Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Similar documents
Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

Duct Humidity Transmitter

Digital input modules

RRV934. Multi-controller. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

Flush-mount room temperature sensor AQR2531ANW.

HCR3.2/.. Chipcard reader HOTEL SOLUTION

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Heating Controller. Building Technologies HVAC Products

TX OPEN RS232/485 module

Air damper actuators

J TB/TW Temperature limiter, temperature monitor

OZS Web server. For LPB/BSB plants

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

OZW30. Central Unit SYNERGYR

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

QFP910. Water detector. Building Technologies. CE1N2732en Synco living

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

DS 600. A contact free flux gate based current measurement sensor 600A rms

Digital inductive conductivity transmitter

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Electronic Control Devices The European Product Catalogue 2007

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Inductive sensor NI10-M18-Y1X-H1141

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Radiant Temperature Sensor TY7321

Room Temperature Sensors

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Incubator with mechanical convection

SINEAX U553 Transducer for AC Voltage

How To Use A Flowmeter

HMI display Installation Guide

Capteur température et humidité pour HVAC

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

HERZ-Thermal Actuators

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB

USER'S GUIDE. Vaisala HUMICAP Humidity Transmitter Series HMP140A U175EN15

RM4TG20 three-phase network control relay RM4-T - range V

Long sensing range. Most suitable for conveyor lines and parking lot applications. 10 m ft (Red LED)

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH

Installation, operation and maintenance manual TX 35A

GREISINGER electronic GmbH

Sealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

T0118 T2118 T3118. Instruction Manual

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

OZW V2.0. Web server. Synco TM, Synco TM living

Pressure transmitter For general industrial applications Model A-10

Temp-485-Pt100. A temperature sensor (Pt100 or Pt1000) communicating over the RS-485 bus with a simple communication protocol

Vario-Series Accessories

SVR 12/24V and SVR Akku 12V Installation instructions

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Terminal Boxes Series 8146

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

aseries A13B Mini Bullet Camera User Manual

Laser diffuse reflection light scanner with background suppression. Dimensioned drawing

Cross-beam scanning system to detect slim objects. 100 mm in

AXIS T81B22 DC 30W Midspan

14 PHOENIX CONTACT Courtesy of Power/mation Energy Lane, Saint Paul, MN

Technical Data. Dimensions

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Monitor and control the sensors through network. supported OPTEX FA CO., LTD. Remote controlling of fiber sensors. Reduces wires and saves space

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Input module, input/output module

Relative and absolute pressure switch type 529

Contents. Document information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

OLI. Oil level indicator

Hand-held thermometer Model CTH7000

Características. Starligh SA 9 de julio 1595 Córdoba Argentina /

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

PHOENIX CONTACT Features

PXM20-E. Operator unit DESIGO PX

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

Electronic Pressure Switch EDS 300

Programmable Terminal. NPSeries. Easy Setup with the Low-cost, Compact NP Series

Mounting Instructions. Torque Transducer. A en

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL CAUTION CONNECTION DIAGRAM

Electronic Control Devices The European Product Catalogue 2007

Safety technique. Emergency stop module BO 5988 safemaster

Instruction Manual. T3111 T3111L T3111P T3111Ex

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

FDCI222, FDCIO222, FDCIO224 Input module Input/output modules

PCS0100en Persy Control Services B.V. Netherlands

Transcription:

1 883 1883P01 1883P02 1859P04 QFM41.. AQF4150 AQF3153 Symaro Duct sensors for relative humidity and temperature with calibration certificates QFM41 Operating voltage AC 24 V / DC 13.5...3 Signal output DC 0...10 V / 4 20 ma for relative humidity and temperature Very high measuring accuracy throughout the entire measuring range Capacitive humidity measurement Recalibration service Test function for loop test Range of use 40 +70 C / 0 100 % r. h. Use The QFM41 sensor is used in ventilation and air conditioning plants requiring: Very high accuracy and reliability for measuring relative humidity and temperature Regular recalibration and readjustment of the sensors Examples: Storage and production facilities in the paper, textiles, pharmaceutical, chemical, electronics industries, etc. Laboratories Hospitals Computer centers Greenhouses CE1N1883en 01.12.2010 Building Technologies

