Product Data Sheet Rosemount 3095FT MultiVariable Flow Data Logger THE PROVEN LEADER IN MULTIVARIABLE MEASUREMENT: Industry leading performance with ±0.05% of DP reading accuracy Ten year stability under actual process conditions Unprecedented reliability backed by a limited 12-year warranty Measures natural gas flow through an orifice plate per AGA, API, and GPA standards Advanced data and event logging, API compliant Coplanar platform enables orifice-based DP Flowmeters Rosemount 3095FT Contents Specifications.....................................................page Pressure-3 Product Certifications...............................................page Pressure-6 Dimensional Drawings...............................................page Pressure-7 Ordering Information................................................page Pressure-9 www.rosemount.com
Rosemount 3095FT Product Data Sheet Rosemount 3095FT Leader in MultiVariable Measurement Developed in coordination with the Gas Research Institute, the state-of-the-art 3095FT is the world s most compact electronic flow measurement (EFM) device. The 3095FT delivers four measurements from one coplanar device while performing user configured data logging. Industry leading performance with ±0.05% of DP reading accuracy Enabled by superior sensor technology and engineered for optimal flow performance, the 3095FT delivers unprecedented reference accuracy with 100:1 rangeability. Superior performance means reduced variability for improved billing accuracy. Ten year stability under actual process conditions Through aggressive simulation testing, the 3095FT has proven its ability to maintain unprecedented performance under the most demanding conditions. Superior transmitter stability decreases calibration frequency for reduced maintenance and operation costs. Unprecedented reliability backed by a limited 12-year warranty Further enhance installation practices with the most reliable platform supported by a 12-year warranty. Four variables in one device The advanced 3095FT measured three process variables simultaneously, while calculating flow through an orifice plate per American Gas Association (AGA), American Petroleum Institute (API) and Gas Processors Associations (GPA) standards. One installation means reduced process penetrations, inventory and installation costs. Advanced data logging With user-configurable data logging exceeding EFM requirements of API MPMS Chapter 21.1, the 3095FT logs the continuously averaged flow data. The nonvolatile memory logs 50 days of daily, variable and event logs. A cost effective solution for natural gas flow monitoring and custody transfer. Coplanar platform enables DP flowmeters The solution arrives factory calibrated, pressure-tested, and ready to install right out of the box. Only Rosemount has a scalable coplanar transmitter design to reduce engineering and inventory costs. Advanced PlantWeb functionality From multiple process variable generation to advanced compensated Mass Flow functionality and highly integrated flowmeter solutions, the 3095 reduces operational and maintenance expenditures while improving throughput and utilities management. Rosemount DP-Flow Solutions Rosemount 3051S Series of Instrumentation Scalable pressure, flow, and level measurement solutions improve installation and maintenance practices. Rosemount 3095 Mass Flow Transmitter Accurately measures differential pressure, static pressure, and process temperature to dynamically calculate fully compensated mass flow. Rosemount 305, 306 and 304 Manifolds Factory-assembled, calibrated, and seal-tested transmitter-to-manifold assemblies reduce on-site installation costs. Rosemount 1495, 1496, 1497, and 1595 Orifice Plate Primary Element Systems A comprehensive offering of orifice plates, flange unions and meter sections that is easy to specify and order. The 1595 Conditioning Orifice provides superior performance in tight fit applications. Rosemount 3051SFA, 3095MFA, 485, and 285 Annubar Series The state-of-the-art, fifth generation Rosemount 485 Annubar combined with the 3051S or 3095 MultiVariable