFCI Duplex Receptacle The AC output neutral conductor is connected to AC ground and inverter chassis ground inside the inverter. This conforms to National Electrical Code requirements that separately derived AC sources (such as inverter and generators) have their neutral conductors tied to ground in the same way that the neutral conductor from the utility is tied to ground at the AC breaker panel. Do not connect AC neutral to AC ground downstream of the GFCI. This would cause the GFCI to trip. Never connect the inverter output to another AC power source such as a generator or utility power. The inverter would be destroyed. 600 Watt VLT Series Inverter - 7 -

3.1.8 Rear Panel Vout Vin REMOTE CONTROL DC INPUT WARNING: REVERSE POLARITY WILL DAMAGE UNIT. NEG (-) POS (+) CHASSIS GROUND 3.1.9 Single Wire Remote Control Remote Control via customer-supplied SPST switch: If it is desired to remotely control the inverter from a customer-supplied remote switch, remove the jumper connecting terminals Vout and Vin. Supply a 12v (24v signal on 24v units) continuous signal to terminal Vin to turn the inverter ON. The source of the 12v signal can be battery voltage for single-wire remote control or terminal Vout for two-wire-remote-control. A common remote control arrangement uses a "hot in run" circuit from the vehicle fuse panel for the voltage signal. This arrangement automatically turns the inverter ON when the vehicle is running and automatically turns the inverter OFF when the vehicle is turned OFF. Vin Details Vin will draw approximately 0.4 amps continuous while holding the inverter ON. If Vout is not used as the remote control signal, use a 5 amp fused circuit for the Vin remote control signal. Vout Details When using Vout as the remote control voltage source, install a 2 amp fuse within 12 of the inverter. The inverter will be damaged if Vout comes into contact with battery negative - 8-600 Watt VLT Series Inverter

3.1.10 DC Input Terminals DC Input terminals are for the included 6AWG ring terminals. The ring terminal entry is limited to a maximum of 4AWG wire. Connect DC Input Terminals to a 12v battery (24v battery for 24v units). (+) is positive,(-) is negative. Reverse polarity connection will blow the internal fuses and may cause permanent damage to the inverter. 3.1.11 Chassis Ground Bonding Lug Connect Chassis Ground Bonding Lug to vehicle chassis using 12AWG or larger copper wire. WARNING! Operating the inverter without a proper ground connection may cause an electrical hazard. 3.1.12 Fan Do not obstruct the rear fan exhaust or front ventilation intake openings. Allow at least 3 inches of clearance for airflow. 3.1.13 Measurements VLTxx-600 Mounting Bolt Pattern 10 3/4" 1 1/2" 7 9/16" Four mounting slots 9/32" wide x 7/16 deep DC Terminals 7 1/16 6 3/8 narrowest bolt hole center to center Top Front Top View VLTxx-600 Inverter 600 Watt VLT Series Inverter - 9 -

