Handbook for Gel-VRLA-Batteries Part 1: Basic Principles, Design, Features



Similar documents
THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

Industrial Batteries Network Power Sonnenschein Solar Safe storage capacity for renewable energy. Specifications

Industrial Batteries Network Power Sonnenschein Solar Safe storage capacity for renewable energy. Specifications

Technical Handbook Valve-Regulated Lead-Acid Batteries

BATTERY BASICS. This Automotive Series 12-volt Lead Acid BATTERY BASICS has been developed by. Kevin R. Sullivan

Substation Battery & Charger Maintenance

Handbook for Gel-VRLA-Batteries Part 2: Installation, Commissioning and Operation

LEAD ACID BATTERY working LIFETIME STUDY

THE FIRST NAME IN BATTERIES

If you accidentally get battery acid on your skin, flush it with lots of water

New York City Fire Code & Energy Storage Systems

Charger Output AC Ripple Voltage and the affect on VRLA batteries

stored energy solutions for a demanding world

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity...

ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

Industrial Batteries Standby Power Classic OPzS Energy storage for economical safety.

NP Series VALVE REGULATED LEAD-ACID BATTERIES

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity

Small Traction powerbloc powerbloc dry Hawker XFC TM

Industrial Batteries System solutions for railways.

DOE HANDBOOK PRIMER ON LEAD-ACID STORAGE BATTERIES. U.S. Department of Energy Washington, D.C METRIC. DOE-HDBK September 1995

Height w/o Terminals (in)

CHARGING METHODS. Methods of Charging the Valve Regulated (Sealed) Lead-Acid Battery. 19 Valve Regulated (Sealed) Lead-Acid Batteries

Height w/o Terminals (in)

VRLA BATTERIES AUGUST

TECHNICAL MANUAL For Sun Xtender Batteries

Lead Acid Battery Terminology Glossary

Carefree Sealed Lead Acid (SLA) MSDS

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

Energy Unlimited. Reinout Vader

Temperature Compensated Charging of Lead Acid Batteries

875 Dearborn Drive Columbus, Ohio Tel: (614) Fax: (614)

BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES

Constant Voltage Charger Selection for VRLA Batteries

Maintenance-free sealed lead accumulators. HAGEN drysafe

Solar Controller / Battery Charger User s Manual

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options

din din-s 90Ah/plate 155Ah/plate 115Ah/plate 140Ah/plate

Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks

LEAD-ACID STORAGE CELL

Stationary Storage Battery Systems

MANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel

1. Connect the charger to the battery. 2. Connect the charger to the wall socket. 3. Press the MODE-button to select charging program.

MULTI XS Battery charger. For lead-acid batteries 1,2-120Ah

Battery Model: 25 Part Number: Nominal Voltage: 12 volts NSN: Number applied for, product currently available

BATTERIES IN PV SYSTEMS JAVIER BERNABÉ MOHEDANO MARTÍNEZ

NorthStar Battery (NSB) Telecom Installation and Operation Guide

EN 3 ABSORPTION, READY TO USE ANALYSE BULK DESULPHATION SOFT START. L: 2000 mm MODE- BUTTON SUPPLY PLUG* SUPPLY

Cycle long life type...lc-xc. Expected trickle life approx. 6(*10) years Standard case...lc-x. Expected trickle life 3-5 (* 6) years...

Ametek Prestolite Power AC power / Charger / Battery terms

REPORT ON THE LONG TERM RESULTS OF BATTERY CAPACITY RECOVERY PROCESSES FOR VRLA CELLS

HYDROGEN GAS MANAGEMENT FOR FLOODED LEAD ACID BATTERIES

MANUAL EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT ABSORPTION, READY TO USE ANALYSE FLOAT, FULLY CHARGED PULSE, MAINTENANCE CHARGING

BATTERIES. Battery Types. General. Battery Functions

Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid Batteries

Charge Regulator SCR 12 Marine

Industrial Batteries / Motive Power Chargers 2100.NET.»For improved efficiency and durability«

A COMPARISON OF LEAD CALCIUM & LEAD SELENIUM ALLOYS: Separating Fact From Fiction. By Carey O Donnell Mesa Technical Associates, Inc.