transmitter creates an accurate, repeatable and dependable insertion-type flowmeter. The Rosemount 285 provides a commercial product offering for your general purpose applications. Rosemount 3051SFC, 3095MFC, and 405 Compact Orifice Series Compact Orifice Flowmeters can be installed between existing flanges, up to a Class 600 (PN100) rating. In tight fit applications, a conditioning orifice plate version is available, requiring only two diameters of straight run upstream and two diameters downstream. Rosemount 3051SFP, 3095MFP, and 1195 ProPlate Series These Integral Orifice Flowmeters eliminate the inaccuracies that become more pronounced in small orifice line installations. The completely assembled, ready to install flowmeters reduce cost and simplify installation. Pressure-2
Product Data Sheet Rosemount 3095FT Specifications FUNCTIONAL Service AGA 8 Natural Gas, AGA 3 Orifice Plates Consult factory for other fluid and primary element combinations Differential Sensor Limits Range 2: 250 to 250 inh 2 O (-62,2 to 62,2 kpa) Range 3: 1000 to 1000 inh 2 O (-249 to 249 kpa) Absolute Sensor Limits Range 3: 0.5 to 800 psia (0,0034 to 5,516 MPa) Range 4: 0.5 to 3,626 psia (0,0034 to 25,00 MPa) Gage Pressure Limits Range C: 0 to 800 psig (0 to 5,516 MPa) Range D: 0 to 3,626 psig (0 to 25,00 MPa) Over Pressure Limit 0.5 psia (0,0034 MPa) to two times the absolute pressure sensor range up to a maximum of 3,626 psia (25,00 MPa). Static Pressure Limit Operates within specifications between static line pressures of 0.5 psia (0,0034 MPa) and the URL of the absolute pressure sensor. Flow Calculations 1992 AGA Report No. 3 (1) API MPMS Chapter 14.3 (1) GPA (1) Flange tap configurable per corresponding AGA calculations Pipe Tap configurable per corresponding AGA calculations NOTE Flow calculations will cease when DP readings are below low flow cut off. Data Logging Exceeds API MPMS 21.1 Daily & Variable Logs have user selected time duration between 1-99 minutes Event Logs record alarms, configuration changes, and significant occurrences affecting flow calculation 50 days of daily logs maintained for user-selected process variables and calculated values when seven required API variables are logged. Logged files saved as ASCII file or comma separated value file. Daily Variable Log Parameters Maximum: DP, PT, and SP Minimum: DP, PT, and SP Average: DP, PT, and SP Total: Energy, Flow, and Flow Time Average: Energy Rate, Flow Rate, Integral Value, C', Z Specific Gravity Heating Value Audit Trail Exceeds API MPMS Chapter 21.1 standards for electronic flow measurement systems. User Interface Software and Hardware Requirements PC with CD-ROM Drive 4 MB RAM minimum Microsoft Windows 98, NT, 2000, or XP 2 MB of free hard disk space Output Two-wire, constant 9.5mA current, data logging Power Supply External power supply required. Data Logger operates on terminal voltage of 7.5 35 V dc with a constant average operating current of 9.5 ma. Compressibility Calculations AGA Report No. 8 API MPMS Chapter 14.2 Gross or Detailed Characterization Method (1) Orifice Metering of Natural Gas and Other Related Hydrocarbon Fluids. Third Edition, August 1992. Part 3 Natural Gas Applications. American Gas Association Report No. 3; American Petroleum Institute API 14.3; Gas Processor Association GPA 8185-92. Pressure-3
Rosemount 3095FT Product Data Sheet Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply, as described by: Load (Ohms) Max. Loop Resistance 1964 250 Temperature Limits 0 7.5 11.0 Power Supply Voltage Process (at transmitter isolator flange for atmospheric pressures and above) 40 to 185 F ( 40 to 85 C) Ambient: -40 to 185 F (-40 to 85 C) With LCD Display (1) : -40 to 175 F (-40 to 80 C) Storage: -50 to 212 F (-46 to 100 C) With LCD Display: -40 to 185 F (-40 to 85 C) Humidity Limits 0 100% relative humidity Power Supply Voltage 7.5 ------------------------------------------------------------------------ 0.014 Operating Region Communication requires a minimum loop resistance of 250 ohms. Failure Mode Alarm If self-diagnostics detect a gross transmitter failure, the output registers an alarm with each message. Turn-on Time Process variables will be within specifications less than 60 seconds after power is applied to transmitter. Damping Response to step input change can be user-selectable from 0 to 15 seconds for one time constant. This is in addition to sensor response time of 0.2 seconds. Real-Time Clock Accuracy ±2 minutes per month at reference conditions = Memory Non-volatile memory per applicable A.G.A., A.P.I., and G.P.A. orifice meter and electronic flow measurement standards. 