ELECTRIC POWER FREQUENCY (60 Hz) ELECTRIC AND MAGNETIC FIELDS (EMFs)

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

Selected Radio Frequency Exposure Limits

Scaling Public Concerns of Electromagnetic Fields Produced by Solar Photovoltaic Arrays

Magnetic Fields and Their Effects

Measurements of radiofrequency fields from a WEL Networks Smart Meter

AN OVERVIEW OF STANDARDS AND REGULATION CONCERNING EXPOSURE TO RADIOFREQUENCY FIELDS

A. ELECTRIC AND MAGNETIC FIELDS (EMF)

Human Exposure Limits

Physics 25 Exam 3 November 3, 2009

Real-life Applications of ICNIRP Guidelines to Various Human EMF Exposure Issues

RF safety at base station sites

Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).

Electric and Magnetic Fields

The Existing Public Exposure Standards Cindy Sage, MA Sage Associates, USA

The Salzburg Model: A Precautionary Strategy for Siting of Base Stations

Numerical Modelling of E-M Occupational Exposures associated with MRI

Physical Science Study Guide Unit 7 Wave properties and behaviors, electromagnetic spectrum, Doppler Effect

Candidate Number. General Certificate of Education Advanced Level Examination June 2014

Magnetic Field of a Circular Coil Lab 12

Operating Frequency Selection for Loosely Coupled Wireless Power Transfer Systems with Respect to RF Emissions and RF Exposure Requirements

Cross-beam scanning system to detect slim objects. 100 mm in

Users Manual FA106 / FA306 version 1.0. Field Analyzer. FA106 and FA306. Users Manual

Elfring Fonts, Inc. PCL MICR Fonts

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

ELECTROMAGNETIC FIELDS AND PUBLIC HEALTH HEALTH AND SAFETY GUIDELINES #1

The field strength measurement and SAR experience related to human exposure in 110 MHz to 40 GHz

Ionosphere Properties and Behaviors - Part 2 By Marcel H. De Canck, ON5AU

Exposures to radiofrequency fields from WiFi in New Zealand schools

From lowest energy to highest energy, which of the following correctly orders the different categories of electromagnetic radiation?

Electric and Magnetic Fields

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

EARTHING SYSTEM CALCULATION

The electrical field produces a force that acts

Annex to the joint statement: Exposure of the general public to radiofrequency fields

FREE FALL. Introduction. Reference Young and Freedman, University Physics, 12 th Edition: Chapter 2, section 2.5

1. The diagram below represents magnetic lines of force within a region of space.

Measurement of RF Emissions from a Final Coat Electronics Corrosion Module

EFFECTS OF ELECTROMAGNETIC FIELDS ON ORGANISMS AND PROTECTION PRINCIPLES

Cellular Antenna Proposal Form

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

Phys222 Winter 2012 Quiz 4 Chapters Name

Energy. Mechanical Energy

EMR Exposure Limits & Assessment Methods for Mobile Phone Communications. Lindsay Martin Manager, Non-Ionising Radiation Section

How To Know If You Are Safe To Use An Antenna (Wired) Or Wireless (Wireless)

University of Northern Iowa Design Documents Standards. October 2014

Chapter 22: Electric motors and electromagnetic induction

104 Practice Exam 2-3/21/02

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

What Does the Normal Distribution Sound Like?

MCS 020. MCS Planning Standards. For permitted development installations of wind turbines and air source heat pumps on domestic premises

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

Development Variance Permit Application Package

COUNCIL RECOMMENDATION of 12 July 1999 on the limitation of exposure of the general public to electromagnetic fields (0 Hz to 300 GHz) (1999/519/EC)

ELFRING FONTS INC. MICR FONTS FOR WINDOWS

WEDNESDAY, 4 MAY AM AM. Date of birth Day Month Year Scottish candidate number

Catalyst RTU Controller Study Report

Drawing a Bedroom Floorplan

MPC STAFF REPORT WIRELESS TELECOMMUNCATIONS FACILITY February 19, 2013 MPC FILE NO PLAN

MD5-26 Stacking Blocks Pages

Effects of Cell Phone Radiation on the Head. BEE 4530 Computer-Aided Engineering: Applications to Biomedical Processes

