WATER TREATMENT PROGRAM FOR GLYCOL SYSTEMS

Similar documents
CONVERTING A CLOSED-LOOP WATER SYSTEM TO A GLYCOL SYSTEM

2014 Service Technician Training Program Closed Loop Systems

Guidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids

NORKOOL Industrial Coolants

Dispelling the Myths of Heat Transfer Fluids. Kevin Connor The Dow Chemical Company

DOWFROST GEO 20: Propylene Glycol-Based Heat Transfer Fluid for Geothermal Heat Pump Systems

ALS TRIBOLOGY Engine Coolant Reference Guide

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

Troubleshooting Salt Generators

A Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE

Safety Data Sheet Avesta Neutralization Agent 502

Water Treatment Program Manual

PEROXIDE SAFETY DATA SHEET (60% H2O2) Safety Data Sheet

MAC-120HE-01 Air-Cooled Chiller

Best Practice in Boiler Water Treatment

EVERYTHING YOU WANTED TO KNOW ABOUT GLYCOL A Brewery Glycol System Guide. Updated

MATERIAL SAFETY DATA SHEET REVISION DATE: 02/01/2005

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Stenner Pump Chlorinator Installation & Start Up Guide

Some Criteria for Choosing a Steam Boiler for a Microbrewery

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

BORYGO EKO car radiator fluid

A Guide to Trouble-Free Cooling Towers

DuPont SUVA 123 Refrigerant

Facilities Maintenance Standards rev

Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources

Fundamentals of Hydronic Design

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

Do not use the Solar Boiler system to heat any treated water system, such as pools, directly.

Defining Quality. Building Comfort. Heating and Cooling Coils

Material Safety Data Sheet Extinguishing agent Forrex AB Identification of the chemical and responsible company

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:

Trifectant Tablet Page 1of 5 Trifectant Tablet SAFETY DATA SHEET (2) HAZARD(S) IDENTIFICATION

Steam System Best Practices Condensate System Piping

Domestic Chemical Water Treatment Manufacturers Association

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

* * * EMERGENCY OVERVIEW * * * High pressure gas. Can cause rapid suffocation. Can increase respiration and heart rate.

MATERIAL SAFETY DATA SHEET CHAINDRITE EXTRA STRENGTH CRAWLING INSECT SPRAY

The National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio

Version 1.4 Print Date 01/14/2008 Revision Date 01/14/2008. Component CAS-No. Weight %

VACUUM REFRIGERATION SYSTEMS

HOT WATER SYSTEMS CONTENTS

Calculating System Flow Requirements

MATERIAL SAFETY DATA SHEET

Swallowed Do not induce vomiting give 250 ml water to drink. Seek immediate medical attention.

Product Name: John Deere Cool Gard II Premix (TY26575, TY26576, TY26577, TY26578) Product description: Ethylene Glycol based Antifreeze/Coolant

Material Safety Data Sheet

Operators manual Basic water heater

ENERGY RETROFIT PROGRAM

Ergolid EKO antifreeze fluid

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

TABLE OF CONTENT

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Element D Services Plumbing

steam centre of excellence Steam Boiler System Optimization

OIL CONDITION MONITORING: AUTOMOTIVE ANALYSIS

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

NYC Department of Education Building Condition Assessment Survey BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

Material Safety Data Sheet

Material Safety Data Sheet

31 Tips on How to Apply Antifreeze to a Hydronic Heating System, and How to Maintain it Afterwards

Mechanical Systems Competency 1.20

Material Safety Data Sheet

Pure Water. Isn t Hard to Find

UNDERSTANDING HOT WATER SYSTEMS IN THE HOME

This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries.

Version 1. Print Date 12/01/2009 Revision Date 11/30/2009 MSDS Number SITE_FORM Number

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET

BASIC WATER TREATMENT OF STEAM BOILERS

Attachment J-C18.1. HVAC Work Instructions

Drinking Water Distribution Pipes

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Magnesium Ascorbyl Phosphate msds

This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries.

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Material Safety Data Sheet POOL TIME TOTAL ALKALINITY INCREASER

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas

MATERIAL SAFETY DATA SHEET

Propane Fuel. Material Safety Data Sheet

This SDS adheres to the standards and regulatory requirements of Great Britain and may not meet the regulatory requirements in other countries.

