Technical Bulletin 005(A) Developed with Communities and Local Government



Similar documents
Rochdale Building Control Guide. Approved Document F Means of ventilation

Te c h n i c a l G u i d a n c e D o c u m e n t

Fire Standards & Regulations Are you confused?

Technical Bulletin 140 Developed in conjunction with the Institution of Gas Engineers and Managers (IGEM)

Compliance Document for New Zealand Building Code Clause G4 Ventilation Third Edition

NUAIRE VENTILATION SYSTEMS FLATMASTER AND FLATMASTER 2000 SYSTEMS

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010

Safe Method: Gas Safety in Catering Establishments

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

NUAIRE VENTILATION SYSTEMS DRIMASTER, DRIMASTER 3S, DRIMASTER 2000 AND DRIMASTER S SYSTEMS

INSTALLATION REQUIREMENTS FOR DOMESTIC GAS WATER HEATERS ( RATED HEAT INPUT UP TO 70 kw )

ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards

Part J - The Requirement 5

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

2010 edition. Ventilation ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION. The Building Regulations F1 Means of ventilation

EAST LONDON GUIDANCE ON HMO STANDARDS (3)

Minimum Housing and Health Standards

HVAC Code Requirements

Technical Bulletin 025

HEAVY DUTY STORAGE GAS

Dwelling Energy Assessment Procedure (DEAP)

Gas Water Heaters Regulation 35A of Building (Planning) Regulations

2014 British Columbia Building Code Changes

The Government s Standard Assessment Procedure for Energy Rating of Dwellings

Energy Efficiency HOSPITALITY.

city of edmonds development information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Introduction. CE marked construction products

EAST LONDON HMO GUIDANCE (4)

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

MP 5.7 RESIDENTIAL SERVICES BUILDING STANDARD


Legislative, Normative & Informative Document List

How To Design A Gas Dryer

For use by landlords of small premises Premises Address

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

Property Accreditation Standards 2014/2015

Chimneys in Thatched Properties

Guidance on loft conversions in two-storey houses

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition

plumbing products guide

Dealing with damp and mould growth

Fire safety for landlords

ONLINE VERSION ONLINE VERSION ONLINE VERSION edition. Ventilation APPROVED DOCUMENT. The Building Regulations Means of ventilation

Fire precautions in dwellings. Private sector housing Providing homes building communities

For use by landlords of small premises Premises Address

Energy Company Obligation (ECO): Technical Monitoring Questions

Permanent Ventilators (for the Supply of Combustion

How To Build A Basement House

HOUSES IN MULTIPLE OCCUPATION STANDARDS. Housing Executive

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS

Contents. 1. Introduction 1.1 Reason for this Guide Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4

HOUSING STANDARDS POLICY TRANSITION STATEMENT IMPLEMENTATION: OCTOBER May 2015

Residential Investment Property Tax Depreciation Explained

Landlord Gas Safety Inspection (CP12) & Landlord Boiler Service Plan

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

G SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Appendix S: Reduced Data SAP for existing dwellings

HVAC Systems in Schools & Commercial Buildings and Radon

Northern Ireland Housing Executive: HMO Fire Safety Guide

Issue ID Description No. of Credits Available. Mandatory Elements Storage of Non-recyclable Waste and Recyclable Household Waste

RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

INVENTORY AND HOME CONDITION REPORT. Keys

Schedule B to By-law

FIRE DETECTION AND ALARM SYSTEMS

ONLINE VERSION. The Building Regulations 2010 The Building (Approved Inspectors etc) Regulations 2010 ONLINE VERSION

Commissioning of Heat Producing Appliances Burning Solid Fuel

- 5 - Table1. Maximum Compartment Volumes

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!

Fire Alarm system Installation Guide

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

READ AND SAVE THESE INSTRUCTIONS

City of Peterborough

Lee Baron FIRE RISK ASSESSMENT

Gas Fired Water Heater Installation

CE29. Domestic heating by oil: boiler systems guidance for installers and specifiers

Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings

Basement Development Construction requirements for the development of basements in residential dwellings.