Type summary Type reference measuring range signal output measuring range signal output Operating voltage QFM4101 - - 0...100 % active, 4 20 ma DC 13.5 3 QFM4160 0...50 C, 40 +70 C or 35...+ 35 C QFM4171 0...50 C, 40 +70 C or 35...+ 35 C active, DC 0...10 V 0...100 % active, DC 0...10 V AC 24 V or DC 13.5 3 active, 4 20 ma 0...100 % active, 4 20 ma DC 13.5 3 Ordering and delivery When ordering, please give name and type reference, e.g.: Room sensor QFM4160 Place a separate order for the service set AQF3153 listed under accessories. The circular connector with its screwed plug is delivered uninstalled. Equipment combinations All systems and devices capable of acquiring and handling the sensor s DC 0...10 V or 4...20 ma output signal. When using the sensors for minimum or maximum selection, for averaging, or to calculate enthalpy, enthalpy difference, absolute humidity, and dew point, we recommend to use the SEZ220 signal converter (see Data Sheet N5146). Technical design Relative humidity Load diagram The sensor acquires the relative humidity in the air duct via its capacitive humidity sensing element whose capacitance varies as a function of the relative humidity of the ambient air. An electronic circuit converts the sensor s signal to a continuous DC 0...10 V or 4 20 ma signal, corresponding to a relative humidity of 0...100 % r. h. The sensor acquires the temperature in the air duct via its sensing element whose electrical resistance changes as a function of the temperature. This variation is converted to an active DC 0...10 V or 4 20 ma output signal, depending on the type of sensor. The output signal corresponds to a selectable temperature range of 0...50 C, 35...+35 C or 40...+70 C. Output signal, terminal I1 / I2 900 800 1883D01en Burden [Ohm] 700 600 500 400 300 Inadmissible range! Admissible range 200 100 0 0 10 20 30 40 Operating voltage [DC V] 2/7

Mechanical design The duct sensor consists of a housing, a printed circuit board, connection terminals, an immersion rod having a measuring tip and a circular connector. The two-part housing comprises a base and screwed removable cover. A rubber seal is installed between the base and the cover in order to satisfy the requirements of IP 65 degree of protection. The measuring circuit and the setting element are accommodated on the printed circuit board inside the cover the connection terminals on the base. The measuring tip is screwed on the immersion rod of the housing. The sensing elements are located at the end of the measuring tip protected by a screwon filter cap. Cable entry is made via the circular connector, which consists of coupling piece with M16 thread and screwed plug. The coupling piece is secured to the housing and internally wired. Immersion rod and housing are made of plastic and rigidly connected. The sensor is fitted with the mounting flange supplied with the sensor. The flange is to be placed over the immersion rod and then secured in accordance with the required immersion length. Setting element Range 123 Measuring range 123 Test function active U1 U2 I1 I2 10 V 20 ma 10 V 20 ma 0 V 0 V 4 ma 4 ma 1883Z03en The setting element is located inside the cover. It consists of 6 pins and a shorting plug. It is used for selecting the required temperature measuring range and for activating the test function. The different jumper positions have the following meaning: For the active temperature measuring range: Jumper in the left position (R1) = 35...+35 C, Jumper in the mid position (R2) = 0...50 C (factory setting) Jumper in the right position (R3) = 40...+70 C For the active test function: Jumper in the horizontal position: The values available at the signal output are those given in the table Test function active Malfunction Calibration certificates Service set AQF3153 Should the temperature sensor become faulty a voltage of 0 V (4 ma) will be applied at signal output U2 (I2) after 60 seconds, and the humidity signal at signal output U1 (I1) will reach 10 V (20 ma). Should the humidity sensor become faulty a voltage of 10 V (20 ma) will be applied at signal output U1 (I1) after 60 seconds, and the temperature signal will remain active. The sensor and its exchangeable AQF4150 measuring tip are numbered, registered and calibrated prior to delivery. Calibration is traceable to national standards, e.g. METAS, NIST, LNE, PTB. The associated calibration certificates are supplied with the sensor. The service set comprises three measuring tips without sensor element. Each tip signals a predefined temperature and humidity value to the basic unit: 85 % r. h., 40 C 50 % r. h., 23 C 20 % r. h., 5 C 3/7

