A New Control System of a Household Refrigerator-Freezer

Similar documents
Experimental Evaluation Of The Frost Formation

Research on the Air Conditioning Water Heater System

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

Troubleshooting Your Refrigerator

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

How To Understand Evaporator

Energy-efficient Products for Better use of Energy in the Home

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

New Trends in the Field of Automobile Air Conditioning

Lesson 36 Selection Of Air Conditioning Systems

Portable Air Conditioner

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

SERVICE MANUAL REFRIGERATION

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS

Undercounter & Slimline Cabinet Range HR/LR 120 HRB/LRB120 HR/LR 140 HR/LR 150 HR/LR 200 HR/LR 240 HR/LR 360 HR/LR 410

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

Refrigeration Manual. Part 3 - The Refrigeration Load

SERVICE MANUAL REFRIGERATION

REMOTE CONTROL MANUAL

Basic Technology Series

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

GUIDE TO AIR SOURCE HEAT PUMPS. Consumer, Specifier, Installer and Merchant guide to Air to water heat pump technology

How Ground/Water Source Heat Pumps Work

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Experimental Study of Frost Accumulation on Fan- Supplied Tube-Fin Evaporators

The Development of a Frost-Less Heat Pump

18th International Congress of Mechanical Engineering

Refrigerant Charge and Ambient Temperature Effects on the Refrigeration Cycle of a Small Capacity Food Freezer

Glossary of Heating, Ventilation and Air Conditioning Terms

Single Zone LCD Thermostat Operating Instructions

SECTION MORTUARY REFRIGERATORS

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

Energy Efficiency. Energy Efficient Home Cooling:

How does solar air conditioning work?

Alternative Energy Test Method for Frost-Free Refrigerators and Freezers

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

HEATER, AIR CONDITIONING AND VENTILATION

Operating Instructions Air Conditioner

Resources for School Energy Managers

Chapter 18 Temperature, Heat, and the First Law of Thermodynamics. Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

ENERGY COSTS A LOT, DON T WASTE IT. Professer. O.Courant SAVE UP TO 15% ON YOUR MONTHLY ELECTRICITY BILL. Konn servi lénerzi, ou ki pou sorti gagnan

Why and How we Use Capacity Control

ALL IN ONE. Heat Pump Water Heater

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Bauknecht AG, Industriestrasse 36, 5600 Lenzburg,

USER S MANUAL HSC-24A

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

SAFETY PRECAUTIONS Read all of the instructions before using this appliance. When using this appliance, always exercise basic safely precautions,

Automobile Air Conditioning Primer

Split units TH with hermetic compressors

- White Paper - Data Centre Cooling. Best Practice

Pool Dehumidification Basics

RESPONSE TIME INDEX OF SPRINKLERS

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

INSTRUCTION MANUAL FOR RECREATIONAL REFRIGERATOR/FREEZER MODEL

MP-4000 Alarm List (Software version or later)

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

A fridge that takes only 0.1 kwh a day?

Table Z. Troubleshooting Chart for Air Conditioners. Cause

How to choose a heat pump and use it wisely

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Air-Conditioning Buying Guide

Failure code manual. content

HEAT TRANSFER ANALYSIS OF COLD STORAGE

To suit Daikin FDY "F" Series and FD "F" Series. (and other models incorporating BRC1B62/52 Remote Controller)

Soil Suction. Total Suction

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Technical Support Bulletin Nr. 20 Special AC Functions

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)

THERMAL MANAGEMENT OF COMPUTER SYSTEMS USING ACTIVE COOLING OF PULSE TUBE REFRIGERATIORS

Specific Heat Capacity and Latent Heat Questions A2 Physics

Benefits of Cold Aisle Containment During Cooling Failure

ASTACEA4 Inspect complex/central air conditioning systems

A/C refrigerant system, overview

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Thermocline Management of Stratified Tanks for Heat Storage

Technical data. Danfoss DHP-A

Natural gas heating versus split system heating and the current and future viability of the Natural gas network

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

SIBIR MANUAL V110 KE. English page 5 RKE - 1D

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

TIPS ON ENERGY SAVING

Dehumidification Frequently Asked Questions

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 A New Control System of a Household Refrigerator-Freezer J. Lee Daewoo Electronics Company K. Y. Cho Daewoo Electronics Company K. T. Lee Daewoo Electronics Company Follow this and additional works at: http://docs.lib.purdue.edu/iracc Lee, J.; Cho, K. Y.; and Lee, K. T., "A New Control System of a Household Refrigerator-Freezer" (1994). International Refrigeration and Air Conditioning Conference. Paper 234. http://docs.lib.purdue.edu/iracc/234 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

