EN54 Power Supplies. Product Data Sheet

Similar documents
FIREDEX Conventional Fire Panels

HM-W536 Install Guide

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

CB200W Water Leak Detection Panel Application Guide

BATTERY BOX INSTALLATION WARNING WARNING CAUTION ATTENTION AVERTISSEMENT ADVERTENCIA PRECAUCIÓN SOLBBOX12V CARTON INVENTORY COMPLETED OVERVIEW

MX-4100, MX-4200, MX-4400,

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

Digital input modules

ST Series POWER SUPPLIES USER INSTRUCTIONS

INSTALLATION & SERVICE MANUAL. Display Panel

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

Wolflite Safety Handlamp H-251E

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING

Charge Regulator SCR 12 Marine

LIEBERT VNSA Installation Sheet

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Emergency Voice Communication Systems EVCS Network 8 Data Sheet

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Repeaters and Mimics Data Sheet

VEGA Analogue Addressable Control Panels

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

12 Volt 30 Amp Digital Solar Charge Controller

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

CO2 Alarm. Operation. Application

ALARMLINE ANALOGUE Linear Heat Detection System

MIC-WKT and MIC-WKT-IR

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Power Generation. Power Control PCL System Generator Set Control

1. Connect the charger to the battery. 2. Connect the charger to the wall socket. 3. Press the MODE-button to select charging program.

FIRERAY 2000 Installation Guide

Floodlight Range Installation Guide

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

EC450 Power Control System

Operating Instructions

ACS-30-EU-EMDR-10-MOD

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

THIS MANUAL REFERS TO THE FOLLOWING MODULES G G G G EG EG EG EG

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

SELECTION, APPLICATION AND MAINTENANCE

AC-115 Compact Networked Single Door Controller. Installation and User Manual

victron energie USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG Victron Atlas 12/850

WD-AMX Water Detection Controllers

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

MANUAL EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT ABSORPTION, READY TO USE ANALYSE FLOAT, FULLY CHARGED PULSE, MAINTENANCE CHARGING

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

Conventional Fire Detection and Extinguishant Control System Specification

Contractors Guide Central Inverter System Installation

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

MANUAL EN 3. Continue to press the MODE-button to combine charging program with charging options.

VoCALL - CFVCM/CFVCWM & CFVCX8. Fire Telephone & Disabled Refuge Network System. User Manual & Log Book

MXS 3. MANUAL FULLY CHARGED PULSE, MAINTENANCE CHARGING EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT CHARGE CABLE ERROR LAMP MODE- BUTTON

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

OZW30. Central Unit SYNERGYR

TMS TANK MANAGEMENT SYSTEM

User Manual for CH-PFC76810

How To Use A Power Supply Unit (Upu)

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Emergency lighting units EM powerled

User s Manual Before using the inverter, you need to read and save the safety instructions.

13 Watt PORTABLE SOLAR POWER KIT

tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

7 Lighting Technology

HP UPS R1500 Generation 3

How To Wire Wireline Cable To A Cell Phone (New Zealand)

EN 3 ABSORPTION, READY TO USE ANALYSE BULK DESULPHATION SOFT START. L: 2000 mm MODE- BUTTON SUPPLY PLUG* SUPPLY

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

INSTALLATION MANUAL. SAILOR 5080 AC Power Supply

USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OUTPUT CABLE CONNECTIONS:

3500/93 System Display

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

CX Zoner Installation & User Guide

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS


Co-location Interconnect Power Panel (CIPP) Installation Guide

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

ADM1TE 5/30A DIN rail single phase two wire energy meter

Single Channel Loop Detector

TrueAlarm Fire Alarm Systems

SYSTEM DESCRIPTION Termination Boards

Installation and Operation Manual

MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Installation and Operating Instructions (for chargers shown below)

Heavy Duty Solenoid Controlled Access Lock. User Manual - Original Language Version

Transcription:

EN54 Power Supplies Features High efficiency switched mode power supplies Compact 1 Amp and 4 Amp versions Fully compliant to EN54-4 Product Data Sheet Models, Sales Order Parts: Mxp-022A: A boxed power supply unit with 4A output, charger facilities for charging up to 24Ah* capacity sealed lead acid batteries and housed in a metal enclosure with LED indication for Power and Fault. (*/D Deeper enclosure required for 24Ah. Standard enclosure houses up to 17Ah capacity batteries). Mxs-022: An unboxed caged 4A power supply with charger facilities for charging up to 24Ah capacity sealed lead acid batteries. This unit is supplied as a spare part or for incorporating within a customers / OEM enclosure. Mxp-023A: A boxed power supply unit with 1A output, charger facilities for charging up to 7Ah capacity sealed lead acid batteries and housed in a metal enclosure with LED indication for Power and Fault. Mxs-023: An unboxed caged 1A power supply with charger facilities for charging up to 7Ah capacity sealed lead acid batteries. This unit is supplied as a spare part or for incorporating within a customers / OEM enclosure. Document Number: 680-044 Revision: 03 ISO9001 ISO9001 34 Moorland Way : Nelson Park : Cramlington Northumberland : NE23 1WE Tel: +44 (0)1670 707 111 Fax: +44 (0)1670 707 222 www.advel.co.uk Email: Sales@Advel.co.uk

Applications / Limitations: For any fire alarm system which specifies EN54-4 power supplies (e.g. BS5839 code of practice). Compatibility: These power supply units can be used in any fire alarm installation requiring a 24Volt supply for operation. Item Approvals Input Supply Output Voltage (All models) Specification Details Both Power Supply Units are designed to comply with the requirements of BS EN54-4 1998, EN55022 class B emissions limits & EN60950: 2000 safety standards. 220-240 Volts AC (+10%, -15% tolerance) 50/60Hz Fuse rating: (Mxp-022A) 3.15A (Mxp 023A) 1.6A (Both Ceramic Anti-surge) To Load: 18.5V minimum (at minimum battery voltage of 19V with mains disconnected & 28V maximum (at minimum load and -5 C) To Battery: 27.4 V nominal at 20 C temperature compensated over the range -5 C to +45 C Output Current Mxp-022A: 4A continuous rating. Mxp-023A: 1A continuous rating Dimensions (H x W x D) Weight (without batteries) Operating temperature Relative Humidity Standby Battery Fault output External Indication On board indication Deep discharge Mxp-022A: 425 x 406 x 125mm. Mxp-022A/D: 425 x 406 x 190mm Both sealed to IP30 Mxp-022A: 5Kg Mxp-022A/D: 7Kg -5ºC to +45ºC @ full load output 95% non-condensing (maximum) Mxp-023A: 320 x 345 x 88mm. Mxp 023A: 3Kg 2 x 12V Sealed Lead-Acid Type (Yuasa or Powersonic recommended) Mxp 022A: 1.2Ahr minimum to 17Ahr maximum (Standard Enclosure) 24Ahr maximum (Deep Enclosure) Mxp-023A: 1.2Ahr minimum to 7AHr maximum Volt free change-over contacts rated 1A @ 30V dc (all models) Green: Power indicator, Amber: Fault indicator Mains Fail, Charger Fail, Battery open circuit, Battery Low & Heartbeat Both models incorporate battery deep discharge protection (19volts) As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice Page 2 of 8

EN54 Functions This Fire Alarm Power Supply is designed to be compliant with the requirements of BS EN54 part 4 (1998). P.S.E Functions Operation from a main power supply Operation from a standby battery Monitor and Charge the Standby Battery Recognise and Notify Supply Faults EN54-4 Clause 5.1 5.2 5.3 5.4 Installation: These instructions cover the installation, commissioning and maintenance of the Mxp-022A and Mxp-023A model Power Supplies. For use of the Mxs-022 & Mxs-023 in an OEM / customer supplied enclosure, these power supplies should be mounted in an appropriate sized enclosure suitable for the intended batteries to be used, the minimum protection rating of the enclosure must be to IP30 and the power supply must be earthed. Take note of the important safety information in the remainder of this document. NB: The batteries must not be mounted in an enclosure separate from the power supply since this could affect the temperature compensating charging characteristics, resulting in incorrectly charged batteries. The power supplies are also incorporated into other boxed peripheral units. The information in this document is applicable to these power supplies. Refer to the additional data sheet supplied with each boxed unit for details on the installation, configuration and use of the peripheral function. Mounting Instructions: The Mxp-022A & Mxp-023A are power supplies mounted within an IP30 steel enclosure. These can accommodate 17A/Hr & 7A/Hr capacity batteries respectively. When batteries are installed, the Mxp- 022A can weigh in excess of 16Kg. Use appropriate fixing hardware to secure the panel to the wall. For example, drill the required holes in the supporting wall using a drill bit diameter 7.0 mm and plug with a suitable 40mm long expansion plug. Affix the panel to the wall with M5 screws (length 40mm) or No.10 screws (length 1½ ). Ensure that there is sufficient space to allow the cover to be removed / opened when the panel is finally mounted. An example of the Mxp-022A is shown opposite. Status Indicators Knockouts PSU Fixing Points x3 Mains Terminal Block Space for Peripheral Cards Page 3 of 8

