SECTION CONTROL VALVE ACTUATORS PART I - GENERAL

Similar documents
Fisher 657 and 667 Diaphragm Actuators

TorqPlus TM Electric Valve Actuators and Controls

Valve and Valve Actuator Selection Guide

Electric Rotary Actuator - On/Off or programmable control actuator

A descriptive definition of valve actuators

Diaphragm Actuators Favorable Variety Pneumatic Diaphragm Actuators Electric Actuators Hydraulic Actuators

2012 Valve & Valve Actuator Catalog. For new construction or retrofits, simplify projects with our complete selection.

BULLETIN OCTOBER DeZURIK ROTARY DIAPHRAGM ACTUATORS

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

WHOLESALE DIRECT INC WEST 65TH STREET

S03, S05 Series Low-Torque Spring- Return Direct-Coupled Actuators

Worcester DS/DM Series UltraSwitch Switch box

Type 3353 Angle Seat Valve

Fisher 377 Trip Valve

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

POWERS Controls No. 4 Pneumatic Damper Actuator

System 6000 Electropneumatic Converter for Direct Current Signals Type 6116 i/p Converter

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features

Type and Type Pneumatic Control Valves Type 3510 Micro-flow Valve

VG7000 Series Bronze Control Valves

Series 71, 72, and 76 Modutrol IV Motors

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

PNEUMATIC CONTROLS Selection and Description

MP8000 Series Pneumatic Valve Actuators

Unit 24: Applications of Pneumatics and Hydraulics

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Introduction to Process Control Actuators

Model 43AP Pneumatic Controller, Style B

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Commercial Semi-Instantaneous Water Heaters

Norbro Series 40R Pneumatic Actuator Double Acting or Spring Return

Know-how makes the difference. Electrical Actuators

Electronic, Digital and Mechanical Vibration Switches

Linear modules Lifting units Rotary modules Grip modules Inductive proximity switches Plug connectors

DIAMOND Gear Company, LTD. an ERIKS Company. Installation, Maintenance, & Operation Manual Declutchable Worm Gear

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

V&A PROCONTROL. Rotary Valve Actuators Pneumatic & Hydraulic On-Off / Control / ESD Double Acting Spring Return All Steel SIL 3

REGULATORS D& HD Series

Specifications. Model Flow type Pressure type. Air Maximum operating pressure. 1.0 MPa Ambient and fluid temperature. 3% F.S.

FAIRBANKS NIJHUIS FIRE PUMPS.

Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

SIS. Fisher FIELDVUE DVC6200 Series Digital Valve Controllers. Contents. Before You Begin... 2

Digital inductive conductivity transmitter

Pneumatic Shut-off Butterfly Valve Type 3335/31a SRP or DAP

Specifying a Variable Frequency Drive s

167D Series Switching Valves

Fisher FIELDVUE DVC6200 SIS Digital Valve Controller for Safety Instrumented Systems (SIS)

Butterfly Valves PN 6/10/16 for flanged connection

Element D Services Heating, Ventilating, and Air Conditioning

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

In-Line Electronic Flow Switches

FCD MMASS (Part V400) AN ISO 9001 REGISTERED COMPANY. Ball Valve Actuator Selection

4 Posiflow Proportional Solenoid Valves

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

Custom configuration such as modified angle dimensions, other flange standards, 3-way function, alternative materials.are available on request.