HS-901(A) BASIC STEAM HEATING SYSTEMS

Sodium Sulphite Anhydrous

Steam Coil Installation, Operation and Maintenance

Keeping Your Swimming Pool and Spa Healthy Environmental Health Guide

IMO Approved Tank Cleaning Chemicals

Indirect-Fired Water Heaters

Zenith Solar thermal 4.5m pump station Installation manual

Product Bulletin INTEROX HYDROGEN PEROXIDE

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Thermo Siphon Solar Systems

PLBG/GAS SAFETY Information Bulletin

21.1 Functions, Basic Configuration, and Interfaces

Autofoam SAFETY DATA SHEET

Ecodan Installation Manual

MATERIAL SAFETY DATA SHEET

Transcription:

WATER TREATMENT PROGRAM FOR GLYCOL SYSTEMS Presented at ALBERTA Public Works, Supply & Services Property Management Operations Division Water Treatment Co-ordinators' Meeting #12 Edmonton, Alberta October 24th 1990 by G.F. Yuzwa, P.Eng. H2O ENGINEERING LTD. 539 Edgemont Bay N.W. Calgary, Alberta T3A 2K7 October 22nd 1990

DESCRIPTION A glycol system (see schematic diagram overleaf) is a cooling or heating system in which an ethylene or propylene glycol-water solution is circulated throughout the building or through cooling/heating coils in an HVAC system in order to provide space cooling/heating without the inherent risk of freeze damage. The principal components of these systems consist of a cooling/heating source (ie., chiller, boiler, converter, etc.), automatic air vents, circulating pumps, flow switch, expansion tank, heat exchangers, either a water make-up line (containing a water meter, backflow prevention device & pressure regulator) or a pumping system to introduce the glycol/water solution into the system, and interconnecting piping, valves & fittings of mixed iron, copper & bronze metallurgy (note that galvanized piping is not recommended in glycol systems since its presence may lead to the precipitation of certain components in the glycol's corrosion inhibitor). After the system is initially charged with the desired glycol-water solution, the quantity of make-up water should be negligible. Therefore, glycol systems are referred to as being closed systems. PAGE 2

SCHEMATIC DIAGRAM OF A TYPICAL GLYCOL SYSTEM PAGE 3

OPERATION and MAINTENANCE Industrial grade glycol is composed of either ethylene or propylene glycol, a corrosion inhibitor, and water. Note that automotive grade glycol should not be used in commercial or industrial glycol systems because their corrosion inhibitors have a limited useful life and they contain silicates which can foul or plug the system. If there is a concern that the glycol may be orally consumed, an industrial grade propylene based glycol should be used because of its low oral toxicity, otherwise an industrial grade ethylene based glycol is the preferred choice. Since dissolved oxygen in the system will decompose the ethylene/propylene glycol into organic acids, particularly at elevated temperatures, thus causing corrosion & fouling, both types of glycol contain corrosion inhibitors. The corrosion inhibitor in propylene based glycol consists of dipotassium phosphate in order to maintain the low oral toxicity of this product, whereas the corrosion inhibitor in the ethylene based glycol consists of a proprietary mixture of numerous corrosion inhibitors. The water which is used in both types of glycol systems must be of the highest possible quality (ie., softened, demineralized, deionized, boiler condensate), otherwise the hardness and corrosive salts in most domestic water supplies will deplete the inhibitor concentration in the glycol. Once the system is filled with the glycol-water solution, every effort must be made to minimize the entrance of additional hardness salts and dissolved oxygen into the system by the operational type methods indicated overleaf. PAGE 4

1. Limit the amount of make-up water as follows: (a) ensure that a water meter is installed in the make-up line; (b)locate & repair system leaks immediately; (c) adjust pump seals with packing so that there is minimum leakage; (d) ensure that pumps with mechanical seals have zero leakage; (e) do not drain & fill the system seasonally; (f) minimize the amount of glycol-water solution lost from the system during maintenance, water sampling. 2. Ensure that there is a positive pressure at the top of the system at all times by maintaining a minimum static system pressure according to the following equation by the addition of air to the expansion tank: P = (H/2.31) + 5 where P: pressure at the circulating pumps with the circulating pumps shut off, psig; H: elevation of the system piping above the circulating pumps, feet 3. Ensure that the expansion tank is properly sized so that there is water in it at all times. 4. Replace faulty automatic vents as required. 5. Confirm the operation of the make-up water meter by noting the changes in its reading before & after such activities as maintenance, sampling, etc. PAGE 5

