Corrosion in Fire Sprinkler Systems

Similar documents
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator

Corrosion Inhibition of Dry and Pre-Action Fire Suppression Systems Using Nitrogen Gas

Inspection and Testing of Water-Based Systems

Nitrogen Blanketing for Methanol Storage and Transportation

FIVE YEAR CERTIFICATION REPORT

CATHODIC PROTECTION SYSTEM DESIGN

Transformer Deluge Systems

SECTION GENERAL REQUIREMENTS, MECHANICAL. 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure #

Pressure Testing Procedures for Building Services Piping

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

Dissimilar Metal Corrosion

Division 21. Fire Suppression

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Steel Fire Sprinkler Pipe

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

This chapter is devided into two sections:

TECHNICAL DATA. Dry 122a. November 12, 2013

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Fire Suppression Systems for Your Home

The Jockey Pump, an Important Part of a Fire Pump System.

Facility Operations Physical Safety Guidance Document

Rajesh Swaminathan. March 13, 2005

Appendix B Forms for Inspection, Testing, and Maintenance

SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN

THE INSTRUCTIONS PRESENTED HERE ARE ORIENTED TO USERS OF CNG CYLINDERS AS WELL AS TO TECHNICIANS IN CHARGE OF THEIR INSTALLATION

LIST PRICE BOOK MALLEABLE CAST IRON PRESS FITTINGS FOR SCH BLACK & GALVANIZED STEEL PIPE

singapore//singapore data center specifications tel: fax: internet + intellectual property + intelligence

FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

Lecture 35: Atmosphere in Furnaces

NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?

Comparison of the Corrosion Protection Effectiveness of Vapor Corrosion Inhibitor and Nitrogen Blanketing System

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

Commercial Fire Inspections

DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.

LHD LINEAR HEAT D ETECTIONN

Underground Storage Tanks

Fire Alarm System Monitoring - CAN/ULC-S561-03

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

Design & Construction Standards, Revised January

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute

Oxygen generation. By Vacuum Pressure Swing Adsorption.

INTRODUCTION INDUSTRIAL INSTALLATIONS AND ERECTIONS QUALITY THAT EXCELS

During Various Aluminum Fabricating Operations

Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

Stainless Steel Pipe Fabrication

esfr pendent sprinkler vk510 (k25.2)

Protecting Galvanized Steel Sheet Products from Storage Stain Rev 2.1 Aug-03

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Metals and Non-metals. Comparison of physical properties of metals and non metals

Best Practice in Boiler Water Treatment

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC DRAFT V0.

FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR

Fighting Fire in Sprinklered Buildings. Student Guide

NFPA31FuelOilPiping 1 Revised

HVAC Super Pro FAQ. Can HVAC SUPER PRO be used on both hard and soft copper and aluminum tubing?

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Gas Marketplace Work? July 9-13, 2007

LASER CUTTING OF STAINLESS STEEL

Recreational Nitrox Diving

Potter Electric Sprinkler Monitoring Training Manual

NITROX // safer diving

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion

DeZURIK 3" (75MM) & LARGER ECCENTRIC PLUG VALVES

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Tentative Interim Amendment NFPA 59A. Standard for the Production, Storage, and Handling of Liquefied Natural Gas (LNG) 2016 Edition

TD01211 PIN: NX nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

C I T Y O F S E L M A F I R E D E P A R T M E N T

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

Hydrogen Sulfide Monitoring and Safety. Nova Safety & Environmental Midland, Texas

Mission-critical fire protection HI-FOG for data centres

LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved

ASMECourseCatalog.

12 Ways To Avoid Boiler Tube Corrosion

Pressure Vessels (Air Compressors) and LPG Tanks

TECHNICAL INFORMATION ABOUT NATURAL GAS TRANSPORT

Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants

AMEC 6007: Linear Velocity and Acceleration Learning Outcome. CHEM 6012: Oil and Gas Compositions and Sales Specifications Learning Outcome

A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL

University of Tennessee Safety Guidelines

NON-PUBLIC FACILITIES MEPS ARTICLE 2 PLUMBING SERVICES SPECIFICATIONS TABLE OF CONTENTS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

New England Pipeline Safety Seminar October 22, 2014

Installation of Underground LP-Gas Systems

Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version

INDEPENDENTS AIL RET 2012

Automatic Fire Sprinkler Submittal Requirements

MECHANICAL PIPING PAINTING & IDENTIFICATION REQUIREMENTS

Transcription:

Corrosion in Fire Sprinkler Systems

Generalized Corrosion Generalized Corrosion, also known as rust, requires 3 things: 1)Water 2)Iron 3)Oxygen Generalized Corrosion Cell (Rust reaction)

MIC in FSS FM Global study found 10-30% of corrosion was influenced by MIC and 70-90% of corrosion was generalized (oxygen) corrosion.