4 INSTALLATION Inverter Installation Considerations Mounting: Locate a flat secure, dry, horizontal or vertical surface large enough to mount the inverter. The location should be as close to the battery as practical, usually within six feet, but not in the same compartment and should provide adequate ventilation while the inverter is operating. The location must be clean, dry and free from road spray, dripping water or other moisture contamination. Cooling Fan Clearance: The mounting location must allow unobstructed airflow for cooling. Allow a minimum clearance of 3 inches on the front and back of the inverter. The Cooling Fan is thermostatically controlled. Obstruction of the fan exhaust or the front intake vents will diminish the inverter output capacity due to overheating. 4.1.1 DC Wiring Considerations Do not connect the 12V model to a 24V battery. The unit will be destroyed immediately. Operation of the inverter without a proper ground connection may result an electrical safety hazard. Damage caused by reversed polarity will void warranty. A DC FUSE IS REQUIRED to protect the DC cables in case of a short circuit. The wiring of the inverter installation should conform to the National Electric Code (NEC) and any other state or local codes in effect at the time of installation. Article 551 of the NEC requires any DC cable from a battery, which measures longer than 18 inches along its length, be protected by a fuse. BE AWARE, as a large number of capacitors become charged upon completion of the DC circuit, THERE WILL BE A LARGE SPARK when the last battery connection is made. The spark is normal and will occur every time the batteries are connected. It is advisable to make the last DC connection at the inverter, not at the battery, to reduce the risk of battery explosion. To minimize electromagnetic radiation that could interfere with sensitive electronics, route the AC output wiring and DC power wiring with as much physical separation as possible from low voltage wiring such as audio and video signal wires. Route the DC positive and negative cables as close together as possible and use cable ties to keep them together. If passing through steel or other ferrous metal walls, the DC input cables need to pass through the same hole to prevent causing a transformer effect. If two holes are required, cut a slot to connect the two holes to prevent heating of the ferrous metal. Proper DC cable size is critical for the performance and safe operation of the inverter system. The DC Cable and Fuse Sizing Chart shows the minimum cable sizes recommended. These sizes allow a ½ volt maximum voltage drop at maximum inverter capacity and will insure optimum inverter performance. DC cable to be used with these fuse sizes should be minimum insulation temperature rating of 105 C and voltage rating of 600V. DC cables should be as short as possible. Do not use the vehicle chassis as the DC negative conductor. The negative cable should be the same size as the DC positive cable and should be connected directly to the battery negative terminal. - 10-600 Watt VLT Series Inverter

4.1.2 DC Cable and Fuse Sizing Chart Model Number VLT12-600 VLT24-600 Distance from battery to inverter in feet Wire Size (Total circuit length is 2 times the distance.) 8 6.5 13.5 6 10.0 20 4 16.0 20 Fuse Rating 80 Amp 60 Amp Fuse Part Number 013910 013909 Fuse Holder Part Number 012992 Ring Terminal 4 AWG,1/4 stud, narrow 011973 4.1.3 DC Wiring Installation Procedure Verify the Power ON/OFF Switch is in the OFF position before connecting inverter to the battery. Route the negative DC cable to the battery. Verify cable polarity before proceeding. The fuse will be blown and inverter may be damaged if the DC cables are reversed. Route the positive DC cable to the fuse and then to the battery. Protect cables with loom and use grommets or other appropriate means where cables may contact hard, sharp edges. Connect Chassis Ground Bonding Lug to the vehicle chassis and/or earth ground using 8AWG or larger copper wire. (The wire must be sized to safely carry DC current as needed to blow the DC fuse located near the battery in the inverter s positive DC input cable.) 600 Watt VLT Series Inverter - 11 -

5 TROUBLESHOOTING WARNING! Do not open or disassemble the Inverter. Attempting to service the unit yourself may result in a risk of electrical shock or fire, and will void warranty. Problems and Symptoms Possible Cause Solutions No AC output voltage Led Blinking Red Fast. High DC input voltage. Check input voltage. Reduce input voltage. Led Blinking Red Slowly. Low DC input voltage. Recharge battery. Check connections and cable. No Led s on No LED s on Fault Led ON Solid Red Unit with remote immediately shuts down following power up sequence. Unit displays the input level led and a solid fault led. Over temperature shut down Blown DC input fuse Overload, short circuit Blown fuse on inverter positive DC input. Improve ventilation. Make sure inverter ventilation openings are not obstructed. Reduce ambient temperature. Unit will automatically turn on when it cools. Replace inverter DC input fuse Remove AC load. Check AC wiring for short circuit. Replace inverter DC input fuse. 6 MAINTENANCE Very little maintenance is required to keep the inverter operating properly. Clean the exterior of the unit periodically with a damp cloth to prevent accumulation of dust and dirt. At the same time, verify the battery and fuse connections are clean and tight. Test and reset the GFCI monthly. - 12-600 Watt VLT Series Inverter

Vanner Incorporated 4282 Reynolds Drive Hilliard, Ohio 43026 Ph: 800-AC POWER Ph: 614-771-2718 Fax: 614-771-4904 www.vanner.com Manual P/N: D916054-B July 2016 600 Watt VLT Series Inverter - 13 -