A New Control System of a Household Refrigerator-Freezer Janghee Lee, Kwang-Yun Cho, Ki-Tae Lee Daewoo Electronics Co., Ltd 64 Yonghyun-dong, Nam-gu Incheon, KOREA ABSTRACT This paper will present the structure of the new system, the control scheme and its performance test results. In this new system, the damper in the conventional refrigerator is replaced by an additional cooling fan Thus, it uses two cooling fans: one (F-fan) is to provide cooled air for freezing compartment (F-compartment) and the other (R-fan) is for refrigerating compartment (R-compartment), respectively. The F-fan and the R-fan are controlled independently by thermo-sensors installed in the F and R-compartments. Experimental results show improved performance of the new refrigerator over the conventional refrigerator. Among them is the lower fluctuation of the R-compartment temperature, which has a significant effect in lowering the refrigerating temperature and storing foods fresh longer. It can quickly response to the load change in the R-compartment The air-defrosting by the use of the R-fan was proved to be an efficient method in saving the energy consumption during the defrosting cycle. INTRODUCTION Household refrigerator-freezer systems can be classified as direct and indirect cooling systems. The direct cooling system utilizes natural convection to cool food storage volume. It has inherent advantages of high energy efficiency and simple structure. This cooling type is used in small size refrigerator and still widely used in European market for bigger size. As the refrigerator becomes bigger, the direct cooling system encounters with a problem in controlling temperatures in the F and R-compartments as mentioned by Onishi. By that reason, large size refrigerators over 2 liters usually adopt the indirect cooling system The indirect cooling system has a cooling fan to circulate cold air through an evaporator and refrigerator-freezer compartments. In this cooling system, the cooling fan and the compressor are typically controlled by a temperature controller installed in the F compartment A damper controls R-compartment temperature by regulating cold air flow rate. A limitation in this type refrigerator comes from the fact that the temperature of the R-compartment depends entirely on the F-compartment temperature. If the R-compartment is excessively loaded, the temperature in the R compartment rises too hlgh while the temperature in the F-compartment is still below its preset temperature. However, the compressor would not restart because the control operation is based on the F-compartment temperature. As a result, the R compartment often fails to maintain its temperature range. Hence, the F-compartment based control has to sacrifice the refrigerating performance to some extent, while it gives good performance in frozen food storage. Some refrigerators are designed to be controlled by the R-compartment temperature in order to improve refrigerating performance, but at the sacrifice of the freezing performance. The new control system development was intended to achleve more improved refrigerating performance without any degradation of the freezing performance. This purpose was obtained by the use of two independently operating cooling fans. DESIGN OF NEW REFRIGERATOR WITH TWO COOLING FANS The conventional indirection cooling system refrigerator has a cooling fan that blows cold air into food storing compartments; usually F and R-compartments. The fan is always running during the compressor is active. As shown in Fig. 1, the cold air is distributed into F and R-compartments. The system control is based on the F-compartment 19

