Milton Hershey School Supply Center

Similar documents
OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Sea Water Heat Pump Project

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Thermal Coupling Of Cooling and Heating Systems

GLOBACON 05 HVAC Systems for Cogen

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Wet Bulb Temperature and Its Impact on Building Performance

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Building Energy Systems. - HVAC: Heating, Distribution -

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

Heat Recovery In Retail Refrigeration

Geothermal Heat Pump Systems: From Basics to Hybrids

Second Place: Industrial Facilities or Processes, New

University of Maryland s Gossett Field House College Park, MD

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Solar Thermal TECHNOLOGY. Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

EnergyPro Building Energy Analysis. Assisted Living Building

Mechanical Systems Proposal revised

NEW JERSEY CENTER OF EXCELLENCE

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

How Ground/Water Source Heat Pumps Work

10 Strategic Steps to Reducing Your Energy Costs AEE Regional Chapter Meeting February 2, 2005

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

VE : Thermal / Systems Pack. 1. Tabular Room Data editing for thermal properties

HVAC Systems: Overview

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Maximizing Boiler Plant Efficiency. Presenter: Dan Watkins, LEED BD+C Sales Engineer Bornquist, Inc.

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Data Center Analysis and Design Analysis of SU s Green Data Center Performance

This presentation is posted for public use. ACEEE does not endorse any product or service.

Nordic Heat Pump Product Guide

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Florida Power & Light Company. Business Heating Ventilation & Air Conditioning ( HVAC ) Program Standards. Effective: November 9, 2015

Gas Absorption Heat Pumps. Future proofing your heating and hot water

High Performance Hot Water Systems Denver July 2010

Chapter 3.4: HVAC & Refrigeration System

Chris Clement 701 Bayou Lane Thibodaux, LA

Heating & Cooling Efficiency

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED

ABSTRACT DCMCCT PROJECT OVERVIEW

THE U.S. ENVIRONMENTAL PROTECTION AGENCY S NATIONAL VEHICLE AND FUEL EMISSIONS LABORATORY, ANN ARBOR, MICHIGAN

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Sino-Italian Environment & Energy Building S I E E B

Printing and Publishing Energy Savings Guide

Georgian Bay General Hospital Strategic Energy Management Plan 2014

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Direct Fresh Air Free Cooling of Data Centres

Sample - Existing Building Commissioning Plan

Commercial Gas Heat Pump - VRF

UTILITIES AND ENERGY MANAGEMENT

Energy Efficiency HOSPITALITY.

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Newport News Virginia Beach

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

Small-Scale Solar Heating and Cooling Systems

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

Simulation Tools for Solar Cooling Systems Comparison for a Virtual Chilled Water System

Subtropical Cities September Design for Energy Efficiency in Commercial Buildings in Queensland

Energy Efficiency in Steam Systems

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Princeton University Microgrid

Analysis of IECC2003 Chiller Heat Recovery for Service Water Heating Requirement for New York State

Less Exhaust Gas Less Pollution More Dollar Savings

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

Calculating System Flow Requirements

Guideline. Absorption Chillers. Southern California Gas Company New Buildings Institute Advanced Design Guideline Series

imagine SOLAR AIR CONDITIONING MADE EASY

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Modeling Guide for Daikin VRV in EnergyPro 6

CSP. Feranova Reflect Technology. klimaneutral natureoffice.com DE gedruckt

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

HEATING, VENTILATION & AIR CONDITIONING

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

A heat pump system with a latent heat storage utilizing seawater installed in an aquarium

Pharmaceutical central utility plants

What are the Carrier ChillerVu Energy Dashboards?

