CAPACITY ENHANCEMENT OF SHORT CIRCUIT LABORATORY USING PARALLEL OPERATION OF TRANSFORMER

Similar documents
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Power Quality Paper #3

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Transformers. Special transformers Reactors products

Step Voltage Regulators

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Full representation of the real transformer

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

EEL303: Power Engineering I - Tutorial 4

Current Transformers

Loading Considerations When Paralleling Transformers

The following table shows approximate percentage wise the

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Study on Differential Protection of Transmission Line Using Wireless Communication

AMSC s Superconductor Cable Technologies for Electric Utilities

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

SYNCHRONOUS MACHINES

Coupling Effect in Substation Ground Measurements

6 ELECTRICAL PARAMETERS

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

Circulating Current Relay. Type IRXm

INDUCTION REGULATOR. Objective:

Chapter 35 Alternating Current Circuits

Line Reactors and AC Drives

Voltage Stability Improvement using Static Var Compensator in Power Systems

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Instrument Transformers Application Guide

EARTHING SYSTEM CALCULATION

High Voltage Power Supplies for Analytical Instrumentation

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Outline. Systems and Signals 214 / 244 & Energy Systems 244 / 344. Ideal Inductor. Ideal Inductor (cont... )

Tutorial One: Calculation of leakage inductance of transformer using FEM MVA, 132 kv/33kv, Y/, Ampere-turns: , No.

First Year (Electrical & Electronics Engineering)

Lecture - 4 Diode Rectifier Circuits

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

High Intensify Interleaved Converter for Renewable Energy Resources

TRANSFORMER: THREE PHASE

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS

Percentage Restrained Differential, Percentage of What?

Current Transformers Ratio / Polarity / Types

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Power Feeding Equipment for Optical Submarine Cable Systems

Radiated emission measurement of a cell phone processor module using TEM cell

Rule Fast Track Analysis for National Life Insurance Co.

IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

CAPACITOR BANK TESTING SWP

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

STANDARDS. Site-Specific Loss Adjustments PUBLIC

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

GUIDE FOR TESTING POWER TRANSFORMERS

Current transformer selection guide

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

Considerations When Specifying a DC Power Supply

Transformer circuit calculations

Three phase circuits

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Electrical Fault Level Calculations Using the MVA Method

How To Limit Voltage Unbalance

Joslyn Clark Controls, Inc.

Paralleling Power Sources Which Share a Common Neutral

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

MV/LV transformer substations: theory and examples of short-circuit calculation

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

CURRENT TRANSFORMERS INSTALLATION GUIDE

Study of Lightning Damage Risk Assessment Method for Power Grid

Short Circuit Current Calculations

A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

ACCURACY OF POTENTIALTRANSFORMERS

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

FUZZY Based PID Controller for Speed Control of D.C. Motor Using LabVIEW

Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application

Transcription:

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 Volume-, Issue-5, May-014 CAPACITY ENHANCEMENT OF SHORT CIRCUIT LABORATORY USING PARALLEL OPERATION OF TRANSFORMER 1 TEJPAL PUROHIT, H. K. MISHRA, 3 HEMANG PANDYA M.Tech. Student (Nirma University), HOD Short Circuit Lab (ERDA, Vadodara), Asst. Professor (Nirma University) Email: tejpal05@yahoo.com, h.mishra@erda.org, hemang.pandya@nirmauni.ac.in Abstract Since capacity of short circuit (S.C.) laboratory depends upon effective impedance of testing transformer and line connecting to the test equipment, which is designed to the optimal level while developing the S.C. Lab but still its fault level is lower. To test higher rating of transformer, a high testing fault level is required. Paralleling of S.C. testing transformer is the only effective way to reduce the effective impedance and increase fault level of the S.C. Lab. Percentage impedance of the conventional power transformer are found to be rated at 7 to 8%, while in case of S.C. testing transformer. This is much lower. S.C. testing transformer is specially designed transformer due to above aspect. This paper targets to provide solution for enhancing S.C. capacity of testing laboratory by connecting another transformer of similar capacity parallel to existing one and to deal with the phenomena of sympathetic inrush current, circulating current etc. This paper diusses simulation in ETAP & PSCAD for fault current estimation for the single S.C. testing transformer and after paralleling of two transformers. Simulation results and mathematical results both are observed identical Keywords Short circuit capacity, Parallel operation of transformer, Sympathetic inrush current, Circulating current. I. INTRODUCTION Short circuit testing laboratory seeks source maximum short circuit power which is generally in two ways 1) Self generating short circuit laboratory (having inbuilt generating facility) and ) On-line (grid connected) short circuit source which is obtained power from power system network. Requirement of short circuit source power is generally eight to ten times of test object short circuit power. In online short circuit laboratory only way to enhance the fault level this is paralleling of transformer. Transformers, can be operated in parallel by connecting similarly marked terminals provided that their ratios, voltages, angular displacement, resistances, reactance s, and ground connections are such as to permit parallel operation The difference in the no-load terminal voltages of the transformers causes a circulating current to flow between the transformers when paralleled irrespective of load. The circulating current is limited by the overall impedance of the circuit, which is usually the sum of the impedances of the transformers that are operating in parallel. The circulating current adds up, considering phasor relationships, to the load current to establish the total current in the transformer. As a result, the short circuit testing capacity of the transformer is reduced by the circulating current when the transformers are paralleled. For voltage ratios with a deviation of less than the 0.5%, as required by the IEEE standards, the circulating current between paralleled transformers is usually insignificant. Transformer is a main component of power system. Generally, the paralleling of lowerpower transformers offers a number of advantages over a single high power transformer. The advantages include improved reliability, higher efficiency, redundancy implementation, expandability of output power, and ease of maintenance. In fact, the paralleling of conventional transformers has been widely used in power system. Failure of transformers due to short circuits is a major concern for power utilities and manufacturers. An inadequate short-circuit strength may lead to a mechanical collapse of windings and deformation or damage to the clamping structure. The short circuit design is one of the most important and challenging aspects of transformer design. Due to this reason short circuit testing transformer is a special design transformer and its impedance is very low. To test higher rating of transformer, a high fault level is required. This is being explored in this paper by putting another transformer in parallel to the existing transformer; Due to this short circuit fault level will be increase. Paralleling of transformers are required special protection heme which is related to inrush and sympathetic inrush current, circulating current. Test object inrush current interferes in short circuit current, so control switching circuitry is required. Enhancement of fault level & respective up gradation in protection hemes are simulated, analyzed & diussed in succeeding section. II. MATHEMATICAL FORMULATION A. Fault Level Calculation for Existing System Fig. Single line diagram for existing system 1) System impedance k V Z S P M V A s c 48

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 0 Z SP 5056 9.578 Ohm on 0 kv side ) Reactance Referred To 33 kv Side Z Z n ss sp 33 9.578 0 0.1539 Ohm..A 3) Power transformer Z power 80 MVA % Z kv Z 100 MVA 4) Z power referred to 33 kv side 833 Z 10080 1.089 Ohm...B 5) Minimum load impedance Z load = 0.08 Ohm...C 6) Total Z on 33 kv = A + B + C = 0.154 + 1.089 + 0.08 = 1.3844 Ohm 7) Fault MVA on 33 kv kv 33 Z 1.3844 = 786.69 MVA (Source short circuit power) 8) Source short circuit power = 8.8 X short circuit power of transformer under test Therefore max short circuit power of transformer under test Volume-, Issue-5, May-014 All mathematical formula for parallel operation is same except two calculations which are written following. 1) Two transformers connected in parallel than effective impedance 1 1 1 =[ ] Z1 Z 1 1 1 =[ ] 1.089 1.089 = 0.5445Ohm MVA = MVA +MVA ) eff 1 = 80 + 80 = 160 MVA All other result are written in table I and II Comparison between existing and proposed system parameters TABLE I COMPARISON BETWEEN EXISTING AND PROPOSED SYSTEM PARAMETERS Source short circuit pow er 8.8 Max short circuit power of transformer under test 786.69 89.187 8.8 MVA Using existing system we can perform maximum 6.37 MVA (%Z=7.15) transformers. It s depends upon impedance of test object which is shown in table II Fault Level Calculation for Parallel Transformer Fig. Fault Level Calculation for Parallel Transformer Calculation for maximum MVA of transformer which can be tested using existing and proposed system which is written in table II 1) Short circuit power of transformer under test MVA rating of test object 100 % Impedance of test object ) Maximum MVA of transformer which can be tested for different impedances MVAt %Zt = 100 Where:- 49