temperature. A thermo-sensor installed in the F-compartment switches the compressor and the cooling fan ON and OFF based on the F-compartrnent temperature. Cold air flow rate into the compartment is regulated by a thermo-damper, which has its own temperature detecting device. Tube Freezing ens or Capillary Tube F-Fan Freezing Damper Compressor Refriserating Fig. 1 Schmatic of the conventional refrigerator with one cooling fan Compressor Refrigerating Fig. 2 Schamatic of the new refrigerator with two cooling fans The damper, located at the end of the duct, is fully opened initially at the start of the compressor and the cooling fan As the R-compartrnent temperature decreases, the damper becomes closed and reduces flow rate into the R compartrnent When a preset temperature of the R-compartment is reached, the damper closes completely. As the F compartment temperature falls below a preset temperature, the compressor and the cooling fan stop. The temperatures in the F and R-compartrnents increase due to the heat leakage through the insulation wall Thus the control of the R compartrnents is inevitably depends upon the F-compartment condition in the conventional refrigerator. Fig. 2 shows the schematic diagram of the new refrigerator. Instead of having a damper regulating cold air flow rate into the R-compartrnent, the new system adopts an additional cooling fan These two cooling fans operate independently each other. One cooling fan (F-fan) feeds cold air into the F-compartments and the other fan (R-fan) provides cold air into the R-compartment respectively. The flow passage is also separated so that the air blown by the F-fan and R-fan can not be mixed The compressor and the F-fan operation depend on the F-compartment temperature as they do in the conventional refrigerator. However, the control method of the temperature in the R-compartment makes a significant difference between them While the conventional refrigerator relies on the F-compartment temperature for the temperature control, the new refrigerator uses thermo-sensors installed in both of the F and R-compartments. The thermo-sensor installed in the R-compartment detects the temperature variation in this compartment and gives control signal to the R-fan. As the R-compartment temperature rises, the R-fan starts to blow cold air into the R compartment This R-fan operates independently regardless of the compressor ON/OFF status. The evaporator temperature remains still around -15 oc even when the compressor is not running. Usually the R-compartment is need to be at 3 oc that is considerably high compared with the evaporator temperature during the compressor stopping period Thus circulating the air in the R-compartment through the evaporator can provide air which is cold enough to compensate the heat leakage. Advantages of the two fan cooling system can be estimated as follows; 1) Small temperature fluctuation in the R-compartment 2) Ability of quick response to the load change in the R-compartment 3) Energy saving effect by the use of air -defrosting These characteristics will be discussed in the following sections with experimental results. llo

CONTROL CHARACTERISTICS Experiments have been performed to investigate the performance of the new refrigerator in comparison with the conventional refrigerator. Both of these refrigerators are 5 liter capacity size. Two refrigerators were installed in a test room; base area of 3 mm x 42 mm and height of 22 mm The test room was conditioned at a room temperature of 3 oc and a relative humidity of6% during the experiments. Thermocouples used in the temperature measurements are T type with a diameter of.3 mm Temperature measurement data were acquired at every 3 second by a data acquisition unit, which is composed of a remote scanner and a data recorder (Yokogawa HR.-25E). A workstation (Sun, SPARC Station LX) read and stored the data from the data acquisition unit through a GPffi communication port 5,-... u '<._...- e Q) -5-15 -25-35 2 4 6 8 Fig. 3 Control characteristics of the conventional refrigerator 1-35 2 4 6 8 1 Fig. 4 Control characteristics of the new refrigerator Control characteristics The control characteristics of the conventional and the new system refrigerators are shown in Fig. 3 and Fig. 4. The temperature variations during the control operation were measured at five measuring positions. For the F and R compartment temperatures, air (T(airo Tr,air) and brass cylinder(t(brass. Tr,brass) temperatures were measured at position halfway between the rear internal wall and the internal wall of the closed door, and one third of the compartment height from the bottom of the compartments. The brass cylinder has!qermal capacity equivalent to 2 g of water, and the size is 26 mm in diameter and 48 mm in height An evaporator surface temperature (T eva> was also measured at the entrance of refrigerant flow. As can be seen in Fig. 3, the air temperatures in the refrigerating (Tr,air) and freezing (Tr,air) compartments, start to decrease as the compressor starts. In this conventional refrigerator, the cooling of the R-compartment can be achieved only during the ON time of the compressor, which is activated by the F-compartment temperature. The temperatures of the brass cylinders show smaller variation and time delays behind the air temperatures because of their thermal capacities. During the test, T(brass was set to be -18 C for both of the conventional and new refrigerators. Tr,brass was set to be 3 C for the conventional refrigerator and 2 oc for the new refrigerator, respectively. The evaporator temperature shows large fluctuation as the compressor starts and stops. It rises up to -15 oc when the compressor is OFF and reaches -28 oc when the compressor is ON. Compared with the conventional refrigerator, the control characteristics of the new refrigerator look more complicate as can be seen in Fig. 4. That is because of the independent R-fan operation The R-fan starts and stops to keep the R-compartment temperature, T r,brnss to a preset level regardless of the compressor running status_ The result shows that evaporator temperature, T eva,is greatly influenced by the R-fan operation When the R-fan is running, the evaporator temperature rises due to heat exchange with the relatively warm air from the R-compartment, and the T r,air decreases. At this time, T(air rises because of the increased evaporator temperature. The evaporator temperature of the new refrigerator in Fig. 4 shows higher temperature than that of the conventional refrigerator shown in Fig. 3 when the compressor is OFF. 111 C