Learn How to Build a Multi Family Apartment Buildings in Madison Wisconsin

MECHANICAL PROJECT PROPOSAL

FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

Thermal Storage System Provides Emergency Data Center Cooling

Energy Action Plan 2015

Case Studies: Infrared Heating in Industrial Applications

Transcription:

8.0 CHILLER-HEATER AND HEAT RECOVERY SYSTEM ANALYSIS The redesigned mechanical system also consists of a modified chiller and boiler plant. This redesign uses the same goals as the air system, integration of other building systems with the mechanical. The goal of the total mechanical redesign is also to lower operating and life cycle cost. Working in conjunction with the DOAS and WSHPs, the redesigned chiller plant must prove to save as much or more energy as compared to the base system to prove beneficial. The existing system comprised of electric driven, water cooled centrifugal chillers. These chillers met the HVAC cooling load and, as shown in the DOAS schematic, also served a heat exchanger that cooled the walk-in freezer s condenser water loop. The existing system does not recover this rejected heat. Therefore, this 106 ton base load is met by the chilled water system 24 hours a day. Taking advantage of the new natural gas service installed at the supply center, the redesigned mechanical system utilizes direct fired absorption chiller-heaters. The goal of the chiller-heater system is to simultaneously meet the cooling demand while producing hot water for domestic and HVAC heating. From the load profiles shown in section 6.0, the base cooling load is formed from the condenser water loop system s heat rejection. Also shown is the high demand for hot water heating during a typical day. With the supply center having consistent heating and cooling demands year round, it becomes an excellent opportunity for simultaneous heating and cooling. The DOAS configuration already incorporates a heat recovery system, but as figure 7-2 illustrates, the condenser water loop, at best, is only cooled to 78 F by the water source loop. This means there is a significant amount of energy still left in the condenser water loop. The redesign will recover more heat from this loop until it is cooled to its 65 F operating temperature by pre-heating the domestic hot water. This will create a lower heating load for the chiller-heater to handle, meaning that on hot design days, more cooling capacity is available. The chiller-heater s operating characteristics are described in more detail in the following subsections. Schematics of the redesigned chiller and boiler plants are also located in this section as well as an overall total mechanical system schematic. 8.1 DESIGN OF DIRECT FIRED ABSORPTION CHILLER-HEATER SYSTEM ANALYSIS Chiller-heaters have three operating modes, cooling only, heating only, and simultaneous cooling and heating. Figure 8-1 illustrates the three modes of chiller-heaters. Building System Integration - 27 -

Cooling mode sees the chillerheater operating like a normal double effect LiBr absorption chiller. Since the chiller-heater is direct fired, the high temperature generator uses a gas-fired burner. The low temperature generator is activated in cooling mode and the evaporator produces chilled water. These chiller-heaters come in sizes from 100 to 1100 tons. When the chiller-heater operates in heating only mode, the condenser section of the process is off, and the evaporator now produces hot water. The refrigerant vapor that is produced in the high temperature generator no longer passes through the low temperature generator and is used to directly create hot water in the evaporator. Hot water production temperatures can rise up to 210 F. When simultaneous heating and cooling production occurs, the cycle operates as in the cooling only mode. However, hot water production takes place by means of an auxiliary heat exchanger. The heat exchanger condenses a portion of the refrigerant vapor that is produced in the high temperature heat generator. Therefore, the remaining refrigerant vapor is used to operate the cooling cycle. As this point forecasts, simultaneous hot water production reduces the Figure 8-1 Double Effect Absorption Cycle Building System Integration - 28 -

amount of cooling output. The more cooling that is required directly affects the amount of hot water production. At full energy input, 100% of the cooling capacity is available. However, if hot water production is required and performed by the chillerheater, the cooling capacity will decrease as low as to 30% of the rated value. Figure 8-2, taken from York s Millennium two-stage direct-fire absorption chillerheater product literature illustrates this point. Figure 8-2 Cooling/Heating Capacities per Input Energy The figure indicates that at maximum energy input, 100-30% of the available cooling capacity is available. At 30% cooling capacity and 100% energy input, approximately 65% of the total available heating capacity is possible for hot water production. When there is a demand for both cooling and heating, the chiller-heater must operate to meet the cooling demand and supplemental boilers will have to turn on to pick up the remaining heat load. Now that the basics behind chiller-heaters are stated, understanding the applicability of using them in the supply center is important for analysis. Figure 8-3 shows the peak cooling loads per month. The figure shows that the redesigned system, including the DOAS and WSHPs and the heat recovery system, has a peak cooling load equal to about 390 tons. The chiller-heaters however are not sized to just meet this peak load. The chiller-heaters are selected based on if there were no heat recovered from the condenser water loop, meaning the chilled water system must cool the CWL Building System Integration - 29 -