The fixed values are available at the signal outputs. The accuracy is the same as for the test function. The measuring tips can be exchanged in operation. The service set allows for easy and quick loop test performance as recommended by Vertical Market Pharma and offered by their calibration service in various countries. Accessories Name Type reference Measuring tip certified (exchangeable) AQF4150 Service set (for loop test) AQF3153 Filter cap (for replacement) AQF3101 3 m cable for remote measurement AQY2010 Engineering notes Cable routing and cable selection Note to QFM4171 A transformer for safety extra low-voltage (SELV) with separate windings for 100 % duty is required to power the sensor. When sizing and protecting the transformer, the local safety regulations must be complied with. When sizing the transformer, the power consumption of the duct sensor must be taken into consideration. For correct wiring of the sensor, refer to the Data Sheets of the devices with which the sensor is used. The permissible line lengths must be considered. It must be considered for routing of cables that the longer the cables run side by side and the smaller the distance between them, the greater the electrical interference. Shielded cables must be used in environments with EMC problems. Twisted pair cables are required for the secondary supply lines and the signal lines. Terminals G1(+) and I1( ) for the humidity output must always be connected to power, even if only terminals G2(+) and I2( ) of the temperature output are used! Mounting notes Location Caution! Mounting instructions Mount the sensor in the center of the duct wall. If used together with steam humidifiers, the minimum distance after the humidifier must be 3 m to max 10 m. Fit the sensor in the extract air duct if the application involves dew point shifting. Fit only the flange to the duct wall. The sensor is then inserted through the flange and engaged. The seal between base and cover must not be removed, or else degree of protection IP 65 will be no longer ensured. The sensing elements inside the measuring tip are sensitive to impact. Avoid any such impact on mounting. Mounting Instructions are printed on the inner side of the package. Commissioning notes Check wiring before switching on power. The temperature measuring range must be selected on the sensor, if required. Wiring and the output signals can be checked by making use of the test function (refer to "Mechanical design"). 4/7

We recommend not to use voltmeters or ohmmeters directly at the sensing element. In the case of the simulated passive output signals, measurements with commercially available meters cannot be made (measuring current too small). Recalibration service Siemens BT provides a recalibration service for used sensors. The recalibration should be performed at 12-month intervals under "normal" conditions, i.e. within the comfort range for humidity and temperature, and at air contamination levels that are not above average. Services provided Technical data The recalibration service includes the following: Delivery and invoicing of the new AQF4150 measuring tip complete with calibration certificate. Delivery of a calibration certificate for the (old) measuring tip returned to Siemens BT, enabling the customer to assess the time of usage of the measuring tip. Power supply Operating voltage AC 24 V ± 20 % or DC 13.5...3 Frequency 50 / 60 Hz at AC 24 V Power consumption 1 VA Cable lengths for the measuring signal Max. perm. cable lengths refer to Data Sheet of the device handling the signal Functional data sensor" Functional data " sensor" Degree of protection Electrical connections Environmental conditions Materials and colors Measuring range 0...100 % r.h. Measuring accuracy at 23 C and AC 24 V 0...100 % r.h. ± 2 % r.h. dependency 0.05 % r.h./ C Time constant < 20 s Supply air velocity 20 m/s Output signal, linear (terminal U1) DC 0...10 V 0...100 % r.h., ± 1 ma max. Output signal, linear (terminal I1) Burden Measuring range Sensing element Pt 1000 Measuring accuracy at AC 24 V in 23 C 15...35 C 35...+70 C Time constant 4 20 ma 0...100 % r.h. refer to "Function" 0...50 C (R2 = factory setting), 35...+ 35 C (R1), 40...+70 C (R3) ± < 0.5 K ± 0.6 K ± 0.8 K < 3.5 min. in with 2 m/s moved air Output signal, linear (terminal U2) DC 0...10 V 0...50/ 35...+ 35/ 40...+70 C max. ± 1 ma Output signal, linear (terminal I2) Burden Housing Safety class III to EN 60 730 Connector with screwed plug Screw terminals for Cable entry Operation to Climatic conditions (housing with electronics) Mechanical conditions Transport to Climatic condition Mechanical conditions Base Cover Immersion rod Filter cap 4...20 ma 0...50/ 35...+ 35/ 40...+70 C refer to "Function" IP 65 to IEC 60 529 in the built-in state Lumberg RSC 4/9 0.75 mm 2 max. 4 8 mm dia. class 4K2 to IEC 60 721-3-4 40...+ 70 C 0...100 % r. h. (with condensation) class 3M2 to IEC 60 721-3-3 IEC 60721-3-2 class 2K3 40...+ 70 C < 95 % r.h. class 2M2 polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7035 (light-grey) polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7001 (silver-grey) 5/7