This results from the heat transferred to the warm air from the R-compartment blown by the R-fan Small temperature fluctuation The function of the R-compartment is to keep food fresh as long as possible. In this point of view, the lower the food storing temperature becomes, the longer the freshness lasts. While pure water will freeze at C, most food starts to freeze at -1 --2 oc. That is a limitation of lowering the refrigerating temperature. Thus, the R-compartment temperature should be kept above zero during control operation in order to prevent the food from being frozen In addition to the storing temperature, temperature fluctuation should be minimized to reduce thermal shock to the food -u s 4 «-- 3... ('3 <l) e. 2 1 s 1. --au'...l...bms 2 4 6 8 1 Fig. 5 Refrigerating compartment temperature, Conventional refrigerator 2 4 6 8 1 Fig. 6 Refrigerating compartment temperature, New refrigerator Figures 5 and 6 show the refrigerating temperatures during control operation of the refrigerators. These are just magnified views oftr,air and Tr,bmss in the Fig. 3 and Fig. 4. In the new refrigerator, the frequent chopping of the cold air supply by the use of the R-fan reduces the temperature fluctuations in the R-compartment Compared with the conventional refrigerator shown in Fig. 5, the new refrigerator shows much smaller fluctuations in both of the T r,air and T r,brass in the R compartment In the conventional refrigerator, the big temperature fluctuation during the control operation restricts lowering the R-compartment temperature, T r,brass, which is set to 3 C. In the new refrigerator, we can set the compartment temperature at 2 oc which is lower than in the conventional refrigerator. Thus it can store 3 food cooler and keep the freshness longer with the new refrigerator. Quick refrigeration There is a quick refrigeration mode in the new refrigerator, which is possible with the help of the independent R-fan operation In the quick refrigeration mode, the compressor and the R-fan are running regardless of the F-compartment condition An experiment on the refrigerating speed has been performed During the control operation, 1 g of water at 25 C contained in a beaker was put into the R compartment to test the cooling speed For the new refrigerator, quick refrigeration mode was activated just after the water was placed in the R-compartment However the conventional refrigerator does not have the quick refrigeration function because its control depends on F compartment temperature. Five minutes after the compressor resumes, the water was placed in the R-compartment in case of the conventional refrigerator. 112,..., 25 2 j 15! 1 <l) s Con\enlional 2 4 6 8 Time(min) Fig. 7 Comparison of the refrigerating speed of 1 g water in the R-compartment

The result can be seen in Fig. 7 as the temperature change of the cooling water. It shows the water in the new refrigerator cools faster than in the conventional one. To cool the water from 25 oc to 1 oc, it takes 58 minutes in the conventional refrigerator, but only 3 7 minutes in the new refrigerator. 5 -s G-tO.._.. E- -15-2 -o-air-defrosting --o--healer-defrosting -25 --t!r-natural defrosting -3 5 1 15 2 25 Fig. 8 Evaporator surface temperature during the defrosting cycle and air temperature in the R compartment 2 3 25 2 ] 15 a1 " 5 -o-air-dcfiusting 1 IS 2 25 Fig. 9 Heat exchanged during the defrosting cycle ; air defrosting and heater defrosting DEFROSTING BY WARM AIR CIRCULATION In indirect cooling refrigerator, moisture contained in the air tends to condense and accumulate on the evaporator surface. The frost accumulation increases resistance to heat transfer and reduces air flow rate by blocking air passages. Thus we need to remove the frost periodically. Usually the frost is removed by applying heat by means of glass enclosed heater or cal-rod, which is a metal jlcketed electric resistance. The portion of defrosting in energy consumption takes about 6-7 %of the total energy consumed in a household refrigerator.freezer. Considering the refrigerating energy to compensate the temperature increase during the defrosting cycle, this portion should be doubled approximately. An efficient method of defrosting, air-defrosting, can be introduced by using the R-fan, in which the relatively warm air in the R-compartment is circulated to warm up the frost on the evaporator during the defrosting cycle. The compressor and F-fan are OFF during the defrosting cycle. The heat exchange rate depends on the temperature difference between the warm air and the evaporator temperature. Thus, air-defrosting must be a powerful method at the initial stage of the defrosting cycle, in which the temperature difference is large. Though air-defrosting is not enough to melt the frost completely, combined use of it with the defrost heater showed significant energy saving effect Experiments The effect of air-defrosting was investigated with an experiment using the new refrigerator. The defrosting experiments have been performed with three methods including heater-defrosting, air-defrosting and natural defrosting. The capacity of the heater enclosed by a glass tube is 195 watt The air flow by the R-fan is 14 m3jhr. Evaporator surface temperatures were measured during the defrosting cycle at five locations; top-right, top-left, bottom-right, bottom-left and center. Before the start of defrosting, the refrigerator had been in steady control operation Frosting was induced in the same experimental conditions for all cases, to ensure constancy of the frost deposited An accumulation of 255 g frost was generated The measured evaporator temperatures for each defrosting method were shown in Fig. 8. Since the evaporator temperature shows slight variation depending on the measurement positions, average value of the temperatures at the five positions is plotted in the Fig. 8. In the air-defrosting, the evaporator temperature shows rapid increase at the initial stage of the defrosting. Then, the increasing rate slows down as it approaches the air temperature of the R-compartment 113