at all times. In addition to the cooling load, the chiller-heaters are also sized large enough so that they can meet the cooling demand and still have capacity for simultaneous hot water heating. In other words, referring back to figure 8-2, the chiller-heaters are selected so that the max cooling load, 390tons, is met operating at approximately 80% capacity. This allows for excess capacity for simultaneous hot water production. The chiller-heater will have more hours operating at full load than at part load in this case, which improves efficiency. Further analysis indicates that the chiller-heater operates at 80-100% capacity 1/3 of the year. Finally, both cooling and heating demands are satisfied using only one fuel source. Peak Plant Load per Month 450 400 June July 350 April August Sept Peak Plant Load (Tons) 300 250 200 150 January February March May October Nov Dec 100 50 0 Figure 8-3 Monthly Peak Cooling Load Figures 8-4 and 8-5 further illustrate how chiller-heaters simultaneously heat and cool. Broad Air Conditioning s direct fired chiller-heater product literature includes diagrams that clearly show how these units operate. Figure 8-4 shows the chilled water production side of the chiller-heater, while figure 8-5 illustrates the hot water portion of the machine. Other important areas of interest include the direct fired burner and natural gas line, shown in figure 8-4, as well as the basic refrigeration cycle parts (the condenser and evaporator). Building System Integration - 30 -

Figure 8-4 Broad Air Conditioning s Direct Fired Chiller-Heater Chilled Water Production Portion Figure 8-5 Broad Air Conditioning s Direct Fired Chiller-Heater Hot Water Production Portion Building System Integration - 31 -

The redesigned chiller and boiler plant is designed for redundancy. Two 240 ton chiller-heaters are utilized in the supply center. This ensures that the total cooling load is met, and the extra capacity needed to produce enough hot water is also available. However, if one of the chiller-heaters must go off line for any reason (maintenance issues for example), the other chiller-heater is capable of handling the critical loads by itself. The supply center does not include any spaces that must have cooling year round such as hospital emergency rooms. Therefore, if a chiller-heater goes off line, the only system that requires chilled water production is the walk-in freezer s condenser water heat rejection. As previously stated, the condenser water loop requires 106 tons of cooling 24 hours a day. One chiller-heater can handle this load while the other is being serviced. The systems that may suffer from only one chiller-heater being available are the 100% OA air handling units that serve the kitchen, bakery, and loading docks. The DOAS units also require chilled water. However, the remainder of the building still can meet the cooling demand via the water source heat pump system. The redundancy design for the supply center ensures all critical systems operate at design conditions and most of the building s cooling demands are satisfied. The redesign considers the cooling demand redundancy; however, having a chiller-heater go offline creates hot water production issues. The remaining chiller-heater must meet the cooling load to operate the walk-in freezer s condensing units, but the remaining capacity of that unit is too small to meet the hot water production demand. As previously stated, the DOAS units do not serve any critical spaces, so for a down period there is no issues with not supplying chilled water to them. Hot water production is critical in the supply center, however. Serving as a back-up when the chiller-heater system can not meet the HVAC and domestic hot water demands is a 9000 MBH natural gas fired boiler. The boiler is sized to completely meet all HVAC and domestic hot water needs. The hot water system of the supply center s redesigned mechanical system is integrated with the chilled water system though the chiller-heater. However, incase there is a problem with one of the machines for any reason; the hot water system has the ability to be totally independent. The following subsection describes the entire heat recovery system using the condenser water loop in detail and includes an overall system schematic of the redesigned chiller and boiler plants. The schematic also shows the integration with the DOAS and heat pump system. Building System Integration - 32 -