Getting Land Survey Vertical & Horizontal Control via the Internet

Problem 1 (25 points)


Physics 30 Worksheet #10 : Magnetism From Electricity

Human exposure to RF

SITE RADIATION SURVEY

Official Journal of the European Communities. (Acts whose publication is not obligatory) COUNCIL

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

Electromagnetic Induction Experiment

within body bioelectricity is a biofield. It is due to concentration gradient generated across membrane of the cell.

Roof Tutorial. Chapter 3:

Automated Meter Reading Frequently Asked Questions. What is AMR?

Avaya WLAN 9100 External Antennas for use with the WAO-9122 Access Point

Electromagnetic Field Safety

A Survey of Radiation Levels Associated with Mobile and Wireless Communication Technology Masts in Public Areas in Kaduna Metropolis

Correcting the Lateral Response Artifact in Radiochromic Film Images from Flatbed Scanners

Barrie Primary Care Campus

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

The University of the State of New York REGENTS HIGH SCHOOL EXAMINATION MATHEMATICS B. Thursday, January 29, :15 a.m. to 12:15 p.m.

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

Specification of 5 Wire Analog Touch Panel

Generic - Hearing Loop - (AFILS) U.S. System Specification

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

3 Radio Waves and Human Body 8 Specific Absorption Rate (SAR)... 8 SAR value of a mobile handset... 8 Radiation level by a mobile tower...

Wireless Broadband: Health & Safety Information

EMF. Questions Answers. June Electric and Magnetic Fields Associated with the Use of Electric Power

Uncertainties of immunity measurements

REVIEW OF EXPOSURE LIMITS AND HEALTH CONCERNS SANTA ANA. Base Station Telecommunication Transmitters UNIFIED SCHOOL DISTRICT

Indoor Environment Electromagnetic Radiation

EMR EMISSIONS FROM REMOTE AREA POWER SUPPLY EQUIPMENT

LONGITUDINAL PROFILE COMPLETION

BUILDING A FENCE? THE CITY OF CAMBRIDGE REQUIRES THAT ALL FENCES WITHIN THE CITY CONFORM TO THE REGULATIONS OF FENCE BY-LAW

Mobile use, radio signals and health

WESTFIELD-WASHINGTON ADVISORY PLAN COMMISSION December 7, SPP-24 & 1512-ODP-24

THE ANSI/IEEE RF SAFETY STANDARD AND ITS RATIONALE. Om P. Gandhi and Gianluca Lazzi Department of Electrical Engineering Salt Lake City, Utah 84112

Lab 1: The metric system measurement of length and weight

2.4 The deflection of beta radiation in a magnetic field. Task. How does β-radiation behave in a magnetic field?

Lab E1: Introduction to Circuits

Mobile Phone Base-Station Audit

Transcription:

W&W Radiological and Environmental Consultant Services, Inc. 1 Glen Park Avenue, Suite 604 Toronto, Ontario, Canada M2K 2H7 EMF SURVEY AND ASSESSMENT MONSIGNOR JOHN CORRIGAN SCHOOL 100 ROYAL CREST ROAD ETOBICOKE, ONTARIO Prepared for: Corrado Maltese Senior Manager Occupational Health and Safety Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario, July 2008

