STUDIES ON THE BEHAVIOR OF GLASS FIBER REINFORCED GYPSUM WALL PANELS ABSTRACT

Similar documents
Technical Notes 3B - Brick Masonry Section Properties May 1993

Optimum proportions for the design of suspension bridge

The following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.

DEVELOPMENT OF A NEW TEST FOR DETERMINATION OF TENSILE STRENGTH OF CONCRETE BLOCKS

Miss S. S. Nibhorkar 1 1 M. E (Structure) Scholar,

INTRODUCTION TO BEAMS

Seismic Risk Prioritization of RC Public Buildings

Numerical modelling of shear connection between concrete slab and sheeting deck

Detailing of Reinforcment in Concrete Structures

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

MODELLING OF AN INFILL WALL FOR THE ANALYSIS OF A BUILDING FRAME SUBJECTED TO LATERAL FORCE

DESIGN OF SLABS. Department of Structures and Materials Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia

16. Beam-and-Slab Design

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:

Seismic performance evaluation of an existing school building in Turkey

bi directional loading). Prototype ten story

New approaches in Eurocode 3 efficient global structural design

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig some of the trusses that are used in steel bridges

Seismic design of beam-column joints in RC moment resisting frames Review of codes

BEHAVIOR OF SHORT CONCRETE COLUMNS REINFORCED BY CFRP BARS AND SUBJECTED TO ECCENTRIC LOAD

MECHANICS OF SOLIDS - BEAMS TUTORIAL 1 STRESSES IN BEAMS DUE TO BENDING. On completion of this tutorial you should be able to do the following.

Aluminium systems profile selection

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar

SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS

Concrete Frame Design Manual

IMPROVING THE STRUT AND TIE METHOD BY INCLUDING THE CONCRETE SOFTENING EFFECT

EVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST

9.3 Two-way Slabs (Part I)

Eurocode 4: Design of composite steel and concrete structures

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

METHODS FOR ACHIEVEMENT UNIFORM STRESSES DISTRIBUTION UNDER THE FOUNDATION

Design of Fibre Reinforced Concrete Beams and Slabs

SECTION 3 DESIGN OF POST TENSIONED COMPONENTS FOR FLEXURE

EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFORMANCE OF BUILDING RESTING ON SLOPING GROUND

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1

DESIGN AND ANALYSIS OF BRIDGE WITH TWO ENDS FIXED ON VERTICAL WALL USING FINITE ELEMENT ANALYSIS

SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California Prepared By

THE DEVELOPMENT OF DESIGN METHODS FOR REINFORCED AND UNREINFORCED MASONRY BASEMENT WALLS J.J. ROBERTS

MATERIALS AND MECHANICS OF BENDING

APE T CFRP Aslan 500

SECTION 3 DESIGN OF POST- TENSIONED COMPONENTS FOR FLEXURE

Hardened Concrete. Lecture No. 14

SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED

Optimising plate girder design

B.TECH. (AEROSPACE ENGINEERING) PROGRAMME (BTAE) Term-End Examination December, 2011 BAS-010 : MACHINE DESIGN

A Case Study Comparing Two Approaches for Applying Area Loads: Tributary Area Loads vs Shell Pressure Loads

Design of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column

4B The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

NONLINEAR BEHAVIOR AND FRAGILITY ASSESSMENT OF MULTI-STORY CONFINED MASONRY WALLS UNDER CYCLIC LOADS

REVISION OF GUIDELINE FOR POST- EARTHQUAKE DAMAGE EVALUATION OF RC BUILDINGS IN JAPAN

NUMERICAL ANALYSIS OF A HORIZONTALLY CURVED BRIDGE MODEL

ANALYSIS FOR BEHAVIOR AND ULTIMATE STRENGTH OF CONCRETE CORBELS WITH HYBRID REINFORCEMENT

Numerical Analysis of the Moving Formwork Bracket Stress during Construction of a Curved Continuous Box Girder Bridge with Variable Width

Stress Strain Relationships

EUROPEAN ORGANISATION FOR TECHNICAL APPROVALS

CE591 Fall 2013 Lecture 26: Moment Connections

Analysis and Repair of an Earthquake-Damaged High-rise Building in Santiago, Chile

Stresses in Beam (Basic Topics)

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA MECHANICAL PRINCIPLES OUTCOME 2 ENGINEERING COMPONENTS TUTORIAL 1 STRUCTURAL MEMBERS

The International Journal Of Science & Technoledge (ISSN X)