Fire Safety Risk Assessment

London Borough of Redbridge

How to report a repair

CHAPTER 4 VENTILATION

Carbon Monoxide Detection in Commercial Buildings (

New York, Dean. Price 182,500

ONLINE VERSION ONLINE VERSION

Building Control Guidance Note

DOMESTIC SMOKE ALARMS

NUNAVUT HOUSING CORPORATION. Home Repair Program (HRP)

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

The client organisation that was best at meeting residents needs in the provision of a maintenance service

CE30. Domestic heating by gas: boiler systems guidance for installers and specifiers

Condensing Boiler Efficiency

LOUTH COUNTY COUNCIL STATEMENT OF POLICY ON DOMESTIC FIRE DETECTION AND ALARM SYSTEMS

How To Understand The Gusp

Transcription:

Technical Bulletin 005(A) Developed with Communities and Local Government Title: Gas cookers in internal kitchens - Ventilation requirements as applied to England, Wales, the le of Man and Guernsey Date issued: 15 October 2010 te: This version of Technical Bulletin (TB) 005 replaces the version originally published 19 August 2010 which is now withdrawn. This version has been reviewed and updated in line with BS 5440-2: 2009 and Approved Document F 2010 of the Building Regulations and applies particularly to installations in England, Wales, the le of Man and Guernsey. This Technical Bulletin provides guidance to Gas Safe registered businesses/engineers on the requirements for gas cooking appliances located in internal kitchens and those kitchens which are now regarded as internal following modifications to the building and applies particularly to England, Wales, the le of Man and Guernsey Background This Technical Bulletin (TB) is intended to provide guidance on the requirements of gas cooking appliances located in internal kitchens and those kitchens which have now become internal due to modifications to the building e.g. due to the addition of a conservatory, or building extension and applies particularly to the requirements for England, Wales, the le of Man (IOM) and Guernsey. te 1: For details on the requirements Gas cookers in internal kitchens in Scotland see TB 005(B) and for rthern Ireland, see TB 005(C). te 2: For a list of definitions used in relation to this TB see page 4. Ventilation requirements The requirements for gas cookers/hobs can be found in the current British Standard (BS) 5440-2 (1) and in particular, Table 6 Minimum permanent opening free-area for flueless appliances gives the recommendations for gas cooking appliances. Part of the Table relevant to gas cooking appliances is reproduced below. Type of appliance Domestic oven, hotplate, grill or any combination thereof (C) Maximum appliance rated input limit (net) ne Room volume (m 3 ) Permanent vent size cm 2 <5 100 5 to 10 50 (D) >10 Nil Openable window or (A) (B) equivalent also required (A) Alternative acceptable forms of opening include any adjustable grille or louvre, hinged panel or other means of that opens directly to the outside air. This is additional to the permanent vent requirement. (B) Where no openable window direct to outside is available, other products shall be sought (see 7.4) Building Regulations advice should be followed, see 7.4 (te: clause 7.4 is reproduced below). (C) The appliance, unless a single burner hotplate/boiling ring, shall not be installed in a bedsitting room of less than 20m 3 volume. (D) If the room or internal space containing these appliances has a door which opens directly to the outside, no permanent opening is required. te 3: Where appropriate, the requirements of BS 5440-2 (1) Clause 6.6 Multi-appliance installations should also be taken into consideration. Page 1 of 6