Valve-Regulated Lead-Acid (VRLA): Gelled Electrolyte (gel) and Absorbed Glass Mat (AGM) Batteries

The Critical Role of AGM Separators in VRLA Car Battery Performance. By George Zguris

BATTERY SERVICE. This Automotive Series BATTERY SERVICE has been developed by. Kevin R. Sullivan. Professor of Automotive Technology Skyline College

RG 7 SERIES AIRCRAFT BATTERY OWNER/OPERATOR MANUAL

How Batteries Work by Marshall Brain

2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:

MANUAL EN 3. Continue to press the MODE-button to combine charging program with charging options.

Schauer 3210 Wasson Road Cincinnati, Ohio For More Information Or Call VOLT (8658).

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR POWER - THE NEW WAY TO RV!

MXS 3. MANUAL FULLY CHARGED PULSE, MAINTENANCE CHARGING EN 3 SUPPLY PLUG* MAINS CABLE CTEK COMFORT CONNECT CHARGE CABLE ERROR LAMP MODE- BUTTON

OPzS Vented Lead-Acid STANDBY POWER BATTERIES

Cat Batteries. Cat Batteries Greater Starting Power Lower Maintenance Longer Life

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Managing a 12-volt solar system

OUTPUT CABLE CONNECTIONS:

Industrial Batteries North America

Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU)

MULTI XS 4003 Battery charger

Recycling Material Identification Guide

Battery Handbook. By: RON SMITH

Battery testing guide

Practical Examples of Galvanic Cells

We ve Got The Power. Features

ECOplus Solar Cylinder

SELECTION GUIDE FIFTH EDITION

Application Manual. Nickel Cadmium 11/06/01 Page 1 of 12

Battery guide. ResMed Ltd 1 Elizabeth Macarthur Drive Bella Vista NSW 2153 Australia Tel: Fax: ABN

Batteries and inverters

Influence of Shallow Cycling on the Ageing of SLI Batteries

TRANSPORT OF DANGEROUS GOODS

Atomic Structure. Atoms consist of: Nucleus: Electrons Atom is electrically balanced equal electrons and protons. Protons Neutrons

A Comparison of Lead Acid to Lithium-ion in Stationary Storage Applications

Spec. No. ICR C Version No. 0.0

User s Manual Before using the inverter, you need to read and save the safety instructions.

Uptimax New Generation Ni-Cd battery. Maintenance-free solution for backup power applications

Conductance Testing as an Integral Element in Battery Management

Transcription:

Handbook for Gel-VRLA-Batteries Part 1: Basic Principles, Design, Features Sonnenschein A 400 Sonnenschein A 500 Sonnenschein A 600 Sonnenschein A 700./. Sonnenschein SOLAR Sonnenschein SOLAR BLOCK Sonnenschein A 600 SOLAR Industrial Energy, Technical Support - 1- Rev. 1, December 2003

CONTENTS Handbook for Gel-VRLA-Batteries Part 1: Basic Principles, Design, Features Page 1. History of SONNENSCHEIN and Gel-Batteries 3 2. Function of VRLA-Batteries 4 2.1 Chemical Reactions 4 2.2 Gassing, Recombination 4 3. Design and Materials 8 3.1 Plate Construction and Alloys 9 3.2 Cell/Monobloc Containers 10 3.3 Terminal Posts 12 3.4 Valves 14 4. Special Features of Gel-Batteries 15 4.1 Capacity Range, Properties, Applications 15 4.2 Deep-Discharge 18 4.3 Heat Evolution and Dissipation 19 4.4 Acid Stratification 20 Industrial Energy, Technical Support - 2- Rev. 1, December 2003