Stainless Steel Valves For the Sanitary Industries

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

Morrison Bros. Co. General Product Specifications

Sanitary Type Electronic Flow Switches

Why and How we Use Capacity Control

Pneumatic Actuators. Crafted without compromise, to make your life easier. The Leader in Actuator Technology

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

How To Drive A Compact Serie 1

Section M POWER LIFTS

LANDFILL GAS ENCLOSED FLARE SYSTEM

Lighting Packages. 230 VAC Fluorescent Enclosure Light:

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

Electronic Flow Switches

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

VAD. Variable Area Desuperheaters

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

FAQ s on Siemens Magmeters

Medical Air Systems: Scroll

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

2.12. page Products for Explosion hazardous Environment

Series 90 Modutrol IV Motors

Solenoid Valve Type 3962

valve solutions Chemical Cosmetic Cryogenic Food & Beverage Marine Mining Nuclear Oil & Gas Paint Pharmaceutical Pulp & Paper

Rotary Actuators, NAMUR interface VDI/VDE 3845 & ISO 5211 (ATEX certified) Series ARP

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Retrofit with Siemens

RUBBER SLEEVE KNIFE GATE VALVE

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

4 Dynamic Solutions. Leadership and Innovation in Valve Products and Valve Systems

Powers Controls TH 192 S Single Temperature Room Thermostat

Transcription:

SECTION 23 09 13.34 - CONTROL VALVE ACTUATORS PART I - GENERAL 1.0 OVERVIEW [Background for AE] A. Control Valve/Actuator Applications 1. See Exhibit 23 09 13.33-1, Control Valve/Actuator Worksheet for approved valve/actuator combinations. B. Preference for Pneumatic Actuators 1. It is acknowledged that the HVAC industry has embraced the use of electric/electronic valve actuators such that they are in widespread use. The University allows the use of such actuators for all applications. However, due to their superior high temperature performance, pneumatic actuators are strongly preferred over electric for steam control valve applications. Experience indicates that electric actuators can t take the heat as compared to pneumatic. Given their superior torque ratings pneumatic actuators are also preferred for large hydronic valve applications (e.g. larger than 3 spring-return, 4 fail-in-place). C. Actuator Grade 1. Within these Specifications a distinction is made between HVAC Grade products and Industrial Grade products. Applications for which HVAC grade products are allowed include terminal/room level devices and unitary equipment. Those that require industrial grade products include steam and large hydronic control valves/actuators. Other applications may be identified as either HVAC or industrial based upon project by project basis. Grade shall be identified in the control valve schedule. 1.1 RELATED DOCUMENTS A. Section 23 09 13.33 Control Valves B. Exhibit 23 09 13.33-1, Control Valve/Actuator Application Worksheet 1.2 CONTROL VALVES A. Valve/actuator combinations 1. See 23 09 13.33-1, Control Valve/Actuator Application Worksheet for approved valve/actuator combinations. 1.3 POSITIONERS A. Positioners shall be provided as scheduled or otherwise indicated within the documents. They are typically required on modulating control valves that serve central station equipment (e.g. AHUs, heat exchangers). If not scheduled or otherwise indicated within the documents, positioners shall be provided as a default requirement for central station equipment. B. When multiple valves are sequenced with one another, a positioner shall be provided on each valve (e.g. parallel control valves at heat exchangers). PART 2 - PRODUCTS 2.1 VALVE ACTUATORS & ACCESSORIES Actuator Identification Number Breakdow n: [Note to AE: This may seem complex, but it is necessary given that there are numerous valve actuator combinations.] HVAC = HVAC Grade IND = Industrial Grade E = Electronic/Electric HP = High Pressure Pneumatic U OF I FACILITIES STANDARDS 23 09 13.34-1 CONTROL VALVE ACTUATORS

