PID Pumping with a NEMA 4X SMVector Drive

Similar documents
MC Series Drives. Flexible, simple, rugged, robust! Phone: Fax: Web: info@actechdrives.

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

Specifying a Variable Frequency Drive s

GPD 506/P5 Start-up Procedure and Checklist

NX Series Inverters. HVAC Pocket Programming Guide

A1000 Cheat Sheet (Open Loop Vector)

Operational Overview and Controls Guide

VLT 6000 HVAC. Contents

PRODUCT PROFILE FEATURES

PID Control. Proportional Integral Derivative (PID) Control. Matrix Multimedia 2011 MX009 - PID Control. by Ben Rowland, April 2011

Speed Control Relays SX2

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

*.ppt 11/2/ :48 PM 1

Installation & Operation Manual for Energenics Air-Flow Optimizer

Centrifugal Fans and Pumps are sized to meet the maximum

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

vacon x series rugged drives for the real world

AC ADJUSTABLE SPEED DRIVES MICRO SERIES INVERTERS

Heating, air-conditioning, cooling

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification


Centro-Matic Automatic Lubrication Systems System Controls

Brushless DC Motor Controller Product Specification Assembly 025F0129

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

PIEZOMETER AIRFLOW MEASURING RING

Introduction to Process Control Actuators

In-Line Electronic Flow Switches

Electronic Flow Switches

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

32VFD Variable Frequency Drives for Centrifugal Chillers

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

Troubleshooting with ABS Service Data Kit

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.

NC-12 Modbus Application

A4 Air Conditioning Control Circuit Troubleshooting Rev 7, 6/18/2009

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April SFC132089M0201 1

Tubular Analog model resolution: 0,5 mm (SLOW mode), 1 mm (FAST mode) Right angle Repeatibility: 0,7 mm Vdc

HEAT HEAT COOL HEAT PUMP COOL

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

INSTALLATION & SERVICE MANUAL. Display Panel

Reliance Electric GV3000/SE Industrial AC Drive

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

Telefon (+45) Telefax (+45) Installation and operating manual

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

PC BASED PID TEMPERATURE CONTROLLER

Industrial Steam System Process Control Schemes

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Commercial Refrigeration Temperature and Defrost Controls

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

Installation, Operation and Maintenance Manual

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

TwinCAT NC Configuration

Application Engineering

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

key- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

APPENDIX. SureSERVO QUICK START GUIDE. In This Appendix... Quick Start for SureServo Drives...A 2. Tuning Quick Start for SureServo Drives...

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

REGAL-BELOIT. Installation and Operation Manual. Variable Speed AC Motor Drives. Micro and PowerWash Series

In-Line Electronic Flow Switches

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

Basics electronic speed Governor

Electronic, Digital and Mechanical Vibration Switches

Sanitary Type Electronic Flow Switches

Process Control Primer

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

ACS800. Master/Follower Application Guide Supplement to Firmware Manual for ACS800 Standard Application Program

Drives 101. Functions of an Adjustable Frequency Drive (AFD) This lesson covers the basic functions of an Adjustable Frequency Drives (AFD).

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

Unidrive M Energy Savings

Technical Guide No High Performance Drives -- speed and torque regulation

THE INPUT/OUTPUT SYSTEM. Key Points

HVAC Processes. Lecture 7

Number 1 in efficiency

TR1 Series VFD. Variable Frequency Drives TR1-SLB005-EN

stable response to load disturbances, e.g., an exothermic reaction.

smd Series Drives Modbus Communications Reference Guide

Application Note AN-SERV-006

VLT AutomationDrive for Marine winch applications

Signature and ISX CM870 Electronics

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

The Do s and Don ts of Pressure Transducers

Introduction. Section 2. Introduction 2-1

Cat Electronic Technician 2015A v1.0 Product Status Report 6/3/2015 4:41 PM

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Electronic Control Devices The European Product Catalogue 2007

MC1000 Series Installation and Operation Manual

Transcription:

PID Pumping with a NEMA 4X SMVector Drive Pump and fan applications make up the majority of the PID applications that employ the SMVector drives. The process feedback used most often is pressure. This is an application example of a SMVector drive in a pumping application using pressure control and demonstrating the capability of a wash-down enclosure. Note: for general PID reference, please refer to application note AN0043: Using the SMVector Drive for PID Process Control. System Overview This demo uses an Emerson pump spraying water through 4 nozzles; the pressure in the water lines is measured by an Ashcroft pressure gauge and transducer. The water flow can be increased or decreased using a valve controlling flow in two of the spray nozzles, this change in flow will also cause a change in pressure causing the SMVector s PID loop to change the drive s output to maintain the system s set point. The NEMA 4X enclosure is demonstrated by spraying the drive with water coming from the 4 nozzles fed by the pump. SMVector Demo Major Demo Components Drive: Lenze ESV371N01SXC SMVector Drive 120V in, 230 V out 0.5Hp, rated to 2.4A Pump: Emerson Pump and motor 0.5Hp, 230V, FLA 1.8 60Hz, 3450 rpm Pressure sensor: Ashcroft GC317M02B1NF4100G GC31 Pressure gauge and transducer 0-100 psi 1-5Vdc analog output Drive options: ESVZXK1 Remote keypad w/ communication module Figure 1: Close-up SMV Shower Demo 1 AN 0053A April 2013

System Block Diagram Figure 2 illustrates the block diagram of the SMV Shower Demo in a PID pumping application. SMVector Drive Process PID Setpoint SMV Remote Keypad Σ - PID Algorithm VFD PI PID Feedback (1-5Vdc representing pressure) Symbol Key: Centrifugal pump & motor PI Pressure indicator Manual valve Electrical User accessible control & display Spray nozzle Water Figure 2: SMV Shower Demo Block Diagram Shower Demo Layout Figure 3 illustrates the layout of the SMV Shower Demo and identifies the major components. Figure 3: SMV Shower Demo Layout 2 AN 0053A April 2013

Drive Wiring Figure 4 provides the simplified wiring diagram of the SMV Shower Demo. ESV371N01SXC Control Terminals Power Terminals 1 2 5 6 25 4 11 13A 13B 13C 14 30 16 17 L1 L2 N PE U V W P3 120 Vac M Keypad Module 1 2 3 4 5 Com Aout P+ Ashcroft GC31... 2 TXA TXB 11 Remote Keypad Figure 4: SMV Shower Demo Wiring Drive s NEMA Rating The SMVector drive in this application is a wash down enclosure. The last letter "C" In the part number ESV371N01SXC, designates the enclosure type. In this case, a NEMA 4X indoor enclosure with convection cooling. Figure 5 (courtesy of: http://www.nema.org) provides a summary of the conditions different enclosure types protect against. The 4X rating is protection against accidental contact, dust, direct water, and corrosive agents. The SMVector 4X indoor enclosure is made from an ABS plastic. This drive is specified as indoor duty only because the ABS plastic used is not resistant to UV light and can warp with sudden temperature swings. Figure 5: Table 1 from NEMA 250-2003 - Enclosure Types 3 AN 0053A April 2013

When installing the drive and wiring it is important to include glands. The glands allow wiring to get to the drive, but still maintain a seal against the environment. The glands are installed into the knockouts in the drive enclosure and have a rubber gasket that is tightened around any incoming or outgoing wires. Drive parameters Figure 5: Glands maintain seal For this specific example, the following SMV drive parameters must be set accordingly. P100= 02 Drive set for remote keypad start/stop P102= 15 Min frequency to 15Hz P103= 75 Max frequency to 75Hz P104= 10 Accel to 10s P105= 10 Decel to 10s P108= 75 Motor overload = (motor FLA / drive output I) * 100 P121= 06 Terminal 13A activates PID control and makes remote keypad PID set point source P156= 01 Analog input on terminal 5 will look for a 0-5V signal P200= 01 Normal acting PID P201= 01 PID feedback set to terminal 5 (analog Vin) P204= -12.5 Min value for scaling of drive to PSI from transducer P205= 50 Max value for scaling of drive to PSI from transducer P207= 6 PID Proportional gain P208= 0.5 PID Integral gain P209= 0 PID Derivative gain P241= 10 Time delay for entering sleep mode P243= 40 Pressure in PSI for entering sleep mode P244= 01 Drive will enter sleep mode (stop motor) if feedback > 243 P246= 0.2 Pressure in PSI for leaving sleep mode P247= 1 Drive will leave sleep mode (start motor) if feedback < 246 P400= 01 Activates communication for remote keypad 4 AN 0053A April 2013

