Operating manual Steam trap

Similar documents
PBX Series Quick Fit Connector Bimetallic Steam Traps

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

Float and Thermostatic Traps Series H, C and X

INSTALLATION, OPERATION & MAINTENANCE MANUAL

Backflush filter R8-30W

SunMaxx Solar Filling Station Operating Instructions

Operating and installation instructions

Hydraulic control unit series

Elektromotoren und Gerätebau Barleben GmbH

IMPORTANT SAFETY NOTICE

FT43, FT44, FT46 and FT47 Ball Float Steam Traps

VdS en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS en : (01)

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN

Unique DV-ST UltraPure - Manuel: for valve sizes DN8 to DN80 (¼ to 3 )

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

Installation and safety instructions for AC/DC built-in devices

FJ2. 2 Ton Trolley Floor Jack Assembly & Operating Instructions

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

TYPE E Main Valve Sizes 3 /8 through 12

Rexroth Hydraulic Pump A10VO Series User Manual

Fig B36 Stainless Steel 'T' Type or Basket Type Strainers

SureSite Magnetic Liquid Level Indicator

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version

Trouble Shooting. Pump

This instruction is valid for all ACD pump models shown on page 2

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

OPERATING AND MAINTENANCE INSTRUCTIONS PUMP TYPE

BRAZED PLATE INSTALLATION MANUAL

Elektromotoren und Gerätebau Barleben GmbH

M A N U A L

CAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.

Quickstart. English Deutsch Français

GATE VALVES ASAHI AV VALVES. Type P (Standard: Plug) Type S (Soft Seal) Contents. (1) Be sure to read the following warranty clauses of our product 1

Air Eliminators and Combination Air Eliminators Strainers

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

Installation, Operating and Maintenance Instructions for AEON Metal Seated Gate Valve (MSGV) Water

Oil and Coolant Circulating Heating System. Model - OCSM

MFP14, MFP14S and MFP14SS Automatic Pumps

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Installation, Maintenance, & Repair Series 4000B/LF4000B

Maintenance and Instruction Manual. December 2011 Rev. 01 Page 1 of 12

STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES

BACKPACK SPRAYERS. MODEL NOS: KSP16 & KSP20 Part Nos: & OPERATING & MAINTENANCE INSTRUCTIONS GC04/12

ALMATEC Series CX CX 10 CX 130

81000 Series Aluminum Gate Valve Installation and Repair Manual

Duplex Filters 40 FLDK 0008(C)-0120(C)

BOWIE PUMPS OPERATION - MAINTENANCE

Explosion proof enclosures

Machine needle shut-off nozzle type HP

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

INSTRUCTIONS FOR USE SAFETY PRINCIPLES, OPERATION AND MAINTENANCE FOR. HYDRAULIC PUMP type HP 03L, 05L, 07L volume 3 l, 5 l, 7 l

Machine needle shut-off nozzle type-a

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Self-operated Pressure Regulators Universal Pressure Reducing Valve Type 41-23

IOM SERIES 820-E/P Electro-Pneumatic Positioner

TECHNICAL DATA. Dry 122a. November 12, 2013

NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE

Maintenance and Service Instruction

Artisan Thermostatic basin mixer. Fitting Instructions & Contents List

Kompressoren. Adsorption Dryer AD

In-Line Filters and Coalescers with Automatic Drains

Turbocharger / TPL-C, TPLVC Original assembly instructions English

Tech. Services: (800) Fax: (800) Order Entry: (800) Fax: (800) Internet Address:

HYDRAULIC LIFT TABLE CART 2200-LB.

P.E.D. 97/23/EC/0424 Butterfly Valves Series SL, SLK Group 1-2 Class I, II, III ATEX CE Ex II 2 GD

PLATE HEAT EXCHANGER. Installation Manual. Customer Name: Serial number: Purchase order number: Project:

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

ATEX-Specific Supplementary Operating Instructions

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25

Select Radiators Installation Guide

Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.

