Installation Instructions

Similar documents
PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

Installation Instructions

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

Tablet Management Rack 16

ADSL Modem Installation Guide. Model # 36R515 Part # Rev. D Revision Date 12/2000. ADSL Modem Installation Guide

Energy Smart Electric Water Heater Controller

StructureScan HD Module. Installation Guide ENGLISH

Installation Instructions. Wireless Adapter/Repeater. Introduction Rev C

Manual. Simrad StructureScan LSS-1 Sonar Module. English

B890 4G LTE Smart Hub Getting Started Guide

INSTALLATION INSTRUCTIONS

Communicating Wall Control Installation Manual TSTAT0101SC

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

19 LED Tube Controller ORDERCODE 41003

High PoE Midspans NPD-6001A NPD-9501A. en Installation Manual

BroadBand PowerShield. User Manual

BOSE. Link AL8 HOMEWIDE WIRELESS AUDIO LINK

Installation Instructions

IMMS-CCC. IMMS-CCC Hardwire Central Interface. Installation Instructions

Installer Guide smart connect

Your safety and the safety of others are very important.

AXIS T81B22 DC 30W Midspan


AC-115 Compact Networked Single Door Controller. Installation and User Manual

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

PITE 3921 Battery Monitoring System User Manual P V1.0

AC1200 WiFi Range Extender

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

Owner's/Installation Manual

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

FUSION R400 RAID USB 3.0

Disclaimers. Important Notice

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

ITC-BTTN Cellular Bluetooth Gateway. Owner s Manual 1

T7560A,B,C Digital Wall Module

MAINTENANCE & TROUBLESHOOTING

OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER

MAINTENANCE & TROUBLESHOOTING

INSTALLATION GUIDE 1

Square D Clipsal C-Bus Network Analyzer

CRYPTOPAY QUICK START GUIDE

RouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP

MCR1900 Media Converter 19-Slot Chassis

Wireless LAN Outdoor Bridge Solution

ADM1TE 5/30A DIN rail single phase two wire energy meter

HLWLAN b/g/n Transceiver Kit

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

XTEND 900 MHZ WIRELESS MODEM For use with VEEDER-ROOT EMR³ DATALINK INSTALLATION INSTRUCTIONS Manual , Rev. B

Are apps available for Virtual Water Assistant? No. We use a mobile website.

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Universal Serial Bus (USB) to DH-485 Interface Converter

HP UPS R1500 Generation 3

Wireless Router Setup Manual

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

Installation Instructions

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Chapter 1 Connecting the Router to the Internet

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

, User s Manual

How To Wire Wireline Cable To A Cell Phone (New Zealand)

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

mysensors mysensors Wireless Sensors and Ethernet Gateway Quick Start Guide Information to Users Inside the Box mysensors Ethernet Gateway Quick Start

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT. Perfect for ANDROID TM

Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC

WF720 Wireless Home Phone User Manual

Power supply unit Model: PAC-SC50KUA

CABLE MODEM QUICK START

Installation Instructions for Alarm Module Kit A043F059

Advantium 2 Plus Alarm

AXIS 205 Network Camera Quick Installation Guide

G670 Intermittent Pilot Ignition Controls

Daily use. Never use alcohol or other solvents to clean any part of the loudspeakers!

InHome Water Leak Detection Package

Infinity C Reference Guide

4P H. Wireless LAN Connecting Adapter <BRP069A41> Installation Manual

BCS1 Bluetooth Aux Car Adapter Kit

Magnetek MLTX, SLTX and Pendant Battery Charger. Instruction Manual. NiMH Battery Charger (Smart Charger) For use in:

WPR400 Wireless Portable Reader

IMPACT ALARM SYSTEM FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION

VK-250 WARRANTY REGISTRATION FORM

Router Setup Manual. NETGEAR, Inc Great America Parkway Santa Clara, CA USA

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

USB/VGA Cat 5 UTP Console Extender

Ethernet Radio Configuration Guide

PCS300 Universal IP Reporting Module V1.0

INSTALLATION & SERVICE MANUAL. Display Panel

N300 WiFi Range Extender WN2000RPT User Manual

Dialog Telephone Interface Module Installation Sheet

AXIS 205 Network Camera Goes anywhere your network goes

PowerLogic Sub Meter Display (SMD and SMDOPN)

