Study on Dynamic Properties of Long-span Power Transmission Tower-Cable System

Similar documents
Numerical Analysis of the Moving Formwork Bracket Stress during Construction of a Curved Continuous Box Girder Bridge with Variable Width

Dynamics of Offshore Wind Turbines

Tower Cross Arm Numerical Analysis

Fluid structure interaction of a vibrating circular plate in a bounded fluid volume: simulation and experiment

EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES

Analysis of seismic response control for long-span cable-stayed. bridge under traveling wave input *

Simulation for the Collapse of WTC after Aeroplane Impact

Dispersion diagrams of a water-loaded cylindrical shell obtained from the structural and acoustic responses of the sensor array along the shell

How To Write An Analysis System For Bridge Test

How To Calculate Tunnel Longitudinal Structure

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

DEVELOPMENT AND APPLICATIONS OF TUNED/HYBRID MASS DAMPERS USING MULTI-STAGE RUBBER BEARINGS FOR VIBRATION CONTROL OF STRUCTURES

Optimal Design of Lattice Wind Turbine Towers

Basic principles of steel structures. Dr. Xianzhong ZHAO

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

Time- Cost Benefit Analysis for Anchor Type Foundation in Transmission Towers

DYNAMICAL ANALYSIS OF SILO SURFACE CLEANING ROBOT USING FINITE ELEMENT METHOD

Coupling Effect in Substation Ground Measurements

Kresimir Bakic, CIGRE & ELES, Slovenia

BLIND TEST ON DAMAGE DETECTION OF A STEEL FRAME STRUCTURE

INTRODUCTION TO BEAMS

OUTPUT-ONLY MODAL ANALYSIS FOR A 50 YEARS OLD CONCRETE BRIDGE

PASSIVE VIBRATION DAMPING IN A TRUSS TELECOMMUNICATION TOWER


Optimum proportions for the design of suspension bridge

SIMULATING THE DYNAMIC RESPONSE OF DIVINE BRIDGES

EN :2005. Wind actions

DYNAMIC ANALYSIS ON STEEL FIBRE

MEMS mirror for low cost laser scanners. Ulrich Hofmann

CHAPTER 3 MODAL ANALYSIS OF A PRINTED CIRCUIT BOARD

8 EXTRA LIGHT GRC SANDWICH ELEMENTS FOR ROOFING IN INDUSTRIAL BUILDINGS

Ultrasonic Detection Algorithm Research on the Damage Depth of Concrete after Fire Jiangtao Yu 1,a, Yuan Liu 1,b, Zhoudao Lu 1,c, Peng Zhao 2,d

CHAPTER 6 WIND LOADS

Designer-Oriented Electric Field Analysis System for Power Cable Accessories

First 14-storey wood building in the world at Bergen in Norway Premier bâtiment en bois à 14 niveaux au monde à Bergen en Norvège

Siemens D3 platform 3.0-MW, 3.2-MW, 3.3-MW, and 3.4-MW direct drive turbines. Reduced complexity, increased profitability. siemens.

Loads Tools Checks Reports

M. Belloli, A. Collina, F. Resta Politecnico di Milano O.I.T.A.F. SEMINAR. Grenoble 27 April 2006

EXPERIMENTAL ANALYSIS OF CIRCULAR DISC WITH DIAMETRAL SLOTS

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

Vincenzo Gattulli. Dipartimento di Ingegneria Civile, Edile-Architettura, Ambientale Università di L Aquila, Italy.

Similar benefits are also derived through modal testing of other space structures.