PRESSURE REDUCING CONTROL VALVE

BoWex SD, SD1 and SD2 Operating-/Assembly Instructions

Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications

REPAIR INSTRUCTIONS UNDER BODY CYLINDER (UM, UL)

API Flanged Safety Relief Valves Series 526 CATALOG

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

VAG Non-Return Valves

ROTEX SD shiftable jaw coupling

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

series Materials Body: 1/2, 3/4 and 1 : dezincification resistant alloy brass EN CW617N

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description

CARING FOR YOUR WATER HEATER

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts.

AIR AND DIRT SEPARATORS. Flamco FLEXVENT. Air and dirt separators FLAMCOVENT FLAMCOVENT CLEAN FLEXAIR FLAMCO CLEAN FLAMCO A-S.

CHEMICAL CLEANING UNIT Product number:

Basic Hydraulics and Pneumatics

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

SELECTION, APPLICATION AND MAINTENANCE

Typical water pump claims and causes

Fisher 249 Caged Displacer Sensors

Flushing and Cleaning the A/C System

Transcription:

Operating manual Steam trap Blatt Nr. KA/4.0.161.1.1 Stand 25.01.2016

Contents Section Title Page 0 Introduction... 1 1 Intended use......1 2 Marking of the fitting... 2 3 Safety instructions... 2-3 4 Transport and storage... 3 5 Installation... 4-6 6 Pressure testing the pipeline section... 6 7 Initial start-up...... 6-7 8 Normal operation...... 7 9 Use in hazardous areas... 7 10 Maintenance... 8 11 Troubleshooting help... 9-10 12 Further information... 10

0 Introduction This manual is intended to assist users of a MANKENBERG steam trap during installation, operation and maintenance. Read the manual thoroughly before installing or putting this valve into service. Failure to follow the following instructions particularly the ary and warning s may lead to hazards and may invalidate the manufacturer's warranty. MANKENBERG is at your servíce for any assistance and queries. See Section 12 <Further information> for the addresses. Technical information is also available at www.mankenberg.de 1 Intended use A MANKENBERG steam trap KA is intended to drain accruing condensate from gas or steam leading systems. To collect the condensate as effectively as possible, the steam trap should be installed at a low point of the pipeline section. This is an automatic function and does not need any additional electrical/pneumatic energy: Depending on the liquid level, a float controls the drainage from the body of the steam trap via a system of levers. The float is dimensioned for draining (non-foaming) condensate of the density of water condensate at saturated steam temperature. The use with condensate of other density must be checked with MANKENBERG. MANKENBERG planning documents are available to give users precise assistance in selecting and designing the appropriate fitting, e.g.: In the section <KA: Level control valves>: <selection guidelines: dimensioning of lines downstream of the steam trap> <Type sheet KA...> with technical data and tables of the setting ranges and the dimensions. Metallic sealed steam traps are no shut-off elements ensuring a tight closing of the valve. In ac-cordance with DIN EN 60534-4 and/or ANSI FCI 70-2 they may feature a leakage rate in closed position in compliance with the leakage class III: Leakage class III (metal sealing cone) = 0.1 % K vs value MANKENBERG valves are supplied as standard for screw-mounted or flange-mounted pipeline/tank connections also for special connections if required. The upper limit of the permitted operating data is permanently marked on each fitting supplied. - 1 -