In order to prevent excessive decomposition of the glycol into organic acids, the operating bulk temperature of the glycol-water solution must be limited to 120 C (250 F). CHEMICAL TREATMENT In order to provide freeze protection (ie., a glycol concentration which is sufficient to prevent the formation of ice crystals at the lowest temperature experienced by the fluid) down to -35 C, the acceptable glycol concentration range for cooling systems which are operational year round and for heating systems is 48-85 vol% for ethylene glycol systems and 49 vol% minimum for propylene glycol systems; however, for the economic reasons, the preferred range is 48-52 vol% for both types of glycol systems. In order to provide burst protection (ie., a glycol concentration which is high enough to prevent bursting of pipes and other mechanical damage, but not necessarily high enough to keep the fluid pumpable) down to at least -35 C, the acceptable ethylene glycol concentration range for cooling systems which are operational only during the summer months is 30-85 vol%; however, for economic reasons, the preferred range is 30-35 vol%. Similarly, the acceptable propylene glycol concentration range is 35 vol% minimum, but the preferred range is 35-40 vol% for burst protection down to -35 C. If the glycol concentration is less than approximately 20 vol%, there is a possibility of bacteria contamination because glycol at low concentrations is a nutrient source. PAGE 6

The following equation may be used to calculate the approximate amount of glycol required to increase the glycol concentration in a system: G = V x (CD-CP)/(100-CP) where G: volume of present glycol solution to be drained from the system and the volume of fresh concentrated glycol to be added to the system, litres CD:desired glycol concentration, vol% CP:present glycol concentration, vol% V: volume of the system, litres In order to provide adequate corrosion protection of the glycol system, the reserve alkalinity based on a glycol concentration of 100% (ie., RA[100%]), which is an indication of the inhibitor level, must be maintained at a level of at least 9.0 for all glycol concentrations by inhibitor additions as required. If the RA(100%) value is less than 9.0 in an ethylene glycol system, the following equation may be used to calculate the first estimate for the amount of inhibitor required to increase the inhibitor concentration: I = 1.75 x V/100 where I: volume of proprietary inhibitor, litres V: volume of the system, litres If the RA(100%) value is less than 9.0 in a propylene glycol system, food grade dipotassium phosphate must be added as required. PAGE 7

CONTROL TESTS In order to minimize fouling and/or corrosion of glycol systems, the following control tests must be performed (note that due to the more sophisticated nature of the chemical tests for glycol systems, the glycol, ph & reserve alkalinity levels in glycol samples are performed by the PWS&S Property Management, Operations Division Laboratory): 1. Document the make-up water meter reading at least once per month; 2. Document the glycol concentration in the system at least once per year; 3. Document the ph level in the system at least once per year; 4. Document the reserve alkalinity level in the system at least once per year; 5. Determine & document the visual appearance of the glycol in the system at least once per month; 6. Document the system pressure at the circulating pumps with the circulating pumps shut off at least once per month. HANDLING and STORAGE The LD50 acute oral toxicities of ethylene and propylene glycols for rats are 6.1 gm/kg and 33.7 gm/kg respectively; therefore, both materials should be considered to be toxic when they are intentionally consumed in thirst quenching quantities. However, propylene glycol is considered safe for use in foods because of its low chronic oral toxicity, whereas ethylene glycol is too toxic for applications where there is a possibility of ingestion. PAGE 8

Both types of glycol produce a negligible degree of irritation upon eye or skin contact; therefore, washing the affected areas after contact is all that is required. Although there is no limit for the prolonged inhalation of propylene glycol mist, the limit of 50 ppm for the vapours of ethylene glycol suggests that leaking coils in HVAC systems should be repaired when there is a noticeable odour of glycol in the building. The freeze point of concentrated ethylene glycol is -17 C; therefore, containers of this fluid must be stored indoors. However, since the freeze point of propylene glycol is less than -50 C at all concentrations greater than 55 vol%, concentrated solutions of these fluids may be stored outdoors. The high flash points of 121 C & 101 C for the respective concentrated ethylene & propylene glycols should not present a problem under normal storage conditions, but if the ambient temperatures are greater than these limits, the glycol should be diluted to less than 80% since there is no flash point for either glycol type at these reduced concentrations. Ethylene and propylene glycol solutions are hygroscopic; therefore, their containers must be kept tightly sealed in order to avoid dilution of the glycol. PAGE 9