Clause 7.4 of BS 5440-2: 2009 (1) states: 7.4 Internal kitchens Open-flued appliances in internal kitchens shall be provided with in accordance with 6.3. Flueless appliances in internal kitchens shall be ventilated in accordance with Table 6. For further information, Commentary on clause 7.4 to BS 5440-2 (1) directs the reader to Approved Document F (2) (ADF (2) ) to the Building Regulations for England and Wales and Gas Safe Register Technical Bulletin (TB) 005. te 4: The current provision for dwellings in England and Wales can be found in ADF 2010 of the Building Regulations England and Wales. In the case of the le of Man and Guernsey, the respective Government websites direct the reader to the Approved Documents (ADs) for Building Regulations in England and Wales for specific guidance. However, it should be noted that the le of Man and Guernsey may not always apply the requirements of the latest published ADs. It may be appropriate to contact Local Building Control for further guidance. te 5: For details of current gas safety legislation, building legislation and industry standards for the geographical areas covered by Gas Safe Register, see TB 999 (3) at: https://engineers.gassaferegister.co.uk - login and visit the Technical Information area. In addition to the requirements for combustion air, there is a need for the provision of, including purge (previously termed rapid ) in dwellings. Purge is provided to aid removal of high concentrations of pollutants and water vapour released from activities such as painting, cooking, etc. Building legislation Approved Document F (ADF (2) ) Ventilation (2010 edition) Building Regulations for England and Wales ADF (2) Clause 5.5 states: Extract to outside is required in each kitchen, utility room and bathroom and for sanitary accommodation. The extract can be either intermittent or continuously operating. The minimum extract air flow rates at the highest and lowest settings should be no less than in Table 5.1a. Clause 5.6 of ADF (2) states: The whole dwelling rate for the supply of air to the habitable rooms in a dwelling should not be less than specified in Table 5.1b. The relevant parts of Tables 5.1a and 5.1b in ADF (2) are reproduced in Table 1 and Table 2 below. Table 1 Kitchen Room Minimum intermittent extract rate 30 l/s (adjacent to hob) or 60 l/s elsewhere 13 l/s Minimum high rate Continuous extract Minimum low rate Total extract rate must be at least the whole building rate in Table 2. Table 2 Whole building rates Number (a) (b) Whole building rate l/s tes to Table 2: of bedrooms in dwelling 1 2 3 4 5 13 17 21 25 29 (a) In addition, the minimum rate should not be less than 0.3 l/s per m 2 of the internal floor area (this includes each floor e.g. for a two storey building, add the ground and first floor areas). (b) This is based on two occupants in the main bedroom and a single occupant in all other bedrooms. This should be used as the default value. If a greater level of occupancy is expected, then add 4 l/s per occupant. Page 2 of 6

Clause 5.7 of ADF (2) advises that purge provision is required in each habitable room and should be capable of extracting a minimum of 4 air changes per hour per room directly to outside. Generally, openable windows or doors can provide this function, otherwise a mechanical extract system should be provided. In other rooms (e.g. kitchens and bathrooms) the mechanical or passive stack extract provisions should be sufficient, although passive stack will take longer to purge the room. Use of extract fans to achieve purge air requirements for gas cookers If the kitchen has no external walls, the provision (background and purge) should be via an intermittent mechanical extraction fan. The extract fan rate should be a minimum of 30 l/s where the fan is located above the hob and 60 l/s if the fan is located elsewhere in the kitchen. Intermittent extract can be operated manually and/or automatically by a sensor (e.g. humidity sensor, usage sensor, etc.). In kitchens, any automatic control should provide sufficient flow during cooking with fossil fuels to avoid the build up of combustion products. Any automatic control should provide a manual over-ride to allow the occupant to turn the extract system on. The fan should have a 15 minute over-run facility. In rooms with no natural light the fan may be controlled by the operation of the main light switch. If the extraction is via a cooker hood, it should be installed paying due regard to both the hood and cooker manufacturer s installation instructions. Mechanical extract terminals and extract fans should be placed as high as practicable but preferably within 400mm of the ceiling. te 6: For further guidance on the effects of extract fans on open flued appliances, see TB 095 (4), which can be viewed at: https://engineers.gassaferegister.co.uk - login and visit the Technical Information area. To ensure good air transfer throughout the dwelling, there should be an undercut equivalent to a minimum area of 7600mm 2 in all internal doors above the floor finish, between the internal kitchen, adjoining room and outside air above the floor finish, e.g. an undercut of 10mm from a standard width 760mm door above the floor finish, or by 20mm undercut above floorboards, or other surface if the finish (e.g. carpet/tiles etc.) has not been fitted. Building extensions/conservatory installations In the event that a building extension or conservatory is added to a dwelling and in the absence of intermittent extraction as described above, the general rate for the building extension or conservatory and where necessary the kitchen behind, can also be achieved by the use of background ventilators in the following manner: 8000mm 2 background in each position Openings to provide at least 1/20 th of the combined floor area Kitchen Conservatory or similar space a) Purge via openable doors windows or similar to outside air with a total opening area equivalent to 1/20 th the total combined floor area of the kitchen and building extension/conservatory; Page 3 of 6 and b) Background (trickle vents) of at least 8000mm 2 which are closable and located at least 1.7m above the floor. te 7: See diagram opposite for the method of providing to an internal kitchen through a conservatory.