2 Marking of the fitting Each fitting bears the following markings as a minimum: For Marking Remark Manufacturer Fitting design Nominal diameter Nominal pressure Working pressure range Max. permitted temp. Body material Flow direction ATEX protection class The markings (in the case of fittings made of deep-drawn stainless steel, they are etched into the body) should neither be covered nor painted over, so that the fitting remains identifiable. 3 Safety instructions 3.1 General pre The same safety regulations apply to a fitting as to the system into which it is installed. These instructions only give those safety recommendations that have to be additionally observed for the fitting. 3.2 Special safety instructions for the plant operator The following requirements for the intended use of a fitting are not the responsibility of the manufacturer but have to be guaranteed by the user. The fitting may only be employed for the purpose described in Section 1 <Intended use>. Only competent specialist personnel may install, operate and service the fitting. Competent as defined in these instructions refers to persons who, because of their training, specialist knowledge and professional experience, are capable of correctly assessing and properly executing the work with which they are entrusted and of recognizing and rectifying hazards. The pipeline system must be properly designed and installed so that the fitting can be mounted and operated without any tension. The fitting must be properly installed in the correct mounting position. MANKENBERG steam trap + type e.g. DN or G and numerical value PN or Class and numerical value Operating pressure range and numerical values Temperature and numerical value e.g. CrNiMo steel Indicated by an arrow II 2G c II A The usual flow rates should not be exceeded in the pipeline section during continuous operation, and abnormal operating conditions such as vibrations, water shocks and cavitation should be avoided or if unavoidable clarified with the manufacturer in advance. The prevailing operating conditions must comply with the limits of the design data stated in the MAN- KENBERG order confirmation. hard or sharp objects in the flowing medium could damage internal functional parts of the fitting. A strainer or filter should be installed upstream of the fitting. The corrosion protection for the fitting must be adapted to the local environmental conditions. The fitting must not be coated with thermal insulation. See Section 12 <Further information> for the address Design name as per accompanying MANKENBERG data sheet Numerical value for DN in [mm], for G in [inches] Numerical value for PN in [bar], for Class in [lbs/square inch] pressure data are displayed as overpressure above the atmospheric pressure Numerical value for the lower and upper limit Temperatures above 50 C entail a reduced pressure resistance. This must be considered for the corresponding material in accordance with the DIN EN 1092 standard CrNiMo steel = high-alloy austenitic steel only for devices with conformity certification according to ATEX Detailed s are provided on some of these prerequisites in the following sections. - 2 -

3.3 Special hazards danger of fatalities Before a fitting is removed from the system or before a fitting is dismantled but partially remains in place, the pressure in the system on both the inlet and outlet side must be completely reduced so that there is no uncontrolled flow of the medium out of the system. In the case of toxic or hazardous media, the system must be completely drained before the fitting is removed. Caution is required with residues that might continue flowing. If a fitting is removed from a system with a toxic medium and is taken out of the plant: it must be properly decontaminated before repair. 4 Transport and storage A fitting must be handled, transported and stored with care: The fitting must be transported and stored in its protective packaging until it is installed. The fitting has moving internal parts. Even packaged fittings should be transported smoothly without any shocks. In the case of a fitting that can no longer be transported by hand, the lifting gear must be attached to a suitable position on the housing (branches). Under no circumstances may the lifting gear be affixed to any attachments. When the fitting is stored prior to installation, it should be kept in closed rooms and protected against harmful influences such as dirt, moisture and frost. In special cases, the fitting is supplied free of oil, grease or silicone and is marked accordingly. A fitting such as this must not come into contact with oil/grease/silicone during storage and handling (particularly when subsequently unpacked). A MANKENBERG fitting generally has functional and/or sealing parts made of elastomer materials. These cannot be stored for an unlimited period. ISO 2230 describes the storage conditions for elastomers in detail and specifies the permissible storage period. Functional and sealing parts must be replaced well before the storage period expires. They are available from MANKENBERG as a service set. See also Section 11 <Troubleshooting help>. MANKENBERG fittings of small and medium nominal diameters are largely made of stainless steel (high-alloy CrNiMo steel). If, under exceptional circumstances, fittings are stored in a unpacked state, they must be protected against ferritic dust to avoid corrosion. The fitting is generally not capable of standing alone: Handle with care so that the fitting does not tip over during transport/storage. - 3 -