NX-591NE-GSM NetworX GSM 3G HSPA+ Module Installation Sheet

Arduino Wifi shield And reciever. 5V adapter. Connecting wifi module on shield: Make sure the wifi unit is connected the following way on the shield:

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

Transcription:

SYSTXCCSAM01 Infinity System Access Module Installation Instructions NOTE: Read the entire instruction manual before starting the installation. pointsett U.S. Pat No. 7,415,102 Fig. 1 - Infinity System Access Module SYSTXCCSAM01 TABLE OF CONTENTS A97040 PAGE SAFETY CONSIDERATIONS... 1 INSTALLATION CONSIDERATIONS... 1 INTRODUCTION... 2 Compatible Systems... 2 INSTALLATION... 2-4 Check Equipment and Job Site... 2 Component Location and Wiring Considerations... 2 Connect Power Source and Antenna... 3 Radio Installation and/or Test... 3 Install Components... 3 Connect Infinity Systems... 3 Connect Auxiliary Sensor... 3 System Start-Up... 4 PIN Number and Serial Number... 4 RS -232 CONNECTOR... 4 UPDATING SYSTEM PROFILE... 4 TROUBLESHOOTING... 4 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency or your distributor or branch for information or assistance. The qualified installer or agency must use factory -authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1. Recognize safety information. When you see this symbol the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and. These words are used with the safety -alert symbol. DANGER identifies the most serious hazards, which will result in severe personal injury or death. WARNING signifies hazards, which could result in personal injury or death. is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. INSTALLATION CONSIDERATIONS Before the actual installation of a System Access Module (SAM01) can begin, determine the mounting location. For previous generation UID/UIZ systems, only, a radio test must be performed with the System Access Module in the intended mounting location. See Step 4 to perform a radio test. The System Access Module is powered with an independent 24 VAC, 40 VA transformer. An accessory plug -in transformer is available to order through Replacement Components (Part No. SYSTXNNXFM01). When using an accessory, plug -in transformer, a 120VAC supply must be near the mounting location of the System Access Module. Provisions must be made to secure the transformer to the outlet, due to its weight. The D -wire (24 VAC) from the Infinity system MUST NOT be used to power the System Access Module. Use this instruction to guide the actual installation process after the Infinity system(s) have been installed. One SAM01 System Access Module is capable of handling two Infinity systems. on