SEISMIC RETROFITTING OF STRUCTURES

ADVANTAGES OF STEEL FIBRE REINFORCED CONCRETE IN INDUSTRIAL FLOORS

Page 1 of Sven Alexander Last revised SB-Produksjon STATICAL CALCULATIONS FOR BCC 250

Methods for Seismic Retrofitting of Structures

REHABILITATION OF THE FIGUEIRA DA FOZ BRIDGE

ASSESSMENT AND PROPOSED STRUCTURAL REPAIR STRATEGIES FOR BRIDGE PIERS IN TAIWAN DAMAGED BY THE JI-JI EARTHQUAKE ABSTRACT

Detailing of Reinforcement in Concrete Structures

Spon Press PRESTRESSED CONCRETE DESIGN EUROCODES. University of Glasgow. Department of Civil Engineering. Prabhakara Bhatt LONDON AND NEW YORK

1.2 Advantages and Types of Prestressing

Behavior of High-Strength Concrete Rectangular Columns

EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES

Requirements for the Use of PRESSS Moment-Resisting Frame Systems

SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP

Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China

1.5 Concrete (Part I)

Code of Practice for Structural Use of Concrete 2013

Structural Design of Multi-story Residential Building for in Salem, India

SPECIFICATIONS, LOADS, AND METHODS OF DESIGN

DESIGN OF BLAST RESISTANT BUILDINGS IN AN LNG PROCESSING PLANT

CE591 Lecture 8: Shear Walls

Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -)

Section 5A: Guide to Designing with AAC

Uniaxial Compressive Strength of Cold-formed Steel Tubular Sections with Recycled Aggregate Concrete Infill

INTRODUCTION TO LIMIT STATES

ARCH 331 Structural Glossary S2014abn. Structural Glossary

Structural Design Criteria & Design Loads on Delhi Metro Rail and Checking of Safety of Radial Joints in Tunnel Lining Segments

In-situ Load Testing to Evaluate New Repair Techniques

Problem 1: Computation of Reactions. Problem 2: Computation of Reactions. Problem 3: Computation of Reactions

DESIGN SPECIFICATIONS FOR HIGHWAY BRIDGES PART V SEISMIC DESIGN

RC Detailing to Eurocode 2

TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION

Objectives. Experimentally determine the yield strength, tensile strength, and modules of elasticity and ductility of given materials.

Structural Axial, Shear and Bending Moments

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA MECHANICAL PRINCIPLES AND APPLICATIONS NQF LEVEL 3 OUTCOME 1 - LOADING SYSTEMS TUTORIAL 3 LOADED COMPONENTS

Transcription:

STUDIES ON THE BEHAVIOR OF GLASS FIBER REINFORCED GYPSUM WALL PANELS Maganti Janardhana 1, A. Meher Prasad 2 and Devdas Menon 2 ABSTRACT Glass fiber reinforced gypsum (GFRG) wall panel is made essentially of gypsum plaster reinforced with glass fibers. The panels are hollow and can be used as load bearing walls. The hollow cores inside the walls can be filled with in-situ plain or reinforced concrete. This paper presents guidelines for the use of GFRG wall panel as a lateral load resisting component in buildings based on a numerical analysis procedure to arrive at its capacity estimation under axial compression, compression with inplane bending and shear. Variation of buckling load of unfilled GFRG wall panels for various widths is reported. The axial load carrying capacity of 1.02 m wide and 2.85 m high wall panel, obtained from the numerical analysis and the test results are comparable for this load case. While assessing the axial load capacity for design under compression, a minimum possible eccentricity (causing out-ofplane bending) is accounted for. An engineering model is proposed to assess the strength of unfilled and concrete filled GFRG wall panels in multi-storied building system subjected to lateral load such as earthquake. Introduction In a high seismic intensity zone, resistance of buildings to earthquakes is often ensured by adopting structural systems where seismic actions are assigned to structural walls (shear walls), designed for horizontal forces and gravity loads while columns and beams are designed only for gravity loads. Structural walls provide a nearly optimum means of achieving the important objectives, viz., strength, stiffness and ductility. Buildings braced by structural walls 1 Ph D Research Scholar, 2 Professor, Structural Engineering Division, Department of Civil Engineering, Indian Institute of Technology Madras, Chennai 600 036, India.