1. INTRODUCTION W & W Radiological and Environmental Consulting Services Inc. was retained by the Toronto Catholic District School Board to evaluate the 60 Hz magnetic field environment inside and external to the Monsignor John Corrigan School at 100 Royalcrest Road in Etobicoke. The school is located beside a Hydro One right-of- way. The school was visited on Thursday July 3, 2008 between the hours of 9:00 AM and 4:00 PM. Corrado Maltese, Safety Manager for the school board and Ross Ferlenda, Certified Worker Member, CUPE Local 1280 were in attendance. All measurements were made under normal building occupancy conditions with computers and lights on Measurements were performed inside the school including hallways and classrooms, outside on the grounds behind the school and on the right-of way west of the school. A picture of the site is shown in Figure 2.1. The findings of the survey are described in this report. 2. MEASUREMENTS OF MAGNETIC FIELDS OUTSIDE THE SCHOOL 2.1 Survey Procedure Power frequency magnetic field measurements were made with a Model 1000 Drexsil Field Star magnetic field recorder, Serial Number 31400342. The Field Star is a multiplefunction recorder for logging 60 Hz magnetic fields. Three orthogonal sensing coils measure the magnitude of the magnetic field component along the x, y and z axes. The Field Star can be used as a survey instrument or, when used with the Field Star Mapping Wheel it can be used as a data logger to record magnetic field data as a function of distance. Complete maps of magnetic field strength can be made of any area or building, such as in a school or under transmission lines. All results are reported in units of milligauss (mg), for consistency with most North American literature. The readings may be converted to microtesla (μt) by dividing by a factor of 10. Following standard EMF procedures, magnetic field strengths are reported at a nominal height of 1 meter above ground or grade level unless otherwise indicated. The field measurements are valid for the time of the measurement. However, it is known that ambient field levels can vary with time as a function of the electrical load on the source wires. Where fluctuations in readings were noted in the present survey, the highest reading was recorded. 2.2 Test Locations and Results A survey was performed on the right-of-way (ROW) north of the sidewalk on Royalcrest Road (see Figure 2.1 dotted line #1). Measurements were made every meter along a line perpendicular to the transmission lines from the fence on the west side of the right-ofway toward the school and to the fence on the east side of the right-of-way. A profile of the magnetic field on the right-of-way is shown in Figure 2.2. The field strength peaked at 120.3 mg, falling to 86.1 mg at the fence beside the school. 1

Figure 2.1 Site Picture of Monsignor John Corrigan School Measurements were also made on the school property from the fence by the right-of-way eastward. The measurement paths are shown by the dotted lines 2-4 in Figure 2.1. A survey was also performed along a similar path further north in the park (not shown). 2

Figure 2.2. Magnetic Field Profile From the West Fence to the East Fence of the ROW The results of the survey for the west side of the school are shown in Figure 2.3. Each square on the grid represents an area of 10m X 10 m. The rectangular area to the left of the school indicates the location of the parking lot. The left border of the figure is at the location of the fence at the edge of the right-of-way, and the bottom of the figure is at the sidewalk. The coloured areas show ranges of magnetic field strength. The dark blue area (labeled as <5) shows where fields are less than 5 mg. The light blue area (labeled as 5-10) marks the area where fields are equal to or greater than 5 mg but less than 10 mg. Areas with the magnetic field strength equal to or greater than 50 mg are shown in red. Figure 2.3 Magnetic Field Levels (in units of milligauss) on West Side of School 3

The map showing ranges of magnetic field strength behind the school is give in Figure 2.4. Each square on the grid represents an area of 10 m X 10 m. The colour coding of ranges is the same as for Figure 2.3. The black line across the coloured area indicates the location of the back fence of the school. North of the fence is a park area. In the park there is a tennis court (shown in green) and a soccer pitch. The short black line represents the goal posts at the south end of the pitch. The left border of the figure coincides with the fence along the right-of way. The vertical dimensions of the school have been reduced for convenience. Figure 2.4 Magnetic Field Levels (in units of milligauss) on North Side of School On the east side of the school there is a fenced play area (see Figure 2.1) that is divided into three sections with a fence between them. Measurements were taken in each of the sections using the Drexsil Meter in order to obtain a map of the fields The measurement results were very uniform, averaging about 10 mg, and so the results are presented in Table 2.1 rather than as a map. The sections number 1-3 from south to north. Table 2.1 Magnetic Field Measurements in Play Areas on East Side of School Section Data Points Minimum Maximum Average Std. Deviation 1 110 9.44 13.08 10.78 1.46 2 77 7.92 11.36 10.36 0.85 3 124 7.72 12.08 9.82 1.16 4