INTRODUCTION The SAM01 is used differently for previous generation Infinity systems using the UID/UIZ wall controls, versus the newer Infinity Touch systems. For previous generation systems using the UID/UIZ wall controls, the SAM01 connects to the SkyTel/American Messaging wireless paging network and allows remote connectivity for up to two Infinity systems within the same building. The Infinity system owner as well as authorized dealer can monitor and control the system via the Internet. The coverage area available to applications using the SAM01for remote access is limited, since the System Access Module communicates through a two -way radio via the Skytel paging network. To check coverage, please visit: http://www.skytel.com/coverage/telemetry_coverage.htm for the particular installation site. The coverage must be listed as Full Service for the System Access Module to function properly. Please note that Skytel is continuously changing their service area so coverage may not be indicated by the web site for a particular area, or coverage may be discontinued at a later date. The SAM01 also provides an interface to Home Automation systems, utilizing the RS -232 serial port connection. The newer Infinity Touch systems, with version 08 or later software, utilize the SAM01 for ONLY interface to Home Automation systems, utilizing the RS -232 serial port connection. Use the Wi-Fi versions of the Infinity Touch wall controls when connection to the Internet is desired. For all systems, the System Access Module can also monitor a dry -contact sensor to provide a warning for the presence of water in the building, or some other use. If the sensor is active, the Infinity system will not be disabled or shut down. Compatible Systems The SAM01 is designed for previous generation UID/UIZ wall controls with version 12 or earlier software. When used with version 13, or later, UID/UIZ wall controls, or with the newer generation Infinity Touch (with version 08 software or later) certain features, such as the Off mode command, will not work properly. See the latest version of the SAM Remote Access Application Specification, available on HVACpartners, for more information. NOTE: The SAM01 is designed for operation with the previous generation UID/UIZ wall control systems. As such, it will operate as- is with the newer Infinity Touch systems, and may display status codes that are unique to the previous generation UID/UIZ systems, but are irrelevant when the SAM01 is used with the newer Infinity Touch systems. In addition, some features of the RS-232/ASCII home automation interface will NOT be available with the newer Infinity Touch systems. See the latest version of the SAM Remote Access Interface Specification, available on HVACpartners, for more details on the home automation interface. Computer Requirements (Previous generation UID/UIZ systems, only) The SAM01 uses a web -based application to control and monitor the Infinity system. This application (www.myinfinity.carrier.com) will work with any graphic user interface PC operating system (Microsoft, Apple, Linux). The web - -based application is optimized for use with Microsoft s Internet Explorer version 6 and above. Other web browsers are compatible with some possible screen formatting issues. NOTE: This web -based application for the SAM01 is NOT available for Infinity Touch systems. When using these systems, Internet access is achieved using the Wi -Fi version of the Infinity Touch control, and accessing the www.myinfinitytouch.com website. The SAM01 is designed for previous generation UID/UIZ wall controls with version 12 or earlier software. When used with version 13, or later, UID/UIZ wall controls, or with the newer generation Infinity Touch, certain features, such as the Off mode command, will not work properly. See the latest version of the SAM Remote Access Application Specification, available on HVACpartners, for more information. INSTALLATION Step 1 Check Equipment and Job Site INSPECT EQUIPMENT File claim with shipping company, prior to installation, if shipment is damaged or incomplete. Step 2 Component Location and Wiring Considerations WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death or possible equipment damage. Disconnect supply power before routing wire. NOTE: All wiring must comply with national, state, and local codes. LOCATING SYSTEM ACCESS MODULE When possible, select a location near the Infinity furnace or fan coil for the SAM01 where wiring from the User Interface, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily. However, if the furnace or fan coil is located in a basement, this may not be possible due to the strength of the radio signal from the SkyTel/American Message transmission tower. See Step 4 for testing the radio for signal strength. This restriction for radio signal strength does not apply for newer Infinity Touch systems. For previous generation UID/UIZ systems, only: Since the System Access Module (SAM) uses two -way radio, choose a potential mounting location that is as high and as close to outside walls or windows as possible to attempt to maximize radio coverage. The coverage is dependent on where the Skytel transmission towers are located. If one location does not work, try the opposite side of the structure to get the device in closer directional proximity to the transmission tower. Temporarily mount the System Access module in the intended permanent mounting location until the radio test has passed 100%. (See Step 4.) For all system types, the System Access Module is approved for indoor use only and should never be installed with any of its components exposed to the elements. The System Access Module may be installed in any area where the temperature remains between -4_F and 158_F (-20_C and 70_C) and there is no condensation. The cover must be installed to prevent damage from other sources. Do not locate where it will be accessible to children. The SAM should be mounted in the vertical position. Remember that wiring access and Skytel reception are the most important installation location considerations. ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in equipment damage or improper operation. To prevent possible damage to the System access Module, do not mount on plenum, duct work, or flush against furnace. 2