are invariably stiffer than framed structures, reducing the possibility of excessive deformations under small earthquakes. The necessary strength to avoid structural damage under moderate earthquakes can be achieved by properly detailed longitudinal and transverse reinforcement. Special detailing measures need to be adopted to achieve, dependable ductile response under major earthquakes (Paulay and Priestley, 1992). Glass fiber reinforced gypsum (GFRG) wall, a new composite wall product known as Rapidwall /Gypcrete in the industry, is made essentially of gypsum plaster, reinforced with chopped glass fibers. The glass fibers about 300 350 mm long are randomly distributed inside the panel skins and ribs in the manufacturing process. The fiber content is 0.8 kg/m 2. The 120 mm thick panels are hollow and can be filled with in-situ plain or reinforced concrete to increase the strength. A typical cross section of the panel is illustrated in the Fig. 1. Length 250mm Thickness = 120mm 94mm Gypsum Plaster 13mm thick flange 20mm thick web 230mm Reinforcement by chopped glass fibers Figure 1. Cross section of GFRG wall panel Wu and Dare (2004) have carried out axial and shear load tests on GFRG wall panels of standard 2.85 m height. The width of panel specimens was 1.02 m for axial load tests, 1.52 m and 2.02 m for shear load tests. They have reported that under axial load, unfilled GFRG wall panels failed due to plaster crushing, irrespective of the eccentricity of axial load. The concrete filled specimens all failed due to buckling and flexural tensile breaking of the GFRG walls. The failure load was governed by the eccentricity and support conditions. The compressive strength of unfilled wall panels was governed by the plaster strength and that of concrete filled panels was governed by out-of-plane buckling. The axial load carrying capacity of concrete filled wall panels was only affected by the axial load eccentricity and support conditions. The failure mode for shear load specimens of concrete filled walls was due to the longitudinal tearing of the GFRG panels, which is very different from the failure mode of a traditional RC wall. As a result, the shear strength is governed by the strength of the GFRG panels and was not affected by the

strength of the concrete infill. Typical shear failure modes for unfilled panels and concrete filled panels are shown in the Fig. 2. (a) Unfilled panel Diagonal cracks (b) Unfilled panel End crushing (c) Concrete filled panel Vertical cracking Figure 2. Typical failure modes for GFRG wall panels subjected to shear (Wu and Dare, 2004) Wu (2004) has reported that there are two types of shear failure modes in a building constructed with GFRG walls. The first mode is the shear failure of the panel itself, and the second is shear sliding at the interface of a wall and the floor slab. The continuity of longitudinal reinforcement at the horizontal joint may affect the shear strength of both the failure modes. Mechanical properties of the GFRG panel, as reported by Wu and Dare (2004) are shown in Table 1. Axial load capacity of wall panels against buckling are estimated and shown in the Table 2 and the in-plane lateral load buckling capacity is shown in Table 5. It is found that the Poisson s ratio of the wall panel is approximately equal to 0.2 from experimental results. The modulus of elasticity of the panel considered is 3000 MPa. Estimation of GFRG Wall Panel Capacities In the present study an attempt is made to estimate for design purposes the capacities of GFRG wall panels under (i) Axial loads, (ii) Axial load with out-of-plane bending (iii) Out-of- Plane bending capacity (iv) Axial load and in-plane bending moment and (v) Capacity of wall panel due to shear load.

Table 1. Mechanical Properties of GFRG Building Panel (Wu and Dare 2004) Mechanical Property Characteristic Value Remarks Unit Weight 40 kg/m 2 Uni-axial Compressive 160 kn/m Strength Uni-axial Tensile Strength 35 kn/m Unfilled Single leaf GFRG Panel. Elastic Modulus 3000 6000 MPa Coefficient of Thermal Expansion 12 x 10-6 mm/mm/ 0 C Water Absorption < 5% By weight after 24 h of immersion Thermal Resistance 0.36 m 2 K/W Unfilled Panel Sound transmission coefficient 28 45 Unfilled panel Concrete filled panel Fire Resistance Level > 3 h For Structural adequacy Axial Load Capacity While assessing the axial load carrying capacity of the wall panels a minimum eccentricity causing out of plane bending is accounted for. As per standards such as IS 456 (2000), the design of reinforced concrete walls should take into account the actual eccentricity of the vertical force subjected to a minimum value of 0.05 times the wall thickness t (6 mm for t = 120 mm). According to masonry design codes such as IS 1905 (1987), the design of a wall shall consider appropriate eccentricity, which in no case shall be taken to be less than t/24 (5 mm for t = 120 mm). In the case of wall panels supporting floor slabs from one side, the eccentricity to be considered should be more than the minimum values indicated above. It is recommended that a value of minimum eccentricity equal to t/6 (20mm for t = 120 mm) shall be considered conservatively. Additional value of eccentricity may be considered when the out of plane bending is explicitly involved. The characteristic values of axial compressive strength of GFRG wall panels are obtained from the compression test results on 2.85 m full height panel subjected to eccentric loading. In general, it is conservative to assume pinned-pinned condition as shown in Fig. 3. It may be noted that for design purposes, the characteristic values should be divided by partial safety factor 1.7. Finite element analysis of the wall panel, using plate-shell elements to model both flanges and webs, was carried using the SAP 2000 NL software. These numerical analysis results are compared in Table 2 with the experimental results reported by Wu and Dare (2004). It is seen that the numerical results are comparable with the experimental results for the 1.02 m panel. The axial load carrying capacity of the unfilled GFRG panels of widths 1.52 m and 2.02 m, estimated by finite element analysis are also shown in the Table 2.