5 Installation 5.1 General s The same installation regulations apply to a fitting as to the system into which it is installed. The following additional s apply: Section 4 <Transport and storage> should also be observed during transport to the installation site. The installation site to allow perfect functioning of a fitting should be a section of pipe without any flow disruptions, without any angles and without any restrictors or shut-off devices close to the fitting, either upstream or downstream (optimum distance = 10 x DN). If this does not apply, the installation situation should be checked with the plant operator and/or MANKENBERG. The statics of the pipeline must be designed so as to take account of the weight of the fitting particularly those with an eccentric mass. If required, the pipeline may have to be properly supported on both sides next to the fitting (or at the fitting itself) particularly in the case of fittings with a substantial mass and especially if vibrations are to be expected in the system. When the fitting is supported, it is important to check that all functioning parts (manual vents, levers, floats) remain capable of moving freely and are not blocked. The fitting must not be coated with thermal insulation. A fitting that is operated at a medium temperature above 130 C needs undisrupted removal of heat if it is to function perfectly. Failure to observe this instruction may cause damage to the fitting and hence in the pipeline system as well. To protect internal functional parts (e.g. the seat) against damage and/or blockages, it may be necessary to install a strainer and/or filter upstream of the fitting. The mesh size of the sieve/filter for protecting against aggregates in the pipe section should be selected by the plant operator according to the operating conditions. Failure to observe this instruction may impair the function of the fitting and lead to damage. 5.2 Installation preparations It is necessary to ensure that a fitting is not installed unless its matches the operating conditions in terms of function, pressure and temperature, range, body material as well as connection type and dimensions. danger of fatalities No fitting may be operated that does not have a sufficient pressure and temperature range for the operating conditions see Section 1 <Intended use> and markings on the fitting. The manufacturer MANKENBERG should be consulted in the case of any applications outside of this range. Failure to observe this regulation may mean danger to life and limb and may cause damage to the pressure-regulating valve. Newly installed tanks and pipeline sections must be thoroughly rinsed and cleaned before commissioning. The corrosion protection for the fitting must be adapted to the local conditions: danger of fatalities As a general rule, the body part of a steam trap bearing the moving float should be installed vertically. See sectional drawing in the type sheet <KA...> also. Failure to observe this instruction may cause functional faults. When draining compressed air or gases, the condensate collecting tank or the pipeline has to be connected to the taphole in the housing cover (Niagara) or to the threaded bushing at the housing upper section (KA 2, KA 2K, KA 2X, KA 3) by an additional compensation pipe. - 4 -

5.3 Installation steps Fittings should only be finally unpacked at the installation site and inspected for damage prior to assembly. Damaged fittings must not be installed. It is necessary to ensure that the covers have been removed from all the connection branches before installation. The fitting should be inspected to ensure that it is clean. Interior parts must be free of liquid (e.g. condensate): if necessary, connecting branches should be cleaned before installation with clean compressed air. The type and dimensions of the line or tank connections must match the fitting to be installed and be flush with the connecting surfaces of the fitting as well as in a parallel plane to the fitting itself. If the fitting is marked with an arrow on the housing, the flow in the pipe section must match the marked direction of flow. If installed in the opposite direction to the arrow, the fitting will not perform its intended function. The fitting mist be installed without any tension. In the case of an already installed system, the geometry of the pipeline must match the face-to-face length of the fitting. It is necessary to ensure that even under operating conditions no tension from the pipeline is transferred to the fitting. The drainage of the condensate from the steam trap at the lower housing nozzle must be provided by the customer. A MANKENBERG fitting made of "high grade" or "high grade pure" stainless steel (austenite, e.g. 1.4404 or 1.4435) does not need any surface protection for normal environmental atmosphere and for normal weather conditions. External parts of the fitting made of low-alloy or non-alloy materials that are supplied ex-works with a primer have to be provided with a suitable coating by the customer. Caution: Never paint over the marking(s) of the fitting (either etched into the body or on nameplate). In addition, the following applies to the pipeline connection: with flanges: The sealing surfaces on the body of the fitting are formed in accordance with the MANKEN- BERG order confirmation. The accompanying flange seals are generally not included in the MANKENBERG supply schedule. During installation, centre the fitting by means of the flange screws on the mating flange before the screws are tightened. with screw-mountings: The connecting surfaces on the body of the fitting are formed in accordance with the MAN- KENBERG order confirmation. The required seals are generally not included in the MAN- KENBERG supply schedule. - 5 -