An example of the Mxp-023A is shown opposite. Status Indicators Knockouts Mains Terminal Block Mounting Peripheral Cards or OEM equipment. Space is provided in which to mount ancillary equipment or printed circuit cards. Space for Peripheral Cards PSU Fixing Points x3 Wiring Installation AC Mains Wiring The power supply is classified as Class1 equipment construction and must be earthed in accordance to EN60950 recommendations. Route the high voltage mains AC wiring into the enclosure at the upper left corner only (Mxp-022A) or upper right corner only (Mxp-023A). Keep the AC wiring away from any circuit boards and all other wiring. The panel must be connected to the supply earth through the power cable. The mains input connector is shown in the diagrams opposite. Note the positions of the earth, neutral and live terminal connections. These are clearly marked on the label next to the connector. The connector block contains an integral fuse holder for a 20mm fuse. Secure the mains input wiring using a tie wrap as close to the terminal block as possible. The fuses are rated as follows: T 1.6A H 250V (for Mxp-023A) T 3.15A H 250V (for Mxp-022A) Replace with correct rating and specification only. Connect the PSU to the mains supply via a readily accessible, disconnect device (Isolation Switch) and suitable earth fault protection incorporated in the building installation wiring. PSU Internal Mains Wiring Brown Grn/Yel Blue FUSE Field Connections LIVE EARTH NEUTRAL AC Mains terminations Mxp-022 The Mains cable should be a minimum cable size of 0.5mm² for the Mxp-023A & 0.75mm² for the Mxp-022A PSU rated at 250V and fused via a 5A anti-surge fuse. Maximum cable size is limited to 4mm². Keep all mains wiring separate from the Extra Low Voltage (ELV) battery cables and power supply output cables. Page 4 of 8

Cable Gland The cable gland and any cord clamp bushings used in routing the Mains cable through the 20mm knockout must have a minimum flame-retardant rating of 94HB. Suggested glands and bushings are: - Type Gland IP65 Brass M20, EExd / Eexe Gland IP68 Nylon 66 M20 Black, UL94V2 Bushing Nylon 66 M20 Black, UL94V2 Manufacturer Lappcable Multicomp Multipcomp Output Connections: To Load: Connect the 28V output connections to the load via terminals VO+ & VO respectively via appropriately rated cable for the output rating: For Mxp-022A a minimum 0.75 mm² For Mxp-023A a minimum of 0.22mm² NB Maximum cable size is limited to 2.5mm² Refer to diagrams opposite for the positions of all output connections. Observe that the load is connected with the correct polarity! Route the wiring away from any mains connections. To Battery: COM N/O N/C Remote LED Reset Switch BAT BAT + VO VO + 4A PSU Fault Output Remote LED Reset Switch COM N/O N/C BAT BAT + VO VO + 1A PSU Fault Output The system is designed to charge 24V batteries or two 12V batteries connected in series. Refer to diagram opposite. Use the short black connection link to connect the batteries. Use the Red & Black leads provided to connect the batteries to the BAT+ & BAT terminals on the PSU. Take care to observe the correct polarity and ensure the battery leads do not become shorted together! Mount the batteries on the bottom of the enclosure. - + RED Link Cable BLACK + - + - #1 #2 Page 5 of 8