LP = Low Pressure Pneumatic R = Rotary LIN = Linear SD = Spring-Diaphragm GV = Globe Valve Actuator Style DMP = Damper Actuator Style SR = Spring Return FIP = Fail in Place DA = Double Acting MOD = Modulating TP = Two Position A. HVAC Grade, Electronic Actuators for Modulating and Two-Position Service (Same specifications for both services) 1. Rotary Actuator, Spring Return (Fail-open or fail-closed) HVAC-E-R-SR a. Brushless DC motor. Stepper motor not allowed b. NEMA 1 or NEMA 2, as appropriate c. Approved for air plenum application, as required d. 24 VAC or 24 VDC power supply e. 0-10, 2-10 VDC or 4-20 ma control input f. Signal inverter switch g. Proportional, floating point or two position as determined by application h. Spring return for fail-safe operation i. 60,000 cycle rated j. 50% duty cycle rated k. Sized for 150% of break-away torque at maximum differential pressure across valve l. Rated for 120 degree F ambient temperature m. Motor overload/stall protection throughout rotation n. Visual valve position indicator o. Manual mechanical override p. Conduit connection (preferred) or prewired cable 3 (minimum) as appropriate for application. Mounting bracket shall be provided for conduit connection if available. q. Two adjustable SPDT auxiliary switches for position indication. Provide if scheduled or otherwise indicated in documents. r. Electric analog feedback. Provide if scheduled or otherwise indicated in documents. s. Adequate mounting height to accommodate 1 thick pipe insulation around valve body t. Multiple tandem-mounted actuators not allowed u. Approved manufacturers: Belimo, Siemens, Schneider/TAC 2. Rotary Actuator, Non-Spring Return (Fail in place) HVAC-E-R-FIP a. Same specification as HVAC-E-R-SR Rotary Actuator, Spring Return except without spring return feature. U OF I FACILITIES STANDARDS 23 09 13.34-2 CONTROL VALVE ACTUATORS

3. Linear Actuator, Spring Return (Fail open or fail closed) For sliding stem globe valve (rare electronic steam applications only) HVAC-E-LIN-SR a. Metal housing b. NEMA 1 or NEMA 2, as appropriate c. 24 VAC power supply d. 0-10 VDC or 4-20 ma control input e. Spring return for fail-safe operation f. 50% duty cycle rated g. Sized for 150% of maximum differential pressure across valve h. Rated for 300 degree F media (steam) temperature i. Rated for 130 degree F ambient temperature j. Motor overload/stall protection k. Visual valve position indicator l. Manual mechanical override m. Dual ½ conduit connections for power and control wiring n. Two adjustable SPDT auxiliary switches for position indication available for external control system use. Provide if scheduled or otherwise indicated in documents. o. Position feedback potentiometer. Provide if scheduled or otherwise indicated in documents. p. Mounting bracket with adequate standoff and isolation to prevent overheating q. Approved manufacturers: Belimo, Siemens, Schneider/TAC 4. Linear Actuator, Non-Spring Return (Fail in place) HVAC-E-LIN-FIP a. Same specification as HVAC-E-LIN-SR Linear Actuator, Spring Return except without spring return feature. B. HVAC Grade, Pneumatic Actuators and Accessories for Modulating and Two-Position Service 1. Linear Actuator, Spring-Diaphragm Type (for globe valves) HVAC-LP-LIN-SD-GV a. Aluminum or steel housing b. Spring-loaded replaceable rolling molded synthetic rubber diaphragm c. Rated for 25 PSIG control air pressure d. Rated for -20 to 150 degree F ambient temperature 2. Rotary Actuator, Spring-Diaphragm Type (Damper actuator with linkage for rotary valves) HVAC-LP-R-SD-DMP a. Aluminum or steel housing b. Spring-loaded replaceable rolling molded synthetic rubber diaphragm c. Rated for 25 PSIG control air pressure d. Rated for -20 to 150 degree F ambient temperature U OF I FACILITIES STANDARDS 23 09 13.34-3 CONTROL VALVE ACTUATORS