with welding ends: Properly performed welding must ensure that no significant tension is transferred to either the section of pipeline or the body of the fitting. Under no circumstances may the body of the fitting exceed the temperature marked on it; otherwise the sealing and functional parts will be damaged and the whole fitting will become unserviceable. When a fitting with a body made of "high grade" or "high grade pure" deep-drawn parts (visible on the body connection with clamp rings) is welded, the welding joint must be carried out with special care; it is recommended that the body should be kept cool with a damp cloth. Failure to observe this instruction may cause distortion of the fitting body: even 0.1 mm of permanent distortion in the seat region may render the fitting unserviceable. 6 Pressure testing the pipeline section The fitting has already been pressure-tested by the manufacturer. The following points should be observed when conducting a pressure test on a pipeline section with a steam trap installed: In accordance with EN 12266-1, the test pressure may under no circumstances exceed 1.5 times the value indicated on the body with PN or Class. If any leakage occurs on the fitting, Section 10 <Troubleshooting help> should be observed. To prevent the float of the fitting from being damaged by pressure surge, the pipeline section has to be filled slowly. Failure to observe this instruction may cause damage to the fitting steam trap. When the housing is filled with water, the steam trap is not sealed. During the pressure test it may be necessary to install a shut-off valve in the drain pipe. If the pipe section is flushed and/or dried after assembly or pressure testing, it is necessary to make sure that the fitting has not been damaged by corrosion or excessively high temperature. 7 Initial start-up During the initial and every renewed start-up, it has to be checked if the fitting is functioning correctly and/or is sealed without condensate drain pipe. If required, the design of the steam trap can be checked in the <Selection guidelines> of the MANKEN- BERG catalogue, section <KA>. MANKENBERG is at your servíce for any assistance and queries, for the addresses see section 12 <Further information>. danger of fatalities No fitting may be operated that does not have a sufficient pressure and temperature range for the operating conditions see Section 1 <Intended use> and markings on the fitting. The manufacturer MANKENBERG should be consulted in the case of any applications outside of this range. Failure to observe this regulation may mean danger to life and limb and may cause damage to the pressure-regulating valve. To function correctly, the system pressure must lie within the range of the working pressure of the steam trap. In cases of doubt contact MANKENBERG service. See Section 12 <Further information> for the addresses. Open the air bleed valve and bleed the system at the beginning of the start-up. After closing the air bleed valve, the regulator works automatically. - 6 -

danger At the beginning of or shortly after the initial start-up, the sieve or the filter insert of any installed strainer/filter should be cleaned in order to avoid blocking the strainer/filter. After the initial start-up: Check the seals on screw-mounted parts of the body and reseal if necessary. Ask MANKENBERG for tightening torque, if necessary. Observe the relevant s in Section 11 <Troubleshooting help>. 8 Normal operation A properly designed steam trap works automatically and does not need any form of auxiliary energy. It is equipped with a device that drains air and other gases that have accumulated inside the housing of the fitting. This device is operated either manually or de-aerates permanently - temperature controlled - via a nozzle. To manually exfiltrate solid particles (e.g. dirt) accumulated in the condensate, the MANKENBERG steam trap KA Niagara is equipped with a drain plug. As a feature, the MANKENBERG steam traps KA 3, KA 8 and KA Niagara 83 are equipped with a temperature controlled shut-off valve that automatically drains air and other gases by thermic steam ventilation. danger of fatalities / danger It is necessary to ensure that the materials selected for the parts of the fitting in contact with media are suitable for the media in use. The manufacturer accepts no liability for any damage due to corrosion by aggressive media on parts made of unsuitable materials. Failure to observe this regulation may mean danger to life and limb and may cause damage to the pipeline system and to the fitting. Shortly after start-up it has to be checked on steam traps equipped with drain screws whether dirt has accumulated during installation or longer standstill. Open drain screw only at low pressure in the fitting. The drain flow must not be directed at persons. Open carefully when handling hot or toxic media, wear protective clothes, use protective gloves! It is recommended that the fitting should be inspected to ensure that it is functioning correctly after each new start-up. 9 Use in hazardous areas With an ATEX declaration of conformity are available for use in hazardous areas up to Zone 1. A compensation line is to be connected to the threaded socket on the upper section of the housing (KA 2K) and connected to the condensate collecting tank or pipe. - 7 -