8.2 CONDENSER WATER LOOP HEAT RECOVERY SYSTEM ANALYSIS The DOAS and heat pump system analysis explained how that portion of the redesign incorporated the condenser water loop from the walk-in freezers for heat recovery. Figure 7-2 in section 7 of this report indicates that the condenser water loop only gets cooled from 84 F to 78 F at peak design by the water source loop. This leaves a good portion of energy to recover that is otherwise wasted in the chilled water system as explained in the previous subsection. The next phase of heat recovery from the condenser water loop includes domestic hot water preheating. The design conditions for domestic hot water production is 50 F entering water temperature and 180 F leaving water temperature at a maximum flow rate of 100gpm. The condenser water loop s maximum temperature is only 84 F. Therefore, the maximum possible domestic water preheated temperature is roughly 79-81 F (dependant upon thermodynamic fluid flow properties). The preheat process occurs though a plate-frame heat exchanger, similar to the water source loop configuration, and is shown in figure 8-6. The next phase of hot water production is to raise the preheated domestic water to design temperature. Since the chiller-heater can only produce one hot water loop, the domestic water is heated though another plate-frame heat exchanger. The chiller-heater plant will produce enough hot water to meet the air handling unit s heating demands and have a branch that services the domestic water heat exchanger. Therefore, there is only one closed hot water loop running into the chiller-heater which helps keep the system running clean. Running domestic water directly into the chiller-heater creates more maintenance issues which is why the redesigned closed loop configuration is used. The hot water system does have redundancy as explained in the previous subsection. If the chiller-heaters are not sufficient to meet the required hot water demands, or if one unit goes off line, the back up boiler is sized large enough to meet all HVAC and hot water needs. Hot water preheat is still available when the chiller-heater system is not working since it is independent. Figure 8-6 illustrates the entire redesign schematic. The schematic illustrates the DOAS and water source heat pump system, the redesigned chiller and boiler plant, and all of the heat recovery mechanisms. For comparison, the existing HVAC system schematic is also shown in figure 8-7. One point of reference in the comparison is that the redesigned system requires less equipment than the existing system. Building System Integration - 33 -

Figure 8-6 Redesigned HVAC System Overall Schematic Building System Integration - 34 -

Figure 8-7 Existing HVAC System Overall Schematic Building System Integration - 35 -

The figures above seem to prove that the existing system is simpler at first glance. However, the existing system is comprised of four totally independent systems. The redesigned system integrates all sections of the HVAC requirements as well as other building systems. The only independent system in the redesign is the back-up supplemental boiler which is still in series with the chiller-heater system. So while the existing system s concept is simpler, the redesign s complexity is used to save as much energy as possible compared to the original. 9.0 MECHANICAL SYSTEM REDESIGN CONCLUSIONS The proposed mechanical system redesign for the Milton Hershey School New Supply Center focused on building system integration and energy savings. Integrating different building systems with the HVAC system is essential in the redesign to save as much energy as possible. The redesign system utilizes more expensive equipment than in the existing system, therefore, this integration process is even more important in an effort to receive reasonable pay back periods (about 2-4 years). The initial cost of each system is required for the economic calculations as well as the results from a yearly energy simulation. Carrier s Hourly Analysis Program (HAP) is used to perform load calculations as well as energy simulations for both the redesigned system and the existing system. The HAP s load results for the DOAS and water source heat pumps are imported in a chiller-heater model performed in Microsoft Excel. An extensive yearly energy simulation model of the supply center using a chiller-heater and the energy recovery system is also created using Excel. The model calculates the total energy consumed by the chiller-heater and the energy savings created by using the heat recovery system. HAP is used to calculate the energy consumed by AHU fans, terminal unit fans, cooling towers, and pumps. 9.1 ECONOMIC ANALYSIS The yearly energy simulations prove that the supply center s existing and redesigned mechanical systems have much different results. Table 9-1 indicates the natural gas rates that are provided by H.F. Lenz Company and are used for each simulation. The electric rate for the supply center used in the analysis is $0.06/kwh Table 9-1 Natural Gas Monthly Rates Jan Feb Mar April May June July Aug Sept Oct Nov Dec $/Therm 1.13 1.13.85.85.85.50.50.50.50.85 1.13 1.13 Building System Integration - 36 -