35 PERFORMANCE Zero-based spans, reference conditions, silicone oil fill, 316 SST isolating diaphragms, and digital trim values equal to the span end points. Specification Conformance The Rosemount 3095 maintains a specification conformance of measured variables to at least 3. Differential Pressure Range 2: 0 2.5 to 0-250 inh2o (0 0,6227 to 0-62,27 kpa) Range 3: 0-10 to 0-1000 inh2o (0 2,491 to 0-249,1 kpa) Reference Accuracy (including Linearity, Hysteresis, Repeatability) Range 2-3 Ultra for Flow (Option U3) (2) ±0.05% of DP reading up to 3:1 DP turndown from URL For DP turndowns up to 100:1 from URL, Accuracy = ± URL 0.05 + 0.0145 --------------------------------- DPReading % of DP Reading Range 2-3 ±0.075% of span for spans from 1:1 to 10:1 of URL For spans less than 10:1 of URL, Accuracy =± 0.025 + 0.005 -------------- URL Span % of Span Ambient Temperature Effect per 50 F (28 C) Range 2-3 Ultra for Flow (Option U3) (2) ±0.130% of DP reading up to 3:1 DP turndown from URL ±[0.05 + 0.0345 (URL/DP Reading)]% of DP reading up to 100:1 DP turndown from URL Range 2-3 ±(0.025% URL + 0.125% span) spans from 1:1 to 30:1 ±(0.035% URL 0.175% span) spans from 30:1 to 100:1 Static Pressure Effects Zero error = ±0.05% of URL per 1,000 psi (6895 kpa) Span error = ±0.20% of DP Reading per 1,000 psi (6895 kpa) Stability Range 2-3 Ultra for Flow (Option U3) (2) ±0.25% of URL for 10 years; for ±50 F (28 C) temperature changes, up to 1000 psi (6895 kpa) line pressure Range 2-3 ±0.125% of URL for five years for ±50 F (28 C) ambient temperature changes, and up to 1000 psi (6895 kpa) line pressure. (1) LCD Display may not be readable and LCD updates will be slow at temperatures below -4 F (-20 C). Pressure-4 (2) Ultra for Flow (option U3) applicable for DP ranges 2 and 3 with SST isolator material and silicone fill fluid options only.
Product Data Sheet Absolute/ Gage Pressure Absolute (100:1 rangeability allowed) Range 3 0.5 8 to 0.5 800 psia (0,0034 0,055 to 0,0034 5,516 MPa) Range 4 0.5 36.26 to 0.5 3,626 psia (0,0034 0,250 to 0,0034 25,00 MPa) Gage (100:1 rangeability allowed) Range C 0 8 to 0 800 psig (0 0,055 to 0 5,516 MPa) Range D 0 36.26 to 0 3,626 psig (0 0,250 to 0 25,00 MPa) Reference Accuracy (including linearity, hysteresis, repeatability) ±0.075% of span for spans from 1:1 to 6:1 of URL For spans less than 6:1 rangedown Accuracy =± 0.03 + 0.0075 ------------- URL % of span Span Ambient Temperature Effect per 50 F (28 C) ±(0.05% URL + 0.125% of span) spans from 1:1 to 30:1 ±(0.06% URL - 0.175% of span) spans from 30:1 to 100:1 Stability ±0.125% of URL for five years for ±50 F (28 C) ambient temperature changes, and up to 1000 psi (6,89 MPa) line pressure. Process Temperature (RTD) Specification for process temperature is for the transmitter portion only. Sensor errors caused by the RTD are not included. The transmitter is compatible with any PT100 RTD conforming to IEC 751 Class B, which has a nominal resistance of 100 ohms at 0 C and = 0.00385.Examples of compatible RTDs include the Rosemount Series 68 and 78 RTD Temperature Sensors. Range 40 to 185 F ( 40 to 85 C). May be limited by the flow calculation characterization method. Accuracy (including Linearity, Hysteresis, Repeatability) ±1.0 F (0.56 C) Ambient Temperature Effects ±0.72 F (0.40 C) per 50 F (28 C) Stability ±1.0 F (0.56 C) for one year PHYSICAL Rosemount 3095FT Security Transmitter security switch mounted on electronics board, when enabled prevents changes to transmitter security. User Interface Software provides three levels of password security, they are as follows: System