1. HISTORY OF SONNENSCHEIN AND GEL-BATTERIES 1910: 1926: 1938: 1946: Foundation of factory Akkumulatorenfabrik Sonnenschein in Berlin by Dr. Theodor Sonnenschein (former student of Max Planck); vented batteries (traction, automotive) Sonnenschein becomes OEM supplier to car industry New factory in Berlin New factory in Büdingen Fig. 1: Factory Büdingen/Germany 1957: Mr. Schwarz-Schilling became managing director and share holder 1957: Invention (by Otto Jache), patent and start of production dryfit Gel Technology; first VRLA battery 1965: First dryfit licence contract with Globe Union (JCI) 1978: First dryfit Gel 2V cells 1987/88: New factory (Weiden/Germany) for Gel 2V cells 1991: Sonnenschein joined the CEAC group 1992: Shut down of Berlin plant ( termination of starter battery manufacturing) 1995: CEAC group bought by EXIDE (USA) 2000: EXIDE buys GNB Technologies (USA); new name: EXIDE Technologies Industrial Energy, Technical Support - 3- Rev. 1, December 2003

2. FUNCTION OF VRLA-GEL-BATTERIES 2.1 Chemical Reactions The following formula shows the chemical reactions as a so-called overall reaction for discharge and charge: Pb + PbO 2 + 2H 2 SO 4 Discharge Charge 2PbSO 4 + 2H 2 O During discharge (reaction from left to right side), the lead of the negative electrode (active material) and the lead dioxide of the positive electrode are transformed into lead sulphate. The sulphuric acid is transformed into sulphate (lead sulphate) and water. The formation of water shows that the acid concentration is decreased. On the other hand, the acid is diluted by the formed water. During charge (reactions from right to left), these processes take place in the reverse direction. 2.2 Gassing, Recombination A special feature of VRLA-batteries consists in the recombination of oxygen during charge. The cycle starts at the positive electrode: H 2 O ½ O 2 + 2H + + 2 e - Water is decomposed and gaseous oxygen is formed. The hydrogen ions remain dissolved in the electrolyte and are not released as gas. The electrons move away via the positive electrode What is happening now with the oxygen? How does it make its way to the negative electrode? In lead-acid batteries of the vented design with free electrolyte, it is practically impossible for the oxygen to move to the negative electrode. Immediately after having left the positive electrode, it bubbles up and escapes through the vent plug. Industrial Energy, Technical Support - 4- Rev. 1, December 2003

In VRLA batteries, a densely porous medium is offered to the oxygen to facilitate its movement (AGM-batteries: pores in the glass mat; Gelbatteries: cracks in the gel). Fig. 2 shows a comparison between vented and VRLA-batteries. Fig. 2: Gassing and recombination in vented lead-acid and VRLA batteries At the negative electrode, the following reactions take place: (1) Pb + ½ O 2 PbO (2) PbO + 2H + + SO 2-4 PbSO 4 + H 2 O (3) PbSO 4 + 2e - Pb + SO 4 2- The oxygen oxidizes lead to lead oxide (formula (1)). This lead oxide is further transformed into lead sulphate with participation of hydrogen dissolved in the electrolyte and sulphate ions (formula (2)). This represents practically a discharge process. Further products of this reaction are water and heat, in addition to the ohmic losses during charging. Thus, the oxygen is recombined and water is re-converted. The circle is closed. The recombination efficiency in Gel-batteries is 95 %, typically 98%. Industrial Energy, Technical Support - 5- Rev. 1, December 2003