2.3 Comments on Outside Measurements A significant fraction of the exterior of the school is located in magnetic fields in the 20-30 mg range, with field strengths reaching 30-40 mg along the west wall of the building. The field strengths in a large fraction of the play areas of the school are equal to or greater than 10 mg, including along the east side of the building where the fields average about 10 mg. Magnetic fields measured in the back of the school along the right-of-way fence reached a maximum value of 85 mg. 5

3. MEASUREMENTS OF MAGNETIC FIELDS INSIDE THE SCHOOL 3.1 Survey Procedure Power frequency magnetic field measurements inside the school were made using the Model 1000 Drexsil Field Star magnetic field recorder and a model 42B-1 AC milligaussmeter manufactured by Monitor Industries of Boulder, CO. The model 42B-1, Serial Number 1350 is a professional quality, true RMS (root-mean-square) reading, single-axis instrument that measures ambient power-system magnetic fields covering a frequency range from 40 Hz to 1000 Hz. Measurements are obtained by rotating the coil to obtain an maximum reading. Following standard EMF procedures, magnetic field strengths are reported at a nominal height of 1 meter above ground or grade level unless otherwise indicated. The field measurements are valid for the time of the measurement. Where fluctuations in readings were noted in the present survey, the highest reading was recorded. In each classroom 5 measurements were made (4 corners and middle of class). In larger rooms such as the library and gymnasium a minimum of 9 measurements were taken 3.2 Test Locations and Results Measurements of the magnetic flux density (in milligauss) were made in each of the school classrooms and common areas occupied by students. The Table 3.1 below is a summary of the measurement results, including minimum, maximum and average flux densities. The average values for each room are also plotted on floor plans for the school. This information can be found in Appendix A of the report Measurements of the magnetic field strength in hallways were made using a Model 1000 Drexsil Field Star magnetic field recorder. Measurements were made in the West hallway (for location of hallways see figure in Appendix 1) starting at the front door and proceeding north to the wall of North hallway. A similar measurement was performed in the East hallway. Measurements in the North hallway started at the inner west doors and proceeded to the doors at the east end of the hallway. Measurements were made every 0.6 meters. The results are shown in Figures 3.1 to 3.3. The peak at 25 meters in the profile for the East hallway was due to fields from the transformer room and associated electrical conductors. The two peaks in the curve for the North hallway are associated with the electrical conductors of the building. 6

Table 3.1 Measurement of Magnetic Field Strength (in units of mg) in Monsignor John Corrigan Public School Room ID Minimum Maximum Average 103 10.8 18.5 14.0 104A 20.1 30.7 24.5 104B 20.8 32.4 25.4 104C 17.2 30.8 24.9 104D 12.3 20.0 14.9 105A 15.2 26.7 21.8 106A 15.6 39.6 27.5 106B 11.5 36.5 23.0 107 17.2 38.7 27.1 109 6.68 18.8 12.8 110 13.6 5.07 10.2 111 4.40 9.52 8.14 112 4.05 9.44 7.30 113 2.24 7.05 6.03 114 3.12 6.08 5.22 115 2.07 6.75 5.23 117 2.09 8.71 5.88 118 6.00 30.8 14.3 119 4.28 13.6 8.51 120/121 3.21 9.85 5.96 125 Mech. Room 5.78 9.81 7.60 Library 6.32 19.2 12.1 Office 14.7 22.0 18.8 Principal s Office 21.2 26.0 23.7 Teacher s Workroom 16.8 28.4 19.8 Gymnasium 2.97 9.95 6.30 Electrical Room 8.36 84.7 18.8 Office by Teacher s Workroom 11.6 16.4 13.6 7