Table 2. Axial Load Carrying Capacity of Unfilled GFRG Wall Panels Width of Numerical analysis Results (kn) Experimental Results** (kn) Panel (m) e = 0 e = 6mm (Minimum) e = 20 mm e = 0 e = 20 mm 1.02 173.7 168.7 158.1 132.4 166.7 119.6 166.7 1.52 245.3 252.4 230.1 2.02 328.7 319.6 300.0 e = Eccentricity ** Wu and Dare (2004) e P 2850 mm Figure 3. Experimental set- up for Pinned-Pinned panels The same finite element model was used to estimate the elastic critical buckling load of the wall panel, and the results are listed in Table 3 for different widths of the wall panel. These results indicate values much higher than those shown in Table 2, confirming that buckling is not a likely mode of failure, as evidenced by the testing (which showed crushing of plaster). Table 3. Buckling Load Values When the Wall is Subjected to only Axial Load Width of GFRG Wall Panel (m) Buckling Load P cr (kn) 1.02 622 1.52 926 2.02 1233

Out-of-Plane Bending Capacity The out-of-plane flexural strength of 120 mm thick GFRG wall panel without filling is shown in Table 4. From the test results, it is found that filling without reinforcement does not improve the out-of-plane moment capacity of the panel. Table 4. Out-of-plane flexural capacity of Unfilled / Concrete filled Panel without Steel Reinforcement Property Ribs parallel to span Ribs perpendicular to span Out-of-plane moment capacity (knm / m) 2.1 0.88 In-Plane Bending Capacity GFRG wall panels can be used as load bearing walls in multi storied buildings capable of resisting fairly large lateral load. Each wall can act as a shear wall resisting vertical load, inplane bending and shear. Invariably, such a wall shall be infilled with reinforced concrete. The following simplified procedure may be used to calculate the ultimate in-plane flexural strength of concrete filled GFRG wall panel. 1. Assess the stress distribution along the cross section of the wall panel based on linear elastic assumption. σ = P M y A ± I (1) 2. Based on the stress distribution from the Eq. 1, there are two different cases to be considered. (a). The whole cross section is under compression or there is no tensile stress in the cross section (σ 0) compare the maximum value of σ in the cross section with the compressive strength of wall panels given in Table 1. If the calculated stress is less than the design compressive strength of the wall, the design is safe otherwise redesign is required. (b) If tension exists in the cross section (σ < 0) go to step 3. The unfilled and concrete filled GFRG wall panel without continuous reinforcement in the cores is not able to transmit tension between floors, therefore case (b) is not applicable to unfilled or concrete filled GFRG wall panel without continuous longitudinal reinforcement. 3. When tension exists in the cross section, the flexural strength can be calculated using the following assumption.

(a) The contribution of the panel to ultimate strength in tension and compression is neglected and the system is treated as filled concrete with concrete effective only in compression and the reinforcement bars in tension. (b) Tension reinforcement (full length bars) are assumed to act as unbonded bars with constant stress, limited to 90 MPa in the entire tension zone (assuming lack of bond between the infilled concrete and the wall panel). The assumed stress distribution across the cross section of a GFRG wall panel is shown in Fig.4. From the test results, it has been found that there is practically no bond between concrete and GFRG wall panel. It is assumed that all reinforcing bars are subjected to same stress and that this stress is limited to the following value based on the studies in prestressed concrete section with unbonded tendons. P u M u D x u D 0.5D x u 0.42x u T C u = 0.36f ck bx u x i Figure 4. Stress Distribution across the GFRG Wall Panels under Axial Load and in-plane Bending Moment. Tensile stress in steel rod, f st 0.85 f ck = 70 + in N/mm 2 (2) Ast 100 bd p Equating forces: P = 0.36 f bx f A (3) u ck u st sti i= 1 where A sti is the area of the i th bar located at a distance x i from the centre. n Equating moments, u n st i= 1 sti ( D / 2 xi ) + 0.36 f ck xu ( D / 2 0. xu ) M = f Σ A 42 where x i is considered to be positive if it is on the tension side of the mid depth. (4)

