General Information B&R Power Supply PS104 1. General Information Features of the B&R power supply PS104: Output voltage adjustable to 28 V 115/230 V auto select input Overload design (high put overload capability) Selectable single/parallel operation (jumper) World-wide certifications (UL, EN, CSA, CB Scheme) for industry and office/home Compact construction Mounted and installed quickly and easily (no tools required) 2. Order Data Model Number Short Description Image 0PS104.0 24 VDC power supply, 1 phase, 100 W, input 115/230 VAC, auto select, DIN rail mounting Table 1: PS104 - order data B&R Power Supply PS104 1
Technical Data 3. Technical Data See also data sheet "Technical Data", which is delivered with the power supply. Product ID General Information C-UL-US Listed Input Input Voltage AC 100-120/220-240 V (Auto-Select), 47-63 Hz, suitable for IT power systems (AC 85-132 V / AC 184-264 V, DC 220-375 V) Input Current <2.1 A (@ AC 100 V, 100 W P ) <1 A (@ AC 220 V, 100 W P ) Starting Current I pk /I 2 t External Fusing Transient Immunity Hold-up Time (see "Hold-up Time with ACin", page 6) Output Output Voltage Voltage Regulation Jumper Pos.: Single Use Jumper Pos.: Parallel Use Ripple/Noise Overvoltage Protection (OVP) Output Noise Suppression Rated Continuous Loading PS104 Yes 22A/0.35A 2 s (120Vin) 45A/1.5A 2 s (120Vin) (typ., T U =50 C, cold restart, power mains according to EN 61000-3-3) Not required, unit provides internal fuse (T3 A15H, not accessible) Transient resistance acc. to VDE 0160 / W2 (750 V / 1.3 ms), over entire load range >40 ms @ AC 230 V, 24.5 V / 4.2 A >20 ms @ AC 196 V, 24.5 V / 4.2 A >20 ms @ AC 100 V, 24.5 V / 4.2 A DC 24-28 V (adj. by front panel potentiometer) Preset: 24.5 V ±0.5% @ 4.2 A Dynamic ±1.5% V overall Static 1% V Static 3% V <50 mv PP (20 MHz bandwidth, 50 Ω measurement) <36 V Radiated EMI values below EN50081-1 (Class B), even with long (>2 m), unshielded put cables Up to 4.2 A @ 24.5 V / 3.6 A @ 28 V Depending on built-in orientation, V in and T amb (convection cooling); see "Derating of Output Power", page 6 Overload Behavior Overload Design: No switch-off at overload/short-circuit, instead: up to 1.9 I rated. Oversizing is not necessary to start heavy or demanding loads. Protection Unit is protected against (also permanent) short-circuit, overload and open-circuit. Derating Depending on built-in orientation (see "Derating of Output Power", page 6) Parallel Operation Yes (selectable by front panel jumper) We recommend that you do not operate more than 5 power supplies in parallel. Power Back Immunity 35 V Operation Indicator Green LED (DC OK) Table 2: PS104 - technical data 2 B&R Power Supply PS104
Technical Data Product ID Efficiency, Reliability Efficiency Typ. 90% (@ AC 230 V, 24.5 V / 4.2 A); see "Efficiency", page 5 Loss Typ. 11.4 W (@ AC 230 V, 24.5 V / 4.2 A) MTBF (reliability) Approx. 500,000 h acc. to Siemens standard SN 29500 (24.5 V / 4.2 A, AC 230 V, T amb = +40 C) Prior to shipment, every unit undergoes the following tests in order to isolate any defective units which might suffer an early failure: Run-in / Burn-in (Full load, T amb = +60 C, on/off cycle) Functional test (100%) Connection Terminals Cage clamp terminals / 2 terminals per put, uniformly firm hold, vibration-resistant and maintenance-free Connector Size Range 0.5-2.5 mm² (20 AWG 12 AWG) Wire tip sleeves can be used Wire Strip Length 6 mm (0.24 in) recommended Additional Features: All terminals are easy to reach as mounted on the front panel. Inputs and