New approaches in Eurocode 3 efficient global structural design

UNIT 7 Crane safety. Engineering CASE STUDY. Cambridge English for. Professional English. Part 1. Part 2

Figure Test set-up

Mechanical Analysis of Crossbeam in a Gantry Machine Tool and its Deformation Compensation

4B The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

Finite Element Simulation of Simple Bending Problem and Code Development in C++

PREDICTION OF MACHINE TOOL SPINDLE S DYNAMICS BASED ON A THERMO-MECHANICAL MODEL

Overhang Bracket Loading. Deck Issues: Design Perspective

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig some of the trusses that are used in steel bridges

Finite Element Analysis of the Seismic Behavior of Guyed Masts

REHABILITATION OF THE FIGUEIRA DA FOZ BRIDGE

New Troja Bridge in Prague Concept and Structural Analysis of Steel Parts

SEISMIC DESIGN OF MULTI-STORY BUILDINGS WITH METALLIC STRUCTURAL FUSES. R. Vargas 1 and M. Bruneau 2 ABSTRACT

Lab for Deflection and Moment of Inertia

LMS Imagine.Lab AMESim Powertrain Transmission

Overhead lines in Ireland

Experimental study on the relation of water rivulet-reynolds number effect-cable vibration

Solved with COMSOL Multiphysics 4.3

User orientated simulation strategy to analyse large drive trains in SIMPACK

Application Study of FLAC in Analysis of Slope Stability

DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit Ann Arbor Mt. Clemens Port Huron

A NUMERICAL ANALYSIS BASED SUBSTITUTE METHOD FOR SHAKING TABLE TEST IN CONSIDERING OF THE SOIL-STRUCTURE INTERACTION

Up and Running with Autodesk Inventor Professional Simulation in 90 Minutes!

Frequecy Comparison and Optimization of Forged Steel and Ductile Cast Iron Crankshafts

CONSISTENT AND LUMPED MASS MATRICES IN DYNAMICS AND THEIR IMPACT ON FINITE ELEMENT ANALYSIS RESULTS

THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS

Modeling Beams on Elastic Foundations Using Plate Elements in Finite Element Method

SEISMIC RETROFITTING OF STRUCTURES

Mounting Instructions. Torque Transducer. A en

ANALYSIS OF A LAP JOINT FRICTION CONNECTION USING HIGH STRENGTH BOLTS

International Journal of Engineering Research-Online A Peer Reviewed International Journal Articles available online

Cross-beam scanning system to detect slim objects. 100 mm in

Analysis of the Response Under Live Loads of Two New Cable Stayed Bridges Built in Mexico

Numerical modelling of shear connection between concrete slab and sheeting deck

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo

EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFORMANCE OF BUILDING RESTING ON SLOPING GROUND

OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTED TO WIND LOADS

Panel Session: Structural Reliability-Based Design of Utility Poles and the National Electrical Safety Code

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

KENTUCKY TRANSPORTATION CENTER. College of Engineering STRUCTURAL EVALUATION OF THE HISTORIC JOHN A. ROEBLING SUSPENSION BRIDGE

Monitoring of Railway Traffic as a Part of Integrated SHM System

3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max

ENGINEERING MECHANICS 2012 pp Svratka, Czech Republic, May 14 17, 2012 Paper #15

DESIGN AND ANALYSIS OF BRIDGE WITH TWO ENDS FIXED ON VERTICAL WALL USING FINITE ELEMENT ANALYSIS

INSTALLATION. General. Important Note. Design. Transport

Offshore Wind Turbine Support Structures

Seismic performance evaluation of an existing school building in Turkey

Numerical Simulation of the External Flow Field. Around a Bluff Car*

V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above

Vehicle-Bridge Interaction Dynamics

ANALYTICAL AND EXPERIMENTAL EVALUATION OF SPRING BACK EFFECTS IN A TYPICAL COLD ROLLED SHEET

Back to Elements - Tetrahedra vs. Hexahedra

PARAMETRIC STUDY OF THE STRUCTURES (INFLUENCE OF THE SHELLS)

AMBIENT VIBRATION TESTING & MODAL IDENTIFICATION OF AN OFFICE BUILDING

Transformers. Special transformers Reactors products

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

Bearing Stiffness Determination through Vibration Analysis of Shaft Line of Bieudron Hydro Powerplant

Transcription:

The 14th International Workshop on Atmospheric Icing of Structures, Chongqing, China, May 8 - May 13, 2011 Study on Dynamic Properties of Long-span Power Transmission Tower-Cable System Jiang Dong, Fei Qingguo *, Zhou Honggang and Han Xiaolin (Department of Engineering Mechanics, Southeast University, Nanjing, 210096) (Jiangsu Key Laboratory of Engineering Mechanics Analysis, Nanjing, 210096) Abstract: High-rising, long-span and significant flexibility are major characteristics of long-span power transmission tower-cable system. Structural instability may occur in all possibility under wind load and ice loads. This paper presents the study on dynamic properties of long-span transmission tower-cable system under instability condition. Finite element model of a long-span power transmission tower-cable system is constructed. Dynamic properties of tower-cable system under wind load are studied. Then, the influence of ice on the dynamics properties of tower-cable system is further discussed. The result could be taken as the reference in the disaster prediction or the structural design of long-span tower-cable systems. Keywords: long-span power transmission tower-cable system; structural instability; ice covered; dynamic properties 1 Introduction Extra-high voltage transmission network, the carrier of power, is the important lifeline system. The long-span power transmission tower-cable system as an integral part of extra-high voltage transmission network, with the common characteristics of high-rise and long-span structures, for instance, tall in height, long span and high flexibility, is possible to cause structural instability and other disastrous accidents by the action of wind load and ice load [1]. Before the accidents occurred, by means of structural health monitoring, structural assessment and take corresponding measures, can reduce the risk of catastrophic accidents, this is the current hotspot of structural engineering [1-5]. The in-depth understanding of dynamic characteristics of long-span power transmission tower-cable system can provide theoretical basis for predict disasters and guide to the design. This paper presents the study of a long-span power transmission tower-cable system. The finite element model is constructed to analysis the dynamic characteristics of wind load caused instability, and the influence of ice-covered load is further considered. The tower-cable system under consideration is constructed by National Grid. Both suspension-type and tension-type, the two groups of power transmission towers according to the way they support power lines, are used in the system. The system in this study included 2 towers, 2 ground lines and 8 conductors for simplified computation. As shown in Fig. 1, the tower studied was a bolt connected * Qingguo Fei (1977- ), corresponding author, Doctoral advisor. qgfei@seu.edu.cn.

steel angle and steel tubular spatial structure, 131 m high. The main span of this power transmission system is larger than 1000m. Fig.1 Power transmission tower Fig.2 FEM of tower-cable system 2 Finite element modeling and analysis Three-dimensional spatial finite element model of the power transmission system was constructed using ANSYS. The main parts of towers were modeled as beam elements, included the main chords and the main web members. The bracing members were modeled as truss elements or beam elements. The subsidiaries were modeled as lumped mass. The ground lines and conductors were modeled by use of truss element, as well as the simulation of insulators. The shapes of lines were found based on catenary theory and the pre-stresses were also inflicted to lines. Fig. 2 shows the FEM of tower-cable system. The modal analysis was then carried out to get the computational frequencies and mode shapes, 6 Eigen-values and Eigen-vectors were figured out, as show in Table 1 and Fig. 3. (a) 1 st transverse bending (b) 2 nd transverse bending

(c) 1 st bending in line direction (d) 2 nd bending in line direction (e) 1 st torsion (f) 2 nd torsion Fig.3 Mode shapes of tower-cable system Table1 Modal frequency of tower-cable system Frequency (Hz) Modes 0.789 1 st transverse bending 0.797 2 nd transverse bending 0.838 1 st bending in line direction 0.861 2 nd bending in line direction 1.220 1 st torsion 1.262 2 nd torsion 3 Wind force Wind speed is a commonly reference to structural engineering design, due to wind loads on structures is a form of force, thus wind speed need to be converted into wind force, usually based on reference [6] to calculate the equivalent force. Wind force is directly bound up with wind speed which is closely related to altitude [7], Fig. 4 is the wind speed distribution with height. Fig.4 Wind speed distribution Fig.5 Wind speed-frequency curve The dynamic characteristics of the single tower in different wind speeds is analyzed, as well as the change of first order frequency (transverse bending), the result is shown in Fig. 5. The rate of