From the Eqs. 3 and 4, the value of x u and A sti can be determined by trial and error. Alternatively, P u M u interaction curves may be generated for a given panel with infill concrete (f ck ) and given area of steel per cavity (A st ). Such an interaction diagram (using non-dimensional coordinates) has been generated and is shown in Fig. 5. The value of p/f ck can be obtained from this diagram and the suitable bar reinforcement can be identified. It may be noted that minimum eccentricity requirement should be satisfied. 0.50 0.45 0.40 0.35 0.30 P u /f ck bd 0.25 0.20 0.15 0.10 0.05 0.00 p/fck = 0.005 p/fck = 0.01 p/fck = 0.015 p/fck = 0.02 0 0.01 0.02 0.03 0.04 0.05 0.06 M u /f ck bd 2 Figure 5. Interaction diagram for panel subjected to axial load P u and in-plane bending moment, M u Shear Capacity of Panels Wu and Dare (2004) have reported that in all of the shear load tests on unfilled panels, there were visible 45 shear cracks, developed before the peak load was reached, as shown in Fig.2(a), and shear strength varies from 19.1 kn/m to 24.5 kn/m. Using strength of materials approach, the capacity of unfilled panels under shear load can be assessed as follows. b Capacity of unfilled panel under shear load = 2 t fσ t cos θ where b = Width of wall panel, θ = Inclination of crack with respect to horizontal axis, t f = Thickness of flange of the wall panel, σ t = Permissible tensile strength of wall panel. This capacity works out to 39 kn/m for a GFRG panel of 1.02 m width.

Buckling Capacity under In-Plane Shear Load The possibility of buckling failure under shear loading was investigated in the present study through numerical analysis using SAP 2000 NL. The results obtained are shown in Table 5, corresponding to three widths of wall panel. The values of lateral load obtained (262 to 596 kn) are significantly higher than the capacities reported by Wu and Dare (2004). Hence it is clear that buckling mode of failure is unlikely to occur not only under axial load but also under shear loading for the unfilled GFRG wall panels. Table 5. In-Plane Buckling Capacity due to shear Load alone Width of Wall Panel (m) Buckling Lateral Load V cr (kn) 1.02 262 1.52 425 2.02 596 Conclusions Axial load carrying capacity of unfilled GFRG wall panels, of various widths when subjected to eccentric loads, is estimated using numerical analysis. The lateral load carrying capacity of panels is also estimated. A simplified procedure has been suggested for assessing inplane flexural strength of concrete filled wall panels. For a given force demand, reinforcement required for a concrete filled GFRG wall panels can be obtained using interaction diagram that has been developed. Using simple approach, the capacity of unfilled panels under shear load is estimated. It is also established by comparing the results of finite element buckling analysis with the available experimental results, that failure of the GFRG wall panel does not occur due to buckling, on account of in-plane axial and shear loads, as the critical loads are much higher than the actual capacities. References IS: 456-2000, Plain and Reinforced concrete - Code of Practice, Bureau of Indian Standards, New Delhi, India. IS: 1905-1987, Code of Practice for Structural use of Unreinforced Masonry, Bureau of Indian Standards, New Delhi, India. Paulay T., and Priestley M.J.N., 1992. Seismic Design of Reinforced Concrete and Masonry Buildings, John Wiley & Sons, New York, USA. SAP 2000 NL. Structural Analysis Program (Static and Dynamic Finite Element Analysis of Structures), Computers and Structures Inc., Berkeley, CA, USA. Wu, Y.F. and Dare, M. P., 2004. Axial and Shear Behavior of Glass Fiber Reinforced Gypsum Wall Panels: Tests. Journal of Composites for Construction, ASCE, 8 (6): 569-578. Wu, Y. F., 2004. The effect of longitudinal reinforcement on the cyclic shear behavior of glass fiber reinforced gypsum wall panels: Tests. Engineering Structures, ELSEVIER, 26 (11):1633-1646.