Slowing Corrosion The largest concern for corrosion is related to oxygen. How do we eliminate oxygen in the fire protection system?

Dry and Pre-action Corrosion flourishes in Dry and Pre-action systems because air compressors supply an unlimited supply of oxygen and water. Trapped water from hydrostatic testing, combined with humid air supplied constantly by the air compressor creates a perfect storm. Typical Dry System

Nitrogen Replace the Oxygen with Nitrogen. Nitrogen is an INERT gas. It does not react with metals. Thus, no oxidation or rust occurs! The earth s atmosphere is 78% nitrogen and 21% oxygen. Strip the oxygen from air and leave pure nitrogen!

Corrosion Comparison Tests Nitrogen Tests

Nitrogen Tests Compressed Air After 20 months 98% Nitrogen

Nitrogen Tests On average, using 98% Nitrogen gas over compressed air increases the life expectancy of a dry fire sprinkler system up to 5.3X

Galvanized Pipe Galvanized is not effective. Galvanized Schedule 10 after only 18 months Galvanized Schedule 40 after only 3.5 years

Galvanized Pipe 11 No Hydraulic Advantage Source: NFPA 13, 2013

FM & Nitrogen FM Global Data Sheets 2-0 2.5.2.5 Use internally galvanized, stainless steel, or similar corrosion-resistant pipe in all new dry-pipe, pre-action, refrigerated-area, deluge, and exposure-protection sprinkler systems. Exception: Black steel pipe can be used in dry-pipe sprinkler systems equipped with closedtype sprinklers if the piping system is filled with an inert gas. Corrosion Technical Report 8 - B.2 Fill dry pipe or preaction systems with nitrogen as supervisory gas (e.g., use onsite nitrogen generator) to mitigate galvanized steel pipe corrosion.

13 How do you supply nitrogen to a fire sprinkler system? Source: NFPA 13, 2013

Nitrogen Strip the oxygen from air and leave nitrogen! The nitrogen membrane is the heart of the nitrogen generator.

Nitrogen Generator Potter offers a complete line of nitrogen generators that provide on-site reliable nitrogen production. Meet NFPA 13, 30 minute fill time requirements Easy installation Sized to meet the needs of systems Cost effective Low maintenance Dependable Four model families NGP-250D, NGP-500D NGP-1000D, NGP-2200D

Nitrogen Generators Purging Process Getting Air Out Initial system fill with air Nitrogen level monitoring Stops purging when nitrogen levels reach target. BMS connectivity and notification Advance Purging Designed for drying and freezer applications, reducing moisture and ice build-up. Manual options also available INS-PV INS-RA NGP-SPV

Nitrogen Generators Economic Impact Use black steel instead of galvanized piping Saves roughly 30% on sprinkler piping Save existing systems from additional corrosion Use a lower supervisory pressure Smaller compressor Smaller membrane Less expensive system Feed more than one system Plant Nitrogen Economies of scale Parking garage installation

Nitrogen Generators Case Study New Assisted Living Facility Design 1 - Traditional: 2 X 425 Gallon Dry Sprinkler Systems 40 PSI Air Compressor Galvanized Steel Pipe (Sch. 10) Galvanized Fittings No Labor Galvanized Material Cost $ 76,553.82 Air Compressor Equipment $ 1,150.00 Total Cost $ 77,703.82 Design 2 - Nitrogen: 2 X 425 Gallon Dry Sprinkler Systems 40 PSI Nitrogen Generator and Purge Valves Black Steel Pipe (Sch. 10) Steel Fittings No Labor Black Steel Material Cost $ 61,112.98 Nitrogen Generator Equipment $ 12,000.00 Total Cost $ 73,112.98 Estimated Galvanized System Life under Compressed Air Estimated Black Steel System Life under Nitrogen 10 years 53 years

Recommendations Dry Systems Use nitrogen over compressed air Use black steel over galvanized Limit addition of new water

Corrosion Monitoring Every corrosion mitigation plan should include a monitoring program. Corrosion Monitoring Station

Questions?