Administrator (one password) Maintenance (three passwords) Operation (six passwords) Electrical Connections ½ 14 NPT, M20 x 1.5 (CM20), PG-13.5 Process Connections Transmitter ¼ 18 NPT on 2 1 /8-in. centers. RTD RTD dependent (see Ordering Information on page 9) RTD Process Temperature Input 100-ohm platinum RTD per IEC-751 Class B Process Wetted Parts Isolating Diaphragms 316L SST or Hastelloy C-276 Drain/Vent Valves 316 SST or Hastelloy C-276 Flanges Plated carbon steel, 316 SST, or Hastelloy C-276 Wetted O-rings Glass-Filled PTFE Non-Wetted Parts Electronics Housing Low copper aluminum Bolts Plated carbon steel per ASTM A449, Grade 5; or austenitic 316 SST Fill Fluid Silicone oil Paint Polyurethane O-rings Buna-N Weight Component Weight in lb (kg) 3095FT Transmitter 6.0 (2,7) LCD Display 0.5 (0,2) SST Mounting Bracket 1.0 (0,4) 12 ft (3.66 m) RTD Shielded Cable 0.5 (0,2) 12 ft (3.66 m) RTD Armored Cable 1.1 (0,5) 24 ft (7.32 m) RTD Shielded Cable 1.0 (0,4) 24 ft (7.32 m) RTD Armored Cable 2.2 (1,0) 75 ft (22.86 m) RTD Shielded Cable 3.1 (1,4) 75 ft (22.86 m) RTD Armored Cable 6.9 (3,1) Pressure-5
Rosemount 3095FT Product Data Sheet Product Certifications Approved Manufacturing Locations Rosemount Inc. Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. Wessling, Germany Emerson Process Management Asia Pacific Private Limited Singapore Beijing Rosemount Far East Instrument Co., Limited Beijing, China European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive. European Pressure Equipment Directive (PED) (97/23/EC) 3095F_2/3,4/D Flow Transmitters QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity Assessment All other 3095_ Transmitters/Level Controller \ Sound Engineering Practice Transmitter Attachments: Process Flange - Manifold Sound Engineering Practice Electro Magnetic Compatibility (EMC) (2004/108/EC) 3095FT Flow Transmitters EN 61326:1997/ A1, A2, and A3 Ordinary Location Certification for Factory Mutual As standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). Hazardous Locations Certifications North American Certifications FM Approvals A Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G. Suitable for Class III, Division 1, indoor and outdoor (Type 4X) hazardous locations. Factory Sealed. Provides non-incendive RTD connections for Class I, Division 2, Groups A, B, C, and D. Install per Rosemount drawing 03095-1025. Canadian Standards Association (CSA) C Explosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G. Suitable for Class III, Division 1, indoor and outdoor hazardous locations, CSA enclosure Type 4X. Factory Sealed. Provides non-incendive RTD connection for Class I, Division 2, Groups A, B, C, and D. Approved for Class I, Division 2, Groups A, B, C, and D. Install in accordance with Rosemount Drawing 03095-1024. European Certifications H P ATEX Flameproof Certificate Number: KEMA02ATEX2320X EEx d IIC T5 (-50 C T amb 80 C) T6 (-50 C T amb 65 C) 1180 II 1/2 G Special Conditions for Safe Use (x): The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. the manufacturer s instructions fro installation and maintenance shall be followed in detail to assure safety during its expected lifetime. ATEX Dust Certificate Number: KEMA02ATEX2321 V = 55 Vdc MAX I = 23 ma MAX IP66 1180 II 1 D IECEx Certifications 7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20 C T a 65 C) Zone 0/1 Ex d IIC T5 (-20 C T a 80 C) V max = 55 Vdc I max = 23 madc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex td A22 T90 C IP66 Pressure-6
Product Data Sheet Rosemount 3095FT Dimensional Drawings Exploded View of 3095FT Certification Label Housing Terminal Block Cover O-ring Cover Electronics Board Nameplate Module O-ring Housing Locking Screw Sensor Module RTD Connector Process Flange O-ring Drain/Vent Valve Coplanar Flange Flange Adapter O-ring Optional Flange Adapters Bolts Pressure-7