Fault Output Connections: Power supply/charger fault outputs are provided for in the form of volt free changeover contacts designated COM, N/O & N/C. These are available via three terminal blocks screws refer to diagram above. The Fault relay is held in a normally energised state. It will fail to safety (de-energise) under any power supply/charger Fault conditions. Remote LED indication: A latched 4 way single in line header, PL2, provides a means for remote/ external indication of Power and Fault indications. The Mxp-022A and Mxp-023A are supplied fitted with Green and Amber LED Indicators. Refer to diagram opposite for how to connect these assemblies to the PSU. Replacement parts are available. Green = Mxs- 026-GRN and Amber = Mxs-026-YEL The Green Power indicator will be ON continuously while ever the power supply is being supplied with mains power. This indicator will flash when the mains supply is off and the power supply is being powered from its battery source. RED BLACK RED BLACK Remote LED Connector FAULT POWER The Amber Fault indicator will be ON continuously if any of the Fault conditions listed below are present: 1) Mains Supply failure 2) Battery disconnected or high impedance cell 3) Battery Charger output terminals low or short circuit 4) Battery charger output failure The above Fault conditions are individually indicated by separate on board LED Indicators. Commissioning: When all connections in the Installation section have been made and checked for correct wiring, switch on the mains power supply; the following conditions should occur: 1) The green Power LED should be ON, the Fault LED should be OFF. 2) The load should be supplied with power, check this with a voltmeter at the VO & +VO terminals, the reading should be between 27 & 28 volts. 3) The batteries should be charging, check this by connecting a voltmeter across the BAT & +BAT connections, depending on the state of discharge of the batteries, the voltage should be greater than 24 volts and for batteries approaching their full charge, the output voltage should be approximately 27.4 volts at an ambient temperature of 20 C 4) All on-board diagnostic LED indicators should be OFF, the Heartbeat indicator should be FLASHING. 5) The Fault relay should be energised. Check the fault output connections between common and the normally open (N/O). This connection should indicate a short circuit when checked with a test meter on the continuity setting. Remove the mains supply and check the following occurs: 1) The green power LED changes state from being ON continuously to a FLASHING state and the Fault indicator should be ON. 2) The load is being supplied via the battery supply, check that +VO &-VO are approximately 0.5 volts below the battery supply voltage. 3) The on board diagnostic LED indicators should be: Mains Fail : FLASHING and on the Mx-022 PSU a Battery On indicator will be illuminated. The Heartbeat indicator should be FLASHING. 4) The Fault relay should de-energise, check between COM & N/C. This connection should indicate a short circuit when checked with a test meter on the continuity setting. Page 6 of 8

Re-apply the mains supply and disconnect the battery, check the following occurs: 1) The green power LED is ON continuously and the Fault indicator ON 2) The load is supplied directly from the PSU between 27 & 28V 3) The on board diagnostic LED indicators should be: Battery O/C : ON. Heartbeat indicator: FLASHING all other indicators OFF. 4) The Fault relay should be de-energised, check as described above. With the battery still disconnected check the output voltage from the charger circuit, @ +BAT & - BAT is within the voltage limits specified in table 1 below: Ambient Temperature C TABLE 1 Charger output voltage (minimum) Charger output voltage (Nominal) Charger output voltage (Maximum) 5 27.90 28.10 28.32 0 27.72 27.96 28.20 5 27.54 27.80 28.08 10 27.36 27.66 27.96 15 27.24 27.50 27.78 20 27.12 27.36 27.60 25 27.00 27.20 27.42 30 26.88 27.06 27.24 35 26.76 26.90 27.06 40 26.64 26.76 26.88 45 26.52 26.60 26.70 NB: The charger is designed to charge Yuasa & Powersonic sealed lead acid batteries only; other manufacturers batteries may have different temperature / charge characteristics. Page 7 of 8

Maintenance: Maintenance of the power supply and charger should be minimal. The batteries, however, do have a limited life span and a maintenance program should be in place to determine battery replacement schedules. It is recommended that the charger output should be checked on a yearly basis to ensure the charging characteristics have not drifted. Refer to Table 1 above for checking this parameter. Standby Batteries Expected Life - 3-5 years at an ambient temperature of 20 C Replacement Schedule - As above. However, note that the expected battery life is shortened by an increase in ambient temperature. The life reduces by 50% for every 10 C rise above ambient. This should be taken into account when assessing battery replacement schedules. Refer to battery manufacturer manuals for further information. Manufacturer / Part Numbers - YUASA POWERSONIC 4AH NP4-12 5AH PS-1250-F1 7AH NP7-12 7AH PS-1270 12AH NP12-12 12AH PS-12100-F1 17AH NP18-12 18AH PS-12180-NB 24AH NP24-12B 26AH PS-12260-NB STOP For optimum performance and charge retention, Yuasa recommend that batteries are topcharged prior to installation. For batteries up to 6 months old from date of manufacture, charge at 2.4V per cell (i.e. 14.4V per battery) for 20 hours prior to installing the batteries. It is not recommended to use batteries that are older than 6 months from the date of manufacture on a new installation. It is quite normal for lead-acid batteries to vent hydrogen when being charged. The enclosure is adequately ventilated to dissipate this hydrogen. DO NOT seal the enclosure or install in a sealed enclosure or cavity. Page 8 of 8