Passive stack Alternatively, guidance given in ADF (2) (Table 5.2b) explains that an open-flued appliance may provide sufficient extract for the room in which it is located when in operation via its chimney/flue system acting as a form of Passive Stack Ventilation (PSV) and can be arranged to provide sufficient when not firing. It is essential that the recommendations of BS 5440-2 (1) are complied with. ADF (2) explains that the provisions may be adequate in the case of: a) A solid-fuel open-flued appliance installed in the internal kitchen is the primary source of heating, cooking or hot water; or b) Where there is an open-flued appliance (e.g. gas-fired, oil-fired), which has a chimney/flue system with a free area equivalent to 125mm diameter and the appliance s combustion air inlet (e.g. air vent) and dilution inlet (e.g. draught diverter) are permanently open, i.e. there is a path with no control dampers which could block the flow or path and can be left open when the appliance is not in use. te 8: For further guidance on PSV systems, see TB 057 (5), which can be viewed at: https://engineers.gassaferegister.co.uk - login and visit the Technical Information area. Additional guidance A flowchart has been developed (see Appendix 1) to provide guidance to Gas Safe registered businesses/engineers when assessing the safety of gas cooking appliances located within internal kitchens in relation to the requirements of the primary legislation concerning the safe installation, maintenance and use of gas systems and appliances, (e.g. in Great Britain (GB) the Gas Safety (Installation and Use) Regulations (GSIUR)) in particular regulation 26(9) of GSIUR and also the current Gas Industry Unsafe Situations Procedure (GIUSP). te 9: Similar legislative requirements apply in other geographical areas covered by Gas Safe Register (see also te 5). te 10: The GIUSP (TB 001) can be viewed at: https://engineers.gassaferegister.co.uk - login and visit the Technical Information area. ADF (2) 2010 also calls up the Domestic Ventilation Compliance Guide (6) which is designed to help persons comply with the requirements of ADF (2). Where appropriate, further help and advice on the suitability of the provision should be sought from the local building control body. Definitions of terms used in this Technical Bulletin Background ventilator: is defined in ADF (2) as a small opening designed to provide controllable whole building. Habitable room: is defined in ADF (2) as a room used for dwelling purposes but which is not solely a kitchen, utility room, bathroom cellar or sanitary accommodation. Internal kitchens: In relation to this TB, examples include but are not limited to: where there is no door, openable window, or equivalent to direct to outside air; where there is no opening communicating directly with the outside air because all walls are internal, e.g. no walls are in direct contact with outside air, such as in residential flats; where a conservatory, or building extension has been built over the only wall of a kitchen communicating with outside air, such as in a terraced property. Outside air: can be hard to define at times and the person carrying out the inspection should treat each case on its own merits. As an example, a route is taken through an exterior wall; however, a car port has since been constructed over the termination. There are gates at either end of the car port which fills 75% of the end space. The roof to the car port is corrugated but the gaps under the corrugations have not been filled. The air in this case may be considered as outside air, as the space cannot be realistically described as overtly enclosed. Page 4 of 6