Explanation of parameters and setting up the PID loop In this application the pressure in the water lines increases the faster the pump spins. This is an example of normal acting PID control. In a normal acting system, as the system feedback increases the motor should slow down, maintaining the process set point. Normal acting PID is set on P200 with a value of 01. With P200 set, when one of the digital inputs set to an auto-reference is activated, the drive will enter PID mode. Setting up the digital input for auto-reference in this particular application is discussed in the next section. Process feedback and set point In a PID system there are two signals required: a system set point and a system feedback. The PID set point tells the PID control in the SMVector what pressure should be maintained. The PID feedback is a signal that tells the PID controller in the SMVector what the actual pressure in the system is. The PID loop in the SMV compares the two signals and adjusts the speed of the motor (using the VFD portion of the SMV) to maintain zero error between the set point and feedback. In this demo, the system feedback is setup with P201, P156, P204 and P205. The Ashcroft sensor used has a total range of 0-100 psi, but has been set for 0-50 psi; the sensor s output to the SMVector is a 1-5Vdc signal. P201 tells the drive to look at terminal 5 to read the system pressure as an analog voltage input, P156 means the input will be read as a 0-5Vdc signal. P204 and P205 are used to scale the feedback so the drive can read and display the feedback as PID units (psi in this case). P204 has been set to -12.5 psi and P204 is set to 50 psi. This means the drive reads 0 psi at 1Vdc and 50 psi at 5Vdc (transducer output is 1-5V). The other required signal is the system set point. This has been setup by P121 = 06. That means that the jumper wire between terminal 4 and 13A does two things. First of all this activates the PID loop, and the secondly this selects the remote keypad as the set point source. This means the pressure maintained by the PID loop can be changed on the SMV remote keypad. Figure 6 shows where the set point and feedback are in the block diagram for a PID loop. Setpoint from keypad (Pressure to be maintained) P t + I r DRIVE - ERROR o SPEED D COMMAND C on l l e r FEEDBACK Process feedback (actual line PSI) Figure 6: Setpoint and Feedback in the PID Loop Sleep mode Sleep mode is part of the PID control of the drive. This can be used to start and stop the motor if the process is getting outside of the acceptable operating range. Is this case if the water pressure gets too high the drive will shut the motor off and restart the system once the pressure has dropped. P244 has been set to 01; this means if pressure gets above a threshold for a set amount of time, set in P243 and P241, the drive will go to sleep. P243 has been set to 40 psi for the pressure limit; P241 is a time delay of 10 seconds for entering sleep mode. P247 sets up the drive to leave sleep mode; with P247 = 01 the drive will leave sleep mode if the pressure drops below a value set in P246. P246 is set at 0.2 psi, meaning once the water pressure is below 0.2 psi the drive will restart the pump motor. 5 AN 0053A April 2013

PID gain values PID control has 3 gain values associated with it: proportional gain (P207), integral gain (P208), and derivative gain (P209). These gain values mathematically tell the PID loop in the drive what the physical process actually is. This allows the drive to speed up or slow down the motor to maintain pressure at the desired set point. The gain values affect the system in different ways. Proportional gain is the main value; it is a constant value used a multiplier for the error between the feedback and set point. The integral gain is a time constant in seconds for the integration of the error signal. The error is summed over a period of time, this helps remove error between the feedback and set point that can t be taken care of with proportional gain alone. The final gain value is derivative gain, with derivative gain the PID loop is looking at the rate of change of the error signal. D gain is used in systems that have very rapid changes in the process that the PID loop needs to respond to quickly. For most applications in which the SMVector is as a PID controller, derivative gain is left set to 0. Since D gain is used to respond to rapid changes in a process this value can easily make a system unstable. For a PID system to operate properly the gain values of the system must be tuned, because every system is physically different the values can be drastically different. One of the simplest ways to tune P207, P208, and P209 is to use a guess and check method. Tuning the PID loop In this demo, use the keypad to set the desired pressure, in this case 25 psi was used. Look at the actual value measured for pressure, if this is below 25, increase the P gain (P207) until 1: the system reaches a stable 25 psi or 2: the system becomes unstable. You can tell the system is unstable in a couple ways. One is watch the pressure, if the pressure is oscillating up and down, the P gain is set too high; the other is the motor speed. P527 show the actual output frequency, small fluctuations in speed are not a problem for most systems, however large changes can cause the drive to trip into an overload condition because the oscillation in speed uses more current. If increasing P207 has made the system unstable, decrease P207 to about P207*.90 or P207*.85, the system should be stable at this level, but the actual pressure may not be equal to the set point. This is where the integral gain (P208) can be used. Increase P208 until the system pressure reaches the 25 psi (set point). The I gain can stably remove the last bit of error because it looks at the error over time. For the final gain value, derivative gain (P209), leave that set at 0. Summary This application note is a specific example of using an SMVector drive as a PID controller to control the pressure in a pumping system. The SMVector used in conjunction with an Ashcroft sensor and an Emerson pump/motor combo is used to control the PSI of water lines feeding spray nozzles with a variable flow rate. The wiring and parameters are specific to this set up but can be used as a guideline for any pumping system. The installation and use of the drive in a wash-down environment is also demonstrated by spraying the drive with the water flow controlled by the drive s PID loop. 6 AN 0053A April 2013