The continuous flowing current during charge reconverts the lead sulphate into lead (formula (3)). One could say that in this way the negative electrode is constantly acting with a charging process and therefore cannot produce hydrogen. Otherwise, hydrogen would be produced which could not be reconverted because recombination of hydrogen does not happen. The hydrogen would be lost by diffusion through the cell container (gas permeability of the plastic material!) and through the valve respectively. The consequences would be increased loss of water. So the negative electrode is never fully charged. This is supported by overdimensioning intentionally the negative active material. Naturally the hydrogen production cannot be fully suppressed due to electrochemical reasons. Especially unfavorable operating conditions (high charging voltages and temperatures for instance) can provoke hydrogen production. Anyway, hydrogen is also generated in small amounts during corrosion of the positive plates. The oxygen produces a defined over-pressure within the cell. This is quite normal. The valve should not open at too low pressure because in that case too much oxygen would escape and get irretrievably lost. If the defined opening pressure is achieved (see chapter 3.4), the valve opens for a short time and releases the accumulated gas. Under normal operating conditions this gas consists mainly of hydrogen. Under unfavorable conditions (high charge voltages at high temperatures, for instance) oxygen would also escape. The quantity of electrolyte is dimensioned in such a way that the battery attains the expected design life under normal operating conditions, taking into account - the rate of recombination, - the corrosion of the positive electrode (oxygen consumption!) and - the losses by diffusion through the cell container. Gel-batteries have an electrolyte surplus anyway (see chapter 4.2). Following amounts of gas were determined at Gel-batteries (table 1). Industrial Energy, Technical Support - 6- Rev. 1, December 2003

Charge conditions Measured [ml] Allowed [ml] A 400 Float 2.3 Vpc 21.5 30 Over-charge 2.48 Vpc 94 300 A 500 Float 2.3 Vpc 5 30 Over-charge 2.48 Vpc 90 300 A 600 Float 2.23 Vpc 19 30 Float 2.25 Vpc 18.5 30 Over-charge 2.41 Vpc 300 300 A 700 Float 2.25 Vpc < 20 30 Over-charge 2.46 Vpc < 30 300 Table 1: Gassing acc. to IEC 896-2. Gassing rates measured per cell and per Ah within 30 days. Gas consists of (approx.) 2/3 hydrogen and 1/3 oxygen. Over-charge voltage applied for tests only. Industrial Energy, Technical Support - 7- Rev. 1, December 2003

3. DESIGN AND MATERIALS Fig. 3: Design of a Gel-Valve-Regulated-Lead-Acid cell (Type OPzV) (Gel = with gelled electrolyte, is not visible in the picture. Other details are symbolical.) Industrial Energy, Technical Support - 8- Rev. 1, December 2003

3.1 Plate Construction and Alloys All negative plates are pasted and have common grid design. Alloy: Lead-Calcium (PbCa). The positive plates of all monobloc batteries have also pasted grids: Alloy: Lead-Tin-Calcium (PbSnCa). Gel-cells A 600 and A 600 SOLAR have positive tubular plates. Alloy: Lead-Tin-Calcium (PbSnCa). Calcium gives the grids mechanical stability and guarantees low gassing rates. Tin is good for both, high corrosion resistance and high number of cycles. Highest numbers of cycles can be achieved with tubular plates as shown in fig. 4. Die-casting realizes a very fine grain structure of the spines. The gauntlet keeps the active positive material under high pressure avoiding loss of active material. b) Gauntlet and core, - front view a) Gauntlet and core (spine) c) Finished tubular plate Fig. 4: Design of a tubular plate used in A 600 and A 600 SOLAR Industrial Energy, Technical Support - 9- Rev. 1, December 2003

3.2 Cell/Monobloc Containers Three different kinds of material are used for containers and lids: PP (Polypropylene) ABS (Acrylonitrile-Butadiene Styrene Copolymer) SAN (Styrene-Acrylonitrile Copolymer) The materials are listed in tables 2 to 6 for the different battery types together with the UL-classification regarding flammability. Capacity Material UL - classification Remarks Standard 12 Ah ABS UL 94-HB HB 1.6 mm > 12 Ah PP UL 94-HB Optional 12 Ah ABS UL 94-V0 1.6 and 3 mm > 12 Ah PP UL 94-V2 Table 2: Lid and container material for A 400 Capacity Material UL-classification Remarks Standard 16 Ah ABS UL 94-HB HB 1.6 mm > 16 Ah PP UL 94-HB Optional 16 Ah ABS UL 94-V0 1.6 and 3 mm > 16 Ah PP UL 94-V2 Table 3: Lid and container material for A 500 Material UL-classification Remarks Standard SAN UL 94-HB Halogen-free Optional ABS UL 94-V0 Table 4: Lid and container material for A 600 and A 600 SOLAR Industrial Energy, Technical Support - 10- Rev. 1, December 2003