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 MVAt Maximum short circuit power of transformer under test %Z % Impedance of transformer under test t TABLE II TEST OBJECT MVA RATING V/S % IMPEDANCE Volume-, Issue-5, May-014 Fig.3. Inrush and sympathetic inrush current differential protection based on second harmonics. According to this table we can perform 10.5 MVA (%Z=7.15) transformers using parallel operation. It is also depends upon % impedance of transformer which is 7 to 8% generally. III. PROTECTION OF PARALLED TRANSFORMER There is so many precautions are required for paralleling of transformer. Some of the typical problem deribed following. 1 Inrush and sympathetic inrush current protection Circulating current minimization and protection A Inrush and sympathetic inrush current protection Sympathetic inrush current phenomenon occurs when a transformer is switched on in a power system network containing other transformers which are already energized, incoming transformer realizes inrush current and already energized transformer realize sympathetic inrush current. A number of factors affect the magnitude and duration of the sympathetic inrush and inrush current, such as air core reactance, system fault level, point on wave switching, residual flux density, number of banked transformers, transformer design and rating and load conditions. In this case sympathetic inrush current impact is very low and inrush current in upcoming transformer is very high due to low system resistance which is shown in simulation. Both current contain 68% second harmonic component. Protection using stabilized differential relay SPAD 346 C which is blocking based on the second harmonic of the differential current. B. Circulating current minimization and protection Circulating current depends upon secondary voltage difference and % impedance of paralleled transformer. In this case % impedance of transformer is very low. Due to this small voltage difference, flow high circulating current [9-10] Voltage difference at secondary terminal Es=Vs*(Es/Ep1-Es/Ep) Where:- Es = Voltage difference in secondary Vs = Supply voltage Es = Sec. rated voltage Ep1 = Primary voltage across OLTC1 Ep = Primary voltage across OLTC P.U. difference in sec. voltage = Es/Es P.U. circulating current = P.U. Es/(Zp.u.1+Zp.u) Actual circulating current = Ic(P.U.)*Ic(Base) Mathematical calculation shown in Fig.4 Fig.4. Circulating current flowing diagram Circulating current calculation shown in table III TABLE III COMPARISON OF CIRCULATING CURRENT WITH RESPECT TO % IMPEDANCE 50

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 To control secondary terminal voltage required voltage regulator relay SPAU 341 C1. Volume-, Issue-5, May-014 1.. Fault level calculation of parallel transformer IV. Fig.5. Minimizing circulating current by voltage regulator relay SPAU 341 C1 SIMULATION RESULT The short circuit analysis of the transformer is performed on the ETAP and PSCAD. Fault level calculation done using ETAP software for with and without parallel operation of transformer. Control switching heme and inrush current done using PSCAD software. 1. ETAP simulation 1.1. Fault level calculation of single transformer Fig.7. Short circuit current at 33 kv bus for parallel transformer Fault level at 33 kv bus 3 I VR = 3.733 = 197.47 MVA. PSCAD simulation.1. Short circuit and inrush current for without parallel operation of transformer. Fig.8. Connection diagram for without POT Short circuit current depend upon system impedance and its peak depends upon x/r ratio. In Fig.8 shows connection diagram of existing short circuit laboratory which is perform short circuit test and short circuit current shown in Fig. 9 its maximum peak is 85. ka. Fig 10 and 11 shows inrush current in test object and testing transformer respectively. Fig.6. Short circuit current at 33 kv bus for single transformer Fault level at 33 kv bus = 313.8 33 3 I VR = 788.77 MVA Fig.9. Short circuit current for existing short circuit lab 51