3. Positioner, Relay type (provide if scheduled or otherwise indicated in documents) a. Provided by valve manufacturer C. Industrial Grade, Electric Actuators for Modulating and Two-Position Service (Same specification for both services) 1. Rotary Actuator, Spring Return (Fail-open or fail-closed) IND-E-R-SR a. NEMA 4 aluminum housing b. 24 VAC, 24 VDC or 120 VAC power c. True 50% duty cycle rated d. Sized for 150% of break-away torque at maximum differential pressure across valve e. Rated for 400 degree F media (steam) temperature f. Rated for 150 degree F ambient temperature g. Motor overload/stall protection h. Torque limiting feature i. Positioner with 4-20 ma or 0-10 VDC control input (for modulating applications only) j. Analog position feedback potentiometer or transmitter (for modulating and twoposition applications) k. Two SPDT auxiliary switches for position indication available for external control system use. Provide if scheduled or otherwise indicated in documents. l. Prewired terminal strip m. Dual ½ conduit connections for power and control wiring n. Visual valve position indicator o. Brake or worm gear drive p. Manual mechanical override q. Mounting bracket with adequate standoff and isolation to prevent overheating. r. Approved manufacturers, Building applications: RCS, RCI, Worcester s. Approved manufacturers, Utility plant applications: Limitorque, Rotork, AUMA, EIM 2. Rotary Actuator, Non-Spring Return (Fail in place) IND-E-R-FIP a. Same specification as IND-E-R-SR Rotary Actuator, Spring Return except without spring return feature D. Industrial Grade, Pneumatic Actuators and Accessories for Modulating Service Assembly shall include Actuator 1, 2 or 3 along with items 4 through 9. All components shall be rated for -20 to 150 degree F ambient temperature. 1. High Pressure Rotary Actuator, Spring-Return (Fail-open or fail-closed) IND-HP-R-SR-MOD a. Double rack and pinion type for lower torque applications - Approved manufacturers: Hytork Series XL, Automax SuperNova Series, Worcester Series 39 U OF I FACILITIES STANDARDS 23 09 13.34-4 CONTROL VALVE ACTUATORS

b. Scotch yoke type for higher torque applications - Approved manufacturers: Bettis G Series, Automax HD Series, Rotorq P Series c. Sized for 60 PSIG supply air pressure when used in conjunction with an existing air compressor, 80 PSIG in conjunction with a new compressor, 80 PSIG within a central utility plant. d. Sized for 125% of break-away torque at maximum design pressure differential across valve. e. ISO valve mounting flange and NAMUR mounting pads for all controls. Exception: ISO/Namur not required for spring-diaphragm actuators. 2. High Pressure Rotary Actuator, Double-Acting (Fail in place) IND-HP-R-DA-MOD a. Double rack and pinion type for lower torque applications - Approved manufacturers: Hytork Series XL, Automax SuperNova Series, Worcester Series 39 b. Scotch yoke type for higher torque applications - Approved manufacturers: Bettis G Series, Automax HD Series, Rotork P Series c. Sized for 60 PSIG supply air pressure when used in conjunction with existing air compressor, 80 PSIG in conjunction with new compressor, 80 PSIG within a central utility plant d. Sized for 125% of break-away torque at maximum design pressure differential across valve. e. ISO valve mounting flange and NAMUR mounting pads for all controls. 3. Low Pressure Rotary Actuator, Spring-Diaphragm (Fail-open or fail-closed) --For use with eccentric plug valves only IND-LP-R-SD-MOD a. Industrial grade spring-diaphragm type b. Rated for 35 PSIG supply air pressure minimum c. Sized for 20 PSIG supply air pressure d. Sized for 125% of break-away torque at maximum design pressure differential across valve e. ISO valve mounting flange and NAMUR mounting pads for all controls f. Approved manufacturers: Cashco, Fisher, Masoneilan, Warren 4. Positioner a. Pneumatic, 3-15 PSIG input, 60-80 PSIG supply b. 0.25 SCFM maximum steady state air consumption at 60 PSIG, 0.35 SCFM at 80 PSIG c. Instrument, supply and output pressure gauges d. Approved manufacturers: PMV model P5N low bleed, BLX model V100P low bleed 5. Filter-Regulator a. ¼ NPT connections minimum, larger as appropriate b. Approved manufacturers: ASCO, Bellofram, Control-Air, Fisher, Parker 6. Isolation Valve a. Line-size full-port ball valve, ¼ NPT minimum U OF I FACILITIES STANDARDS 23 09 13.34-5 CONTROL VALVE ACTUATORS