Material UL-classification Remarks PP 94 HB Halogen-free Table 5: Lid and container material for A 700 (4V-, 6V-blocs) Capacity Material UL - classification Remarks Standard 17 Ah (SOLAR only) ABS UL 94-HB HB 1.6 mm > 17 Ah PP UL 94-HB Optional 17 Ah (SOLAR only) ABS UL 94-V0 1.6 and 3 mm > 17 Ah PP UL 94-V2 Table 6: Lid and container material for SOLAR and SOLAR BLOCK Distortion of container walls and lids Gel-batteries work at a maximum internal cell pressure of approximately 0.1 to 0.15 bar ( = opening pressure of valves) because internal gas recombination. This pressure can cause slight bulging of the battery container walls and lids. When the battery is not in use, slight self-discharge, cooling-down during a stand time and other chemical reaction inside the cells can result in an under-pressure since the valves will not allow pressure to become equalized from outside. This results in a "sucking in" (contraction) of container walls and lids. Distortion is visible especially at monoblocs with relatively high capacities having large sizes of both, container walls and lids. Bulging indicates a normal function. Contraction may indicate a deepdischarged state. Industrial Energy, Technical Support - 11- Rev. 1, December 2003

3.3 Terminal Posts The pole construction and the design of the lead-through depend on the battery type and capacity range. Fig. 5 to 7 show the most common post designs of Gel-monoblocs and Gel-cells. The post sealing in monoblocs is carried out by plastic coated lead pole bushing or by design like back cuts. 5a) 5b) 5c) Fig. 5: Terminals A 400, A 500 5a): coated pole bushing 5b): Bushing with back cut 5c): Pole bushing before post welding Gel-cells A 600 and A 600 SOLAR have a patented, so-called Sonnenschein-Post allowing the positive terminals to lift. This lifting is due to the growth of positive plates which is a normal effect during ageing. The plate growth and terminal lifting, respectively, has to be absorbed by the construction of the cells. In fact, the double O-ring construction allows the positive terminals to become lifted keeping the cell sealed regarding electrolyte and gas. Industrial Energy, Technical Support - 12- Rev. 1, December 2003

Growing of about 7 to 8 mm is a normal effect for cells coming to the end of life. The battery should be replaced latest if the second O-ring becomes visible which is equivalent to a growth of approx. 10 mm. Fig. 6: Design of a Sonnenschein-Terminal used for A 600 and A 600 SOLAR. Fig.7: Cross section of a Sonnenschein-Terminal Industrial Energy, Technical Support - 13- Rev. 1, December 2003

3.4 Valves All Gel-batteries and cells are equipped by self-resealing valves. The valves are always closed in normal operation. But, the valves open if a specific amount of gas is accumulated inside a cell. This accumulation runs faster under abnormal operational conditions (high charge voltage, increased temperatures, for instance). The principle of valves used for Gel-batteries is shown in fig. 8. Always the same valve is used, but the used adapter depends on the battery type (see fig. 9, for instance). The valves operate with the following pressures (p): Opening: 0.180 p 0.06 bar Closing: 0.155 p 0.03 bar The valves are approved regarding spark arresting. That means, the construction of the valve (incl. a kind of labyrinth system) avoids that, for instance, an outside spark could penetrate the valve destroying the cell itself. The valves used in Sonnenschein-Gel-batteries are UL-listed ( Yellow card MH 12546). Gas outlet Valve cover Gas outlet Valve body Rubber cap Sealing area Gas inlet Gas inlet Fig. 8: Valve system of Sonnenschein -Gel-batteries (Valve without adapter and without protective cap) Industrial Energy, Technical Support - 14- Rev. 1, December 2003