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 Volume-, Issue-5, May-014 Fig.10. Inrush current of test object 33/0.433 kv, 6.3769 MVA, Z=7.15% Fig.14. Inrush current of test object 33/0.433 kv, 10.5110 MVA, Z=7.15% Fig.11. Inrush current of S.C. testing transformer, 0/33 kv, 80 MVA, Z=8% (a) Rsys=0.763.. Short circuit and inrush current for with parallel operation of transformer. Fig.1. Connection diagram for proposed short circuit lab In Fig.1 shows connection diagram of proposed short circuit laboratory which is perform short circuit test and short circuit current shown in Fig. 13 its maximum peak is 93.44 ka. Whenever two and more than two transformers connected in parallel then effective impedance is reducing and short circuit current increase. If both transformers are energized at different moment then inrush current and sympathetic inrush current are realized in already connected transformer which is depended upon system resistance. Fig.15 (a) and (b) are showing both current due to parallel and parallel series transformer respectively. Proposed system can test higher rating of transformer, its means inrush current also increase which is shown in Fig. 14. Fig.13. Short circuit current at 0.433 kv side (b) Rsys=0 Fig.15. Inrush current of S.C. testing transformer, 0/33 kv, 80 MVA, Z=8%.3. Inrush and sympathetic inrush current phenomena Fig.16. Connection diagram for sympathetic inrush phenomena Fig. 17 shows connection diagram for sympathetic inrush current no load configuration. These current depend upon many factor which is deribe above but it s mainly depends upon input fault level, If input fault level is high then sympathetic inrush is low and inrush current is high and vice-versa which is shown Fig.17 (a) and (b). Sympathetic inrush will persists for longer duration of time as compare to inrush current. 5

International Journal of Electrical, Electronics and Data Communication, ISSN: 30-084 Volume-, Issue-5, May-014 (b) HV1=16 kv, HV=5 kv, Zt1=16%, Zt=16% Fig.. Circulating current for paralleling transformer CONCLUSION (a) Rsys=0.763 The paper presented solution to enhance capacity of short circuit lab by paralleling of short circuit testing transformer by simulating the same problem & phenomena viz. inrush and sympathetic inrush current which is mainly depend on system resistance. The circulating current is limited by the overall impedance of the circuit, which is usually the sum of the impedances of the transformers that are operating in parallel. The short circuit testing capacity of the transformer is reduced by the circulating current when the transformers are paralleled. REFERENCES (b) Rsys=0 Fig.17. Inrush and sympathetic inrush current, when.4. Circulating current simulation Fig.18. Connection diagram for circulating current Circulating current directly proportional to induced voltage difference at secondary terminal and limit by some of the % impedance of both the transformers. If % impedance of transformers is low then circulating current is high and vice-versa which is shown in Fig.1 and (a) HV1=16 kv, HV=5 kv, Zt1=8%, Zt=8% [1] Shri K.N.S. Murthy Test requirement and test method for testing transformer and LT switchgear". CPRI Bhopal, 1996. [] Shri J. M. Malik Short circuit strength of power transformer". BHEL Jhansi, 1996 [3] Haibo Liu, Chengxiong Mao, Member, IEEE, Jiming Lu, and Dan Wang. Parallel Operation of Electronic Power Transformer and Conventional Transformer", DRPT008 6-9 April 008 Nanjing China [4] T. Ise, Y. Wutani, Y. Murakami, E.Yoneda and R. Sugawara, Toshiba Co., Kawasaki, Japan, Characteristics of a 4OkVA Three Phase Superconducting Transformer and its Parallel Operation with a Conventional Transformer", IEEE Transactions on Applied Superconductivity, Vol. 5, No., June 1995 [5] Yong-Cheol, Kang, Mi-Sun, Lee, Byung-Eun, Lee, and Sung-Il, Jang, 664-14 Dukjin-dong, Chonju, 561-756, Korea, Estimation of the circulating currents in the parallel operation of transformers", The International Conference on Electrical Engineering 008, No. O-150. [6] IEC-60076-5(Second Edition) Ability to withstand short circuit-power transformer",part-5, 000-07. [7] Martin J. Heathcote. J P Transformer Book,". McGraw-Hill, (Chapter 10):Page no 45 [8] G. B. Kumbhar and S. V. Kulkarni, Member, IEEE. Analysis of Sympathetic Inrush Phenomena in Transformers Using Coupled Field-Circuit Approach, 1-444-198-6/07/$5.00 007 IEEE. [9] John J. Winders, Jr. Power transformers principles and applications Copyright 00 by Marcel Dekker, (Chapter 3, page no. 105) [10] James H. Harlow, Electrical power transformer engineering Copyright 004 by CRC Press LLC(Chapter 3, page no. 338) 53