Passive stack (PSV): is a device using ducts from terminals in the ceiling of rooms, to terminals on the roof that extract air to outside by a combination of natural stack effect and the pressure effects of wind passing over the roof of the building. Open-flued systems such as those utilised by gas appliances operate in a similar manner. Purge : is defined in ADF (2) as manually controlled of rooms or spaces at a relatively high rate to rapidly dilute pollutants and/or water vapour. Purge may be provided by natural means (e.g. an openable window) or by mechanical means (e.g. a fan). te 11: For general information about the process behind the development of Gas Safe Register Technical Bulletins and the expectations for all Stakeholders, see TB 1000 at: https://engineers.gassaferegister.co.uk - login and visit the Technical Information area. Bibliography (1) BS 5440-2: 2009 Flueing and for gas appliances of rated input not exceeding 70kW net (1 st, 2 nd and 3 rd family gases) Specification for installation and maintenance of provision for gas appliances (2) Approved Document F (ADF) Means of : http://www.planningportal.gov.uk/uploads/br/br_pdf_adf_2010.pdf (3) TB 999 - Gas Safe Register rmative Document List (4) TB 095 - Effect of mechanical fans on open-flued appliances (5) TB 057 - Passive stack (6) Domestic Ventilation Compliance Guide: http://www.planningportal.gov.uk/uploads/br/domestic compliance_guide_2010.pdf -o0o- Page 5 of 6

Appendix 1 - Ventilation requirements for flueless gas cooking appliances in internal kitchens as applied to England, Wales, le of Man and Guernsey START Section A Section A Providing that the installation passes all relevant safety checks, (GSIUR Regulation 26(9)), the cooker installation can be regarded as satisfactory Where a building extension or conservatory is built over an existing kitchen go to Section B Does the room volume and where required, combustion air meet the requirements of BS 5440-2? Classify cooking appliance as At Risk ( AR ) in accordance with current GIUSP Section B START Section B Classify cooking appliance as t to Current Standards ( NCS ) in accordance with current GIUSP there sufficient continuous/intermittent purge provided (extract fan) ducted to outside air? See te 1. Where a building extension or conservatory is built over an existing kitchen Assuming the general requirements of BS 5440-2 are met, additional requirements apply for internal kitchens, or where a building extension or conservatory is built over an existing kitchen. Where no opening to outside via door, window or similar exists, Building Regulations ADF Means of Ventilation also applies Mechanical method Natural method Classify cooking appliance as t to Current Standards ( NCS ) in accordance with current GIUSP purge provided through openable doors/windows/ PSV in kitchen and adjoining room/ conservatory to outside air? extract rate via Intermittent Either: A) at least 30 l/s (extract hood or canopy over hob), or B) 60 l/s extract located elsewhere in kitchen? Or if Continuous extract See te 2. te 1: Refer to guidance in the main Technical Bulletin under Use of extract fans to achieve purge air requirements for gas cookers. te 2: Refer to Table 1 and Table 2 in the main Technical Bulletin under Building legislation Approved Document F (ADF) Ventilation (2010 edition). te 3: Refer to guidance in the main Technical Bulletin under Building extensions/conservatory installations and also Passive stack. provision equivalent to 5% (1/20 th ) of combined floor area of kitchen and adjoining room/conservatory? Or 125mm PSV (minimum CSA 12000mm 2 )? Or open-flued gas/oil appliance with minimum 125mm chimney/flue, correct, no dampers or flue stabilisers? Or solid fuel appliance where it is the primary central heating, hot water or cooking source? See te 3. there provision for air transfer between rooms equivalent to 7600mm 2 e.g. a vent, or 10mm cut off a 760mm wide door? Classify cooking appliance as NCS in accordance with current GIUSP Has closable background between kitchen and adjoining room/conservatory to outside air equivalent to 8000mm 2 been provided at least 1.70m above floor level? Providing that the installation passes all relevant safety checks, (GSIUR Regulation 26(9)) the cooker installation can be regarded as satisfactory FW V1 15.10.10 Page 6 of 6