WIRING CONSIDERATIONS Ordinary thermostat wire is ideal when wiring the System Access Module (shielded cable is not necessary). Use 22 AWG or larger for normal wiring. Lengths over 100 ft. should use 20 AWG or larger wire. Step 3 Connect Power Source and Antenna UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation. Improper wiring of the ABC connector will cause the System Access Module to operate improperly. Check to make sure all wiring is correct before proceeding with the installation or turning on power. For previous generation UID/UIZ systems, ONLY, screw the antenna to the radio connector. See Fig. 2 for antenna attachment location. For all systems, an independent 24 VAC, 40 VA transformer is required to power the System Access Module. An accessory plug -in transformer is available to order through Replacement Components (Part No. SYSTXNNXFM01). The accessory transformer is heavy. Make sure it is secured to the power outlet with an appropriate screw through the base on the transformer. DO NOT connect the D -wire (24 VAC hot) from the Infinity system. Step4 RadioTest For newer generation Infinity Touch systems, the SkyTel radio is NOT USED. Disconnect the radio module from the main SAM01 module by removing the cable between the two circuit boards. (See Fig. 2.) Note that none of the radio test functions will be applicable to systems using the newer generation Infinity Touch systems, including any error status codes that may be generated by the system that are associated with the radio test or failures of the radio. For previous generation UID/UIZ systems, verify that the SkyTel radio module is connected to the main circuit board via the cable between the main SAM01 circuit board and the radio module. Apply power to the SAM01 in order to perform the radio test, ONLY, at this time. UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation. Improper wiring of the ABC connector will cause the System Access Module to operate improperly. Check to make sure all wiring is correct before proceeding with the installation or turning on power. The purpose of the radio test is to verify effective 2 -way communications at the installation site. The test must pass 100% before the installation of the SAM can continue. Press and hold the RADIO TEST button for at least 5 seconds. A flashing Yellow LED will indicate the test is in progress. A flashing Yellow and Green LED means the transmission is complete and the System Access Module is waiting for a reply. A constant Green LED means the radio test has passed. The radio will perform three message tests, so this sequence will occur three times. If the System Access Module has errors during the process, the test could take up to 15 minutes. If the LED is lit solid, then the System Access Module failed to send the message. Try a new mounting location for the System Access Module. If the Yellow LED is lit solid, then the System Access Module sent its message but did not receive a reply. The Carrier server may be down or the received signal is weak. Try a new mounting location for the System Access Module. Aborting Test - There is no method to abort a radio test once it is started, other than to remove power. The LEDs will maintain their state for one hour after the test. Pressing the Radio Test button momentarily will clear the LEDs. Pressing the Radio Test button again for five seconds will repeat the radio test. See Fig. 3 for a description of the radio test and LED sequence. REMOVE POWER and continue with the installation. Step 5 Install Components INSTALL SYSTEM ACCESS MODULE Once the previous step has been completed, the System Access Module can be permanently installed. The System Access Module is designed so that wires can enter it from behind, above, or below. Plan wire routing before mounting. 1. Remove cover to access mounting holes. 2. Mount back plate to wall using screws and wall anchors provided. 3. Level back plate and tighten screws. Step 6 Connect Infinity Systems UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation. Improper wiring of the ABC connector will cause the System Access Module to operate improperly. Check to make sure all wiring is correct before proceeding with the installation or turning on power. Connect the A, B, and C wires from the Infinity system to terminals labeled A1, B1, and C1. Connect the second Infinity system (if present) to the terminals labeled A2, B2, and C2. ABC bus wiring only requires a three wire connection; however, it is good practice to run thermostat cable greater than three wires in the event of a damaged or broken wire during the installation. It is recommended that the following color code be used when wiring each ABC connector: A Green Data A B Yellow Data B C White 24VAC (Com) NOTE: The D -wire (red - 24 VAC hot) from the Infinity system is not connected to the System Access Module. It is not mandatory that the above color code be used, but each ABC connector in the system MUST be wired consistently. Step 7 Connect Auxiliary Sensor (optional) The System Access Module will support a dry contact sensor for use with water detection or some other use as seen fit. Connect one side of the contacts to connector AUXC (common) and the other side to connector AUX (input). The sensor input can provide up to 20mA at 5 volts d.c. If the sensor input is active, it will not shut down or affect operation of the HVAC system(s). A pop -up message will appear on the user interface indicating the auxiliary sensor is active. The homeowner can also be notified via email, if so chosen, by selecting the appropriate options on the Internet website user 3