b. Piped to filter-regulator inlet connection with union fitting (or equivalent) to allow convenient removal of filter-regulator / positioner without shutting down supply air source. c. Back-bleed feature to vent downstream air pressure when valve is closed. 7. Limit Switch Assembly Provide if scheduled or otherwise indicated in documents. a. Two end-of-travel SPDT limit switches. b. NEMA 4 metal enclosure. Plastic enclosure not acceptable. c. Approved manufacturers: Accord, ASCO, PMV, Stonel, Westlock, TopWorx. 8. Analog position feedback module Provide if scheduled or otherwise indicated in documents. 9. Visual position indicator a. High visibility dome type or equivalent. 10. Hand wheel manual override - Provide if scheduled or otherwise indicated in documents. 11. Assembly a. Actuator and accessories shall be pre-assembled, pre-piped, pre-wired and mounted on the valve b. Any required brackets and hardware shall be included c. Drive pinion adapters shall be standard products designed for the specific valve/actuator combination rather than custom fabricated components. Pinned adapters are not allowed. Any free-play that results from standard manufacturing tolerances shall be eliminated by permanent means requiring no consideration when actuator is removed and reinstalled in field. d. Hand wheel manual override shall be provided if indicated on the valve schedule. e. Assembly work shall be accomplished at the valve manufacturer s or supplier s facility and warranted as a complete unit. (Allowable exception: Isolation valve may be field installed to prevent damage during shipment). E. Industrial Grade, Pneumatic, Rotary Actuators and Accessories for Two-Position (On-Off) Service Assembly shall include Actuator 1, 2 or 3 along with items 4 through 10. All components shall be rated for -20 to 150 degree F ambient temperature. Full stroke time shall not exceed 20 seconds. 1. High Pressure Rotary Actuator, Spring-Return (Fail-open or fail-closed) IND-HP-R-SR-TP a. Same specification as IND-HP-R-SR-MOD High Pressure Rotary Actuator, Spring- Return 2. High Pressure Rotary Actuator, Double-Acting (Fail in place) IND-HP-R-DA-TP a. Same specification as IND-HP-R-DA-MOD High Pressure Rotary Actuator, Double- Acting 3. Low Pressure Rotary Actuator, Spring-Diaphragm (Fail-open or fail-closed) For use with eccentric plug valves only IND-LP-R-SD-TP a. Same specification as IND-LP-R-SD-MOD Low Pressure Rotary Actuator, Spring- Diaphragm U OF I FACILITIES STANDARDS 23 09 13.34-6 CONTROL VALVE ACTUATORS

4. Solenoid Valve a. ¼ NPT connections, minimum b. Dual coil type (not spring return) for true fail-in-last-position operation c. 24 VAC or 24 VDC d. Manual override e. Pre-mounted to switch box and pre-wired to terminal strip f. Approved manufacturers: ASCO, Burkert, Honeywell, Parker/Skinner, TopWorx 5. Filter-Regulator a. ¼ NPT connections minimum, larger as appropriate b. Approved manufacturers: ASCO, Bellofram, Control-Air, Fisher, Parker 6. Isolation Valve a. Line-size full-port ball valve, ¼ NPT minimum b. Piped to solenoid valve inlet connection with union fitting (or equivalent) to allow convenient removal of solenoid valve without shutting down supply air source. c. Back-bleed feature to vent downstream air pressure when valve is closed. 7. Bi-directional Speed (Flow) Control a. Heavy duty brass or stainless steel body, drilled and tapped b. Adjustable control air supply and exhaust bleed rates c. ¼ NPT connections, minimum 8. Limit Switch Assembly Required for building service entrance chilled water return isolation valve. Otherwise, provide only if scheduled or otherwise indicated in documents. a. Two end-of-travel SPDT limit switches b. NEMA 4 metal (not plastic) enclosure c. Approved manufacturers: Accord, PMV, Stonel, Westlock, TopWorx 9. Visual position indicator Provide with or without limit switch assembly. a. High visibility dome type or equivalent 10. Hand wheel manual override Provide if scheduled or otherwise indicated in documents. 11. Assembly a. Actuator and accessories shall be pre-assembled, pre-piped, pre-wired and mounted on the valve. b. Any required brackets and hardware shall be included. c. Drive pinion adapters shall be standard products designed for the specific valve/actuator combination rather than custom fabricated components. Pinned adapters are not allowed. Any free-play that results from standard manufacturing tolerances shall be eliminated by permanent means requiring no consideration when actuator is removed and reinstalled in field. d. Hand wheel manual override shall be provided if indicated on the valve schedule. U OF I FACILITIES STANDARDS 23 09 13.34-7 CONTROL VALVE ACTUATORS