frequency change is calculated by ( ) k = f0 f 100 f, where 0 f0 is the first order frequency of the unloaded tower, f is the frequency of loaded tower. From Fig. 5, if wind speed is 45m/s, the first order frequency reduced by 10%, if wind speed is 47m/s, the frequency dropped fast, it shows that the stiffness of the transmission tower decreased significantly, and there is the risk of occurrence of catastrophic accidents. The analysis above is the consideration of the single tower. Actually, strong nonlinear coupling occurs between transmission tower and the cable under wind excited, the mass and the vibration of the line are big influences to the dynamic properties of transmission tower. Analyses were conducted for a wind direction perpendicular to the transmission line, comparison of rate of frequency change between tower-cable system and the single tower is shown in Fig. 6. The rate of frequency change of tower-cable system is bigger than the single tower in the same wind speed, and as the wind speed increased, the difference became clear. Fig.6 Wind speed-frequency curves Fig.7 Wind speed-frequency curves 4 Ice load Ice covered is great harm to the safety of transmission tower-line system [8]. Three cases of the dynamic characteristics of transmission tower-line system with different ice thickness (respectively 5mm, 10mm, and 15mm) are analyzed, the result is shown in Fig. 7. As shown in Fig. 7, as the increase of ice thickness, the maximum wind speed transmission tower can bear reduced, no ice-covered the speed is 44m/s while 34m/m the thickness is 15mm. Wind speed is 25m/s, the smallest rate of frequency change is 6% (no ice), while the largest close to 10%

(thickness of ice is 15mm). The stiffness of transmission tower decreases significantly if the rate of frequency change is more than 10%. 5 Conclusion This paper presented analyses of the dynamic characteristics of long-span power transmission tower-line system, the finite element model was constructed, the dynamic properties under instability caused by wind load and ice loads are discussed. The results support the following conclusions: 1) When the wind speed is low, the tower-line system can be simplified to a single tower and focus on static analysis, but when the speed of wind becomes higher, there is no shortcut. 2) The ultimate bearing capacity of tower-line system is smaller than the single tower, the single tower can withstand the maximum wind speed is 47m/s, while the system is 44m/s. 3) The 1 st order frequencies in transverse direction of tower-line systems are constant with respect to the thickness of ice. The frequencies change significantly when the wind-speed exceeds a certain value. 4) The ice thickness of line increases, the ultimate bearing capacity of transmission tower decreases. 5) Wind speed is 25m/s, the smallest rate of frequency change is 6% (no ice), while the largest close to 10% (thickness of ice is 15mm). The stiffness of transmission tower decreases significantly if the rate of frequency change is more than 10%. References [1] H. N. Li, H. F. Bai. State-of-the-Art Review on Studies of Disaster Resistance of High-Voltage Transmission Tower-Line Systems. China Civil Engineering Journal, 2007, 40 (2): 39-46 [2] Q.W. Yang. A Review of Vibration-Based Structural Damage Identification Methods. Journal of Vibration and Shock, 2007, 26 (10): 86-91 [3] P. McComber, A.Paradis. A Cable Galloping Model for Thin Iced Accretions. Atmospheric Research, 1998, 46: 13-25 [4] J. H. Yuan, X. L. Jiang, H. Yi etc. The Present Study on Conductor Icing of Transmission Lines. High Voltage Engineering, 2004, 30 (01): 6-9 [5] H. Yasui, H. Marukawa, Y. Momomura, T. Okamura. Analytical study on wind-induced vibration of power transmission tower[j ]. Journal of Wind Engineering and Industrial Aerodynamics, 83(1999) 431-441 [6] Technical code for designing 110~500kV overhead transmission line, DL/T 5092 1999P, State Economic and

Trade Commission. [7] X. T. Zhang. Wind Load Theory and Wind Resistance Calculation Manual in Engineering. Tongji University Press, Shanghai, China, 1990 [8] H. N. Li, X. Li, G. Li, L. Z. Huang. Wind-Induced Dynamic Response Analysis of Iced Transmission Tower-Line System. 2008, 28 (2): 127-134