puts are strictly separated from each other (inputs below, puts above) and therefore cannot be mixed up. Mounting and connection with requiring a screwdriver! Easy, quick, durable and reliable installation. Operational Conditions Environmental Temperature during Operation Relative Humidity during Operation Storage and Transport Conditions -10 to +70 C (see "Derating of Output Power", page 6) Max. 95%, non-condensing Storage Temperature -25 to +85 C Relative Humidity for Storage Max. 95%, non-condensing Transport Temperature -25 to +85 C Relative Humidity for Transport Max. 95%, non-condensing Mechanical Characteristics Dimensions Width Height Depth Weight Housing Montage 73 mm 75 mm 103 mm (+ DIN rail) 360 g Robust plastic housing, fine ventilation grid on three housing sides to keep small parts, IP20 Easy snap-on mounting onto the DIN rail (TS35/7.5 or TS35/15). Unit sits safely and firmly on the rail; no tools required, even to remove. Mounting Orientation, or (see "Derating of Output Power", page 6) Ventilation/Cooling Normal convection, no fan required: Leave sufficient space for cooling! When the convection is strong enough, the temperature difference T between air intake and put in the housing should not exceed approx. 15K. Recommended space on sides with ventilation holes: 25 mm PS104 Table 2: PS104 - technical data (cont.) Specifications are valid for 230 VAC input voltage, +25 C ambient temperature, and 5 min run-in time, unless otherwise stated. They are subject to change with prior notice. B&R Power Supply PS104 3
Dimensions 4. Dimensions Figure 1: PS104 - dimensions 5. Installation See also the basic installation manual "Installation and Operation". The basic installation manual is delivered with each power supply. 4 B&R Power Supply PS104
Diagrams 6. Diagrams 6.1 Output Characteristics 35 30 Output Voltage V [V] 25 20 15 10 V in = 115/230 VAC Single Use 5 V in = 115/230 VAC Parallel Use 0 0 1 2 3 4 5 6 7 8 Output Current I [A] Figure 2: PS104 - put characteristics V /I (min.) 6.2 Efficiency Efficiency [%] 91 90 89 88 87 86 85 84 115 VAC in 230 VAC in 83 1 1.4 1.8 2.2 2.6 3 3.4 3.8 4.2 Output Current I [A] Figure 3: PS104 - efficiency (@ V = 24.5 V, typ.) B&R Power Supply PS104 5
Diagrams 6.3 Derating of Output Power 120 100 A Output Power [W] 80 a 60 b 40 Mounting 85-132 VACin A-a A-b A-b 20 185-264 VACin A-a A-b A-b 220-375 VDCin A-a A-b A-b 0-10 0 10 20 30 40 50 60 70 Ambient Temperature [ C] 6.4 Hold-up Time with ACin Figure 4: PS104 - derating of put power Hold-up Time [ms] 160 140 120 100 80 60 40 P P P P =100W, typ. =100W, min. =50W, typ. =50W, min. 20 0 80 120 160 200 240 280 Input Voltage VAC [V] in Figure 5: PS104 - hold-up time with ACin (@ V = 24.5 V, typ. + min.) 6 B&R Power Supply PS104
Standards and Certifications 7. Standards and Certifications Electromagnetic Emissions (EME) EN 50081-1 (includes EN 50081-2) Class B (EN 55011, EN 55022) incl. Annex A, thanks to noise suppression EN 61000-3-2 (PFC) Electromagnetic Immunity (EMI) EN 61000-6-2 (includes EN 55024) Safe Low Voltage SELV (EN 60950, VDE0100/T.410), PELV (EN 50178) Protection Class/Degree Class I (EN 60950) / IP20 (EN 60529) The PSU complies with all major safety certifications for EU (EN 60 950, EN 60204-1, EN 50178), the USA (UL 60950, E137006, UL508 LISTED, E198865), Canada (CAN/CSA-C22.2 No. 60950 [CUR], CAN/CSA-C22.2 No. 14 [CUL]), CB Scheme (IEC 60950). CB scheme Table 3: PS104 - standards and certifications B&R Power Supply PS104 7
Standards and Certifications 8 B&R Power Supply PS104