interface application. See the appropriate website user interface application for more information: S For previous generation UID/UIZ systems,use www.myinfinity.carrier.com. S For newer generation Infinity Touch systems, use www.myinfinitytouch.com. The Auxiliary Sensor email alerts are enabled when the Urgent notifications are enabled. Step 8 System Start -Up After the previous steps have been performed, power may be applied to the system, including both the SAM01 and the Infinity system. The Infinity wall control will automatically find the SAM01 at system power on during the system self -installation sequence. If the SAM is being added to an existing system, initiate a full system re-install sequence to ensure that the SAM is discovered properly. The wall control will enter the system installation screens automatically and will display the Equipment Summary screen when finished. For previous generation UID/UIZ systems, the Equipment Summary screen will display REMOTE ACCESS YES near the bottom. For the newer Infinity Touch systems, theword SAM will appear toward the bottom right of the Equipment Summary screen. If REMOTE ACCESS YES or SAM is not displayed on the Equipment Summary screen, or if no sam is displayed in the Infinity Touch Equipment Summary screen, check connections to the ABC wires as well as ensure the Yellow LED is lit on the SAM01 (this ensures the module has power). The Green LED will be lit next to each ABC connection if the User Interface (wall control) has established communications. NOTE: The Yellow Status LED may begin to flash status codes when used with newer generation Infinity Touch systems. This is likely due to the fact that the network interface within the SAM enclosure has been disconnected. The following status codes should be ignored when using the SAM with newer generation Infinity Touch controls: Code 61: Radio out of range Code 62: Loss of communication with radio or Ethernet device Code 63: Radio not registered Code 66: Ethernet/Wi-Fi not detected Code 67: No communication with server Step 9 PIN Number and Serial Number (For previous generation UID/UIZ systems, only) The PIN and Serial number of the System Access Module are used by the system owner to register their system with the Carrier web server Remove the sticker containing the PIN number from the radio and install at the front of the Owner s Guide. Also, write down the SAM serial number in the Home Owner s Guide. The serial number can be found on the SAM packaging, at the bottom of the large SAM circuit board or in the user interface Service Menu. If PIN number is lost or missing, it can be found by entering the Service Menu of the User Interface (10 second press of the Advance button) and looking at the Model/Serial Numbers screen. The PIN will be listed with the System Access Module model and serial numbers. RS -232 CONNECTOR An RS -232 port has been provided for connection to home automation equipment. Consult your home automation supplier for support. If the particular home automation supplier needs information for the interface, you may supply the latest version of the SAM Remote Access Interface Specification, found on HVACpartners, to the home automation supplier. Designing and providing the interface to the Infinity system through the RS -232 communication port on the SAM is the responsibility of the home automation supplier. Contact your Distributor Service Manager for details, if required. UPDATING SYSTEM PROFILE (For previous generation UID/UIZ systems, only) The Infinity System will automatically send system information to Carrier s computer servers within one hour after the system has been successfully installed. Access to the system via the Internet or telephone will not be available until this occurs. The system can be forced to send its information through the following process if Internet and telephone access is required immediately. Press and hold the RADIO TEST button for 15 seconds. When the button is first pressed, the LED will turn on. Five seconds into the press, the Yellow LED will turn on. Fifteen seconds into the press, the Green COM1 LED will turn on. Release the button when the Green LED turns on. The LED will flash when messages are being sent. The and Yellow LEDs will flash when the SAM is waiting for message replies. Upon successful profiling, both Green LEDs will be lit. If profiling is not successful, the LED will be lit solid. The entire profiling process can take up to 15 minutes per Infinity System. If two systems are connected to one SAM, then the profiling process can take up to 30 minutes. If the Infinity system ABC wiring is moved from connector 1 to connector 2 (or vice versa), or Infinity equipment has changed, the System Access Module must update Carrier s servers with the new information. This will happen automatically within one hour, or can be manually forced with the process described above. TROUBLESHOOTING FAULT INDICATORS Under normal operation, the Yellow and Green LED will be on continuously (solid). If the System Access Module does not receive communications with the Infinity system, the Green LED will not be on. If there are faults present, the Yellow LED indicator will blink a two digit status code. The first digit will blink at a fast rate, the second at a slow rate. NOTE: When the SAM01 is used with the newer Infinity Touch systems, it may display status codes that are unique to the previous generation UID/UIZ systems, but are irrelevant when the SAM is used with the newer Infinity Touch systems. See the note below for these codes that should be ignored. STATUS CODE DESCRIPTION 45 Board Failure 61 Radio out of range (no coverage for five minutes) 62 Loss of communication with the radio 63 Radio not registered with the local network (unregistered for five minutes) 64 Auxiliary sensor active NOTE: The 61, 62, and 63 status codes should be IGNORED for newer generation Infinity Touch systems. 4

Antenna Connection RADIO Home Automation Connection (RS-232) WLS WLSC RADIOTEST A1 B1 C1 STATUS COMM1 A2 B2 C2 COMM2 24VAC+ 24VAC- Fig. 2 - System Access Module Control Board A04224 5

Send Message 1 (short) Flash Yellow at 1Hz Failed Flash Yellow at 1Hz and solid Wait for Reply (short) Flash Green and Yellow at 1 Hz Timeout Flash Green and Yellow at 1Hz and solid Send Message 2 (short) Flash Yellow 2 times, 1 second off Failed Flash Yellow 2 times and solid Wait for Reply (long) Flash Green and Yellow 2 times Timeout Flash Green and Yellow 2 times and solid Send Message 2 (long) Flash Yellow 3 times 1 second off Failed Flash Yellow 3 times and solid Wait for Reply (long) Glash Green and Yellow 3 times Timeout Glash Green and Yellow 3 times and solid All tests passed Solid Green LED Yellow and off Fig. 3 - Radio Test Process and LED Sequence A05073 Copyright 2013 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 04/13 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Catalog No: SAM01 --- 03SI Replaces: SAM01---02SI 6