O-Ring Cage prevents that liquid comes into the valve Fig. 9: Valve and adapter 4. SPECIAL FEATURES OF GEL-BATTERIES 4.1 Capacity Range, Properties, Applications Sonnenschein -Gel batteries are available in a very wide capacity range from 1.2 Ah to 3500 Ah depending on the requested application: Sonnenschein A 500 1.2 to 200 Ah (C 20 ) Service life: 6 years @ 20 C Cycle life acc. to IEC 896-2: 600 Dedicated for universal stand-by applications Industrial Energy, Technical Support - 15- Rev. 1, December 2003

Sonnenschein A 400 5.5 to 180 Ah (C 10 ) Service life: 10 years @ 20 C Cycle life acc. to IEC 896-2: 600 Developed as medium life product (e.g. for Telecom, UPS) Sonnenschein A 700 21 to 280 Ah (C 10 ) Service life: 12 years @ 20 C Cycle life acc. to IEC 896-2: 700 Developed as medium life product (e.g. for Telecom, UPS) Sonnenschein A 600 200 to 3000 Ah (C 10 ) Service life: 15 to 18 years @ 20 C Cycle life acc. to IEC 896-2: 1200 Long life product for sensitive and high reliability application (e.g. Telecom) Industrial Energy, Technical Support - 16- Rev. 1, December 2003

Sonnenschein SOLAR 6.6 to 230 Ah (C 100 ) Cycle life acc. to IEC 896-2: 800 (S12/85: 400) For smaller solar applications (e.g. for weekend houses, parking meters, street solar stations) Sonnenschein SOLAR BLOCK 60 to 330 Ah (C 100 ) Cycle life acc. to IEC 896-2: 1200 For medium power performance (e.g. small solar stations, offshore buoys, measuring stations) Sonnenschein A 600 SOLAR 240 to 3500 Ah (C 100 ) Cycle life acc. to IEC 896-2: 1600 For high capacity requirements (e.g. solar and wind power stations, power distribution stations, telecommunication) Industrial Energy, Technical Support - 17- Rev. 1, December 2003

4.2 Deep-Discharge Gel-batteries are proof against deep-discharge (acc. to DIN 43 539, part 5). That means the battery is connected to a load resistor equivalent to a discharge current of at least 2 * I 20 and kept in this state for 30 days. After having disconnected the load and re-charged over 48 hours the battery a capacity of at least 75% has to be achieved. Gel-batteries withstand deep discharges much better than AGM-batteries due to - surplus of electrolyte and - micro-porous separator used. The following cell and monobloc types with equivalent nominal capacities were compared regarding amount of electrolyte: Cell type Amount of electrolyte [%] Amount of electrolyte [%] Vented (OPzS) 100 Gel-VRLA (OPzV- A600) 100 85 to 99 AGM-VRLA (Absolyte IIP) 61 to 68 55 to 64 7a Monobloc type Amount of electrolyte [%] Gel-VRLA (A400) 100 AGM-VRLA (Marathon M, FT) 56 to 73 7b Table 7: Comparison,- relative amounts of electrolyte in cells (7a) and monoblocs (7b) Of course, vented cells or monoblocs have always the highest amount of electrolyte. The comparison Gel vs. AGM states 1.5 to 1.7-times more electrolyte in Gel-cells and 1.4 to 1.8-times more electrolyte in Gel-blocs. Industrial Energy, Technical Support - 18- Rev. 1, December 2003