When the compressor stops, hot refrigerant from the condenser leaks through the capillary tube. This hot gas leakage suddenly warms up the evaporator even though no external heat is applied (natural defrosting). In the evaluation of the heat applied in defrosting (air-defrosting, heater-defrosting), the heating by the hot refrigerant should be subtracted The net amount of heat used in defrosting is obtained by measuring the temperature of the evaporator. Qdefrost = Ceva (DoT defrost -DoT natural) It is assumed that the frost temperature is equal to the evaporator temperature. The frost evaporated directly to the air is neglected so that all the heat transferred to the frost is used to warm up the evaporator and the frost The net heat during defrosting process is obtained applying the above equation, where Ceva is the thermal capacity of the evaporator including the frost accumulated on it The results are shown in Fig. 9 for the heater-defrosting and air-defrosting. Air-defrosting shows higher defrosting rate than heater-defrosting at the beginning of defrosting. It is attributed to the low evaporator temperature causing high convective heat transfer from the air to the evaporator. As the defrosting proceeds, the evaporator temperature rises quickly so that the air-defrosting becomes less efficient compared with the heater-defrosting which has almost constant defrosting rate. One critical factor to be considered in the defrosting cycle of the household refrigerator-freezer is the F compartment temperature. If the defrosting takes too long, F-compartment fails to keep food frozen because of the temperature rise resulted from the heat leakage through the insulating wall. That restricts the use of the air-defrosting only. In order to solve this problem, it was tried to use the air-defrosting followed by the heater-defrosting. That is to run the R fan for the first I minutes of the defrosting cycle; after that the defrost heater is powered until the defrosting cycle finishes. From the experimental data in Fig. 9, I minutes of air-defrosting has the same effect as 7.5 minutes of heater-defrosting in the refrigerator used in this experiment Usually one defrosting cycle for the test refrigerator takes about 25 minutes with the heater-defrosting. Hence about 25 %of the energy required for a defrosting cycle will be saved even if considering the power consumed by the R-fan. Moreover, it shows an additional effect of cooling the R-compartment during defrosting cycle as shown in Fig. 8. CONCLUSIONS The performance of the newly developed household refrigerator-freezer was presented The new refrigerator adopts two cooling fans for the control of the freezing and R-compartment independently. Experimental work shows the new refrigerator demonstrates its advantages as follows; 1. Smaller temperature fluctuation and lower average temperature in the R-compartment which have significant effect in improving food freshness 2. Faster refrigerating speed and quick response to the load change in the R-compartment 3. Energy saving by the use of the air-defrosting and maintaining the R-compartment cool during the defrosting cycle. REFERENCES Onishi, T., "A new Power Saving Household Refrigerator-Freezer," ASHRAE Trans., vol. 86, part 2, 198 International Standard ISO 8187, Household Refrigerator Appliances -- Refrigerator-Freezer-- Characteristics and Test Methods, International Organization for Standardization, 1991 Potter, N. N., Food Science, 4th ed, The A VI Publishing Company, West Port, Connecticut, 1986 Ameen, F. R, Coney, J. E. R and Sheppard, C. G. W., "Experimental Study of Melting Ice Cylinders in a Warm Air Cross-Flow," Int J. ofrefrig., vol. 14, No.3, 1991 Ameen, F. R, Coney, J. E. R and Sheppard, C. G. W., "Experimental Study of Warm-Air Defrosting of Heat-Pump Evaporator," Int J. of Refrig., vol. 16, No. 1, 1993 114