Standards and directives Environmental compatibility Weight Mounting flange Circular connector Connector with screwed plug Contact carrier and body Knurled nut and contact Coupling piece Contact carrier Casing and contact Sensor (complete assembly) Packaging PA66 GF35 (black) Lumberg RSC 4/9 PA, black CuZn, nickel-plated Lumberg RKFM 4/0,5 M TPU CuZn, nickel-plated silicon-free corrugated cardboard Product standard Automatic electrical controls for household and similar use EN 60 730-1 Electromagnetic compatibility Immunity Emissions conformity to EN 61 000-6-1 EN 61 000-6-3 EMC directive 2004/108/EC C-tick conformity (EMC) to EN 61 000-6-3 conformity UL 873 Environmental product declaration CE1E1882en provides ISO 14001 (environment) information on environmentally compatible product design ISO 9001 (quality) and assessment (RoHS compliance, composition of substances, SN 36350 (environmental comp. products) packaging, environmental benefit, disposal). RL 2002/95/EC (RoHS) Incl. packaging AQF3153 AQF4150 0.244 kg 0.066 kg 0,050 kg Connection terminals QFM4160 G (R1 = 35...+35 C / R2 = 0...50 C / (r.h.) R3 = 40...+70 C) G0 U1 U2 1859G01 G0 (3) U1 (2) 3 2 4 1 G (4) U2 (1) 1883G02 Front view: Connector fitted, body removed QFM4101, QFM4171 G1 (r.h.) I1 G2 (R1 = 35...+35 C / R2 = 0...50 C / R3 = 40...+70 C) I2 * * 1882G02 I1 (3) G2 *(2) 3 2 4 1 G1 (4) I2 *(1) 1859G04 Front view: Connector fitted, body removed * G2, I2 Only with QFM4171. G, G0 Operating voltage AC 24 V (SELV) or DC 13.5...3 G1, G2 Operating voltage DC 13.5...3 U1 Signal output DC 0...10 V for relative humidity 0...100 % U2 Signal output DC 0...10 V for temperature range 0...50 C (R2 = Werkeinstellung), 35...+ 35 C (R1) oder 40 +70 C (R3) I1 Signal output 4 20 ma for relative humidity 0...100 % I2 Signal output 4 20 ma for temperature range 0...50 C (R2 = Werkeinstellung), 35...+ 35 C (R1) oder 40 +70 C (R3) Note on connection terminals of the QFM4171: Terminals G1(+) and I1 ( ) for the humidity output must always be connected to power, even if only the temperature output G2 (+) and I2 ( ) is used! 6/7

Dimensions 80 60 57 14,5 274 39 ø 20 80 50 235 ø 15 (41) 1883M01 28 3 min. 90, max. 206 AQF4150 (62,8) 21(16) 60 Drilling template with (without) mounting flange Dimensions in mm 2006 2010 Siemens Switzerland Ltd. Subject to change 7/7