What happens during a discharge, especially during a deepdischarge? - Sulphuric acid: Concentration decreases by conversion into lead sulphate - Water is generated - The acid density comes closer to the density of water with ongoing discharge - Solubility of lead sulphate (also pure lead) increases at lower acid density Soluble in water Solved ions in the electrolyte - Lead ions re-convert to pure lead during a following re-charge Re-converted lead growths as dendrites Short circuits can be caused, - so-called soft shorts! In Gel-batteries, the acid density does not decrease during a discharge, e.g. a deep discharge, as much as in AGM-batteries due to the surplus of electrolyte. Therefore, the tendency of generating short circuits is in Gelbatteries not as strong as in AGM-batteries (the generation of dendrites is supported in AGM-batteries due to the structure of the glass fiber mat). In addition, the used micro-porous separator in Gel-batteries prevents short circuits. 4.3 Heat Evolution and Dissipation Due to less void volume in the separator/electrolyte less heat evolution occurs in Gel-batteries compared to AGM-batteries by oxygen recombination. The heat dissipation in Gel-batteries is quite on the same level as in vented batteries and much better than in AGM, - once again due to the surplus of electrolyte. The electrolyte of Gel-batteries is not only inside and between the plates (AGM!). The Gel is filled completely to a level above the straps realizing a direct contact to the container walls. By this, excellent heat dissipation is guaranteed. Industrial Energy, Technical Support - 19- Rev. 1, December 2003

Efficient heat dissipation is necessary in order to avoid Thermal Runaway in a VRLA-battery being operated under harsh conditions (e.g. high ambient temperature, missing or insufficient air-conditioning, missing or wrong temperature compensation of charge voltage). In fact, Thermal Runaway has not occurred in Gel-batteries till now. 4.4 Acid Stratification This term describes a non-homogeneous vertical acid distribution within a cell. Origins are insufficient charging and the gravity effect. Acid stratification occurs especially during cyclical applications. It causes shorter battery life by effects like stronger corrosion and sulphation. Therefore, acid stratification should be compensated during each re-charge process. Generation and compensation of acid stratification Concentrated sulphuric acid is generated during all re-charge processes. It has a higher specific weight compared to diluted acid. Therefore, it trends to deposit in the lower parts of the cell container directly after leaving the pores of the active material. One can measure, for instance, 1.10 kg/l in the upper part of a cell whilst the acid concentration may achieve 1.40 kg/l in the lower parts. 3 to 4% more Ampere hours than discharged have to be re-charged in order to re-convert all active material. This is due to different charging behavior of the positive and negative electrodes. Acid stratification can be prevented by: - High absorption of the generated sulphuric acid (escaping from the pores of the active material) directly after leaving the pores Therefore, Gel-batteries show no stratification Absorption by AGM is lower compared to Gel - In case of vented batteries (free flooded electrolyte) the stratification cannot be prevented and has to be compensated Industrial Energy, Technical Support - 20- Rev. 1, December 2003

at the end of charge by gas evolution. The gas bubbles mix the electrolyte. The same effect can be achieved by inserting air from outside. Overall, a re-charging process is expressed by a charge coefficients (also called charge factor ). The following values represent charge coefficients after a 10h-discharge: - 1.04 to 1.06, typically 1.05, for Gel-batteries, - 1.05 to 1.12, typically 1.08, for AGM-batteries and - 1.15 to 1.30, typically 1.20, for vented batteries. Due to reasons as mentioned above, clear differences between vented, AGM- and Gel-batteries are visible regarding the charging coefficient. In Gel-batteries, the acid stratification is quite zero. Fig. 10 shows the relative differences between the lead-acid battery systems regarding acid stratification. kg/l vented AGM below AGM top vented Number of Cycles Fig. 10: Acid stratification in lead-acid battery systems Industrial Energy, Technical Support - 21- Rev. 1, December 2003

Important Notice: The manufacturer of batteries EXIDE Technologies do not take over responsibility for any loyalties resulting from this paper or resulting from changes in the mentioned standards, neither for any different national standards which may exist and has to be followed by the installer, planner or architect. EXIDE Technologies Network Power Im Thiergarten 63654 Büdingen (Hessen) Phone: + 49 60 42 81 70 Fax: + 49 60 42 81 233 www.exide.com State: Dec. 2003 Industrial Energy, Technical Support - 22- Rev. 1, December 2003