Rosemount 3095FT Product Data Sheet 3095FT Dimensions are in inches (millimeters). Meter Cover (Optional) 5.00 (127) 4.30 (110) ½ 14 NPT Conduit Connection (Two Places) 4.20 (107) 4.09 (104) Certification Label 0.75 (19) Clearance for Cover Removal 0.75 (19) Clearance for Cover Removal Transmitter Circuitry This Side Nameplate Drain/Vent Valve Transmitter Connections This Side Housing Rotation Set Screw 7.07 (180) 8.17 (208) 6.40 (163) ½ 14 NPT on optional mounting adapters. Adapters can be rotated to give connection centers of 2.00 (51), 2.125 (54), or 2.25 (57). ¼ 18 NPT on Coplanar flange for pressure connection without the use of mounting adapters Dimensions are in inches (millimeters). 2.82 4.30 (72) (110) Mounting Configurations for 3095FT 7.07 (180) 1.10 (28) 6.15 (156) 2.81 (71) 6.25 (159) 4.73 (120) 3.54 (90) Pressure-8
Product Data Sheet Rosemount 3095FT Ordering Information Model 3095F H (1) Product Description MultiVariable Flow Data Logger Output Data Log via PC based User Interface Software Differential Pressure Ranges 2 0 2.5 to 0 250 inh 2 O (0 0,622 to 0 62,27 kpa) 3 0 10 to 0 1000 inh 2 O (0 2,49 to 0 249 kpa) Static Pressure Ranges 3 0.5-8 to 0.5 800 psia (0,0034 0,055 to 0,0034 5,516 MPa) 4 0.5-36.26 to 0.5 3626 psia (0,0034-0,250 to 0,0034 25,00 MPa) C 0-8 to 0-800 psig (0 0,055 to 0 5,516 MPa) D 0-36.26 to 0-3626 psig (0-0,250 to 0 25,00 MPa) Isolator Material Fill Fluid A 316L SST Silicone B (2) Hastelloy C-276 Silicone F Gold Plated SST Silicone Flange Style Material A Coplanar CS B Coplanar SST C Coplanar Hastelloy C-276 J DIN compliant traditional flange, SST 10 mm adapter/manifold bolting SST, 7 /16 20 Bolting 0 None (Required for Option S5) Drain/Vent Material A SST C Hastelloy C-276 0 None (Required for Option S5) O-ring 1 Glass-filled PTFE Process Temperature Input (RTD ordered separately) 0 No RTD Cable 1 RTD input with 12 ft. (3,66 m) of Shielded Cable (intended for use with conduit) 2 RTD input with 24 ft. (7,32 m) of Shielded Cable (intended for use with conduit) 7 RTD input with 75 ft.(22,86 m) of Shielded Cable (intended for use with conduit) 3 RTD input with 12 ft. (3,66 m) of Armored, Shielded Cable 4 RTD input with 24 ft. (7,32 m) of Armored, Shielded Cable 8 RTD Input with 75 ft. (22,86 m) of Armored, Shielded Cable A RTD input with 12 ft. (3,66 m) ATEX/IECEx Flameproof Cable B RTD input with 24 ft. (7,32 m) ATEX/IECEx Flameproof Cable C RTD input with 75 ft. (22,86 m) ATEX/IECEx Flameproof Cable Transmitter Housing Material Conduit Entry Size A Polyurethane-covered Aluminum ½ 14 NPT B Polyurethane-covered Aluminum M20 1.5 (CM20) Adapter C Polyurethane-covered Aluminum PG 13.5 Adapter J 316 SST ½ 14 NPT K 316 SST M20 1.5 (CM20) Adapter L 316 SST PG 13.5 Adapter Pressure-9
Rosemount 3095FT Product Data Sheet Terminal Block A Standard B With Integral Transient Protection Display 0 None 1 LCD Display Bracket 0 None 1 Coplanar SST flange bracket for 2-in. pipe or panel mount, SST bolts 2 Traditional Flange Bracket for 2-in. Pipe Mounting, CS Bolts 3 Traditional Flange Bracket for panel Mounting, CS Bolts 4 Traditional Flange Flat Bracket for 2-in. Pipe Mounting, CS Bolts 5 Traditional Flange Bracket for 2-in. Pipe Mounting, 300-Series, SST Bolts 6 Traditional Flange Bracket for panel Mounting, 300-Series, SST Bolts 7 Traditional Flange Flat Bracket for 2-in. Pipe Mounting, 300-Series, SST Bolts 8 SST Traditional Flange Bracket for 2-in. Pipe Mounting, 300-Series, SST Bolts 9 SST Traditional Flange Flat Bracket for 2-in. Pipe Mounting, 300-Series, SST Bolts Bolts 0 CS bolts 1 Austenitic 316 SST Bolts N None (Required for Option S5) Product Certifications 0 None A FM Explosion-proof, Dust Ignition-proof C CSA Explosion-proof, Dust Ignition-proof, Division 2 H ATEX Flameproof P ATEX Dust 7 IECEx Flameproof 8 IECEx Dust Engineered Measurement Solution (EMS) A Averaging Method: Flow Dependent Time-weighted Formulaic Averaging Compressibility Factor: A.G.A. Report No. 8 /API MPMS Chapter 14.2 Options Performance Class U3 (3) Ultra for Flow: ±0.05% DP reading accuracy, up to 100:1 rangedown, 10 year stability, limited 12 year warranty S5 (4) Assembly with Rosemount 305 Integral Manifold S6 (4) Assemble to Rosemount 304 Manifold or Connection System (Required traditional Flange Style Option J, K, and L) C1 Custom Configuration (requires completed Configuration Data Sheet) DF Flange Adapters Adapter Type Determined by Selected Flange Material: Plated CS, SST, Hastelloy C-276 P1 Hydrostatic Testing with Certificate P2 Cleaning for Special Services Q4 Calibration Certificate Q8 Material Traceability Certification per EN 10204 3.1B Typical Model Number (1) Communication based on Digital HART Protocol. 