Figure 3.1. Magnetic Field Profile Along West Hallway Figure 3.2. Magnetic Field Profile Along East Hallway Figure 3.3 Magnetic Field Profile Along West Hallway 8

School rooms that recorded field strengths greater than 10 mg were revisited and additional measurements taken. For rooms 106, 106B and 107 measurements were taken every 0.30 metes from the west wall of the rooms to the east wall. Results are shown in Figures 3.4 to 3.6. Figure 3.7 shows the field gradient in Room 118 that resulted from magnetic fields emitted from the transformer room located south of Room 118. Measurements were made from the south wall to the north wall. Figure 3.4 Magnetic Flux Density (mg) In Room 206 Figure 3.5 Magnetic Flux Density (mg) In Room 206B Figure 3.6 Magnetic Flux Density (mg) Figure 3.7 Magnetic Flux Density (mg) In Room 107 In Room 118 9

Measurements for the other rooms where field strengths exceeded 10 mg are summarized in Table 3.2. The fields in these rooms showed less of a gradient and were weaker than those shown in the above figures. In the library the fields were highest near the south windows and along the west side of the south wall of the room. Table 3.2 Statistical Data for Rooms with Magnetic Fields Greater Than 10 mg Room Data Points Minimum Maximum Average Std. Deviation 109 27 7.52 15.4 10.2 2.05 110 63 5.48 12.5 8.11 2.17 119 83 5.1 16.0 8.45 2.71 Library 119 7.12 21.3 12.3 3.51 3.3 Comments on Inside Measurements Rooms with the highest fields are located along the west side of the building, including staff areas, classrooms and daycare. The elevated fields in these rooms are associated with the transmission lines west of the building. Magnetic fields from the transformer room and associated conductors produce elevated fields in adjacent classrooms and hallway. 10

4. COMPARISON OF FIELD LEVELS TO INTERNATIONAL ACCEPTED STANDARDS AND GUIDELINES There are no recommended standards in Canada either at the federal or provincial level for 60 Hz electric and magnetic fields. The federal limits for electromagnetic radiation contained in Safety Code 6 do not address power frequency fields. However, in January 2005, the Federal-Provincial-Territorial Radiation Protection Committee (FPTRPC), organized under Health Canada s Radiation Protection Bureau, issued a Position Statement stating that adverse health effects from exposure to power frequency EMFs at levels normally encountered in homes, schools and offices have not been established. FPTRPC is of the opinion that moderate measures and the participation in the process of acquiring new knowledge are sufficient. These types of activity are consistent with the Canadian government framework on precaution." A few international organizations have published recommended exposure limits for workers and members of the general public. Since these bodies have concluded that the available scientific data on the long-term effects, such as cancer, are insufficient to provide a basis for setting exposure restrictions, these guidelines are based on preventing short-term immediate effects. These include effects such as stimulation of peripheral nerves and muscles, shocks and burns caused by touching conduction objects, and elevated tissue temperature resulting from absorption of energy during exposure to EMF. These organizations introduced additional safety factors beyond those applied to workers in order to further reduce the recommended exposure limits for members of the public. The recommended exposure limits are provided in Table 5.1 Table 5.1 Recommended Exposure Limits for 60 Hz Magnetic Fields Organization Protected Group Magnetic Flux Density (milligauss) ICNIRP Workers 4167 General Public 833 IEEE/ICES General Public 9040 (632000 for arms and legs) ACGIH Workers 10000 ICNIRP: IEEE/ICES: ACGIH: International Commission on Non-Ionizing Radiation Institute of Electrical and Electronic Engineers/International Committee on Electromagnetic Safety America Conference of Industrial Hygienists The maximum field level measured inside the school was 84.7 mg in the Electrical Room. The maximum outside measurement on the school grounds of 85 mg occurred at the fence of the right-of-way. These levels are of the order of 10% of the most restrictive (ICNIPR recommended level of 833 mg)) levels recommended for members of the general public, which includes children. 11

5. APPENDIX A: MAP OF SCHOOL WITH MEASUREMENTS 12