PART 3 - EXECUTION 3.1 WIRING METHOD e. Assembly work shall be accomplished at the valve manufacturer s or supplier s facility and warranted as a complete unit. (Allowable exception: Isolation valve may be field installed to prevent damage during shipment). A. Electronic Actuators 1. If actuator is provided with both conduit connecter and prewired cable, conduit connector shall be used. 2. If provided with conduit connecter, final connection to actuator shall be made with flexible metal conduit. 3. If provided with prewired cable only, cable shall be terminated within junction box or enclosure. Junction box shall be located near actuator to prevent free-air splice. 4. Rubber strain relief grommet shall be provided at junction box or enclosure to protect cable from damage. 3.2 ORIENTATION A. Rotary Control Valves/Actuators 1. For hydronic applications, preferred valve orientation is with shaft oriented horizontally. Valve shall not be installed such that shaft is oriented vertically downward (i.e. with actuator at bottom). Exception: Small rotary valves with electronic actuators (e.g. at reheat coils and fan coil units) may be installed in any orientation. 2. For steam applications, valve/actuator shall be installed such that shaft is oriented horizontally. In no case shall shaft be oriented in vertically upward position. Vertical upward orientation results in overheating of actuator and accessories. B. Linear (Sliding Stem) Control Valves/Actuators 1. For hydronic applications, valve/actuator shall be installed such that stem is oriented within 45 degrees of vertical upward position. If this orientation cannot be practically achieved, valve may be installed such that stem is oriented horizontally. In no case shall valve be installed such that stem is oriented vertically downward. 2. For steam applications, valve/actuator shall be installed such that stem is not oriented in vertically upward position. Vertical upward orientation results in overheating of actuator and accessories. Preferred orientation is 45 degrees from vertically upward position. If this orientation cannot be practically achieved, valve may be installed such that stem is oriented horizontally. In no case shall valve be installed such that stem is oriented vertically downward. 3.3 MOUNTING BRACKET A. Standoff 1. As applicable, actuator mounting bracket shall have adequate standoff to accommodate insulation. In steam applications mounting bracket shall have adequate standoff to protect actuator from excessive radiant, convective and conductive heat. B. Isolation 1. In steam applications, actuator mounting bracket and linkage shall provide adequate isolation to protect actuator from excessive conducted heat. 3.4 SPECIAL NOTE A. Electronic Actuators 1. Electric/electronic actuators are especially vulnerable to damage by heat (radiant, convective and conductive). It is essential that they be installed in strict compliance with requirements of 3.1 and 3.2 above. U OF I FACILITIES STANDARDS 23 09 13.34-8 CONTROL VALVE ACTUATORS

END OF SECTION 23 09 13.34 This section of the U of I Facilities Standards establishes minimum requirements only. It should not be used as a complete specification. U OF I FACILITIES STANDARDS 23 09 13.34-9 CONTROL VALVE ACTUATORS