3095F H 2 3 A B A 1 1 A B 1 1 0 A A (2) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (3) Ultra for Flow (Option U3) applicable for DP ranges 2 and 3 with SST isolator material and silicone fill fluid only. (4) Assemble-to items are specified separately and require a completed model number. Pressure-10
Product Data Sheet OPTIONS Standard Configuration Unless otherwise specified, the transmitter is shipped as follows: Engineering units: Differential inh 2 O at 60 F (All ranges) Absolute/gage psi (all ranges) Output: 9.5mA with Data Logging Flange type: Specified model code option Flange material: Specified model code option O-ring material: Specified model code option Drain/vent: Specified model code option Flow Configuration Factory default Parameters: Software tag: (Blank) Custom Configuration (Option C1) If Option C1 is ordered, the customer specifies the following information for the 3095FT in addition to the standard configuration parameters. Configuration Data Sheet (see page Pressure-12): Gas composition parameters, contract hour, log parameters, LCD display parameters, meter run configuration parameters, low flow cut-off, passwords, static pressure tap location, static pressure measurement, damping, descriptor, message, and upper and lower trim points for each process variable. ACCESSORIES Rosemount 3095FT 3095FT User Interface Software Packages All configurations are packaged separately. Windows 98, NT, 2000, and XP Single PC license: 03095-5100-0104 Site license: 03095-5100-0105 Single PC license, Serial Port HART Modem and cables: 3095-5100-0102 Single PC license, USB HART Modem and Cables (Requires Windows XP or 2000 Operating System): 03095-5100-0103 Communication Accessories Item Description Part Number Serial Port HART Modem and Cables Only 03095-5105-0001 USB Port HART Modem and Cables Only 03095-5105-0002 Tagging Three customer tagging options are available: Standard SST tag is wired to the transmitter. Tag character height is 0.125 in. (3,18 mm), 85 characters maximum. Tag may be stored in transmitter memory. Software tag (8 characters maximum) is left blank unless specified. Tag may be permanently stamped on transmitter nameplate upon request. Tag character height is 0.0625 in. (1,59 mm), 65 characters maximum. Software tag (8 characters maximum) is left blank unless specified. ADDITIONAL INFORMATION Rosemount transmitters are available as fully assembled and factory calibrated flowmeters. Flowmeter Product Data Sheets are listed below: Orifice Plate Primary Element Systems: 00813-0100-4792 Rosemount 1495 Orifice Plate Rosemount 1496 Flange Union Rosemount 1497 Meter Section Pressure-11
Rosemount 3095FT Product Data Sheet Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. Annubar, ProPlate, Rosemount and the Rosemount logotype are registerd trademarks of Rosemount Inc. Coplanar and Multivariable are trademarks of Rosemount Inc. HART is a registered trademark of the HART Communications Foundation. Modbus is a trademark of Modicon, Inc. Hastelloy C and Hastelloy C-276 are registered trademarks of Cabot Corp. Microsoft and Windows are registered trademarks of Microsoft Corp. PlantWeb is a mark of one of the Emerson Process Management companies. All other marks are the property of their respective owners. Emerson Process Management Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1 800 999 9307 T (International) (952) 906 8888 F (952) 949 7001 www.rosemount.com Emerson Process Management Heath Place Bognor Regis West Sussex PO22 9SH England T 44 (0) 1243 863121 F 44 (0) 1243 867554 Emerson Process Management Asia Pacific Private Limited 1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 Enquiries@AP.EmersonProcess.com 00813-0100-4015; 2008 Rosemount Inc. All rights reserved.