10 Maintenance The automatic function of the fitting requires maintenance to ensure that it continues to operate perfectly. It is important for maintenance work to take place in a planned manner at periodic intervals. The maintenance plan in Table 1 is a recommendation by the manufacturer MANKENBERG, which should be supplemented by practical experience gained by the user under the prevailing operating conditions. MANKENBERG shall assume no liability resulting from improper maintenance and/ or repairs. Table 1: Sample plan for maintenance work Type of maintenance Work to be performed Period 1) Check function De-aerate housing Clean condensate tank Check seals on the body and the pipe connection If installed upstream of the fitting: clean strainer Preventive maintenance Check whether function is fulfilled as per Section 1) <Intended use> MANKENBERG steam traps are equipped with de-aeration. When operated manually: de-aerate until steam or gas escape Risk of injury To prevent any risk for operating personnel, the drain flow must not be directed at persons. Wear suitable protective equipment! Some MANKENBERG steam traps are equipped with a drain screw: Remove accumulated dirt Risk of injury To prevent any risk for operating personnel, make sure that this is carried out at low pressure in the fitting. Wear suitable protective equipment! Visual inspection According to the manufacturer's instructions Dismantle fitting, see Section 9.Visual inspection of the functional parts. Replace all parts of the maintenance set 2) at least 1x per week Depends on the properties of the medium Depends on the properties of the medium at least 1x per month Depends on the contamination of the medium at least 1x per year 1) See comment at the beginning of this section: The time intervals are guides which should be adapted to match the prevailing operating conditions, the properties of the medium in the system and the user's experience. 2) Request maintenance set and replacement instructions from MANKENBERG danger During maintenance work (apart from visual inspections) the relevant recommendations and warning s in Section 11 <Troubleshooting help> should be observed. Failure to observe this warning may mean danger to life and limb and may cause damage to the pipeline system and to the fitting. - 8 -

11 Troubleshooting help When a fitting that has previously been dismantled is being put back into service, the fitting should be checked for proper sealing capacity and function! Be sure to observe Section 3 <Safety instructions> when rectifying faults. Spare parts must be ordered with all the details on the nameplate. Only original parts from the manufacturer MANKENBERG may be installed. MANKENBERG experts are available to help in rectifying faults as quickly as possible. See Section 12 <Further information> for the addresses. If functional or corrosion damage is detected during maintenance or after a fault: consult MANKENBERG to find out whether a more suitable fitting is available or whether the damaged part can be supplied in a better-suited material. Type of fault Leakage at a connection body parts (flange or clamp ring): reseal connection Action Tighten the screws clockwise (tighten flange screws crosswise). If the screws of the body connection have to be loosened or removed (= unscrewing in the anticlockwise direction): Functional fault Medium is constantly draining from leakage of the seat: Clean the functional parts Danger of fatalities To prevent any risk for operating personnel, make sure that this repair measure is only carried out on a section of pipe that is not under pressure. Take of Section 3.3 <Special hazards> and then Section 5 <Installation in the pipeline>. Possible reasons: - A foreign object may be jammed in the seat and be preventing proper sealing. - or float/lever are moving to heavy due to dirt, deposits or corrosion Cleaning is necessary: The fitting must be disassembled Danger of fatalities To prevent any risk for operating personnel, make sure that this repair measure is only carried out when the fitting is not under pressure. Take of Section 2.3 <Special hazards>. When the fitting is not under pressure, disassemble the fitting by releasing the screw connection of the housing (clamp rings or flange) and dismantle the functional parts for cleaning. Here all parts of the maintenance set should be renewed. Afterwards, assemble the fitting and reassemble it, as described in Section 5 <Installation>. - 9 -

Functional fault: If during cleaning it is found that the seat sealing, the float, the lever or other functional parts are damaged: Cleaning alone see above cannot rectify the fault: Repair is necessary: damaged parts have to be replaced The fitting must be If the repair is to be carried out in the customer's workshop: repaired make a of all data according to the markings on the fitting and order the spare parts and necessary instructions from MANKENBERG. See Section 12 <Further information> for addresses. or: Send the fitting to the manufacturer for repair. See Section 12 <Further information> for the addresses 12 Further information You can obtain these instructions, the MANKENBERG data sheets quoted as well as further information including English language versions from the following addresses: Mankenberg GmbH Spenglerstrasse 99 D-23556 Lübeck Phone. +49-451 -8 79 75 0 Fax +49-451 -8 79 75 99 Email info@mankenberg.de www.mankenberg.de - 10-2014 2016 MANKENBERG GmbH